You are on page 1of 8

Measurement 113 (2018) 38–45

Contents lists available at ScienceDirect

Measurement
journal homepage: www.elsevier.com/locate/measurement

Monitoring power transformers oils deterioration using structured laser MARK


illumination planar imaging
Guy-Oscar Regnimaa, Amidou Betiéa,b, Thomas Koffia, Olivier K. Baguia, Issouf Fofanab,

Abaka Kouacoua, Jérémie Zoueua,
a
Laboratoire d’Instrumentation, Image et de Spectroscopie (L2IS), INPHB, DFR-GEE, B.P. 1093 Yamoussoukro, Cote d’Ivoire
b
Research Chair on Aging Power Equipment Infrastructure (ViAHT), Université du Québec à Chicoutimi, Chicoutimi, Québec, Canada

A R T I C L E I N F O A B S T R A C T

Keywords: Reliable quality assessments of oils in power transformers are important as they provide valuable information
Extinction coefficient regarding the proper functioning of transformers. Thus, an early and accurate diagnostic of power transformers
Structured illumination oils can prevent potential failures of transformers. In this paper, an imaging technique known as Structured Laser
Transformers oil diagnosis Illumination Planar Imaging (SLIPI) was used to monitor the extinction coefficient μe in various oil samples. The
Dense turbid media
proposed technique offers the advantage of extracting the light intensity contribution from singly scattered
photons and rejecting most of the light intensity from photons that have been scattered many times. This leads to
more accurate and reliable measurement of the extinction coefficient μe , in optically dense oil samples. The
variation of the extinction coefficient was therefore determined as a function of oil aging. The results demon-
strate that SLIPI is reliable as a practical measurement method for the diagnosis of power transformer oils and
present an attractive solution, alternative to the conventional methods such as Dissolved Decay Products,
Interfacial Tension and Turbidity.

1. Introduction very important to monitor the condition of the transformer by com-


parison with previous or suggested limit values. Physicochemical
Power transformers are key components for electrical energy gen- methods, such as the water content in oil [7–9], and the analysis of
eration and delivery [1]. Degraded oil in transformers affects the power dissolved gas in the insulation oil are also widely used. Various stan-
delivery and can lead to functioning failures. It is therefore critical to dards/methods have been developed for the interpretation of these
control and anticipate the proper functioning of power transformers by dissolved gas analysis. The most commonly used interpretation
monitoring their insulation. The diagnosis of transformers is thus vital methods are [10]: the IEEE C57.104–1991, Doernenberg, Rogers, IEC
for their proper maintenance and to improve their operating conditions, 60599 and the Duval’s triangle. The main problem concerning this
which ensure a reliable and efficient supply of electricity [2]. The oil technique lies in the determination of the limit values for simple gases.
content and condition tell us about the degradation and the Aging of However, gas chromatographs are very expensive. Other techniques
power transformers; therefore, it serves as diagnostic target as it con- such as the total acid number in oil [11], the interfacial tension (IFT)
tains approximately 70% of these diagnostic information [3–5]. Thus, [12] are also widely used. IFT test require experienced user and also,
the diagnosis of oils has long been the focus of several research projects, some precautions have to be taken as indicated in the American Society
ultimately leading to the development of various diagnostic tools. for Testing and Materials (ASTM), ASTM D971 in order to do mea-
Among these diagnostic tools, electrical-based methods allow to de- surements. Methods based on spectral analysis also exist, including
termining certain properties non-destructively such as the relative spectrophotometric absorption measurements of the oil samples. In this
permittivity and dissipation factor, the capacitance, polarization index, case, light that passes through the contaminated oil is attenuated by the
resistivity, dielectric strength, partial discharges, electrostatic charging absorbing elements [13]. The results obtained allow assessing the re-
tendency, etc [6]. The results of these measurements provide an lative amount of dissolved decay products (DDP) in oil. Furthermore, it
average value of the whole insulator volume, electrically and geome- should be noted that these different diagnostic methods mentioned
trically heterogeneous, and they do not characterize the status in a above are for the most part time consuming and very expensive.
specific point of the material. The role of these methods is nevertheless Moreover, regarding the methods based on spectral analysis, not all of


Corresponding author.
E-mail addresses: betie@yahoo.fr (A. Betié), Jeremie.zoueu@inphb.edu.ci (J. Zoueu).

http://dx.doi.org/10.1016/j.measurement.2017.08.019
Received 6 May 2017; Received in revised form 7 August 2017; Accepted 11 August 2017
Available online 23 August 2017
0263-2241/ © 2017 Elsevier Ltd. All rights reserved.
G.-O. Regnima et al. Measurement 113 (2018) 38–45

them provide knowledge about the degree of degradation of the oils


namely due to the high density of some of them. For spectrophotometry
using the Beer-Lambert-Bouguer within the limits of its application, it is
necessary to dilute the solution by a solvent thus modifying the initial
state of this solution. Otherwise, there are measurement errors due
mainly to multiple scattering of light [14].
In this article, a new assessment technique based on optical imaging
called SLIPI (Structured Laser Illumination Planar Imaging) is proposed
[14]. This technique could serve as a better alternative approach for the
diagnosis of oils in power transformers. The main advantage of the
technique is its capability in providing reliable results even within
optically dense liquids as recently demonstrated in [14]. Thus, one does
not need, for the dense samples, to perform dilution processes,. In ad-
dition to being fast and cost-effective, it has a simplified optical setup.
No need to shift the lines pattern to record images and it is suitable for
recording series of successive images. The most important advantage is
its ability to suppress multiple scattering effects on instantaneous
imaging in turbid media [14].
The SLIPI method consists in imaging, from the side, a modulated
light sheet crossing the turbid sample. Then, the intensity contribution
from multiple light is suppressed after post-processing of the recorded
image, and an exponential intensity decay is obtained as light crosses
the sample. By making a curve fit on this decay and using the Beer-
Lambert law, the extinction coefficient of the sampled liquid is obtained
[14]. Note that Bagui et al. [15] have used the SLIPI technique to es- Fig. 1. Overview of the transformer oil samples. The first range of transformer oils from
tablish ground coffee classification. S1 to S4 are pale yellow and are unaged (0 h). The second range of transformer oils from
S5 to S8 are brown and are those aged at 1000 h. Their appearance indicates bad con-
In this article, the extinction coefficient of transformer oils is mea-
dition. The last range from S9 to S12 are black and are those aged at 2000 h. Their
sured using the so-called single-phase SLIPI approach [14,16]. The re- appearance indicates extremely bad condition. (For interpretation of the references to
sults are compared with those obtained from the methods commonly color in this figure legend, the reader is referred to the web version of this article.)
used for the diagnosis of power transformer oils, such as Dissolved
Decay Products (DDP), Interfacial Tension (IFT) and Turbidity. A de-
2.2. Analysis of the oils using Turbidimetry
scription of the equipment and methodologies used is provided, fol-
lowed by the results and finally the discussion and conclusion are
Turbidity defines the disorder of a transformer’s oil caused by sus-
presented.
pended solids which are generally invisible to the naked eye. Usually,
an oil contains suspended solids, which consist of a large number of
particles of different sizes. The suspended particles are responsible of
2. Description of the investigated oils and standard analysis
the turbidity of the oil in the transformers. The instrument used to make
the measurements is the nephelometer 2100AN of the manufacturer
2.1. Description of the oils
HACH [17]. Measurement of turbidity has been performed according to
the ASTM D 6181 [18]. The turbidimeter uses the principle of the in-
The preparation of oil samples of transformer has been made in
teraction between an incident light and the suspended solids in oil
laboratory, at the University of Quebec in Chicoutimi, Canada. The si-
leading to several phenomena such as diffusion, reflection, absorption
mulation of the aging of the different oils is made by taking into ac-
and refraction. These suspended solids in oil, according to their size,
count the conditions of aging in the power transformers. Aging was
kind, shape, refractive index and its intensity cause a dispersion of the
carried out in a mechanical convection oven whose temperature was set
incident light in all directions [19]. The optical system consists of a
to 115 °C. To accelerate the aging, catalysts such as the powder of
tungsten filament lamp, lenses and apertures for concentrating light, a
copper (3 g per liter of oil) were used. Several samples were prepared.
detector placed at 90 degrees from the light detector, a forward scatter
The list of samples analysed is shown in the Table 1.
detector, a backscatter detector and a transmitted light detector. The
The paper behaves as a filter and decreases the dissolved decay
instrument measures the Turbidity using the complete set of detectors
products (see Fig. 1).
(ratio measurement). The microprocessor of the instrument uses a
mathematical calculation from the signals ratio of each detector. The
Table 1 advantages of using the ratio for measurements include excellent line-
Description of Transformer oil samples.
arity and stability of calibration and ability to measure turbidity in
Name of the samples Samples description presence of color.
The turbidity is expressed in NTU (Nephelometric Turbidity Unity).
Sample S1 0 h before test of stability As advantages, the Turbidimetry is very accurate and useful for mea-
Sample S2 0 h with 150 strains and strong electric discharges
suring very low turbidity (less than 5 NTU). However, there is a number
Sample S3 0 h with 0% of ratio paper-oil
Sample S4 0 h with 10% of ratio paper-oil of limitations: the high cost, high power needed and the fragility of the
Sample S5 1000 h before test of stability system [19].
Sample S6 1000 h with 150 strains and strong electric discharges Some guidelines for turbidity values of oils are given in Table 2.
Sample S7 1000 h with 0% of ratio paper-oil
The results of turbidity obtained for each sample of transformer oils
Sample S8 1000 h with 10% of ratio paper-oil
Sample S9 2000 h before test of stability as a function of aging duration are shown on Fig. 2.
Sample S10 2000 h with 150 strains and strong electric discharges In the analysis of the results obtained (Fig. 2), the increase of the
Sample S11 2000 h with 0% of ratio paper-oil values of turbidity reflects the aging of the power transformers oils
Sample S12 2000 h with 10% of ratio paper-oil [19,21]. According to the guidelines suggested for turbidity given in

39
G.-O. Regnima et al. Measurement 113 (2018) 38–45

Table 2
Guidelines suggested for turbidity [20].

Oil condition Turbidity (NTU)

Good oils 0–1


Proposition an oils 1–4
Marginal oils 4–10
Bad oils 10–30
Very bad oils 30–150
Extremely bad oils > 150

Fig. 3. Interfacial tension of each sample of transformer oils as a function of aging


duration. When the aging duration is high, the IFT for each sample of power transformer
oil decreases.

some precautions have to be taken as indicated in the ASTM D971 in


order to do measurements.
Some guidelines for IFT values of oils exist. Good and clean oils have
IFT number between 40 to 50 dynes per centimeter. For IFT value
below 25 dynes per centimeter, the oil is recommended to be reclaimed
because the oil is contaminated by sludge, which begins at around 22
dynes per centimeter [25].
Fig. 2. Turbidity of each sample of transformer oils as a function of aging duration. When The results of IFT values obtained for each sample of transformer
the aging duration is high, the turbidity for each sample of power transformer oil in- oils are shown on Fig. 3.
creases. Fig. 3 shows a decay of the values of IFT. Indeed, for in-service
transformer oil, the decrease of the values of IFT indicates the accu-
table 2 [20], classification of the oils samples has been made. At 0 h, all mulation of contaminants and/or oxidation products in the oil. One
the oil samples are in the range of “Good oils”. the oil ssamples with may notice that with increasing aging duration, the IFT value decreases
aging duration equals to 1000 h are “Marginal oils” and those aged at [19,21]. This value is constant and is equal to 15 dynes per centimeter
2000 h correspond to “Marginal or bad oils”. from 1500 h. Classification of transformer oils samples has been es-
tablished by using data reported in [24]. At 0 h, all the oils samples
have IFT values higher than 25 dynes per centimeter. They are refereed
2.3. Analysis of the oils using interfacial tension as “Good oils”. The oils with aging duration at 1000 h and 2000 h have
IFT values lower to 22 dynes per centimeter. They are classified as “bad
The interfacial tension (IFT) allows evaluating the oxidation degree quality oils” and reclamation is recommended .
of the mineral oils, by detecting the presence of polar compounds [22].
It represents the force in dynes per centimeter required to rupture a
platinum ring at the interface between the oil and distilled water [23]. 2.4. Analysis of the oils using dissolved decay products
Measurement of the interfacial tension to assess the condition of the
liquid insulation is performed according to the ASTM D971-12 [12] The measurement of the relative quantity of Dissolved Decay
using a surface tensiometer. The instrument used is a DuNouy type from Products in oil or DDP is carried out by spectrophotometry UV/VIS
Fisher Scientific brand tensiometer which uses a plane ring of Pla- (ultraviolet/visible) according to the ASTM 6802. The instrument used
tinum/iridium alloy. The measurement shall be made within 60 s of for measurements is a Thuramed T60 UV/Vis spectrophotometer. The
formation of the interface. When certain contaminants such as oxida- spectrophotometer sheds a monochromatic incident light I0 through a
tion products are present in the oil, the strength of the oil film is length L (the length of the cuvette) of the oil sample to test and mea-
weakened, requiring less tension to break the film. For oils in service, a sures the absorbance A (size linked to the quantity of light absorbed by
decreasing value of IFT points out the accumulation of contaminants, the solution). From this study one determines the absorbance A and
oxidation products or both. It is a measurement indicating the presence transmittance T defined respectively by the Beer-Lambert-Bouguer law:
of oxidation products that can attack the solid insulation and influence I
the cooling of the transformer. The more the oil degrades, the more this A = −logT and T = = e−μe L
I0 (1)
value has a tendency to decrease.
The IFT test provides information on polar contaminants and oxi- where I is the intensity transmitted from the light and µe is the ex-
dation products. However, due to the high hydrophilic nature of the oil, tinction coefficient.
the interfacial tension test may not be very sensitive to changes in the For each wavelength, the absorbance of each power transformer oil
fluid quality [24]. Moreover, IFT test requires trained person and also, is measured and the data collected are used to plot the absorbance

40
G.-O. Regnima et al. Measurement 113 (2018) 38–45

Table 3 with respect to those of 0 h (fresh oils).


Guidelines for Dissolved Decay Products (DDP) [20].

Oil condition DDP (a.u) 3. Single-phase SLIPI experiment


Good oils 0–10
Proposition an oils ± 10–25 3.1. Experimental setup
Bad oils 25–50
Very bad oils 50–300 The SLIPI technique has been developed in 2008 by Edouard
Extremely bad oils > 550 Berrocal and Elias kristensson [26,27]. This technique, which has been
both demonstrated by simulation and by experimentation, possesses a
large capacity for the suppression of multiple light scattering in the
curve A (on the ordinate) as a function of the Wavelength λ (on the
planar spray imaging, thereby strongly improving the visualization
abscissa). The graph thus obtained constitutes the UV/visible spectrum.
[28–31]. With the conventional method, there is a multitude of scat-
The numerical integration of the surface below the absorbance curve
tering in all directions which seriously affect the expected results. The
allows determining the relative amount of the Dissolved Decay Products
main motivation for developing this new technique is to eliminate
(DDP: peroxides, Aldehydes, ketones and organic acids) in liquid sam-
blurring effects due to multiple scattering of light in order to obtain
ples.
qualitative and quantitative information such as the extinction coeffi-
This technique is used routinely for the quantitative study of organic
cient [32]. While the transmission measurement records the light in-
molecules (molecules composed essentially of carbon and hydrogen)
tensity of a single beam crossing the sample of interest (where the in-
and functional groups by measuring the absorbance of the oil samples.
itial and final intensities are recorded), SLIPI makes the imaging of the
While being very useful, these measurements are, unfortunately, no
spatially modulated light sheet. (from 90° angle).
longer valid when applied to optically dense scattering media such as
In this contribution, the single-phase SLIPI approach [14,16] is used
turbid liquids. This limitation is due to both the strong reduction of
for the measurements of the extinction coefficients. Fig. 2 shows a
desired unscattered light and the large increase of unwanted scattered
schematic of the experimental setup. A sample of transformer oil into a
photons reaching the detector. Using more sensitive sensors or brighter
silica cuvette, is illuminated by a spatially modulated laser sheet. The
light sources can compensate the reduction of the desired signal.
light sources consist of two continuous wave (CW) laser beams of
However, the effects of multiple light scattering are more challenging to
450 nm and 638 nm, which are recombined along the same optical path
account for [14].
using a dichroic mirror. One laser is activated at a time and a neutral
Table 3 highlights the guidelines for DDP values, expressed in ar-
density wheel is used to adjust the incident irradiance in order to op-
bitrary unit (a.u.).
timize the signal to noise ratio, while avoiding saturation. The laser
The results of DDP obtained for each sample of transformer oils as a
sheet is performed by means of a succession of spherical and cylindrical
function of aging duration are shown on Fig. 4.
lens. Subsequently, a reflecting mirror is placed at 45° which returns the
Concerning the evolution of the DDP in the power transformer oils
laser sheet on the sample after passing through a Ronchi grating (2 lines
seen on Fig. 4, there is a general increase in the values of the areas
pairs/mm) creating intensity modulation. The images are recorded
calculated under the curves as the aging duration increases from 0 h to
using a 14 bit Electron Multiplying CCD camera, Luca (r) from Andor
2000 h. The increase of the values of DDP reflects the aging of the
with 1002 × 1004 pixels and the final image is the results of the ac-
power transformer oils [19,21].
cumulation over 200 single-shot images. This camera located at 90°,
From the analysis of the results of the physicochemical techniques
perpendicular to the direction of propagation of the laser sheet, cap-
used, it emerges that power transformer oils undergo a rapid dete-
tures images of the modulation created into the cuvette. The camera
rioration as aging duration increases. Thus, oils aged at 2000 h are
objective is set to F# = 5.6 and the exposure time ranges between
more degraded than those at 1000 h which in their turn are degraded
0.002 and 0.015 s to optimize the dynamic range for each sample of oils
concentration. The camera linked to a computer records the different
images obtained. Fig. 5 is the schematic of the experimental set up.

3.2. Single-phase SLIPI post-processing

The single-phase SLIPI approach used in the current study and


shown in [14] is based on an analytical tool known as lock-in detection
[33]. Lock-in detection is most often associated with analysis of tem-
porally varying signals but it works equally well for spatially modulated
signals. To explain the principle of lock-in detection, consider a 1D
signal, I(x), with a superimposed periodic variation of an amplitude IS
in space:

I (x ) = IS sin(2πνx + ϕ) + IMS (x ) (2)


−1
where ν equals the spatial frequency (mm ) of the modulation and ϕ is
the spatial phase, which is unknown. The IMS term represents any un-
wanted non-modulated intensity contribution also being detected, such
as, multiple light scattering or any surrounding light background. The
purpose of the lock-in analysis is to extract IS and reject IMS. To achieve
this end, the signal I is multiplied with two reference signals R1 and R2,
created computationally, that have a relative phase shift of π/2 :
Fig. 4. Dissolved Decay Products of each sample of transformer oils as a function of aging R1 (x ) = sin(2πνx ) and R2 (x ) = cos(2πνx ) (3)
duration. When the aging duration is high, the quantity of DDP for each sample of power
transformer oil increases.
Multiplying I with these reference signals yields:

41
G.-O. Regnima et al. Measurement 113 (2018) 38–45

Fig. 5. SLIPI optical set-up: After expanding the


incident laser beam, a light sheet is formed using
a cylindrical lens focusing the beam into the
cuvette. The light sheet is modulated just prior to
enter the cuvette containing the oil sample by a
Ronchi grating of 2 lp/mm frequency. The images
are recorded using an EM−CCD camera.

1
I1 (x ) = IS (cos(ϕ)−cos(4πνx + ϕ)) + IMS sin(2πνx )
2 (4)

1
I2 (x ) = IS (sin(ϕ) + sin(4πνx + ϕ)) + IMS cos(2πνx )
2 (5)

The frequency analysis of I1 and I2 reveals three components; (1) a


DC component, (2) one modulated with 2ν and (3) one modulated with
ν. The two latter components can be suppressed by means of a low-pass
filter in the Fourier domain, with a cut-off frequency less than ν, re-
sulting in the following expressions:
∼ 1∼ ∼ 1∼
I1 (x ) = IS cos(ϕ) and I2 (x ) = IS sin(ϕ)
2 2 (6)

where the tilde assignment indicates the applied frequency filtering.



From these, IS can finally be extracted by calculating:
∼ ∼ ∼
IS = 2 (I1)2 + (I2)2 (7)

An illustration of the single-phase SLIPI process is given in Fig. 6.


From a modulated image, the amplitude of the modulation is extracted
using Eqs. (3–7). The modulated component, IS, corresponds to the
single light scattering which reduces exponentially with distance. By
applying an exponential fit to IS the extinction coefficient, µe, can be
directly extracted as stated in the Beer-Lambert-Bouguer law (see Eq.
(1)).

4. Results and discussion

The experimental results of SLIPI measurements are presented from


Figs. 7–10 for the different samples of power transformers oils. The
values of the extinction coefficients obtained at the different wave-
lengths (450 nm, 638 nm) are reported on Figs. 9 and 10.
The results of the extinction coefficients values obtained from the
curves on Fig. 9 are reported in the Fig. 11. These curves show how the
extinction coefficients of power transformers oils change as a function
of aging duration.
In regard to the results obtained with SLIPI technique (Fig. 9), for an
Fig. 6. Principle of single-phase SLIPI. The example shows the signal from a structured
in-service transformer oil (2000 h and 1000 h), the exponential decay
laser sheet, with cross-sections extracted from two different depths, marked as A and B.
of the light intensity as function of distance through the cuvette (a and Notice the decrease in amplitude from column A to B. The 1 D Fourier transforms of
b respectively) is more pronounced than the exponential decay of light curves A and B, shows the reduction in strength of the 1st order peak (modulation fre-
intensity as function of distance through the cuvette (c) obtained for the quency). This frequency is then isolated using frequency filtering (red area) after applying
fresh oils (0 h). These observations point out the effect of transformers the lock-in algorithm. Finally, the exponential decay is revealed, as shown in the SLIPI
oils aging. In fact, its express the fact that SLIPI technique is able to see image and related curve IS. (For interpretation of the references to color in this figure
legend, the reader is referred to the web version of this article.)
the effect of aging on power transformers oils.
From the presented results on Fig. 10, one can divide for each power

42
G.-O. Regnima et al. Measurement 113 (2018) 38–45

Fig. 7. Images of the structured light sheet


crossing the cuvette containing the samples
S5, S6, S7 and S8 of power transformer oils
for 450 nm illumination wavelength. The
corresponding SLIPI images are compared in
the figures below. As these oils are mostly
absorbing, the blurring effects due to mul-
tiple scattering are less apparent. However
there is still some remaining undesired
scattered light which must be suppressed
using SLIPI. The resulting SLIPI images de-
pict, thus, the correct light extinction where
an exponential fitting of the intensity decay
provide the corresponding extinction coeffi-
cient.

transformer oil samples S9, S10, S11 and S12, the extinction coeffi- oils (0 h), the extinction coefficients are very low which show that they
cients obtained for 450 nm and 638 nm illumination wavelengths such are not deteriorated. When the oils are in service, they change their
that R = μe (450 nm)/ μe (638 nm) . R corresponds to the ratio of the ex- appearance with the time and become more and more optically dense.
tinction cross-sections (σe(450 nm)/σe(638 nm)). This ratio calculated Moreover, there is an increase in the concentration of chromophores in
for each sample is more or less equal to R = 26. It value is constant and the samples. This aging is reflected in some research works by an in-
is, therefore, an optical parameter characterizing the probed liquid. crease of the absorbance as a function of the aging duration or wave-
This implies that measurements are reliable. It means that power length [34,35]. Furthermore, there is a relationship linking the absor-
transformer oil particles diffuse and absorb the blue light 26 times more bance to the extinction coefficient. This relationship is given by the Eq.
than the red light. Thus from this experimentation, behave power (8):
transformer oil when it is in interaction with a radiation can be assess. It
μe = A. ln(10)/ L (8)
can be observed that it would be better to use red laser at 638 nm il-
lumination wavelength to perform measurements in the case of power
where L is equal to 16 mm, corresponding to the length of the cuvette
transformer oils with aging duration superior or equal to 2000 h.
used in the measurements.
The curves in Fig. 11 show for 450 nm illumination wavelength
A is the absorbance value.
used, an increase in the values of the extinction coefficients of different
From Eq. (8), it is clear that if the absorbance increases, the ex-
power transformers oil samples when the aging duration increases. By
tinction coefficient will increase too. Thus, the values of the IFT, DDP
comparing curves, the extinction coefficients of the in-service trans-
and turbidity measurements agree with the obtained results. The in-
former oils (2000 h and 1000 h) are higher compared to the one of fresh
service transformer oils (2000 h and 1000 h) have high extinction
oils (0 h). The increase of this optical parameter indicates that power
coefficients than the new oil (0 h). So the SLIPI has the great ability to
transformers oils are subjected to an aging. In fact, in the case of fresh
analyse the oil condition to large scale.

Fig. 8. Images of the structured light sheet


crossing the cuvette containing the samples
S9, S10, S11 and S12 of power transformer
oils for 638 nm illumination wavelength.
The corresponding SLIPI images are com-
pared in the figures below. As these oils are
mostly absorbing, the blurring effects due to
multiple scattering are less apparent.
However there is still some remaining un-
desired scattered light which must be sup-
pressed using SLIPI. The resulting SLIPI
images depict, thus, the correct light ex-
tinction where an exponential fitting of the
intensity decay provide the corresponding
extinction coefficient.

43
G.-O. Regnima et al. Measurement 113 (2018) 38–45

1 Fig. 9. Curves obtained by vertically integrating the SLIPI


2000 hours S11 µe = 1.989 mm-1
image results of the power transformer oils for 2000 h (a),
2000 hours S12 µe = 2.011 mm-1 1000 h (b) and 0 h (c) for 450 nm illumination wavelength.
Normalized intensity [au]

0.8 2000 hours S10 µe = 1.998 mm-1 The exponential decay of the light intensity as function of
distance through the cuvette is obtained here and the ex-
2000 hours S9 µe = 1.966 mm-1
tinction coefficient has been deduced from those decays.
(c) 1000 hours S7 µe = 0.406 mm-1
0.6
1000 hours S8 µe = 0.387 mm-1
(a) 1000 hours S6 µe = 0.537 mm-1
0.4 1000 hours S5 µe = 0.513 mm-1

0 hour S1 µe = 0.053 mm-1

0.2 0 hour S4 µe = 0.064 mm-1


(b) 0 hour S3 µe = 0.061 mm-1

0 hour S2 µe = 0.059 mm-1


0
0 2 4 6 8 10 12 14
Distance [mm]

For 450 nm illumination wavelength (Fig. 9), the extinction coeffi-


cient of fresh oils is between 0.053 mm−1 and 0.064 mm−1. For those
at 1000 h, the extinction coefficient is between 0.387 mm−1 and
0.537 mm−1. Finally, at 2000 h, it is between 1.966 mm−1 and
2.011 mm−1.
The results of the accuracy measurements have been obtained by
performing for the same sample of transformer oil for 450 nm illumi-
nation wavelength, about ten measurements of the extinction coeffi-
cient. The extinction coefficient measurement for each sample in-
cluding the deviation of the measurements are given in Table 4. Table 4
summaries also the guidelines for extinction coefficients values at
450 nm wavelength, expressed in mm−1.
These different intervals found will constitute therefore, the inter-
vals of decision which gives us the state of good or bad quality of power
transformer oils.
The increase of the extinction coefficients values determined by
means of SLIPI reflecting the level of degradation of oils, justifies the
evolution of the different physicochemical parameters determined. By
comparing both the different results obtained (SLIPI technique and
physicochemical methods), a good agreement was observed.
Besides, note that SLIPI technique has been able to detect a change
in the value of the extinction coefficient around by 0.1 [14]. In the case
of aging oils without color large change, SLIPI has demonstrated its
Fig. 11. Evolution of the extinction coefficient of each sample of transformer oils as a
ability in detecting a change in the value of extinction coefficient which function of aging duration at λ=450 nm illumination wavelengths.
approach 0.01. This order of magnitude was obtained by making the
subtraction between the extinction coefficients for each aging duration.
5. Conclusion
It is therefore a technique which is able to detect the slightest aging
effect of power transformer oils.
In this article, a new technique of optical imaging called SLIPI has
been investigated. Since SLIPI technique gives excellent results, it can

1 Fig. 10. Curves obtained by vertically integrating the SLIPI


[ 450 nm ] image results of the power transformer oils for 2000 h for
2000 hours S11 µe = 1.989 mm-1 450 nm (a) and 638 nm (b) illumination wavelengths. The
exponential decay of the light intensity as function of dis-
Normalized intensity [au]

0.8
2000 hours S12 µe = 2.011 mm-1 tance through the cuvette is obtained here and the extinction
(b) coefficient has been deduced from those decays.
2000 hours S10 µe = 1.998 mm-1
0.6
2000 hours S9 µe = 1.966 mm-1

[ 638 nm ]
0.4 2000 hours S11 µe = 0.076 mm-1

(a) 2000 hours S12 µe = 0.079 mm-1


0.2
2000 hours S10 µe = 0.078 mm-1

2000 hours S9 µe = 0.075 mm-1


0
0 2 4 6 8 10 12 14
Distance [mm]

44
G.-O. Regnima et al. Measurement 113 (2018) 38–45

Table 4 [12] American Society for Testing and Materials (ASTM), D 971-12 Standard test method
Guidelines for extinction coefficient values at 450 nm. for interfacial tension of oil against water by the ring method, vol. 10.03, 2012.
[13] N. Thakur, O.P. Rahi, Transformer diagnosis using UV-spectrophotometer, Int. J. of
Electron. Signals Syst., www.interscience.in, 2015 (accessed 18.05.15).
Oil condition Extinction coefficient (mm−1)
[14] G.O. Regnima, T. Koffi, O. Bagui, A. Kouacou, E. Kristensson, J. Zoueu, E. Berrocal,
Quantitative measurements of turbid liquids via structured laser illumination planar
Good oils 0–0.0640.006
imaging where absorption spectrophotometry fails, Appl. Opt. 56 (13) (2017)
Proposition an oils 0.064 ± 0.006–0.387 ± 0.092 3929–3938, http://dx.doi.org/10.1364/AO.56.003929.
Marginal oils 0.387 ± 0.092–0.537 ± 0.014 [15] O.K. Bagui, K.A. Kaduki, E. Berrocal, J.T. Zoueu, Structured laser illumination
Bad oils 0.537 ± 0.014–1.996 ± 0.024 planar imaging based classification of ground coffee using multivariate chemo-
Very bad oils 1.966 ± 0.024–2.011 ± 0.02 metric analysis, Appl. Physics Research 8 (3) (2016) 32–44, http://dx.doi.org/10.
Extremely bad oils > 2.011 ± 0.02 5539/apr.v8n3p32.
[16] E. Berrocal J. Johnsson E. Kristensson M. Aldén Single scattering detection in turbid
media using single-phase structured illumination filtering. J. Eur. Opt. Soc-RAPID-7
2012.
be used to serve as a tool for diagnosis of the state of the power [17] HACH. 2100AN Laboratory Turbidimeter Manuel d'Utilisation, 2nd ed., http://
transformers oils for their deterioration and aging. It is a non-destruc- www.hach.com/2100an-laboratory-turbidimeter-epa-115-vac/productdownloads?
tive technique with no need to perform dilution like the UV–visible id=7640450972, (accessed 06.06.15).
[18] American Society for Testing and Materials (ASTM), D 6181 – 03 Standard test
spectroscopy technique. The results obtained have been compared to
method for measurement of turbidity in mineral insulating oil of petroleum origin,
existing physicochemical techniques and were found very satisfactory. in: Electrical insulation and electronics, USA, ASTM, 2003, p. 5.
The technique of SLIPI offers a real opportunity and a better alternative [19] J.S. N’cho, I. Fofana, Y. Hadjadj, A. Beroual, Review of physicochemical-based di-
for diagnosis of oils compared to other techniques which are time agnostic techniques for assessing insulation condition in aged transformers,
Energies 367 (9) (2016), http://dx.doi.org/10.3390/en9050367 10.
consuming and expensive. [20] I. Fofana, A. Bouaicha, M. Farzaneh, J. Sabau, D. Bussières, Decay Products in the
Liquid Insulation of Power Transformers, IET Electr. Power Appl. 4 (2010)
Acknowledgement 177–184.
[21] K.S. Kassi, 1. Fofana, F. Megnefi, A. Betie, Z. Yeo, Decay products in mineral oil: a
comparative study between hybrid and conventional insulation systems, IEEE
The authors would like to thank the International Science Program International Conference on Liquid Dielectrics, Bled, Slovenia, June 30 - July 3,
(ISP) of Uppsala University for the donation of equipment and financial 2014.
[22] American Society for Testing and Materials (ASTM), D 971 – 99a standard test
support as well as the TWAS. The authors would like to thank Assoc. method for interfacial tension of oil against water by the ring method1, in:
Prof. Edouard Berrocal for useful discussions and valuable guidance. Electrical insulating liquids and gases, electrical protective equipment, USA, ASTM,
1999, p. 3.
[23] American Society for Testing and Materials (ASTM), Standard Test Method for
Conflicts of interest Interfacial Tension of Oil against Water by the Ring Method. D 971, http://www.
biolinscientific.com/zafepress.php?url=%2Fpdf%2FAttension%2FApplication
The authors declare no conflict of interest. %20Notes%2FAT_AN_10_astm.pdf (accessed 12.02.16).
[24] J.S. N'Cho, I. Fofana, A. Beroual, T. Aka-Ngnui, J. Sabau, The gassing tendency of
various insulating fluids under electrical discharge, IEEE Trans. Dielectr. Electr.
Appendix A. Supplementary material Insul. 18 (5) (2011) 1616–1625.
[25] FIST Volume 3–5, Maintenance of Liquid Insulation: Mineral Oils and Askarels,
Supplementary data associated with this article can be found, in the http://www.worldcat.org/title/maintenance-of-liquid-insulation-mineral-oils-and-
askarels/oclc/45032750, 1992, (accessed 10-01-16).
online version, at http://dx.doi.org/10.1016/j.measurement.2017.08. [26] E. Berrocal, Multiple scattering of light in optical diagnostics of dense sprays and
019. other complex turbid media, PhD. Dissertation, School of Engineering, Cranfield
University, England, 2006.
[27] E. Kristensson, Structured laser illumination planar imaging SLIPI. Applications for
References spray Diagnostics, PhD. Dissertation, Division of combustion physics, Lund
University, Sweden, 2012.
[1] H. Boyer, M. Norbert, R. Philippe, Cours de construction du matériel électrique- [28] E. Kristensson, E. Berrocal, M. Richter, S.G. Pettersson, M. Aldén, High-speed
Tome 3, La Capitelle ed., France, 1981. structured planar laser illumination for contrast improvement of two-phase flow
[2] J. Zhang, X. Qian, Y. Zhou, Application of extension neural network in transformer images, Opt. Lett. 33 (2008) 2752–2754.
fault diagnosis, J. Comp. Eng. Appl. 47 (7) (2011) 8–11. [29] E. Berrocal, E. Kristensson, M. Richter, M. Linne, M. Aldén, Application of struc-
[3] S.D. Myers, Presentation on transformer oil testing, http://www.slideshare.net/ tured illumination for multiple scattering suppression in planar laser imaging of
JoeloRoss/transformer-oil-testing-sd-myers, 2016 (accessed 11.10.16). dense sprays, Opt. Express 16 (22) (2008) 17870–17881, http://dx.doi.org/10.
[4] L.O. Séraphin, Bien-fondé des analyses d’huiles pour le diagnostic d’état des 1364/OE.16.017870.
transformateurs immergés. http://www.laboratoireoksman.com/Analyse_ [30] E. Kristensson, E. Berrocal, M. Richter, M. Aldén, Nanosecond structured laser il-
transformateur.pdf, 2016 (accessed 11.10.16). lumination planar imaging for single-shot imaging of dense sprays, Atomization
[5] I. Fofana, Insulating oil - another vital part of transformer body, In the IEEE seminar Spray 20 (2010) 337–343.
Section DEIS Chapter, Ottawa-Montreal, Canada, June 17th 2010. [31] M. Storch, Y. Nath Mishra, M-. Koegl, E. Kristensson, S. Will, L. Zigan, E. Berrocal,
[6] R. Fournié, Les isolants en électrotechnique: Essais, Mécanisme de dégradation, Two-phase SLIPI for instantaneous LIF and Mie imaging of transient fuel sprays,
Applications industrielles, Eyrolles ed., France, Paris, 1990. Opt. Lett. 41 (2016) 5422–5425.
[7] Y. Du, Moisture equilibrium in transformer paper-oil systems, IEEE Electr. Insul. [32] E. Kristensson, E. Berrocal, M. Aldén, Extinction coefficient imaging of turbid media
Mag. 15 (1) (1999) 11–20. using dual structured laser illumination planar imaging, Opt. Lett. 36 (2011)
[8] T.V. Oommen, On-line moisture sensing in transformers, in: Proceedings of the 1656–1658.
electrical electronics insulation conference, Boston, USA, 7-10 October 1991. [33] M.L. Meade, Advances in lock-in amplifiers, J. Phys. E. Sci. Instrum. 15 (1982)
[9] B.K. Gupta, Direct determination of moisture in solid oil-paper insulation, in: 395–403.
Conference record of IEEE international symposium on electrical insulation, [34] J.S. N’cho, A. Beroual, I. Fofana, T. Aka-Ngnui, J. Sabau, Verification of Oil
Ontario, Canada, 7–10 June 1998. Reclamation Process by Turbidity and Spectrophotometry Measurements, J. Energy
[10] T.K. Saha, Review of modern diagnostic techniques for assessing insulation condi- Power Eng. 6 (2012) 703–712.
tion in aged transformers, IEEE Trans. Dielectr. Electr. Insul. 10 (5) (2003) [35] R. Shoureshi, V. Permana, R. Wood, R. Swartzendruber, M. Simoes, Intelligent
903–917. transformer monitoring system utilizing neuro-fuzzy technique approach, power
[11] American Society for Testing and Materials (ASTM), Annual Book of ASTM systems engineering research center, school of engineering and computer science,
Standards, in: Electrical insulation and electronics, 2005, p. 577. University of Denver, USA, 04-27 July 2004.

45

You might also like