You are on page 1of 16

Installation

Operation
Maintenance
ODYSSEY
Light Commercial
Split System 5-20 Tons
TTH Model 50 Hz

Air Handling Models


TTH 060 BD
TTH 075 BD
TTH 100 BD

March 2001 TTH-IOM01-EN


Model Nomenclature

Air Handling Unit


Model Nomenclature

TWE 120 A D O O B A

TTH = Cooling Only Air Handling Unit Service Digit


(Horizontal Discharge) A = First Parts list
TWE = Cooling Only and Heat Pump Minor Design Sequence
Air Handling Unit (Convertible) A = First Design Sequence
B = Second Design Sequence
Nominal Gross Cooling Capacity (MBh)
Factory Installed Options # 2
060 = 60 MBh
O = No Options
075 = 75 MBh For TTH model
A = Discharge Plenum
100 = 100 MBh
B = Return Air Grille (TWE model only)
C = Discharge Plenum and Return Air Grille
120 = 120 MBh
(TWE model only)
180 = 180 MBh For TWE model
S = Special request to be defined and approved
240 = 240 MBh
Major Design Sequence Factory Installed Options # 1
A = First Design O = No Options
B = Second Design A = 1 HP Fan Motor
B = 2 HP Fan Motor
C = 3 HP Fan Motor
D = 5 HP Fan Motor
E = 7.5 HP Fan Motor, 380/3/50
F = 7.5 HP Fan Motor, 415/3/50

Electrical Characteristics
D = 380-415/3/50

2
© American Standard Inc. 2000 TTH-IOM01-EN
Contents

Model Nomenclature 2
General Information 4
Unit Installation 5
General Data 7
Electrical Wiring 8
Dimensional Data 10
Operation and Start-up 12
Maintenance 13
Trouble Shooting 14

TTH-IOM01-EN 3
General Information

Foreword Note
These instructions do not attempt “Warnings” and “Cautions” appear
to cover all variations in systems, at appropriate places in this manual.
nor to provide for every possible Your personal safety and the proper
contingency to be met in connection operation of this machine require
with installation. Should further that you follow them carefully. The
information be desired or should manufacturer assumes no liability for
particular problems arise which are installations or servicing performed by
not sufficiently covered for the unqualified personnel.
purchaser’s purpose, the matter
should be referred to the Handling
manufacturer. The unit will be supplied with a
shipping base and protective
Reception packaging over the unit casing. The
On arrival, inspect the unit before packaging should be kept on the unit
signing the delivery note. Specify any during handling or storage on site.
damage on the delivery note, and
send a registered letter of protest to If it is necessary to remove the
the last carrier of the goods within 72 packaging for inspection prior to
hours of delivery. Notify the local Trane completion of on site handling, retain
Sales Office at the same time. The unit packaging parts and reapply them by
should be totally inspected within 15 tapping in position to prevent damage
days of delivery. If any concealed to the casing. The unit as supplied has
damage is discovered, stop unpacking a shipping base which is suitable for
the shipment. Take photos of the handling by a fork lift truck. If it is
damage material if possible. Notify the necessary to sling the unit, use
carrier immediately by phone and spreader bars under the shipping
registered mail. Notify the local Trane base.
Sales Office. Concealed damage must
be reported within 15 days of delivery. Ensure that ropes do not cause
Check the unit nameplate to confirm abrasion to the surface of the unit.
that the proper unit was shipped.
Available power supply must be Warning
compatible with electrical Open and lock unit disconnect to
characteristics specified on prevent injury or death from electric
component nameplates. shock or contact with moving parts
before attempting any installation or
General Information maintenance.
This manual covers the Installation,
Operation, and Maintenance of the Inspection
TTH060B, TTH075B, and TTH100B, Inspect material carefully for any
single circuit air handlers. These new shipping damage. If damaged, it must
air handler models are completely be reported to, and claims made
redesigned to incorporate a single against the transportation company.
slab coil assembly, improved Replace damaged parts with autho-
application flexibility, servicing and rized parts only. Check the unit
maintenance accessibility, and an nameplate to confirm that the proper
improved accessory line. They are unit was shipped. Available power
horizontal type with special drain supply must be compatible with
pan (for TTH model). electrical characteristics specified on
component nameplates.

4 TTH-IOM01-EN
Unit Installation

Warning Table 1 - Unit weight and corner weight (Lbs)


Open and lock unit disconnect to
prevent injury or death from electric Net weight Corner weight (Lbs)
shock or contact with moving parts
Model (Lbs) Maximum #1 #2 #3 #4
before attempting any installation or
maintenance. TTH060B 194 46 45 52 51
TTH075B 205 49 47 55 54
The general location of the air handler
is normally selected by the architect, TTH100B 304 72 70 82 80
contractor, and/or buyer. For proper
installation, the following items must The unit can be moved using a forklift For servicing and routine
be considered. of suitable capacity. For lifting the unit maintenance, provide access to the
into an elevated mounting position, unit through removable panels in the
1. Available power supply must agree run lifting straps or slings under the ceiling see Figure 1b.
with electrical data on component unit and attach securely to the lifting
nameplate. device. Use spreader bars to protect
2. Air handler shipped wired for 380 the unit casing from damage. Test lift
Volt applications. the unit to determine proper balance Min Min
3. If external accessories are installed and stability. 850 mm. 850 mm.
on the unit, additional clearance
must be provided. Caution Figure 1b
4. All duct work should be properly Use spreader bars to prevent straps
insulated to prevent condensation from damaging the unit, install the (b)Location, Mounting and
and heat loss. bars between lifting straps, both Positioning
underneath the unit and above the Before installing any unit make sure
Note unit. This will prevent the straps from proper preparation has been made at
It is recommended that the outline crushing the unit cabinet or damaging each unit locating for piping and
drawings be studied and dimensions the unit finish. electrical connections.
properly noted and checked against
selected installation site. Installation Considerations The unit should be installed in horizon-
For proper installation and operation, tal applications only. Suspend the unit
Important check each of the following before using the factory-provided threaded
If adding external accessories to the mounting the units. mounting holes on bottom of the unit.
unit, additional clearance must be This is usually accomplished through
considered for the overall space (a) Space Requirement and the use of spring or rubber isolators.
needed. Clearances Which are to be furnished by the
Allow adequate space for the unit and installer see Figure 2.
Lifting Recommendations free air or service clearance. See
Before preparing the unit for lifting, Figure 1a and 1b.
the center of gravity should be W4
determined for lifting safety.
Because of the placement of internal
components, the unit weight may be
unevenly distributed. Approximate to
total unit weight and corner weight mm
.
50
.8
are given in Table 1. MI
N W2

Warning W3
On site Lifting Equipment must be
capable of lifting the weight of the unit m.
M 0m W1
IN
.8 85
N.
with an adequate safety factor. The 50
mm MI
.
use of under-capacity lifting devices
Figure 2
may result in personal injury ordeath Figure 1a
Position of corner weight
and cause damage to the unit.
TTH model

TTH-IOM01-EN 5
Unit Installation

Check that the supporting structure (g) Electrical Connections


is strong enough to support unit
weights. 101 mm min. Warning: when installing or servicing this
Materials equipment, always exercise basic safety
Align the mounting holes with 1 Tea precautions to avoid the possibility of
1 Plug
structural support and secure 70 mm min. 3 Street Ell
electric shock that could result in severe
suspension rods, to the structure, to 1 140 mm Nipple personal injury or death.
the air handler cabinet. If the mounting 1. All electrical lines, sizing,
holes locations do not permit proper protection and grounding must be
alignment with existing structure, it Figure 3 in accordance with the National
may be necessary to field fabricate 1 inch (25.4 mm) Galvanized Electric Code and local codes.
cross members on existing structure Pipe and Fittings. 2. If conduit is used, isolate whenever
beams. vibration transmission may cause a
noise problem within the building
All units must be mounted level to structure.
assure proper drainage and 3. Ensure all connections are tight
101 mm min.
operation. Materials and no wires exposed.
1 Tea 4. All accessories must be installed
1 Plug
(c) Coil Piping Connections and wired according to the
70 mm 3 90 Ell
All refrigerant piping connection are min. 1 152 mm Nipple instructions packaged with that
made outside the unit. 2 50 mm Nipple accessory.
1 1" NPT to PVC
or copper adapter
Caution Installation Checklist
• Protect adjacent surfaces from Figure 4 Complete this checklist once the
heat damage, when brazing 1 inch (25.4 mm) PVC or Copper unit is installed to verify that all
around the air handler. Tubing and Fittings. recommended procedures have been
• These air handlers are shipped accomplished before the system is
with a holding charge of N2 until (e) Filters started. Operational checks cannot
refrigerant lines are ready to be These air handlers are shipped with 1" be performed until the system
connected. washable filters installed in the unit. interconnection is complete.
To replace filters from either side and • Verify that the unit electrical power
All refrigerant suction line piping slide old filters and replace with new is disconnected.
should be insulated. ones. • Inspect all field wiring connections.
Coil
All connections should be clean
Important and tight.
Ensure that the refrigerant lines • Inspect unit ground connection(s).
passing through the cabinet are not Ground must comply with all
resting on sharp sheet metal edges. applicable codes.
• Inspect unit suspension arrangement
Installation, brazing, leak testing, and (if used). Unit position must be
evacuation of refrigeration lines are secure. Remove any tools or debris
covered in the installation instructions Either side found in or near the unit.
packaged with the outdoor unit. Read • Inspect duct outlets. Outlets must
Figure 5 be open and unrestricted.
the instructions before beginning
installation of refrigerant lines. • Inspect unit drain lines. Pipe
(f) Duct Connections connections must be tight and
(d)Condensate Drain Connections The supply and return ducts should be drain line unrestricted.
These air handlers come standard with connected to the unit with flame • Inspect fan assembly to insure all
a drain pan. Drain connections are retardant duct connectors to reduce moving parts move freely.
provided on both sides of the air vibration transmission. The return • Inspect unit for proper filters,
handlers. duct should be sized to the same securely installed. All cabinet
dimensions as the return inlet of panels must be secured.
For a typical drain trap assembly, see the unit. • Instruct owner/operator on proper
Figure 3 and 4. system operating and maintenance
procedure.

6 TTH-IOM01-EN
General Data

General Data - Air Handler Units

INDOOR UNIT MODEL TTH 060 BD TTH 075 BD TTH 100 BD


POWER CONS-V/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50
INDOOR COIL-TYPE SLIT FIN SLIT FIN SLIT FIN
Row/FPI 3/14 3/14 3/14
Face Area (Sq.Ft.) 5.14 6.16 8.20
Tube Size inch 3/8 3/8 3/8
Refrigerant Control CAP.TUBE EXPANSION VALVE EXPANSION VALVE
Drain Conn. Size inch STEEL PIPE 1" MPT. STEEL PIPE 1" MPT. STEEL PIPE 1" MPT.
No. of Refrigerant Circuit 1 1 1
INDOOR FAN-TYPE Centrifugal Type, Belt-Adjustable Drive
Dia x Width inch 10x10 10x10 10x8
No. Used 1 1 2
Nominal CFM 2,000 2,500 3,400
No. Motors-HP 1-3/4 1-1 1-2
Motors Speed RPM. 1,400 1,450 1,450
Volts/Ph/Hz. 380-415/3/50 380-415/3/50 380-415/3/50
F.L.Amps-L.R.Amps. 1.4-5.2 1.8-10.0 3.3-19.0
FILTER-TYPE Aluminium/Washable Filter
(No.)-Size x Thk. inch (2)-17x20x1 (2)-17x23x1 (3)-17x20x1
Refrigerant Factory Holding Charge
Ref. Line Connection Braze Braze Braze
Suction Line Size (each) inch 1 1/8 1 1/8 1 3/8
Liquid Line Size (each) inch 3/8 1/2 1/2
DIMENSIONS HxWxD
Crated mm 673x1,410x970 673x1,410x970 673x1,778x970
Uncrated mm 520x1,312x841 520x1,312x841 521x1,680x841
WEIGHT
Net Weight kg 88.5 93.5 138.5

TTH-IOM01-EN 7
Electrical Wiring

TTH060-100 (EXPORT)

8 TTH-IOM01-EN
Electrical Wiring

TTH060-100 (DOMESTIC)

TTH-IOM01-EN 9
Dimensional Data

TTH 060-075 BD

10 TTH-IOM01-EN
Dimensional Data

TTH 100 BD

TTH-IOM01-EN 11
Operation and Start-up

Preparation Start-Up Procedures


Perform the following checks and After completing all times under
inspections before operating the unit: “Pre-Start-Up”, the unit may be
started and the following checks
Inspection Checklist and adjustments performed.
• Unit is mounted securely to the
ceiling support rods (mounting a. Measure the motor voltage and
units). amps on all phases to insure proper
• Ductwork connections are operation. Compare these readings
complete. with the motor nameplate.
• Coil connections are complete and b. Disconnect load and start motor to
tight. check the direction of rotation. If
• Condensate drain pan connections the rotation need to be changed,
are complete and tight. stop the motor completely and
• Electrical connections are change the direction of rotation.
completed. Wiring is correct and c. After connecting the load, the
in accordance with the wiring motor should start quickly and run
diagram. smoothly. If it does not, the power
• Ground connection is completed. supply should be switched off at
• Check and re-tighten if necessary once and all connections, as well
set screws on the drive, fan pulley, as the power supply, be re-checked
fan bearings and wheel. before re-starting.
• Rotate fan by hand, to ensure that it d. In the event of excessive vibrations
runs freely and that there is no or unusual noises, the motor should
interference. be disconnected from the load and
• Check that fan is centrally located checked for poor alignment, loose
in the housing, axially and radially. mounting bolts, etc.
• Check and re-tighten, if necessary, e. When the motor has been operated
drive and bearing bolts, motor under load for a short period of
clamp plate bolts and isolator bolts. time, check that the operating
• Check to ensure that pulley are current totally with the nameplate
correctly aligned and that shafts current.
are parallel.
• Check belt tension as per
instruction given in the
maintenance section.

12 TTH-IOM01-EN
Maintenance

Warning To clean permanent filters, remove the


Disconnect electrical power source filter media and wash it in water to
and secure in disconnected position remove dust, dirt and lint; allow to dry
before servicing the unit. Failure to do thoroughly before re-installing in the
so may result in personal injury or units. Do not rub or wring.
death from electrical shock.
Permanent filters can also be cleaned
Monthly Inspection by blowing with compressed air in
1. Check condition of air filters and opposite direction of filter airflow.
replace them if necessary.
2. Check the drain pan to be sure that Belt Maintenance
it is clean and free to carry the flow Clean fan belts and pullies with a dry
of condensate through the drain cloth. Oil and grease must be kept off
line. belts. The use of a belt dressing is not
3. Check the coil surface for recommended. When replacing belts,
cleanliness. Clean if necessary. use a matched set.

Yearly Inspection Do not force belts onto pullies, but


1. Replace filters. adjust motor position to allow
2. Check coil surface. Clean by mounting and then re-tighten.
vacuuming or flushing with cold
water. Do not use steam or hot
water.
3. Carry out checks as detailed in
inspection checklist in the
Operation Section.
4. Inspect the condition of the
evaporator fan belt and replace if Span
Force
necessary. The belts fitted to TTH
units cannot achieve design
performance without the correct
Deflection
tensioning.
5. Check condition of vibration
isolators, replace if there is any
sign of wear, loosening or material
deterioration.
6. Check fan bearings for noisy
operation and excessive lubricant Figure 6
leakage. Replace if necessary. Belt Tension Measurement
7. Inspect the condensate drain pan
and condensate piping to make
sure they are clear and will carry To measure belt tension, use a belt
away all water. tensioner as shown in Figure 6.
8. Inspect the control panel wiring to Determine actual deflection by
make sure connections are tight depressing one belt with the belt
and insulation is intacted. tensioner and then adjust the belt
tension to the correct pounds force
Change/Clean Filters and tighten all setscrews to the proper
Change or clean air filters at least torques.
twice a year. Filters will be required
more frequent care under high load
condition or dirty air. A clogged air
filters reduces airflow, cooling capacity
and increases energy usage.

TTH-IOM01-EN 13
Trouble Shooting

Restriction (TXV or CAP)


Check Valve (Leaking)
Excessive Evap. Load
Refrig. Undercharge
Control Transformer
High Voltage Wiring

High Indoor Airflow


Low Voltage Wiring

Low Indoor Airflow

Refrig. Overcharge

Restriction LD Coil
Low Voltage Fuse
System

Curcuit Breaker

Thermal Cutout
Capacitor (Fan)
Power Supply

Faults
Thermostat

Relay (Fan)
Refrigerant Circuit

Head Pressure Too High P

Head Pressure Too Low P P

Suction Pressure Too High P P P P

Suction Pressure Too Low P P P P

Indoor Coil Frosting P P P P

Liquid Floodback (TXV) P

Liquid Floodback (Cap. Tube) P

Electrical

I.D. Motor Won’t Start P P P P P P P P P

P Primary Causes - S Secondary Causes

14 TTH-IOM01-EN
Trouble Shooting

Safety recommendations Maintenance Contract Training


To avoid accidents and damage, the It is strongly recommended that you The equipment described in this
following recommendations should be sign a maintenance contract with your manual is the result of many
observed during maintenance and local Service Agency. This contract years of research and continuous
service visits: provides regular maintenance of your development. To assist you in
1. The maximum allowable pressures installation by a specialist in our obtaining the best use of it, and
for system leak testing on low and equipment. Regular maintenance maintaining it in perfect operating
high pressure side are given in the ensures that any malfunction is condition over a long period of time,
chapter “Installation”. Always detected and corrected in good time the constructor has at your disposal
provide a pressure regulator. and minimizes the possibility that a refrigeration and air conditioning
2. Disconnect the main supply before serious damage will occur. Finally, service school. The principal aim
any servicing on the unit. regular maintenance ensures the of this is to give operators and
3. Service work on the refrigeration maximum operating life of your maintenance technicians a better
system and the electrical system equipment. We would remind you knowledge of the equipment they are
should be carried out only by that failure to respect these installation using, or that is under their charge.
qualified and experienced and maintenance instructions may Emphasis is particularly given to the
personnel. result in immediate cancellation of importance of periodic checks on the
the warranty. unit operating parameters as well as
on preventive maintenance, which
reduces the cost of owning the unit
by avoiding serious and costly
breakdown.

TTH-IOM01-EN 15
Trane Thailand Literature Order Number: TTH-IOM01-EN 0301
7th Floor, Ploenchit Center Building
Supersedes: S/S-IN-2 (EN) (TTH) 0397
2 Sukhumvit Road, Klongtoey
Bangkok 10110 Stocking Location: Bangkok, Thailand
Amair Limited
35 Mu 8, Poochaosamingprai Road ∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸÉ‡®â“ ¡‘ßæ√“¬ µ. ”‚√ß„µâ Õ.æ√–ª√–·¥ß ®. ¡ÿ∑√ª√“°“√ 10130
Samrong Tai, Samutprakarn 10130
http://www.trane.com Since The Trane Company has a policy of continuous product and product data improvement,
An American Standard Company it reserves the right to change design and specifications without notice.

You might also like