Professional Documents
Culture Documents
1
10/13/2018
1. TRANSFORMER
FUNDAMENTALS
2
10/13/2018
3
10/13/2018
Transformer
• Alternating current in
one circuit induces an
alternating current in a
second circuit
• Transfers power between
the two circuits
• Doesn’t transfer charge
between the two circuits
4
10/13/2018
E.M.F equation
Ns – Secondary winding turns.
Np – Primary winding turns.
Φ max – max. flux linking with both windings.
f– Frequency.
1
Flux grows from zero to max in 4cycles i.e in a time
t= 1
second.
4f
Avg. rate of change of flux is max
4 max f lines / sec .
t
= 4Φ max. f lines/sec.
contd.
10/13/2018 www.cisat.co.in; 7709012815 10
5
10/13/2018
6
10/13/2018
7
10/13/2018
8
10/13/2018
Construction of Transformer
Magnetizing circuits: Limbs, yoke & clamping structures.
Electric circuits: Windings, insulation & bracings.
Terminals: Tapings & Tapping switches, bushings
& leads.
Tank: Oil, cooling devices, dryers, conservators
& ancillaries.
Core: Made up with laminations from C.R.G.O steel
strip of about 3% silicon content.
9
10/13/2018
Accessories of Transformers
• Terminals & Bushings.
• Cable Boxes.
• Oil conservator.
• Constant oil pressure system.
• Breather.
• Oil Gauge (oil level indicator).
• Oil Temperature Indicator (OTI).
• Winding Temperature Indicator (WIT).
• Oil temp – Alarm - 70°c, Trip - 80°c.
Contd.
10/13/2018 www.cisat.co.in; 7709012815 19
10
10/13/2018
Transformer construction
configuration
11
10/13/2018
12
10/13/2018
Surge relay
13
10/13/2018
14
10/13/2018
Wound in specially
condenser graded over
central conductor for field
control .
Porcelain insulator on top.
Marshalling panel
Schematic Description
• All control connections from
transformer accessories are
brought out on the terminal
strips in the marshalling
panel.
• Houses all indicators ,
control relays and other
electrical accessories.
15
10/13/2018
16
10/13/2018
17
10/13/2018
Transformer oil
18
10/13/2018
Insulation System
Class:
class Y A E B F H C
temp°C 90 105 120 130 155 180 >180
Cooling:
AN, AF, ONAN, ONAF, OFAN, OFAF, ONWF, OFWF.
contd..
19
10/13/2018
20
10/13/2018
21
10/13/2018
3. TECHNICAL
PARTICULARS
1.NP Details
22
10/13/2018
Transformer regulation
Flux density
Volts per turn ratio
No Load current
Transformer losses .
Insulation class
Insulation level
One minute PF Withstand voltage
TRANSFORMER
A few important standards (out of many)
• IS:2026 (Part III)
– 1977 Power TRS Insulation level and dielectric tests.
• IS:3024 – 1965 Elect. sheets.
• IS:3637 - 1966 Gas operated relays.
• IS:6088 – 1971 Heat exchanger.
• IS:8468 – 1977 O.L.T.C.
• IS:1886 –
– 1967 Code of practice for installation and
maintenance.
23
10/13/2018
IS:9434 –
1979 guide for sampling & analysis of free and dissolved gases
& oil from oil filled equipments.
IS:335
1983 New insulating oils for TR. & SW. gears.
IS:1448 –
1977 Methods of test for petroleum and its products.
IS:6855 –
1973 Methods of sampling for oil dielectrics.
IS:2071 –
Part I-1974, Part II-1974, Part III-1976
High voltage test.
10/13/2018 www.cisat.co.in; 7709012815 47
Transformer Protections
24
10/13/2018
CAUSES OF FAILURES
• Short circuits.
• O.V, U.V & V.DIPS.
• O.F, U.F & df/dt.
• Switching surge.
• Lightning.
• Improper Selection.
• Wrong layouts.
• Improper load distribution.
• Equipment failures.
• Protection failures.
• Improper relay co-ordination.
• Tripping of drives, loaded feeders & large
generators.
• Islanding failures.
• Hot spots, high temp.
• Ageing.
• Natural causes.
25
10/13/2018
REMEDIES
• Foresee imminent problems.
• Analyze failures.
• Take corrective measures.
• Exchange experience.
• Innovative measures.
• Adopt modern management techniques.
• Periodical training.
and so on…
26
10/13/2018
• Erection.
• Testing.
• Commissioning.
• Operation
• Maintenance.
27
10/13/2018
Instrument Trs.:
Secondary windings and the bodies are earthed.
Earthing Tr. Neutral point is either directly or
through a resistance connected to earth as per
requirement.
Isolation:
A circuit breaker of requisite breaking capacity
should be installed on both sides of Tr.
Oil soakpit:
It is provided wherever oil exceeds 2000 ltrs.
contd..
55
• Site preparation.
Outdoor and indoor
• Filling of Tr. with oil.
• Drying of Tr. & oil purification (filtration).
• Check list: (a few important ones)
• Earth pits→ min. 2 for neutral and min. 2 for
body earthing and E.R. remaining < 1 ohm.
• Breather, bushings, arching horns, Buchholz
relay, cooling, T.C, OLTC etc.
• Marshalling box, explosion-vent, radiators,
oil level etc.
28
10/13/2018
29
10/13/2018
OP R
R
UNIT
CT CT
CT
CT
OP TR
R R CT
STATION
SERVICE TR.
The zone of combined differential protection includes gen. Wdg., main step up Tr.
And the auxiliary transformer
59
www.cisat.co.in; 7709012815
10/13/2018
30
10/13/2018
31
10/13/2018
32
10/13/2018
33
10/13/2018
34
10/13/2018
35
10/13/2018
36
10/13/2018
37
10/13/2018
Special Tests:
By mutual agreement between the purchaser and Supplier:
Dielectric Tests
Measurement of zero-sequence impedance of three-phase
transformers
Short-Circuit Test
Measurement of acoustic noise level
Measurement of the harmonics of the no-load current and
Measurement of the power taken by the fans and oil pumps
Tests on bought out components / accessories such as buchholtz relay,
temperature indicators, tr.oil, pressure relief devices, oil preservation
system etc.
38
10/13/2018
At Site :
Pre-Commissioning Tests
1. Insulation Resistance Test
(use 1000 V Meggar. For EHV class, 2.5 kV Meggar)
a) Continuity
b) I.R Values – Standard values given at 60oc. For every 10oc rise,
I.R values get halved.
2 . Ratio test
3. Vector group Test
4. Excitation current test
5. Core magnetic balance test
6. Short circuit tests
7. Oil dielectric strength and acidity
39
10/13/2018
10 20 30 40 50 60 70
2. Ratio Test:
Apply 3Φ, 415 VAC on H.V side.
2
3
4
5
6
40
10/13/2018
UV U
VW V
UW W
yn - rn - yn - bn - Ry - yB - BR-
bn - rn - yn - bn - Ry - yB - BR-
41
10/13/2018
a) Dielectric Strength
b) Acidity
7. Vector group test
Refer test procedure
(Contd)
Idle Charging
• After conducting all
Pre-commissioning Checks
&
Pre-Commissioning Tests
Idle charge the transformer and observe temperature rise of oil and
windings. Then load the transformer and observe temperature rise.
42
10/13/2018
Power Transformers
Dispatching of Transformers :
When transformer is dispatched filled with oil, sufficient space is
left above the oil to take care of expansion of oil. This space is
filled with pure dry air / nitrogen gas under atmospheric pressure.
When any internal parts like tap changers etc or removed for
transportation, they are dispatched in tanks filled with oil / inert
gas or suitable measures taken so that they do not absorb
moisture.
Large rating power transformers are transported to site without oil
and filled with dry air or nitrogen due to weight limitations. During
transportation, positive pressure of 0.175 kgs / m² is to be
maintained.
43
10/13/2018
Bushings
Oil level should be checked.
The porcelain portion is to be checked for any cracks or chipping.
The terminals should be checked for any bends.
Storage:
After arrival at site, as far as possible, transformer should be
commissioned with minimum delay. If not possible to commission
immediately, the tank shall be preferably filled with processed oil up
to core and winding level, with dry air / nitrogen filling above the oil.
Gas pressure is to be monitored periodically.
The transformer shall never be stored in polluted areas likely to cause
corrosion.
44
10/13/2018
Precautions:
Every precaution shall be taken to avoid moisture absorption,
particularly during rainy season / wet conditions
Extreme care must be taken to prevent any foreign material from being
dropped into the transformer.
Detailed Testing
Procedures
45
10/13/2018
46
10/13/2018
(ii) Difference between top & bottom temp should be less than
5˚C.
(iii) Resistance shall be measured at all taps.
Volt Meter – Ammeter Method
(a) Measurement is done with D.C
(b) To minimize observation errors, polarity of the core
magnetization shall be kept constant during all
resistance readings.
(c) Volt meter leads shall be independent of the current leads.
(d) Reading shall be taken after the current and voltage have
reached steady – state values.
47
10/13/2018
48
10/13/2018
49
10/13/2018
A a
A a
A a
A a
b b
b c b
c
c
c
C B B
C B C B
C
DY 11 Aa = 0
DY 11 Aa = 0
VAb = VAc Ab = bc = ca
VAb = VAc Ab = bc = ca
VBb = VBc Bb = Cc
VBb = VBc Bb = Cc
VCb > VCc
VCb > VCc
10/13/2018 www.cisat.co.in; 7709012815 99
50
10/13/2018
51
10/13/2018
The general pattern is two similar high readings on the outer phases
and one lower reading on the centre phase, in case of three phase
transformers.
52
10/13/2018
AN BN CN Applied Voltage
230 180 50
Induced
50 180 230
53
10/13/2018
54
10/13/2018
55
10/13/2018
56
10/13/2018
57
10/13/2018
58
10/13/2018
6. Marshalling Box
The wiring from various accessories to marshalling box shall be
checked.
7. Oil
Oil samples from top and bottom of main tank are tested as per IS
1866. DGA tests are to be done to obtain bench mark before
charging, one month after charging, three months after charging,
and thereafter every year.
Oil of diverter switch should be checked for BDV at the time of
commissioning and subsequently yearly or 5000 operations,
whichever is earlier.
General Checks
(i) All oil valves are in correct position : closed or open
as required.
(ii) All air pockets are cleared.
(iii) Thermo meter pockets are filled with oil
(iv) Oil is at correct level in the bushings, conservator,
diverter switch and tank etc.
(v) Earthing connections are done.
(vi) The colour of silica gel and oil in the breather cup.
(vii) Arcing horn gaps on bushings (where provided) are
properly adjusted.
(viii) Heaters in cubicles, marshalling boxes etc where
provided shall be checked.
10/13/2018 www.cisat.co.in; 7709012815 118
59
10/13/2018
Charging procedure
(i) Set the protective relays to the minimum extent possible.
(ii) Wherever possible, the voltage should be built up in steps.
10/13/2018 www.cisat.co.in; 7709012815 119
60
10/13/2018
Principle of Measurement
61
10/13/2018
62
10/13/2018
63
10/13/2018
64
10/13/2018
(v) The main capacitance of the bushing i.e. the capacitance between
high voltage terminal and test tap is not affected by the
surrounding conditions and the accepted deviation from the
values measured at factory tests should be less than 10%.
iv) The capacitance between bushing test tap and ground is largely
influenced by the stray capacitances in the ground parts in the
transformer and hence large deviation in the measured value
shall be accepted when compared with the factory test value
65
10/13/2018
Certain Guide Lines for Capacitance and Tan Delta Values (Cont’d)
Certain Guide Lines for Capacitance and Tan Delta Values (Contd)
(xi) Rate of rise of tan delta value for bushings and windings
should not be more than 0.001 per year. The rate of change of
tan delta more than 0.001 per year needs further investigation
66
10/13/2018
CAUSES OF FAILURES
• Short circuits.
• O.V, U.V & V.DIPS.
• O.F, U.F & df/dt.
• Switching surge.
• Lightning.
• Improper Selection.
• Wrong layouts.
• Improper load distribution.
• Equipment failures.
• Protection failures.
• Improper relay co-ordination.
• Tripping of drives, loaded feeders & large
generators.
• Islanding failures.
• Hot spots, high temp.
• Ageing.
• Natural causes.
• Faults caused by lizards, rats, snakes, birds etc.
• Improper operation and maintenance.
• Lack of training.
67
10/13/2018
REMEDIES
• Foresee imminent problems.
• Analyze failures.
• Take corrective measures.
• Exchange experience.
• Innovative measures.
• Adopt modern management techniques.
• Periodical training.
and so on…
• Erection.
• Testing.
• Commissioning.
• Operation
• Maintenance.
68
10/13/2018
TRANSFORMER
A few important standards (out of many)
IS:335 – 1983 New insulating oils for TR. & SW. gears.
69
10/13/2018
Types of Transformers
• Ordinary transformer.
• Core type Tr.
• Shell type Tr.
• Power Tr.
• Distribution Tr.
• Auto Tr.
• Block Tr.
• Furnace Tr.
contd.
• Variable Tr.
• Tee – Tee (T – T) or Scott connection.
• Open delta Tr.
• Control Tr.
• Instrument Tr. :
Current Tr. (C.T)
Potential Tr. (P.T)
Capacitor Voltage Tr. (C.V.T)
70
10/13/2018
Special Tests:
As agreed by the manufacturer & the customer.
For example:
• High voltage test.
• Measurement of acoustic noise level.
• Measurement of power taken by fans & oil pumps.
• Measurement of harmonics of no load current etc.
71
10/13/2018
• S/S transformer.
• Instrument Trs.:
• Isolation:
A circuit breaker of requisite breaking capacity should be
72
10/13/2018
• Site preparation.
• Earth pits→ min. 2 for neutral and min. 2 for body earthing and E.R.
remaining < 1 ohm.
• Breather, bushings, arching horns, Buchholz relay, cooling, T.C, OLTC etc.
Tests:
• Oil:
• Dielectric-strength.
• Tanδ.
• Acidity.
• Resistivity.
• Dissolved-gas analysis.
• I.R.
• P.I.
Contd.
10/13/2018 www.cisat.co.in; 7709012815 146
73
10/13/2018
• Voltage/turn.
• polarity,.
• Sequence.
• Vector Group.
• Winding resistance.
• Magnetizing current .
• Efficiency.
• Buchholz’s Relay.
C.T:
• Continuity Test.
• Polarity Test.
• I.R Test.
• Magnetization characteristics.
P.T.
• Voltage Ratio.
• Protective Devices.
Contd.
10/13/2018 www.cisat.co.in; 7709012815 148
74
10/13/2018
Loss angle:
(measured by schering bridge)
cosΦ= cos(90-δ)
= sinδ
δ being small, sinδ=tanδ ic=Vcω
δ
tanδ= V/Ri
Vcω
tanδ= 1/RiCω Φ
iL=V/Ri
Where ω=2πf, RI= insulation resistance,
IL= leakage current, Ic = Charging Current
V= Voltage, C= Capacitance in farads.
75
10/13/2018
SCHERING BRIGDE
(FOR MEASURING DIELECTRIC LOSS AND P.F.)
Why testing ?
76
10/13/2018
Transformer Maintenance.
77
10/13/2018
Oil in OLTC - do - - do -
Contd.
78
10/13/2018
*Gaskets,
Cable box, Check all
Relays, & Take n.a .
Alarms and Test.
Their ckts.
Temp. , oil-
Level Indicator,
painting,
E. R.
79
10/13/2018
80
10/13/2018
D.E. I.R.
strength
Time
Time
TRANSFORMER OIL
It serves the double purpose of insulating and cooling.
Characteristics of oil as per IS: 335 - 1983
Contd.
10/13/2018 www.cisat.co.in; 7709012815 162
81
10/13/2018
Contd.
10/13/2018 www.cisat.co.in; 7709012815 164
82
10/13/2018
83
10/13/2018
•Shorted conductors, Poor connection in joint & tap switch and magnetic system
of core
** Arcing (Insulation damage, shorted turns, flash over in tap-changer)
Contd.
84
10/13/2018
Contd.
Then vacuuming is done for the Transformer Tank with core &
winding (without oil) through dry ice (solid CO2 ) which
solidifies. The drawn moisture is weighed.
Failures in Transformers
a. Magnetic Circuit
b. Windings
c. Dielectric circuit
d. Structure
85
10/13/2018
Thank you
ANY
QUESTIONS
PLEASE
??????
10/13/2018 www.cisat.co.in; 7709012815 172
86