The terminal blocks used in junction boxes and cubicles are of screw type design and of the
following two types:
All types are of isolating design, i.e. they are equipped with a disconnecting device. The
disconnection is done using a screwdriver.
The terminals are also equipped with sockets for quick connection of a test instrument.
Page 2 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
The URTK / S-BEN type is used in circuits designed for higher current than 15 Amps or in circuits
carrying current or voltage from the generator measuring transformers.
Page 3 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Page 4 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Page 5 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Phoenix screwdriver
Page 6 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
The naming code for the terminals is designed to give information concerning general
requirements regarding voltage level and signal types.
X0 : AC Power ≥ 1 kV
X1 : AC Power < 1 kV
X2 : UPS Power
X3 : DC Power feeder < 75 VDC
X4 : DC Power feeder ≥ 75 VDC
X5 : Frequency converter
X6 : Control power ≥ 50 VAC, ≥ 75 VDC
X7 :
X8 : Control signal < 75 VDC, < 50 VAC
X9 : Data Communication
Page 8 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
AC Power < 1 kV
Terminal
Signal type Remarks
Designation
X10 Terminals for free use within voltage restriction.
Feeder < 1 kV X11 Ex. Motor Cables, feeders, lighting, heaters terminals etc.
Current signals terminals from current transformers in high
Current signals X12
voltage equipment (1-5 amp)
Page 9 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
UPS Power
Terminal
Signal type Remarks
Designation
Control and
X20 Terminals for free use within voltage restriction.
indication
UPS Feeder X21 Distribution / feeder terminals of UPS power
Page 10 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
DC Power feeder
< 75 VDC
Terminal
Signal type Remarks
Designation
X30 Terminals for free use within voltage restriction.
Page 11 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
DC Power feeder
> 75 VDC
Terminal
Signal type Remarks
Designation
X40 Terminals for free use within voltage restriction.
Page 12 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Frequency
converter
Terminal
Signal type Remarks
Designation
X50 Terminals for free use within voltage restriction.
Power Cable X51 Motor cable terminals from frequency converter
Page 13 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Control power
≥ 50 VAC, ≥ 75 VDC
Terminal
Signal type Remarks
Designation
Page 14 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Control signal
< 75 VDC, < 50 VAC
Terminal
Signal type Remarks
Designation
X80 Terminals for free use within voltage restriction.
Feeders X81
Orders X82 Digital out (DO)
Indications X83 Digital in (DI)
Analogue signals X84
Thermocouple X85
RTD X86
Vibration X87
Speed Signals X88
Page 15 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Data
Communication
Terminal
Signal type Remarks
Designation
Communication
X90 Copper Cable
signals
Communication
X91 Optical Fibre
signals
Page 16 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Terminal side one “1” = Internal connection above or left side of terminal row.
Terminal side two “2” = External connection under or Right side of terminal row.
Connection table:
Terminal : X84
Terminal Pin : 33
Page 17 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD
Standard Terminal Designation
Terminal side one “ I ” = Internal connection above or left side of terminal row.
Terminal side two “ O ” = External connection under or Right side of terminal row.
Connection table:
Terminal : X21
Terminal Pin : 7
Terminal side : O
Page 18 Restricted For training only © Siemens AG 2016 - 2017. All rights reserved. Stojcic S / PS DG FS TCI ITR TRD