Professional Documents
Culture Documents
This document has been complied under guidance of ASDMA membership to provide information on
the requirements of Part M of the Building regulations with regards to the opening and closing
forces permitted to a door assembly.
Part M of the Building regulations, ‘Access to and use of buildings’ requires service providers to
make reasonable provision for access by people to buildings, regardless of disability, gender or age,
to live or work in, or use the facilities, of buildings and this, coupled with the obligations of the
equality act, requires service providers and employers to have regard for potential barriers which
physical building features in buildings may create.
The GAI, in July 2015, issued technical briefing No 15 which has a section that outlines whether or
not various documents are guidance or law.
With our grateful permission from the GAI we quote that section below (Added as an image for this
draft)
1.1 0 to 30 degrees (from the closed door position) is Max 30N. However section 6.5.2, in
BS8300:2009+A1:2010 NOTE 2, Where measurements cannot be taken at the leading
edge, they can be taken at a point up to 60mm in from the edge and approximately
vertically in line with the spindle or centre line of a pull handle in which case the opening
force limits can be increased by 2n, a further 2 to 3 N can also be added due to the
imprecision of the measuring device – therefore the max allowance is 35N
1.2 30 to 60 degrees = Max 22.5N ( again the same clause as noted in item 1 is allowed)
therefore the max allowance is 27.5N
1.3 For a fire rated door assembly it should be noted that Building Regulations Approved
Document B states that fire doors must be fitted with a self-closing device ( except for
fire doors to cupboards and service ducts which are normally kept locked shut) and,
based on BS EN 1154, which requires a minimum of power size 3 fitting to a fire door
giving a minimum closing force of 18Nm
Smoke, acoustic and privacy seals around the perimeter of the door will affect the opening force due
to the friction resistance they produce.
3.1.1 Brush or blade type seals, which are typically fritted In swipe/wipe (see fig 1) mode against
cold smoke and acoustic penetration provide the biggest resistance and it is therefore unlikely that
smoke seal or certain acoustic door assemblies will maintain the minimum opening force identified
in Document M
Frame
Seal
Door
3.1.2 Compression seals that are generally fitted on the face of the doorstop (see fig 2) produce less
friction than seals in swipe/wipe mode and therefore are subject to lower opening forces
Frame
Seal
Door
3.1.3 Meeting stiles of pairs tends to cause the biggest area of concern as the modern requirement is
for square meeting stiles to be employed which usually means the use of seals in swipe/wipe mode
(see fig 3) and the forces created here are unlikely to maintain the minimum opening force identified
in Document M.
Door Door
One possible solution is to incorporate a surface mounted astragal with a compression seal at the
meeting stiles (see fig 4), but this is far from ideal, requiring the use of door selectors, additionally it
does create other problems where occupants try to open both doors together.
Astragal Seal
Door Door
Weight , height and width are, however, less significant factors than, for example, the quality of the
hinges
Closers with higher efficiency provide less resistance (65% efficiency or better is essential) and as a
result they require less force to open.
The set-up of the closer is also very important as even a high efficiency set incorrectly will exceed
the maximum opening force. Section 4 advises on the correct set up of the closer.
Similarly, with an ongoing maintenance regime in place, the fit of the door will be regularly
monitored with parts replaced or maintained as per the manufacturer’s recommendations and or
warranties.
It should be noted that the threshold does not form part of the calculation for the UK smoke leakage
requirement of 3m3 /mtr/ hour.
The provision of seals for smoke leakage are considered in section 3.1 of this document.
For door assemblies with lower acoustic performance less seals tend to meet the requirement and
there is less impact on the opening forces but the higher the acoustic performance the amount of
seals can tend to increase and thus cause increased resistance and higher opening forces.
Acoustic door assemblies will generally have some form of threshold sealing mechanism and these
again can have an impact on the opening forces.
There are generally two options for sealing at the threshold and figs 5 and 6 noted below illustrate
the two most popular options name bladed seals and dropseals
Frame
Door
Seal
Fig 6 shows a typical dropdown seal at the threshold that may or may not incorporate a metal or
timber threshold fitted to the floor. This type of seal will engage with the threshold and or floor
finish when the door is in the closed position and will retract back up into the door once the door
commences its opening sequence so will, therefore, have a similar effect to compression mode seals
as illustrated in fig 2. and fig 4. in that the opening force will generally be lower
Frame
Door
DropSeal
The provision of seals in the door frame and meeting stiles for acoustic door assemblies are
considered in section 3.1 of this document
INITIAL SETUP
For fire resisting doorsets install and adjust to ensure minimum 18Nm (power size 3) and that the
door closes from any angle and over any latch that may be fitted.
• Open the door and allow the door to close at a rate of 1 degree / second whilst holding the
force measuring instrument against the face of the door and moving it back in time with the door.
• This will give a value “N” which is the Newton force exerted when the door closes e.g.20N.
N(c) = The Newton force exerted by the closer when the door closes e.g. 20N
m= The distance from the hang edge of the door to the point where the force measuring
instrument was located e.g. 0.884m
You may need to adjust the closer in order to achieve 18Nm several times but once each closer is set
up no further adjustment will be required to the unit unless a greater speed is required to enable the
door to latch.
Annex A to BS EN 1154 states that due to their low closing moments door closers size 1 & 2, without
adjustable closing force, are NOT considered suitable for use on fire/ smoke door assemblies. Door
closers with adjustable closing force shall be capable of adjustment at least to power size 3.
A power size 3 closer is required to exert a minimum closing force of 18NM, or 21.2N closing force
when measured from the handle of a standard 926mm wide door.
However, fitting door closing devices greatly disadvantage people, including children, with a wide
range of disabilities. It is extremely difficult for wheelchair users, and for people with assistance
dogs, low upper body strength or walking aids, to manoeuvre through a door opening against the
force exerted by the device and additionally any extra resistance exerted by
weather/smoke/acoustic/privacy seals and air pressure differentials.
Where needing to be opened manually, the opening force at the leading edge of the door is not
more than 30N from 0o (the door in the closed position) to 30o open, and not more than 22.5N from
30o to 60o of the opening cycle.
5.4 BS 8300:2009 – Design of buildings and their approaches to meet the needs of disabled people –
Code of practice
BS 8300 advocates for single or double swing doors, the opening force should not be more then 30N
– see extract:
For most disabled people to have independent access through single or double swing doors, the
opening force, when measured at the leading edge of the door, should be not more than 30N from
0o (the door in the closed position) to 30o open, and not more than 22.5N from 30o to 60o of the
opening cycle.
This means that, in general, only high efficiency door closers mounted on doors with a width greater
than 900 mm are likely to meet fire door requirements as well as the opening force limits described
above. Controlled door closing devices of a lower power size and with relatively low efficiencies,
with a lower power size and/or of a width less than 900mm may only be suitable for non-fire
resisting doors.
5.5 BS8300 also recognises that ‘The accuracy of force measuring instruments available on the
market varies and there are inherent difficulties in measuring forces on site. It is recognized,
therefore, that any measurements are subject to a degree of imprecision which could give rise to
variations of between 2N and 3N.’
Without regular maintenance of all door fittings, the resistances to opening and closing can increase
to an extent that the ability of disabled people to pass through the door may be affected. The
opening force at the door opening angles described above should therefore be checked at regular
intervals.
5.6 BS8300 also recognises the importance of hinges with regards to opening force compliance.
BS8300:2009+A1:2010, section 6.5.3 – Hinges
Where it is important to minimize resistance to door opening and closing, hinges with low friction
bearings should be selected to carry the appropriate mass of the door.
5.7 BS8300 reiterates the requirements for controlled door closing devices stating; ‘The choice of
controlled door closing devices should take account of the efficiency of the closer, as well as the
resistances from edge seals, hinge friction, latch resistance and differential air pressure.
The effect of using a low efficiency controlled door closing device is to reduce the closing force to a
point where, coupled with the other resistances to closing, the door may not latch, or stay closed if
unlatched. The use of high efficiency closers can reduce the force required to open the door and
increase the proportion of the disabled population who can pass through independently.
Where the force required to open a fire0resisting door on a circulation route exceeds the limits (as
stated in BS8300 section 6.5.2) an electrically powered hold-open device, either stand alone or
integral in the body of the closer, which confirms to the requirements of BS EN 1155 should be
installed.
These hold open devices will close upon the interruption of the electrical supply.
The use of swing-free controlled door closing devices should be limited to applications where doors
are located for access to rooms or similar locations and not part of a circulation route. The use of
delayed action controlled door closing devices should similarly be avoided in circulation areas
The maximum closing force exerted by a controlled self-closing device should be within 0° and 15° of
final closure. Controlled door closing devices that do not have this characteristic should be avoided.