You are on page 1of 10

2740 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO.

4, APRIL 2021

A Multicell Network Control and Design for


Three-Phase Grid-Connected Inverter
Li Peng , Member, IEEE, Weibiao Wu , and Ke Hu

Abstract—Three-phase grid-connected inverter with the controller such as sliding-model control, robust H control,
LCL filter is commonly controlled in synchronous frame Lyapunov function-based control, and so on [4]. Among them,
in order to independently control active power and reac-
PI controller is extensively adopted because of zero steady-state
tive power. And proportional-integral controller is usually
adopted in synchronous frame to achieve zero steady error error response in synchronous frame for fundamental current,
of inverter fundamental current. However, d–q axes cross- simple, and easy implementation.
coupling issue may deteriorate the dynamic and steady- However, there is d–q axes cross-coupling issue when grid-
state performance. Moreover, the weak damping character- connected inverter is controlled in synchronous frame. To elimi-
istic of the LCL filter will lead to resonance issue. Both nate switching frequency harmonics of the inverter, the LCL filter
issues are analyzed by the established complex-vector
model of the inverter in this article. A novel multicell net- is widely used due to high attenuation rate of −60 dB/dec [5].
work control structure is proposed to address both cou- But the LCL filter causes the increase of d–q axes cross-coupling
pling and resonance problems. To design all parameters terms and the resonance issue [6], [7]. These issues will worsen
of the multicell network controller, a multiple parameter dynamic and steady-state performances of the grid-connected
design method is proposed. Moreover, this design method
inverter. Meanwhile, the active power and reactive power current
can adapt to weak grid well. Based on the proposed con-
trol structure and design method, d–q axes cross-coupling of inverter cannot be controlled full independently.
issue can be addressed thoroughly, and the damping per- Some researchers have made large contributions on the d–q
formance is also improved obviously. Besides, the excel- axes cross-coupling issue. In [8], multivariable-PI-based dq con-
lent steady-state and dynamic performances are realized troller is presented. The parameters design method is derived by
simultaneously. Finally, the superior performances of the
the internal-model principle. However, the proposed decoupling
proposed control are verified by simulation and experimen-
tal results. controller is difficult to implement in practice due to high-order
transfer function. In [9], the intelligent optimization control
Index Terms—Control parameters design, decoupling,
grid-connected inverter, LCL filter, multicell network con- based on loop shaping idea is proposed. Its design process is
trol, response performances. complicated due to the optimization algorithm calculation bur-
den. And this controller is also a high-order one. In [10], a simple
I. INTRODUCTION decoupling solution using the command current proportional
feed-forward is presented. The work in [11] is similar to that
ANY grid-connected converters are expected to be
M able to control independently active power and reactive
power, so they are commonly controlled in synchronous refer-
in [10], presents a preprocessed reference current feed-forward
decoupling method. In [12], a simplified feedback lineariza-
tion control is proposed to solve d–q axes cross coupling by
ence frame. For a three-phase grid-connected inverter, current
a step-by-step decoupling design method. However, multiple
control is the vital part because it is responsible for regulating
physical variables need to be measured and the design process
active power current and reactive power current into grid [1],
is complex. A similar control to [12] is found in [13]. The authors
[2]. Thus, many researchers are aimed at presenting different
in [14] use the approximate L filter instead of the LCL filter to
current controllers and analyzing their control performances [3]–
simplify controller and design process. The solutions in [10],
[5]. There are not only proportional-integral (PI), proportional-
[11], and [14] only are approximate decoupling for the inverter
resonant, repetitive controller [3], but also the nonlinear
with the LCL filter. Other solutions in [12] and [13] are full
Manuscript received September 29, 2019; revised December 25, decoupling, but the control structures are complex and large
2019 and February 16, 2020; accepted February 20, 2020. Date of pub- number of measured variables are needed. It is seen that simple,
lication March 18, 2020; date of current version December 8, 2020. This
work was supported by National Natural Science Foundation of China
exact, and full decoupling of high-order converter need to be
under Grant 51577078. (Corresponding authors: Li Peng; Weibiao Wu.) explored.
The authors are with the State Key Laboratory of Advanced Elec- To address resonance issue caused by the LCL filter, there are
tromagnetic Engineering and Technology (AEET), School of Electri-
cal and Electronic Engineering, Huazhong University of Science and
also many references based on novel ideas [5], [15]–[17], which
Technology, Wuhan 430074, China (e-mail: pe105@mail.hust.edu.cn; are mainly divided into two types: passive damping and active
wuweibiao@hust.edu.cn; d201780384@hust.edu.cn). damping method. The latter is more popular due to high effi-
Color versions of one or more of the figures in this article are available
online at http://ieeexplore.ieee.org.
ciency. Active damping methods are usually realized by different
Digital Object Identifier 10.1109/TIE.2020.2978712 feedback (e.g., capacitor current, capacitor voltage, inverter-side

0278-0046 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
PENG et al.: MULTICELL NETWORK CONTROL AND DESIGN FOR THREE-PHASE GRID-CONNECTED INVERTER 2741

current, grid-side current, combined multiple feedback, and so


on) or different filters (e.g., notch filter, SOGI, and so on) [5],
[15]–[17]. Among them, the capacitor current feedback active
damping method is the most commonly used due to simple and
the good damping performance [5]. However, these references
are either focused on only active damping issue or both decou-
pling and active damping issues. For the latter, because control
parameters of decoupling and damping are designed separately, Fig. 1. Three-phase grid-connected inverter circuit with the LCL filter.
their interaction is overlooked.
With extensive applications of the grid-connected inverter
with the LCL filter, it is necessary to explore new control LCL filter parameters are designed by [18]–[21]. In general,
structure and the new controller design method in order to L1x = L1 , R1x = R1 , L2x = L2 , R2x = R2 , and Cx = C (x =
meet the increasing power quality requirements of the grid. a, b, c) are obtained. Here, a factor δ is introduced. Based on
Based on complex-vector analysis, a novel multicell network KCL and KVL rules, the unified differential equations of the
control structure is proposed in this article to address coupling, grid-connected inverter are derived by
resonance problem, dynamic, and steady-state performances
di1,zb
simultaneously. To design all control parameters of the control uinv,zb = R1 i1,zb + L1 + (1 − δ)jωL1 i1,zb + uC,zb
structure, a multiple parameter design method called zero-pole dt
(1a)
full placement is proposed. The LCL filtered grid-connected
inverter with the proposed control can be completely decoupled duC,zb
i1,zb = C + (1 − δ)jω CuC,zb + i2,zb (1b)
to realize independent control of active and reactive power. The dt
damping of the inverter has been greatly improved at the same di2,zb
time. Besides, the excellent steady-state and dynamic perfor- uC,zb = R2 i2,zb + L2 + (1 − δ)jωL2 i2,zb + u2,zb
dt
mances are realized simultaneously. Finally, the simulation and (1c)
experiment are presented to confirm the effectiveness of the
proposed control. where the subscript zb = abc, αβ or dq. When zb = abc or
αβ reference frame, δ = 1; when zb = dq reference frame,
δ = 0. uinv,zb is the inverter bridge output voltage, iinv,zb is the
II. MODELING AND ANALYSIS inverter-side current, ω is the fundamental angular frequency,
uc,zb is the filter capacitor voltage, i2,zb is the grid-side current,
A. Complex-Vector Model and u2,zb is the grid voltage.
The three-phase three-line grid-connected inverter circuit The d–q axes components of all physical variables are written
with the LCL filter is shown in Fig. 1, in which udc is the dc as the complex-vector type, i.e., χdq = χd + jχq [22]. It is noted
voltage, L1x and R1x (x = a, b, c) are the inverter-side inductor that the three-phase grid-connected inverter is commonly con-
and its parasitic resistor, Cx are the filter capacitor, L2x and trolled in synchronous reference frame in order to independently
R2x are the grid-side inductor and its parasitic resistor. The control active power and reactive power. Therefore, δ = 0 is

i2,dq = Gp−orig uinv,dq + Gdis−orig u2,dq (2a)


1
Gp−orig = (2b)
L1 L2 C(s + jω) + (R1 L2 C + R2 L1 C)(s + jω)2 + (L1 + L2 + R1 R2 C)(s + jω) + R1 + R2
3

p−orig =
Gself
 
L1 L2 Cs3 + s2 (L2 R1 C + L1 R2 C) + L1 + L2 + R1 R2 C − 3CL1 L2 ω 2 s + R1 + R2 − (L2 R1 C + L1 R2 C) ω 2
⎧    ⎫
⎨ L1 L2 Cs3 + s2 (L2 R1 C + L1 R2 C) + s L1 + L2 + R1 R2 C − 3CL1 L2 ω 2 + R1 + R2 − (L2 R1 C + L1 R2 C) ω 2 2 ⎬
⎩ + 3L L Cωs2 + 2 (L CR + L CR ) ωs + (L + L + R R C) ω − L L Cω 3 2 ⎭
1 2 2 1 1 2 1 2 1 2 1 2
(2c)

p−orig =
Gcross
3L1 L2 Cωs2 + 2 (L2 CR1 + L1 CR2 ) ωs + (L1 + L2 + R1 R2 C) ω − L1 L2 Cω 3
⎧    ⎫
⎨ L1 L2 Cs3 + s2 (L2 R1 C + L1 R2 C) + s L1 + L2 + R1 R2 C − 3CL1 L2 ω 2 + R1 + R2 − (L2 R1 C + L1 R2 C) ω 2 2 ⎬
⎩ +3L L Cωs2 + 2 (L CR + L CR ) ωs + (L + L + R R C) ω − L L Cω 3 2 ⎭
1 2 2 1 1 2 1 2 1 2 1 2
(2d)

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
2742 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 4, APRIL 2021

TABLE I
MAIN CIRCUIT PARAMETERS

Fig. 3. Inverter plant model and the conventional control block


diagram.

There are three pairs of d–q axes cross-coupling paths (i.e., ωL1 ,
ωC, and ωL2 ). If the grid-voltage disturbance is eliminated by
feedforward control [23], (3a) can be simplified as
i2,dq
= Gp . (3b)
uinv,dq

The imaginary part of the denominator in the plant complex-


Fig. 2. Bode diagrams of the original plant transfer functions. (a) Self-
vector transfer function (3b) reflects the coupling influence. On
axis. (b) Cross axis. the other hand, the real part of the denominator in (3b) lacks the
s2 term, which illustrates the serious resonance issue caused by
the LCL filter. Similarly, the imaginary part of the denominator
substituted into (1) and the complex-vector expression of the in (3b) is also short of s term, which means the weak damping
inverter plant is derived by equation (2a)–(2b) shown at the performance. Note that the analysis process will be simple and
bottom of the previous page, where Gp−orig is the complex- understandable if the real and the imaginary part of complex-
vector transfer function of the original plant and Gdis-orig is vector transfer functions are separately looked at.
the complex-vector disturbance transfer function of the original
plant. In addition, the self-axis and cross-axis transfer functions B. Conventional Control Analysis
of the original plant (2b) are also derived by equation (2c)–(2d) To decouple three pairs of d–q axes cross-coupling terms, the
shown at the bottom of the previous page. conventional decoupling control is depicted in Fig. 3 (marked
Based on simulation values in Table I, the Bode diagrams of by red line) and feedback factor K = ω(L1 + L2 )/Ginv is
p−orig and Gp−orig (e.g., R1 = R2 = 0.01 Ω) in Fig. 2 show that
Gself cross
proposed to simplify implementation, where Ginv is the inverter
there are multiple resonance peaks in self-axis and cross axis of equivalent gain [24]. Note that control delay time impacts on
the original plant. They illustrate that both self-axis and cross the inverter performance. However, with the development of
axis of the inverter original plant will cause the stability issue new semiconductor devices and microprocessor technique, high
easily. switching frequency and fast control process of converter are
Considering the worst stability condition, the parasitic re- being realized gradually [25]. The influence of delay time will
sistors (i.e., R1 and R2 ) are omitted, so Gp−orig and Gdis−orig be decreased. Here, control methods are analyzed under ignoring
become Gp and Gdis given as follows: delay time. Based on (3b), Fig. 3 and the value of K, the closed-
i2,dq = Gp uinv,dq + Gdis u2,dq loop transfer function matrix of the control with the conventional
decoupling (called control  1 ) is derived by
1
= uinv,dq   A 1 B1   ∗ 
Dpr + jDpi i2,d − D1 i2,d
= D 1
(4)
s2 L1 C + 1 − ω 2 L1 C + j(s2ωL1 C) i2,q B1 A 1
D1 D1
i∗2,q
− u2,dq (3a)
Dpr + jDpi
where A1 = Ginv Gi D1r , B1 = −Ginv Gi D1i , D1 = D1r 2
+
where Dpr = s L1 L2 C + s(L1 + L2 − 3ω L1 L2 C) and
3 2
D1i , D1i = −ω L1 L2 C + s 3ωL1 L2 C − Ginv K + ωL1 +
2 3 2

Dpi = s2 3ωL1 L2 C + ωL1 + ωL2 − ω 3 L1 L2 C are the real ωL2 = −ω 3 L1 L2 C + s2 3ωL1 L2 C, D1r = s3 L1 L2 C +
and imaginary part of the characteristic equation in the s(L1 + L2 − 3ω 2 L1 L2 C) + Ginv Gi . It is seen from B1 = 0
plant complex-vector transfer function, respectively. The that the inverter is not decoupled fully. Moreover, the existence
resonance
angular frequency of the LCL filter is ωr = of coupling will also impact on other response performances.
(L1 + L2 )/(L1 L2 C) under the worst condition R1 = R2 = 0 Considering the resonance issue caused by the LCL filter, the
[5]. The plant model in synchronous frame is plotted in Fig. 3. capacitor current feedback is usually adopted and the factor is

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
PENG et al.: MULTICELL NETWORK CONTROL AND DESIGN FOR THREE-PHASE GRID-CONNECTED INVERTER 2743

Kd . This conventional active damping control is also shown in


Fig. 3 (i.e., marked by blue line). In [14], the active damping
factor is given as Kd = 2ξωn L1 /Ginv , where ξ is the damping
ratio, ωn is the natural angular frequency. As for the current
controller, Gi = kp + ki /s is usually adopted. Based on (3b)
and Fig. 3, the closed-loop transfer function matrix of the control
with the conventional active damping (called control  2 ) is
yielded by
  A 2 B2   ∗ 
i2,d − D2 i2,d
= D 2
(5)
i2,q B2 A 2
D2 D2
i∗2,q Fig. 4. Multicell network control structure.

where A2 = Ginv Gi D2r , B2 = −Ginv Gi D2i , D2 = D2r 2

+ D2i , D2r = s L1 L2 C +s Kd Ginv L2 C +s(L1 +L2 − 3ω 2


2 3 2
GM 2 , KC1 , and KC2 , respectively. Based on the proposed con-
L1 L2 C) + Ginv Gi − Kd Ginv ω 2 L2 C, D2i = 3ωL1 L2 Cs2 + trol structure, its closed-loop complex-vector transfer function
2Kd Ginv ωL2 Cs + ωL1 + ωL2 − ω 3 L1 L2 C. It is seen that the is derived by
resonance issue of the self-axis closed-loop transfer function
i2,dq Ginv (skp + ki )
(i2,d /i∗2,d or i2,q /i∗2,q ) in (5) is solved. Note B2 = 0 when ∗ = (7)
Kd = 2ξωn L1 /Ginv is substituted into (5), which indicates i2,dq Dcr + jDci
the d–q axes cross-coupling still exists. Although this active where Dcr = s4 L1 L2 C + s3 KC1 Ginv L2 C +s2 (L1 +L2 −2ω
damping can suppress resonance peak, but its damping effect KC2 Ginv L2 C − 3ω 2 L1 L2 C) + s(kp Ginv − KC1 Ginv ω 2 L2
in this situation is different from that in single-phase inverter C + GM 1 Ginv ) + ki Ginv and Dci = s3 (3ωL1 L2 C + KC2
because of the existence of d–q axes cross coupling. Ginv L2 C) + s2 (2KC1 Ginv ωL2 C) + s(ωL1 + ωL2 − ω 3 L1
When the decoupling and active damping control are com- L2 C − KC2 Ginv ω 2 L2 C + GM 2 Ginv ) are the real part and
bined together as shown in Fig. 3 (i.e., marked by red and blue imaginary part of the closed-loop characteristic equation.
line), the closed-loop transfer function matrix of the control with It is seen that the d-axis and q-axis components can be
the conventional decoupling and active damping (called control fully decoupled if the imaginary part Dci of the closed-loop
3 ) is derived by
characteristic equation in (7) is zero by the designing multicell
  A 3 B3   ∗  network control cells parameters properly. Then, the coupling
i2,d − D3 i2,d
= D 3
(6) issue between d- and q-axis can be solved completely. On the
i2,q B3 A 3
i∗2,q
D3 D3 other hand, the real part Dcr can make the inverter achieve
where A3 = Ginv Gi D3r , B3 = −Ginv Gi D3i , D3 = D3r 2
+D3i2
, high stability and good dynamic response by selecting suitable
D3i = s 3ωL1 L2 C +s2Kd Ginv ωL2 C − ω L1 L2 C + Ginv K
2 3 multicell network control cells parameters. It means that the
+ ωL1 + ωL2 , D3r = D2r . When K = ω(L1 + L2 )/Ginv and resonance issue is addressed. Moreover, this control structure
Kd = 2ξωn L1 /Ginv are both substituted into (6), it is found can not only make the inverter decouple fully in synchronous
that B3 = 0 and D3i = s2 3ωL1 L2 C + s2Kd Ginv ωL2 C − reference frame and improve damping performance, but also
ω 3 L1 L2 C. It illustrates that the conventional combined control give consideration to dynamic and steady-state performances.
does not fully achieve decoupling, and its damping effect is
also different from that of the single-phase inverter circuit. IV. MULTIPLE PARAMETER DESIGN METHOD
There are multiple control cells parameters to be designed
III. MULTICELL NETWORK CONTROL in the multicell network control structure. However, multiple
For the conventional decoupling control, only d→q axis and parameter design is difficult, especially for the goal of all control
q→d axis decoupling path are adopted when the number of cells cooperative modulating. To address this issue, a zero-pole
the measured variables is small, the decoupling is incomplete. full placement method is proposed in this article. In order to
For the conventional active damping control, its damping achieve full decoupling, good damping, and control accuracy
effect is not the same as that of single-phase circuit because under the measured variables as few as possible, and to avoid
the coupling exists. For the abovementioned two combined noise amplification caused by second-order differential term,
conventional control, the coupling and resonance issues also here select the control cell Gi = kp + ki /s, GM 1 = d0 + sd1 ,
are not addressed well. and GM 2 = e0 + se1 (d0 , e0 are proportional factor, d1 , e1 are
Motivated by the basic neural network concept, a novel multi- derivative factor). Then, the real part and imaginary part of the
cell network control structure is proposed in this article, as shown closed-loop characteristic equation in (7) is derived by
in Fig. 4. The idea is to make different control “cells” cooperative Dcr = s4 L1 L2 C + L2 CKC1 Ginv s3 + s2 (L1 + L2
to achieve full decoupling and good damping simultaneously
under the measured variables as few as possible, and to improve − 3ω 2 L1 L2 C − 2ωKC2 L2 CGinv + d1 Ginv )
the dynamic and steady-state performances together. In the
− s(L2 CKC1 ω 2 Ginv − d0 Ginv − Ginv kp )
proposed control structure, there are five pairs of control cells,
cell 1–cell 5 and cell 1–cell 5, which are composed of Gi , GM 1 , + Ginv ki (8a)

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
2744 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 4, APRIL 2021

Dci = s3 (3ωL1 L2 C + KC2 L2 CGinv ) + (2ωKC1 L2 CGinv


+ e1 Ginv )s2 + [(ωL1 + ωL2 − ω 3 L1 L2 C
− KC2 L2 Cω 2 Ginv ) + e0 Ginv ]s. (8b)

Select the desired closed-loop transfer function as following:


i2,dq A(s + hξc ωc )
=
i∗2,dq L1 L2 C(s2 + 2ξc ωc s + ωc2 )(s + mξc ωc )(s + nξc ωc )
(9) Fig. 5. Parameters design process of the proposed method.

where ξc and ωc are the desired damping ratio and natural angular
frequency of the closed-loop inverter, respectively, m and n are
the ratios of the distance from nondominant poles to imaginary where Tc = Ginv (skp + ki )/Dcr , which is the same as (9). It is
axis and the distance from dominant poles to imaginary axis, h seen that the cross-axis transfer function in (12) is zero, and this
is the ratio of the distance from zero to imaginary axis and the illustrates the proposed control can fully address the coupling
distance from dominant poles to imaginary axis, A is the middle issue in synchronous reference frame. Moreover, Tc shows the
variable. Comparing (7), (8a) and (8b) to (9), the following inverter can achieve excellent dynamic and steady-state perfor-
equations can be obtained by: mances due to the expected zero and poles.

⎪ L CKC1 Ginv = L1 L2 C[(m + n)ξc ωc + 2ξc ωc ]
⎪ 2
⎪ V. CHARACTERISTICS OF THE PROPOSED CONTROL

⎪ L1 + L2 − 3ω 2 L1 L2 C − 2ωKC2 L2 CGinv + d1 Ginv

⎪ The conventional decoupling control (control 

⎪ = L1 L2 C[(mn + 2m + 2n)ξc2 ωc2 + ωc2 ]
1 ) has only




d→q and q→d cross-decoupling paths and the inverter is not

⎪ d0 Ginv + Ginv kp − L2 CKC1 ω 2 Ginv = L1 L2 C[2mnξc3 ωc3 decoupled fully. The conventional active damping (control 


2 )

⎪ +(m + n)ξc ωc3 ]


has only self-axis damping paths, it is not easy to take care
⎨G k = L L Cmnξ 2 ω 4 of both self-axis and cross-axis damping effect of the inverter.
inv i 1 2 c c
.

⎪ G k = A However, the proposed control has not only cross axis but also


inv p

⎪ Ginv ki = Ahξc ωc self-axis decoupling paths, and this control includes both self-



⎪ 3ωL
axis and cross-axis active damping paths at the same time. So

⎪ 1 L2 C + KC2 L2 CGinv = 0


the performances of decoupling, damping, dynamic, and steady-
⎪2ωKC1 L2 CGinv + e1 Ginv = 0



state response can be regulated collaboratively for the proposed

⎪ (ωL1 + ωL2 − ω 3 L1 L2 C − KC2 L2 Cω 2 Ginv ) + e0 Ginv


control.
=0 The structure of the proposed control seems more complex
(10) than that of control  3 from Figs. 3 and 4. In fact, both self-
axis and cross-axis control cells are utilized together in the
By solving the nine linear equations in (10), all control pa- proposed control to achieve unified adjustment, and self-axis
rameters of control cells are derived by and cross-axis control cells are symmetrical structure, and these
⎧ control cells all adopt simple P, PI, or PD control algorithms. It

⎪ kp = L1 L2 Cmnξc ωc3 /(Ginv h)

⎪ is easily implemented in practice. However, the conventional

⎪ k = L1 L2 Cmnξc2 ωc4 /Ginv control 
⎪i
⎪ 3 with approximate decoupling cannot achieve full

⎪ KC1 = L1 ξc ωc (2 + m + n)/Ginv

⎪ decoupling [14], and it will affect damping effect. In addition,

⎪ KC2 = −3ωL1 /Ginv

⎪ the conventional combined control [12], which is an improved

⎪ method by using full decoupling based on control 

⎨d0 = L1 L2 C[ω ξc ωc (2 + m + n)+ξc ωc (m + n + 2mnξc )
2 3 2 3 , contains
−mnξc ωc /h]/Ginv
3
. complex structure, second-order differential term in algorithms

⎪ (i.e., may magnify high-frequency noise), and large number of

⎪ d1 = −L1 L2 C[ωr + 3ω − ωc − ξc ωc (2m + 2n + mn)]/
2 2 2 2 2

⎪ measured variables [12]. Comparing with the existing controls

⎪ G

⎪ inv combining full decoupling and active damping together, the


⎪e0 = −ωL1 L2 C[ωr2 + 2ω 2 ]/Ginv
⎪ complex degree of the proposed control is not increased.


⎪e1 = −2ωL1 L2 Cξc ωc (2 + m + n)/Ginv
⎪ The proposed zero-pole full placement design method directly


A = L1 L2 Cmnξc ωc3 /h gives the theoretical design expressions of all control parameters.
(11) The design method is more precise and concise than conven-
tional parameters design or trial-and-error methods. As shown
Under the designed values of these parameters, the closed- in Fig. 5, all parameters of control cells are obtained directly by
loop transfer function matrix becomes one step, so the design process is also simpler and does not need
  ∗  to repeat one or more times. In summary, the design method,
i2,d Tc 0 i2,d
= (12) design process, and implementation of the proposed control are
i2,q 0 Tc i∗2,q simple, and its computational burden is small.

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
PENG et al.: MULTICELL NETWORK CONTROL AND DESIGN FOR THREE-PHASE GRID-CONNECTED INVERTER 2745

Fig. 6. Decoupling, damping, and tracking ability comparisons. (a) i2,q /i∗2,d Bode diagrams with the proposed control and control  1, 
3.
(b) i2,q /i∗2,d Bode diagrams with the proposed control under parameters shift. (c) Equivalent open-loop Bode diagrams of i2,d /i∗2,d with the proposed
control and control  2,3 (—: normal parameters, ----: parameters shift). (d) i2,q /i∗2,d pole-zero map of control 
2 . (e) i2,q /i∗2,d pole-zero map of
control  3 . (f) Step responses of i2,q /i∗2,d with the proposed control, control 
2 and 3.

TABLE II based on control parameters in Table II, several controls are


CONTROLLER PARAMETERS
evaluated easily by (4), (5), (6), and (12).

A. Decoupling Capacity Comparison


The i2,q /i∗2,d closed-loop Bode diagrams of different controls
are depicted in Fig. 6(a). Under normal main circuit parameters,
the magnitude curve of i2,q /i∗2,d with the proposed control is
negative infinity in Fig. 6(a). The maximum magnitude values
of i2,q /i∗2,d with control 1 and 3 are −14.6 dB and −19.5 dB,
respectively. It shows that the proposed control can achieve full
decoupling but control  1 and 3 cannot.
When main circuit parameters shift as shown in Fig. 6(b),
i2,q /i∗2,d magnitude curve of the proposed control has the largest
value of −37.9 dB (i.e., the worst case: 0.8L1 , 1.2L2 , 1.2C). It
For comparison, take a 18.7 kW three-phase grid-connected
is seen that the proposed control has better decoupling capacity
inverter for an example, when the main circuit parameters are
than conventional controls, even if main circuit parameters shift.
listed in Table I and the desired performances of the proposed
control for (9) are selected as following. The natural angular
frequency ωc is 0.7 times of ωr , the damping ratio ξc is 0.707. B. Damping and Tracking Performance Comparison
According to state-space theory [26], select m = n = 5 and The equivalent open-loop Bode diagrams of i2,d /i∗2,d with the
h = 10. Then, the control parameters of the proposed control are proposed control, control  2 and  3 are depicted in Fig. 6(c).
designed by (11), listed in Table II. As for control 
3 , ξ = 0.707, The equivalent open-loop transfer function of i2,d /i∗2,d with the
ωn = ωr , and PI controller parameters are designed by [14], proposed control is the minimum phase system, but that with
[24], [27], also listed in Table II. The control parameters of control 2 and  3 are both nonminimum phase system. When
control  1 and  2 are selected like control  3 . Accordingly, the cut-off frequencies are selected the same (i.e., 764 Hz) for fair

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
2746 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 4, APRIL 2021

comparison, the phase margin with the proposed control is 63.8° but i2,abc under control  3 has the overshoot of 15.5%. The
while those with control  2 and  3 are both 53.2°. The three overshoot and settling time of control  3 are bigger than that
control methods can improve damping; however, the proposed of the proposed control. It illustrates that the decoupling ability
control can obtain the larger phase margin (corresponding to and tracking performances of the proposed control are better
better damping) than control  2 and  3 under the same band- than that of control  3 .
width. Considering various influence such as temperature, aging, 2) Response When q-Axis Reference Changes: The re-
grid impedance variation, and so on, L1 , L2 , and C will vary. sponse waveforms when the reactive current reference i∗2,q steps
From the perspective of general analysis, the case where the from 0 to 20 A then to 0 A and the active current reference i∗2,d
parameter shift in the range of ±50% has the greatest influence is 20 A are shown in Fig. 7(d) and (f). As shown in Fig. 7(d),
on the inverter, i.e., 0.5L1 , 1.5L2 , and 1.5C, is selected. Under i2,q under the proposed control tracks the command current
this parameter shift case, the phase margin with control  2 and smoothly with settling time of 0.5 ms, overshoot of 2%, and
3 are decreased by 24.8° while that with the proposed control i2,d remains largely unchanged when i∗2,q changes. For control
is only reduced by 8.8° in Fig. 6(c). This is because the inverters 3 , i2q has the overshoot of 19% and its settling time is 2.5 ms, as
using control  2 or  3 are the nonminimum phase system, while shown in Fig. 7(f). Due to coupling, i2,d has also the overshoot of
the inverter using the proposed control is the minimum phase 15% when i∗2,q steps up or down, and both i2q and i2,d includes
system. So the proposed control has stronger robustness than considerable ripple. i2,abc under control  3 has the overshoot
control  2 and  3 . of 27.8% (2.3 A/8.28 A) and their waveforms are worse than
As for the cross-axis damping performance, the transfer func- those of i2,abc under the proposed control. It also illustrates that
tion i2,q /i∗2,d with the proposed control is equal to zero, and the performances of the proposed control are superior to that of
the pole-zero maps and step responses of i2,q /i∗2,d with control control  3 .
2 and  3 are shown in Fig. 6(d)–(f). The step response of 3) Main Circuit Parameters Shifting: Considering the
i2,q /i∗2,d with control 2 and  3 have both big overshoot due to worst shifting condition of the abovementioned, the main circuit
the influence of zeros z2 /z3 . It is seen that the cross-axis damping parameters are set to: 0.8L1 , 1.2L2 , and 1.2C. For the proposed
performance with control  2 and  3 is not improved well, while control, the response waveforms of i2,d , i2,q , and i2,abc under
the proposed control has no problem. Thus, the damping ability the parameters shifting in Fig. 7(b) are almost the same as those
of control  2 and  3 are both limited and the proposed control under the normal parameters in Fig. 7(a) when i∗2,d changes.
has better damping effect. When i∗2,q varies, the response waveforms under the parameters
It is known from abovementioned paragraph that the proposed shifting in Fig. 7(e) are also the same as those under the normal
control can make the grid-tied inverter achieve completely in- parameters in Fig. 7(d). It is obvious that the proposed control
dependent control of active and reactive power, fundamental has strong robustness.
current tracking without steady-state error. The control pa- 4) Considering Weak Grid Condition: If weak grid is con-
rameters designed by the proposed zero-pole full placement sidered, grid inductance Lg−x is calculated in terms of SCR = x
method ensure that the inverter has fast dynamic response, [28]. L2  = L2 + Lg−x is used to replace L2 , then design all con-
small overshoot, and strong robustness. Moreover, the proposed trol cells parameters by (11). Thus, the designed control parame-
multiple parameter design method directly gives the theoretical ters can make the inverter be suitable for weak grid. For example,
expressions of all control parameters, and it is convenient for Lg−5 = 4.9457 mH when SCR = 5, control parameters under
researchers and engineers to design controller. weak grid condition are calculated as follows: kp = 0.0734,
ki = 2800, KC1 = 0.1132, KC2 = −0.00233, d0 = 0.9560, d1
VI. SIMULATION AND EXPERIMENT = 0.0001653, e0 = −0.004959, and e1 = −0.00000762. For
the weak grid from SCR = 1–5, the open loop Bode diagram of
A. Simulation the inverter with the proposed control illustrates that the PM is
The responses of several controls under different conditions 22.8° (i.e., the inverter is stable) even if SCR = 1. The simulation
are tested in MATLAB/Simulink platform. The inverter main under SCR = 5 and SCR = 3 are shown in Fig. 8(a) and (b),
circuit parameters and control parameters are listed in Tables I respectively. Both the cases are stable. It means that the proposed
and II, respectively. control and control parameters design method can adapt to weak
1) Response When d-Axis Reference Changes: Fig. 7(a) grid very well.
and (c) gives the simulation results of the proposed control and
control  3 when the active current reference i∗2,d changes as
0 A→40 A→0 A and the reactive current reference i∗2,q is 0 A. B. Experiment
Fig. 7(a) shows that i2,d under the proposed control reaches the The experimental inverter prototype parameters are listed in
reference value quickly with settling time of 1.0 ms, overshoot of Tables I and II. The control is implemented in TMS320F28335
3% and steady-state error of near 0, and i2,q is almost unaffected and AD sampling chip is MAX1324. All test results are recorded
when i∗2,d steps up or down. It is observed in Fig. 7(c) that i2,d by Yokogawa ScopeCorder DL750. There are different solutions
under control  3 has the overshoot of 13.8% and the settling to decrease control delay [5], [29]. A shifting sampling instant
time of 3.0 ms. Meanwhile, i2,q under control  3 is obviously method has been adopted to decrease delay in this article.
affected by i∗2,d , and has considerable overshoot (4 A). So it Test 1: i∗2,d changes. Fig. 9(a) and (b) shows the response
is seen that i2,abc under the proposed control has no overshoot waveforms of the proposed control under normal and shifted

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
PENG et al.: MULTICELL NETWORK CONTROL AND DESIGN FOR THREE-PHASE GRID-CONNECTED INVERTER 2747

Fig. 7. Simulation waveforms when i∗2,d changes for (a) the proposed control and (b) under its parameters shift, (c) control 
3 ; when i∗2,q changes
for (d) the proposed control and (e) under its parameters shift, (f) control 
3.

under the proposed control have no overshoot when i∗2,d varies


as 0 A→17 A→0 A and i∗2,q = 0 A. The response time of the
proposed control is 3 ms. In Fig. 9(b), the response time (i.e.,
3.1 ms) of the proposed control under shifted parameters is
slightly larger than that of Fig. 9(a) and there is also no overshoot.
For control  3 , as depicted in Fig. 9(c), i2,abc and i2,d have
overshoot of 2.9 A (17%) and 1.6 A (9.4%), respectively. When
i∗2,d changes, i2,q also produces overshoot due to coupling. Its
overshoot is obvious bigger than that of i2,d , and is consistent
with the analysis in Fig. 6(e) and (f). The settling time of control
 3 is about 4.5 ms, longer than that of the proposed control.
Test 2: i∗2,q changes. Fig. 9(d) and (e) shows the exper-
Fig. 8. Simulation results of the proposed control under weak grid. imental results of the proposed control under normal and
(a) SCR = 5. (b) SCR = 3. shifted parameters (0.8L1 , 1.16L2 , 1.25C). When i∗2,q steps from
0 A→13 A→0 A and i∗2,d = 8 A in Fig. 9(d), i2,abc , i2,d , and i2,q
parameters (0.8L1 , 1.16L2 , 1.25C), which contain the grid volt- under the proposed control have no overshoot. And i2,d is rarely
age u2,abc , grid-side current i2,abc and their d–q axes component found to be affected by i∗2,q . The response time of the proposed
i2,d , i2,q from top to bottom. In Fig. 9(a), i2,abc and i2,d , i2,q control is 3.1 ms. In Fig. 9(e), the response time (i.e., 3.3 ms) of

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
2748 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 68, NO. 4, APRIL 2021

Fig. 9. Experimental waveforms when i∗2,d changes for (a) the proposed control, (b) the proposed control under parameter shift and (c) control
3 ; when i∗2,q changes for (d) the proposed control, (e) the proposed control under parameter shift and (f) control 
 3.

the proposed control under shifted parameters is slightly larger design expressions of all control parameters. The design process
than that of Fig. 9(d) and there is also no overshoot. For control was precise and very simple, and does not need to repeat one
 3 , as shown in Fig. 9(f), the overshoots of i2,abc and i2,q are or more times. It also avoids the interaction issue of decoupling
1.0 A (14.3%) and 1.3 A (10.4%), respectively. The overshoot of and damping in conventional combined control with decoupling
i2,d , which is obvious bigger than that of i2,q means the coupling and active damping, because their control parameters were de-
influence, and is consistent with the analysis in Fig. 6(e) and (f). signed separately in conventional combined control. It was very
The waveforms of i2,abc under control  3 are worse than those convenient for researchers or engineers. The proposed control
under the proposed control. The settling time of control  3 when and parameters design method can adapt to weak grid well.
i∗2,q changes is 4.5 ms, longer than that of the proposed control. Moreover, the inverter with the proposed control was a minimum
The abovementioned results indicate that the decoupling abil- phase system, and the inverter had smaller overshoot and settling
ity and tracking performances of the proposed control are better time than that with the conventional control, which is a non-
than those of control  3 due to the proposed control structure minimum phase system. The proposed complex-vector transfer
and parameters design method. function-matrix analysis method can quantitatively analyze the
influence of coupling in theory and bring convenience to the
design. The proposed control, parameters design, and analysis
VII. CONCLUSION methods were also suitable to other converters.
A novel multicell network control structure and a multiple
parameter design method were proposed in this article. The
proposed control can make the grid-connected inverter with the REFERENCES
LCL filter to realize full independent control of active and re- [1] N. Hoffmann, F. W. Fuchs, and M. P. Kazmierkowski, “Digital current
active power, and good dynamic and steady-state performances control in a rotating reference frame—Part I: System modeling and the
discrete time-domain current controller with improved decoupling capa-
without resonance issue. The multiple parameter design method bilities,” IEEE Trans. Power Electron., vol. 31, no. 7, pp. 5290–5305,
called zero-pole full placement directly give the theoretical Jul. 2016.

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.
PENG et al.: MULTICELL NETWORK CONTROL AND DESIGN FOR THREE-PHASE GRID-CONNECTED INVERTER 2749

[2] R. Vijayapriya, P. Raja, and M. P. Selvan, “A modified active power [24] J. Dannehl, C. Wessels, and F. W. Fuchs, “Limitations of voltage-oriented
control scheme for enhanced operation of PMSG-based WGs,” IEEE PI current control of grid-connected PWM rectifiers with LCL filters,”
Trans. Sustian. Energy, vol. 9, no. 2, pp. 630–638, Sep. 2018. IEEE Trans. Ind. Electron., vol. 56, no. 2, pp. 380–388, Nov. 2009.
[3] Q. Zhao and Y. Ye, “A PIMR-type repetitive control for a grid-tied inverter: [25] N. He, M. Chen, J. Wu, N. Zhu, and D. Xu, “20-kW zero-voltage-switching
Structure, analysis, and design,” IEEE Trans. Power Electron., vol. 33, SiC-mosfet grid inverter with 300 kHz switching frequency,” IEEE Trans.
no. 3, pp. 2730–2739, Mar. 2018. Power Electron., vol. 34, no. 6, pp. 5175–5190, Aug. 2019.
[4] I. Sefa, S. Ozdemir, H. Komurcugil, and N. Altin, “An enhanced Lyapunov- [26] R. C. Dorf and R. H. Bishop. Modern Control Systems, 12th ed. Englewood
function based control scheme for three-phase grid-tied VSI with LCL Cliffs, NJ, USA: Prentice-Hall, 2011.
filter,” IEEE Trans. Sustain. Energy, vol. 10, no. 2, pp. 504–513, May 2019. [27] J. Wang, J. D. Yan, and L. Jiang, “Pseudo-derivative-feedback current
[5] D. Pan, X. Ruan, C. Bao, W. Li, and X. Wang, “Capacitor-current-feedback control for three-phase grid-connected inverters with LCL filters,” IEEE
active damping with reduced computation delay for improving robust- Trans. Power Electron., vol. 31, no. 5, pp. 3898–3912, Jul. 2016.
ness of LCL-type grid-connected inverter,” IEEE Trans. Power Electron., [28] A. Egea-Alvarez, S. Fekriasl, F. Hassan, and O. Gomis-Bellmunt, “Ad-
vol. 29, no. 7, pp. 3414–3427, Jul. 2014. vanced vector control for voltage source converters connected to weak
[6] Y. Wang, W. Wang, C. Wang, and X. Wu, “Coupling analysis on current grids,” IEEE Trans. Power Syst., vol. 30, no. 6, pp. 3072–3081, Jan. 2015.
control at low switching frequency for the three-phase PWM converter [29] C. Zou, B. Liu, S. Duan, and R. Li, “Influence of delay on system stability
based on RGA and a novel output feedback decoupling method,” IEEE and delay optimization of grid-connected inverters with LCL filter,” IEEE
Trans. Ind. Electron., vol. 63, no. 11, pp. 6684–6694, Nov. 2016. Trans. Ind. Informat., vol. 10, no. 3, pp. 1775–1784, Aug. 2014.
[7] B. Bahrani, A. Rufer, S. Kenzelmann, and L. A. C. Lopes, “Vector control
of single-phase voltage-source converters based on fictive-axis emulation,”
IEEE Trans. Ind Appl., vol. 47, no. 2, pp. 831–840, Dec. 2011.
[8] B. Bahrani, S. Kenzelmann, and A. Rufer, “Multivariable-PI-based cur-
rent control of voltage source converters with superior axis decoupling
capability,” IEEE Trans. Ind. Electron., vol. 58, no. 7, pp. 3016–3026,
Jul. 2011. Li Peng (Member, IEEE) received the B.S.,
[9] B. Bahrani, M. Vasiladiotis, and A. Rufer, “High-order vector control of M.S., and Ph.D. degrees in power electronics
grid-connected voltage-source converters with LCL-filters,” IEEE Trans. from the Huazhong University of Science and
Ind. Electron., vol. 61, no. 6, pp. 2767–2775, Jun. 2014. Technology (HUST), Wuhan, China, in 1989,
[10] Z. Yao, L. Xiao, and J. M. Guerrero, “Improved control strategy for the 1992, and 2004, respectively.
three-phase grid-connected inverter,” IET Renew. Power Gener., vol. 9, In 1992, she joined the HUST, where she is
no. 6, pp. 587–592, Aug. 2015. currently a Full Professor of Power Electronics
[11] S. Zhou, J. Liu, L. Zhou, and Y. Zhang, “DQ current control of voltage with the School of Electrical and Electronic En-
source converters with a decoupling method based on preprocessed refer- gineering. Her research interests include power
ence current feed-forward,” IEEE Trans. Power Electron., vol. 32, no. 11, electronic conversion, its control and applica-
pp. 8904–8921, Jan. 2017. tions, modular power supply and parallel control
[12] X. Bao, F. Zhuo, Y. Tian, and P. Tan, “Simplified feedback linearization technique, renewable energy generation, power quality control, and
control of three-phase photovoltaic inverter with an LCL filter,” IEEE Modular Multilevel Converters (MMC) for High Voltage direct current
Trans. Power Electron., vol. 28, no. 6, pp. 2739–2752, Oct. 2013. (HVdc) applications.
[13] S. A. Khajehoddin, M. Karimi-Ghartemani, P. K. Jain, and A. Bakhshai,
“A control design approach for three-phase grid-connected renewable
energy resources,” IEEE Trans. Sustain. Energy, vol. 2, no. 4, pp. 423–432,
Jun. 2011.
[14] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Gen-
eralized design of high performance shunt active power filter with output
LCL filter,” IEEE Trans. Ind. Electron., vol. 59, no. 3, pp. 1443–1452,
Sep. 2012. Weibiao Wu was born in Jiangxi, China, in
[15] W. Wu, Y. Liu, Y. He, H. S. Chung, M. Liserre, and F. Blaabjerg, “Damping 1988. He received the B.S. degree in measure-
methods for resonances caused by LCL-filter-based current-controlled ment and control technology and instrument
grid-tied power inverters: An overview,” IEEE Trans. Ind. Electron., from the East China University of Technology,
vol. 64, no. 9, pp. 7402–7413, Jun. 2017. Fuzhou, China, in 2010, and the M.S. degree
[16] X. Wang, F. Blaabjerg, and P. C. Loh, “Grid-current-feedback active in control science and engineering from Cen-
damping for LCL resonance in grid-connected voltage-source converters,” tral South University, Changsha, China, in 2013.
IEEE Trans. Power Electron., vol. 31, no. 1, pp. 213–223, Jan. 2016. He is currently working toward the Ph.D. de-
[17] X. Li, J. Fang, Y. Tang, X. Wu, and Y. Geng, “Capacitor-voltage feed- gree in electrical engineering with the Huazhong
forward with full delay compensation to improve weak grids adaptability University of Science and Technology, Wuhan,
of LCL-filtered grid-connected converters for distributed generation sys- China.
tems,” IEEE Trans. Power Electron., vol. 33, no. 1, pp. 749–764, Feb. 2018. His research interests include control and analysis of grid-connected
[18] X. Ruan, X. Wang, D. Pan, D. Yang, W. Li, and C. Bao, Control Techniques power converter for photovoltaic generation systems and active power
for LCL-Type Grid-Connected Inverters. Singapore: Springer, 2018, ch. 2, filter application.
pp. 31–61.
[19] M. Liserre, F. Blaabjerg, and S. Hansen, “Design and control of an LCL-
filter-based three-phase active rectifier,” IEEE Trans. Ind Appl., vol. 41,
no. 5, pp. 1281–1291, Sep./Oct. 2005.
[20] S. Jayalath and M. Hanif, “Generalized LCL-filter design algorithm
for grid-connected voltage-source inverter,” IEEE Trans. Ind. Electron.,
vol. 64, no. 3, pp. 1905–1915, Sep. 2017. Ke Hu was born in Hunan, China, in 1995. He
[21] Q. Liu, L. Peng, Y. Kang, S. Tang, D. Wu, and Y. Qi, “A novel design and received the B.S. degree in electrical engineer-
optimization method of an LCL filter for a shunt active power filter,” IEEE ing in 2017 from the Huazhong University of
Trans. Ind. Electron., vol. 61, no. 8, pp. 4000–4010, Aug. 2014. Science and Technology, Wuhan, China, where
[22] L. Harnefors, “Modeling of three-phase dynamic systems using complex he is currently working toward the Ph.D. degree
transfer functions and transfer matrices,” IEEE Trans. Ind. Electron., in electrical engineering.
vol. 54, no. 4, pp. 2239–2248, Jul. 2007. His major research interests include control
[23] W. Li, X. Ruan, D. Pan, and X. Wang, “Full-feedforward schemes of grid and analysis of active power filter.
voltages for a three-phase-type grid-connected inverter,” IEEE Trans. Ind.
Electron., vol. 60, no. 6, pp. 2237–2250, Apr. 2013.

Authorized licensed use limited to: MALAVIYA NATIONAL INSTITUTE OF TECHNOLOGY. Downloaded on December 22,2020 at 05:59:24 UTC from IEEE Xplore. Restrictions apply.

You might also like