You are on page 1of 2

Job Name: AER-24-03-0320-VG Cut Sheet

Tag: MK-1
Quantity: 1
Printed Date: October 17, 2023

Model: AER-24-03-0320-VG
Sidewall Direct Drive Exhaust Fan
Standard Construction Features: Galvanized steel panel with fabricated galvanized steel drive frame
(optional wall housing or wall collar). Propeller, fabricated steel (02) or cast aluminum (03). Direct driven
motor in the airstream.

0.04
Fan Configuration

Drive type Direct


306
FRP
0.03 M
Performance
Static Pressure (in. wg)

Requested Volume (CFM) 1,540


Actual Volume (CFM) 1,540
Fan RPM 306 0.02
Operating Power (bhp) 0.01
Startup Power (bhp) 0.01
Air Stream Temp (F) 70
e

a
Start-up Temp (F) 70 ar
0.01 ed
Air Density (lbs/ft^3) 0.073 ad
sh
Elevation (ft) 797 in
te
Outlet Velocity (ft/min) 475 era
op
o not
D
0
0 2 4 6 8 10 12 14
Motor
Volume (CFM) x 100
Size (hp) 1/4
V/C/P 115/60/1
Sound
NEC FLA (Amps) 3.8
Octave Bands (hz) LwA dBA Sones
Min Circuit Ampacity (MCA) 4.8
62.5 125 250 500 1000 2000 4000 8000
Max Overload Production (MOP) 15
Short Circuit Current Rating (SCCR) 5 kA Inlet 52 50 46 43 39 33 27 21 45 33 1.2

Greenheck Fan Corporation certifies that the model shown herein


is licensed to bear the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311 and comply with the
requirements of the AMCA Certified Ratings Program.The AMCA
certified ratings seal applies to sound and air performance ratings
only.Performance certified is for installation type A: Free inlet, free
outlet.Power rating does not include transmission
losses.Performance ratings do not include the effects of
appurtenances.The sound ratings shown are loudness values in
hemispherical sones at 1.5 m (5 ft) in a hemispherical free field
calculated per ANSI/AMCA Standard 301. The A-weighted sound
FLA - based on tables 150 or 148 of National Electric Code 2002. Actual ratings shown have been calculated per AMCA International
motor FLA may vary, for sizing thermal overload, consult factory. Standard 301.Values shown are for Installation Type A: free inlet
MCA and MOP values shown only account for the motor, not accessories hemispherical sone levels.dBA levels are not licensed by AMCA
(damper actuator, field supplied VFD, etc.). International. The AMCA Certified Ratings Seal applies to LwiA and
SCCR is a rating on components and assemblies representing the inlet sone ratings only.
maximum level of short-circuit current that a component or assembly can
withstand without causing a fire or shock hazard. A short circuit
exceeding this rating can cause catastrophic and violent equipment,
component and enclosure failure.

Page 1 of 2 Version 3.6.0, September 2023


Job Name: AER-24-03-0320-VG Cut Sheet
Tag: MK-1
Quantity: 1
Printed Date: October 17, 2023

Dimensions and Weights

Label Value Description


- 63 Weight w/o accessories (lbs)
A 32 Overall Height (in)
B 32 Overall Width (in)
C 19 Overall Length (in)
- 26.5 Wall Opening Width (in)
- 26.5 Wall Opening Height (in)

*All dimensions are in inches.