You are on page 1of 2

Job

Name: USF-49-B4 Cut Sheet


Tag: MK-1
Quantity: 1
Printed Date: April 26, 2022

Model: USF-49
Universal Single Width Blower
Standard Construction Features: Galvanized Steel scroll (optional painted), PermaLock seam (optional
welded seam). Centrifugal backward inclined steel wheel (optional aluminum). Steel inlet cone (optional
aluminum). Belt driven motor mounted out of the airstream.

1.5 5
Fan Configuration 3 6 6 F R P M

Class I 1.2 4

Brake Horsepower (BHP)


Arrangement 10 Static Pressure (in. wg)

area
Discharge position UB
Wheel rotation CW 0.9 3

e d
Fan material Steel

ha d
Drive type Belt

s
0.6 2

in

m
e
rat

te
ys
S
pe

Performance 0.3 1
t o
no

Requested Volume (CFM) 17,000


o
D

Actual Volume (CFM) 17,000 0 0


Total External SP (in. wg) 1 0 4 8 12 16 20 24 28
Fan RPM 366 Volume (CFM) x 1000
Drive Loss (%) 6
Fan curve
Operating Power (bhp) 4
Brake horsepower curve
Startup Power (bhp) 4
FEI 1.64 Operating Point SP

Air Stream Temp (F) 70 Operating Bhp point


Start-up Temp (F) 70 Max system curve
Air Density (lbs/ft^3) 0.074 System curve
Elevation (ft) 207
Static Efficiency (%) 72
Outlet Velocity (ft/min) 1,232
Nameplate Model USF-49-3-B4-0

Sound
Octave Bands (hz) LwA dBA Sones
Motor
62.5 125 250 500 1000 2000 4000 8000
Size (hp) 7-1/2
Inlet 87 80 74 70 69 64 57 49 74 62 12.4
V/C/P 460/60/3
NEC FLA (Amps) 11 Greenheck Fan Corporation certifies that the model shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on tests and procedures performed in
accordance with AMCA Publication 211 and comply with the requirements of the
AMCA Certified Ratings ProgramThe AMCA certified ratings seal applies to air
performance and FEI ratings only.Performance certified is for installation type B:
Free inlet, ducted outlet.Power rating includes transmission losses.Performance
ratings do not include the effects of appurtenances.The sound power level ratings
are shown in decibels, referred to 10^-12 watts calculated per AMCA Standard 301.
The A-weighted sound ratings shown have been calculated per AMCA International
Standard 301.Values shown are for inlet Lwi, LwiA and outlet Lwo, LwoA sound
power levels for installation Type B: free inlet, ducted outlet. Ratings for outlet
sound include the effects of duct end correction.dBA levels are not licensed by
AMCA International. The AMCA Certified Ratings Seal for Sound applies to inlet Lwi,
LwiA and outlet Lwo, LwoA ratings only.

Page 1 of 2 Version 3.1.0, January 2022


Job Name: USF-49-B4 Cut Sheet
Tag: MK-1
Quantity: 1
Printed Date: April 26, 2022

Dimensions and Weights

Label Value Description


- 1038 Weight w/o accessories (lbs)
A 92 Overall Height (in)
B 92 Overall Width (in)
C 82 Overall Length (in)
- 55 Inlet Diameter (in)
- 38.75 x 51.69 Outlet Size (W x H) (in)

Wheel rotation is defined as being viewed from the drive side.

*All dimensions are in inches.


Page 2 of 2 Version 3.1.0, January 2022

You might also like