Maxseal Solenoid Valves: Upto4"
Maxseal Solenoid Valves: Upto4"
Up to 4"
Maxseal Technology
from FCX Thompson Valves.
Approvals and
Certification.
Maxseal solenoid valves are designed for use in
hazardous areas and conform to BASEEFA / SIRA and
European CENELEC specifications.
2
The Industry Standard Maxseal Solenoid Valve.
Model Shown:
ICO4S 1/4" Stainless Steel EEx d Valve.
Ingress protection
to IP66.
Position feedback
(larger models).
Class “H”
insulation.
DC coils with
suppression diodes.
Low power
direct acting lift.
High-thrust
return spring.
Threaded or
flanged process
connections Low-friction
(larger models). poppet design.
Seal/body options
2/2, 3/2 and 0-207 bar (0-3000 psi)
5/2 port gases and liquids.
configurations.
Full flow capability.
Manual and
tamper-proof
reset options.
resources.
FCX Thompson Valves packaged and component
solutions are specified worldwide for their high
technical added value and fitness for purpose in
exacting control and instrumentation applications.
A Tradition of
Integrity.
Maxseal solenoid valves produced by FCX Thompson
Valves consistently set rigorous standards for
process management in the most demanding
environments: aerospace, defense, gas turbine,
mining, nuclear power, offshore and petrochemical
industries.
www.fcx-thompson-valves.c
We are here to help!
sales@fcx-thompson-valves.com
+44 1202 697521
com
Automatic Latching Lever 34
Tamperproof Manual Reset 34
Special Valve Features
Indicating Switches 35
High Temperature Spacer 35
Horizontal Mounting 35
Hazardous Area Guidelines
Intrinsic Safety 36
Installation Guidelines 37
Coding System 38
Valve Flow Characteristics 40
Valve Flow Performance Charts
1. Air Flow, ICO4 1/4", Low Pressure 43
2. Air Flow, ICO4 1/2", Low Pressure 43
3. Liquid Flow, ICO4 1/4", Low Pressure 44
4. Liquid Flow, ICO4 1/4", High Pressure 44
5. Flow Test, ICO4 1/4" 45
6. Flow Test, ICO4 1/2" 46
7. Flow Test, ICO4 1/2" 46
Conversion Chart 47
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
EEx ia
Certification Description
II 1G A pilot operated solenoid
SIRA / CENELEC approved valve certified for use with
EEx ia IIC T6 Ta (-40ºC to +64ºC) hazardous gases.
Complies with EN 50014:1997 (incl. amendments A1 and A2), EN 50020:1994
and EN 50284:1999
Complies with ATEX Directive 94/9/EC
Complies to Electrical Safety Standard IEC 1010
Assessed compliant to Pressure Equipment Directive 97/23/EC
FM approved to I.S. Class I Division 1 Groups A.B.C.D.
A B A
C B A B A B
D C
E
6
Hazardous Area
Zone 0
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
EEx ia
ICO2S 1/4" - 2"
Technical Specification
Protection Ingress IP66 / X8. NEMA 4X
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges (main valve)
1/4" model 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) (option)
0 - 103 bar(g) (0 - 1494 psi) (option)
0 - 207 bar(g) (0 - 3000 psi) (option)
1/2" - 2" models Please contact us
ø 58 (2.28) 47 (1.85)
2 x M6
mounting
studs Pilot
vent
port
202 (7.95)
Pilot
170 (6.69)
inlet
port
11 (0.43)
45 (1.77)
124.5 (4.90)
118 (4.65)
Port A
Inlet
(0.87)
22.2
Port B
Outlet
Port C
Exhaust
(0.83)
21
7
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
EEx d
Certification Description
II 2G A direct-acting solenoid
EECS (BASEEFA) / SIRA CENELEC approved valve certified for hazardous
EEx d IIC T6 (Ta = -60ºC to +40ºC) or area use as well as general
EEx d IIC T4 (Ta = -60ºC to +90ºC) air and gas purposes in the
Complies with BS 5501: Part 5:1977, EN 50014:1977 (amendments 1 and 2) offshore and petrochemical
and EN 50018:1994 industries.
Complies with ATEX Directive 94/9/EC
A B A B
C D C
E
8
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
EEx d
ICO4D 1/4"
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) (option)
0 - 103 bar(g) (0 - 1494 psi) (option)
0 - 207 bar(g) (0 - 3000 psi) (option)
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
conduit entry
(0.86)
20 (0.78)
2 x M8
mounting studs
30 (1.18)
192 (7.56)
150 (5.90)
11 (0.43)
85 (3.34)
Port A
62 (2.44)
(0.85) (0.87)
Inlet
21.5 22.2
Port B
Outlet
Port C
Exhaust
9
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
EEx d
Certification Description
II 2G A direct-acting solenoid
EECS (BASEEFA) / SIRA CENELEC approved valve certified for hazardous
EEx d IIC T6 (Ta = -60ºC to +48ºC) or area use as well as general
EEx d IIC T4 (Ta = -60ºC to +90ºC) air and gas purposes in the
Complies with EN 50014:1997 (amendments 1 and 2) and EN 50018:1994 offshore and petrochemical
Complies with ATEX Directive 94/9/EC industries.
FM approved to Class I Division 1 Groups A. B. C. D
A B A B
C D C
E
10
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
EEx d
ICO4S 1/4"
Technical Specification
Protection Ingress IP65 / X8. NEMA 4X
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) (option)
0 - 103 bar(g) (0 - 1494 psi) (option)
0 - 207 bar(g) (0 - 3000 psi) (option)
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
We recommend installing a
strainer or filter as close as
possible to valve inlet. While
protecting seating areas
from potential damage, this
helps maintain air quality -
Talk to us about filtration!
11
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
EEx d
Certification Description
II 2G A direct-acting solenoid
EECS (BASEEFA) / SIRA CENELEC approved valve certified for hazardous
EEx d IIC T6 (Ta = -60ºC to +40ºC) or area use as well as general
EEx d IIC T4 (Ta = -60ºC to +90ºC) air and gas purposes in the
Complies with BS 5501: Part 5:1977, EN 50014:1977 (amendments 1 and 2) offshore and petrochemical
and EN 50018:1994 industries.
Complies with ATEX Directive 94/9/EC
A B
C
12
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
EEx d
ICO4D 1/2"
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) non-universal (option)
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
conduit entry
20 (0.78)
30 (1.18)
2 x M8
mounting studs
247 (9.72)
205 (8.07)
22 (0.86)
Port A
140 (5.51)
Inlet
117 (4.60)
44 (1.73)
Port B
Outlet
Port C
Exhaust
(1.41)
36
ø 76 (3.0) 70 (2.76)
13
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
EEx d
Certification Description
II 2G A direct-acting solenoid
EECS (BASEEFA) / SIRA CENELEC approved valve certified for hazardous
EEx d IIC T6 (Ta = -60ºC to +48ºC) or area use as well as general
EEx d IIC T4 (Ta = -60ºC to +90ºC) air and gas purposes in the
Complies with EN 50014:1997 (amendments 1 and 2) and EN 50018:1994 offshore and petrochemical
Complies with ATEX Directive 94/9/EC industries.
FM approved to Class I Division 1 Groups A. B. C. D
A B
C
14
Hazardous Area
Zone 1
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
EEx d
ICO4S 1/2"
Technical Specification
Protection Ingress IP65 / X8. NEMA 4X
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) non-universal (option)
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
20
30 (1.18)
(0.78)
2 x M8
mounting
studs
240 (9.45)
203 (7.99)
22 (0.86)
Port A
134 (5.27)
Inlet
117 (4.60)
44 (1.73)
Port B
Outlet
Port C
Exhaust
36 (1.41)
ø 76 (3.0) 70 (2.76)
15
Hazardous Area
Zone 1
Maxseal
Direct Solenoid-Operated
Control Valve for Hazardous Areas
EEx d
Certification Description
EECS (BASEEFA) / CENELEC approved A direct-acting solenoid
EEx d IIC T6 or EEx d IIC T4 (Ta = 90ºC) valve certified for hazardous
Complies with EN 50014:1997 and EN 50018:1977 area use as well as general
air and gas purposes in the
offshore and petrochemical
industries.
A B A B
C D C
E
16
Hazardous Area
Zone 1
Maxseal
Direct Solenoid-Operated Control Valve for Hazardous Areas
EEx d
SOV, Sizes 1 & 2 (1/2" - 3/4")
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in: please contact us
Drop-out: please contact us
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) bar stock body (option)
0 - 103 bar(g) (0 - 1494 psi) bar stock body (option)
0 - 207 bar(g) (0 - 3000 psi) bar stock body (option)
Dimensions in mm (inches)
(Size 2 3/4" solenoid 3/2 Uni configuration illustrated)
conduit entry
25.4 (1.0)
2 x M8
(1.38)
mounting
35
304 (12)
studs
242 (9.52)
162 (6.38)
Port A
25.4 (1)
107 (4.21)
Inlet
50.8 (2)
Port B
Outlet
Port C
Exhaust
(1.26)
32
We recommend installing a
strainer or filter as close as
possible to valve inlet. While
protecting seating areas
from potential damage, this
helps maintain air quality -
Talk to us about filtration!
17
Hazardous Area
Zone 1
Maxseal
Direct Solenoid-Operated
Control Valve for Hazardous Areas
EEx d
2-port, EO 2-port, EC
Standard Features
Port thread 1" - 2" NPT
Port configuration 3/2 Uni
Operating pressure 0 - 20 bar(g) (0 - 290 psi)
Actuation method Automatic
Valve material Stainless steel
BS EN 10088 Options
Seat / Seal material High nitrile (Buna N) Port connections
Operating voltage Female threaded 1" - 2" BSPP / BSPT
at 20ºC (68ºF) Flanged 1" - 3" BS 10, BS 1560
Size 3 24V DC; 40W or BS 4504
Size 4 24V DC; 75W Port configuration 5/2 Uni; 2/2 EO; 2/2 EC
Size 5 24V DC; 100W
Size 6 24V DC; 150W Actuation method Autolatch, lever manual
reset (LMR), lever manual
Conduit / Signal entry M20 x 1.5 mm ISO (F) override (LMO),
Paint finish Standard (green) 40 µm tamperproof manual reset
Coil housing material Cast iron (see "Optional Valve
BS EN 1561: 1997 Features")
18
Hazardous Area
Zone 1
Maxseal
Direct Solenoid-Operated Control Valve for Hazardous Areas
EEx d
SOV, Sizes 3, 4, 5 & 6 (1" - 3")
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in: please contact us
Drop-out: please contact us
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) bar stock body (option)
0 - 103 bar(g) (0 - 1494 psi) bar stock body (option)
0 - 207 bar(g) (0 - 3000 psi) bar stock body (option)
Dimensions in mm (inches)
(Size 3 1" solenoid 3/2 Uni configuration illustrated. Double conduit thread for switches)
50 (1.96)
2 off 25 (0.98)
M8 x
(1.57)
1.25 mm 30 (1.18)
40
mounting
studs 15 (0.59)
250 (9.84)
60 (2.36)
157.5 (6.20)
15 (0.59)
90 (3.54)
85 22
(3.34) (0.86)
403 (15.86)
59 (2.32)
85.7 (3.37)
(2.37)
60.3
Port A
Inlet
Port B
50.8
(2.0)
Outlet
Port C
(0.375) (1.25)
Exhaust
31.7
9.5
19
Hazardous Area
Zones 1 and 2
Maxseal
Solenoid/Pilot-Operated Valve
for Hazardous Areas
EEx d, Ex N
Certification Description
Pilot operated valve A pilot-operated valve
optionally supplied with certified for hazardous area
ICO4S, ICO4D or ICO4N. use as well as general
Refer to the relevant valves liquid and gas purposes in
for certification data. the offshore and
petrochemical industries.
C
A
C
A
C
A
C
A
A B C
C D A B A B A B
E
20
Hazardous Area
Zones 1 and 2
Maxseal
Solenoid/Pilot-Operated Valve for Hazardous Areas
EEx d, Ex N
POICO4 1/4"
Technical Specification
Protection Ingress IP65 / IP68
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges
Main valve 0 - 20 bar(g) (0 - 290 psi) 2/2 and 3/2 ports
Up to 207 bar(g) (3000 psi) 2/2 and 3/2 ports
0 - 20 bar(g) (0 - 290 psi) 5/2 port
Pilot signal 2 - 10 bar(g) (29 -145 psi) 2/2, 3/2 and 5/2 ports
Dimensions in mm (inches)
(ICO4N 3/2 Uni configuration illustrated)
ø 82.6 (3.25)
22
(0.86) 4 6 (1.81) 4 8 (1.88)
tsu ah x E C t r o P
2 off
t el t u O B t r o P
M8 x 1.25 mm
t el n I A t r o P
mounting
studs
O SI m m 5.1 x 0 2 M
(2 positions)
y r tn e tiudno c
3)
4.5
)0.1(
)1
11 (0.4
2 .4( 701
)75.
2
69( 761
)
3 4.0( 11
Pilot inlet
)0
2 - 10 bar(g)
3. 3 ( 4 8
4.5
)0.1( )
Pilot exhaust
)7
5.
2 .1(
23
2
6 8 .0(
22
)7
2. 2 2
8 .0(
21
Hazardous Area
Zones 1 and 2
Maxseal
Dual Shuttle Valve
for Hazardous Areas
EEx d, Ex N
Certification Description
Dual shuttle valve A valve certified for
optionally supplied with hazardous area use as well
ICO4S, ICO4D or ICO4N. as general liquid and gas
Refer to the relevant valves purposes in the offshore
for certification data. and petrochemical
industries.
5-port 3-port
2 3 2
4 5 3
1 1
22
Hazardous Area
Zones 1 and 2
Maxseal
Dual Shuttle Valve for Hazardous Areas
EEx d, Ex N
Dual Shuttle Valve 1/4" - 1/2"
Technical Specification
Protection (solenoid) Ingress IP65 / IP68
Surge suppression diodes
Response times Pull-in: Please contact us
(typical, dependent on coil size) Drop-out: Please contact us
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Dimensions in mm (inches)
(5/2 1/4" configuration illustrated)
183 (7.2) 2 x M8
mounting studs
27.2 (1.07) 2 positions
2 3
55 (2.16)
4 1 5
54.4 (2.14)
89.4 (3.51)
M20 x 1.5 mm ISO
59 (2.32)
ø 80 (3.14)
conduit entry
20 (0.78)
186 (7.32)
158 (6.22)
116 (4.56)
Exhaust
86 (3.38)
port
21.5 (0.87)
27.3 (1.07)
51(2.0)
58 (2.99) 234 (9.21)
We recommend installing a
strainer or filter as close as
possible to valve inlet. While
protecting seating areas
from potential damage, this
helps maintain air quality -
Talk to us about filtration!
23
Hazardous Area
Zones 1 and 2
Maxseal
Solenoid/Pilot-Operated Valve
for Hazardous Areas
EEx d, Ex N
C
A
C
A
Pilot operated valve A pilot-operated valve
optionally supplied with certified for hazardous area
ICO4S, ICO4D or ICO4N. use as well as general
Refer to the relevant valves liquid and gas purposes in
for certification data. the offshore and
A B C
petrochemical industries. C D A B
E
2-port, EO 2-port, EC
Standard Features
C
A
C
A
Port thread 1/2" - 2" NPT
Port configuration
1/2" - 4" 2/2 EO, 2/2 EC
1/2" - 3" 3/2
1/2" - 2" 5/2 A B A B
Operating pressure
Main valve 0 - 20 bar(g) (0 - 290 psi) Options
Pilot valve 2 - 10 bar(g) (29 - 145 psi)
Port thread (pilot body) 1/4" BSPP; 1/4" BSPT
Actuation method Solenoid-operated,
external pilot liquid/gas Port connections
assisted Female threaded 1/2"- 2" BSPP / BSPT
Flanged 1/2"- 4" BS 10, BS 1504
Valve material Stainless steel or BS 4504
BS EN 10088
Valve material Brass BS EN 12163: 1998
Seat / Seal material High nitrile (Buna N)
Seat / Seal material Viton®, nylon 66
Operating voltage 24V DC; 4.5W (ICO4D/S) (high pressure seat only)
at 20ºC (68ºF) Alternative materials
Conduit / Signal entry M20 x 1.5 mm ISO (F) available on request
Paint finish Standard (green) 40 µm Operating voltages DC: 12, 24, 48, 110, 125,
Coil housing material 240
ICO4D and ICO4N Cast iron BS EN 1561:1997 AC: 24, 50, 110, 240, 440
ICO4S Stainless steel BS 3146 Conduit / Signal entry 1/2" NPT, 13.5 PG
ANC.4 BFC.316 Paint Epoxy (light grey) 150 µm
Weight Please contact us CV value 0 - 50 bar(g) (0 - 725 psi)
Cv value at 20 bar (290 psi) 0 - 103/207 bar(g)
1/2" model 3.2 (Kv 2.7) (0 - 1494/3000 psi)
3/4" model 6.8 (Kv 5.8) Please contact us
1" model 12.8 (Kv 11)
11/2" model 28 (Kv 24)
2" model 48 (Kv 41)
3" model 100 (Kv 86)
4" model 165 (Kv 142)
24
Hazardous Area
Zones 1 and 2
Maxseal
Solenoid / Pilot-Operated Valve for Hazardous Areas
EEx d, Ex N
POV 1/2" - 4"
Technical Specification
Protection Ingress IP65 / IP68
Surge suppression diodes
Response times Pull-in: please contact us
Drop-out: please contact us
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges
Main valve 0 - 10 bar(g) (0 - 145 psi) 2/2 port 1/2" - 4" (option)
3/2 port 1/2" - 3" (option)
5/2 port 1/2" - 2" (option)
0 - 20 bar(g) (0 - 290 psi) 2/2 port 1/2" - 4" (standard)
3/2 port 1/2" - 3" (standard)
5/2 port 1/2" - 2" (standard)
0 - 50 bar(g) (0 - 725 psi) 2/2 port 1/2" - 2" (option)
3/2 port 1/2" to 11/2" (option)
0 - 103 bar(g) (0 - 1494 psi) 2/2 port 1/2" to 11/2" (option)
3/2 port 1/2" to 1" (option)
0 - 138 bar(g) (0 - 2001 psi) 2/2 port 1/2" to 11/2" (option)
3/2 port 1/2" - 1" (option)
0 - 207 bar(g) (0 - 3000 psi) 2/2 port 1/2" to 11/2" (option)
3/2 port 1/2" - 1" (option)
Pilot signal 2 - 10 bar(g) (29-145 psi) 2/2, 3/2 and 5/2 ports
Dimensions in mm (inches)
(3/2 Uni 3/4" configuration illustrated)
54 (2.12) 54 (2.12) 52 (2.05)
1/4"NPT
76 (3.0)
Conduit op. air inlet
entry 2 - 10 bar(g)
63.5 (2.5) 45 (1.7)
160 (6.30)
x 1.5
Port C
Port B
Port A
118 (4.65)
Outlet
mm
Inlet
210 (8.26)
ISO
11 (0.43)
Port A
Inlet
50.8 (2.0)
Port C
22.2 (0.87)
Vent
25.4
(1.0)
2 off
M10 x 1.5 mm
mounting studs 161 (6.33) 89 (3.5) 31.75
(1.25)
We recommend installing a
strainer or filter as close as
possible to valve inlet. While
protecting seating areas
from potential damage, this
helps maintain air quality -
Talk to us about filtration!
25
Hazardous Area
Zone 2
Maxseal
Instrument Changeover and Process
Control Valve for Hazardous Areas
Ex N
Certification Description
EECS (BASEEFA) approved A direct-acting solenoid
Ex N IIC T6 valve certified for hazardous
Ex N IIC T4 (Tamb = 90ºC) area use as well as general
Complies with BS 6941: 1988 air and gas purposes in the
offshore and petrochemical
industries.
A B
C
26
Hazardous Area
Zone 2
Maxseal
Instrument Changeover and Process Control Valve for Hazardous Areas
Ex N
ICO4N 1/4"
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in < 150 ms
(typical, dependent on coil size) Drop-out < 80 ms
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) (option)
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
conduit entry
(0.86)
2 x M8 mounting
studs (inline)
25.4
(1.0)
164 (6.45)
140 (5.5)
11 (0.43)
84 (3.30)
Port A
Inlet
62 (2.44)
(0.85) (0.87)
21.5 22.2
Port B
Outlet
Port C
Exhaust
27
Hazardous Area
Zone 2
Maxseal
Direct Solenoid-Operated
Control Valve for Hazardous Areas
Ex es
28
Hazardous Area
Zone 2
Maxseal
Direct Solenoid-Operated Control Valve for Hazardous Areas
Ex es
SOV, Sizes 1, 2, 3, 4, 5 & 6 (1" - 4")
Technical Specification
Protection Ingress IP65 - IP68
Surge suppression diodes
Response times Pull-in: Please contact us
(typical, dependent on coil size) Drop-out: Please contact us
Response times settings Pull-in: within 87.5% of nominal (factory set at less than 75% of nominal)
Drop-out: normally 10-20% of nominal
Operating pressure ranges 0 - 20 bar(g) (0 - 290 psi) (standard)
0 - 50 bar(g) (0 - 725 psi) bar stock body (option)
0 - 103 bar(g) (0 - 1494 psi) bar stock body (option)
0 - 207 bar(g) (0 - 3000 psi) bar stock body (option)
Dimensions in mm (inches)
(Size 2 3/4" solenoid 3/2 Uni configuration illustrated)
conduit thread
25.4 (1.0)
2 off
M8 x 1.25 mm
mounting studs
189 (7.4)
(1.37)
66 22 (0.86)
35
135 (5.31)
(2.6)
318.5 (12.5)
64.6 (2.54)
38.1
(1.5)
63.5 (2.5)
Port A
Inlet
130 (5.1)
50.8
(2.0)
Port B
Outlet
Port C
Exhaust
41.24
(1.6)
82.55 (3.25) ø 89 (3.5)
We recommend installing a
strainer or filter as close as
possible to valve inlet. While
protecting seating areas
from potential damage, this
helps maintain air quality -
Viton® is a registered trademark of DuPont Dow Elastomers LLC. Talk to us about filtration!
29
Unclassified
Maxseal
Air Operated Valve
Description
A general purpose
direct-acting valve for
liquid and gas
management in industrial
applications.
A B A
C B A B A B
D C
E
30
Unclassified
Maxseal
Air Operated Valve
AOV 1/4"
Technical Specification
Response times 60 - 100 ms
Operating pressure ranges
Main valve 0 - 20 bar(g) (0 - 290 psi) 2/2 and 3/2 ports
Up to 207 bar(g) (3000 psi) 2/2 and 3/2 ports
0 - 20 bar(g) (0 - 290 psi) 5/2 port
Pilot signal 2 - 10 bar(g) (29 - 145 psi) 2/2, 3/2 and 5/2 ports
Dimensions in mm (inches)
(3/2 Uni configuration illustrated)
58 (2.28) 58 (2.28)
Note: Housing
2 x M8 size may vary
mounting with different
studs pressure ratings
115 (4.52)
11 (0.43)
Port A
Inlet
Port B
(0.87)
22.2
62 (2.44)
Outlet
Port C
Exhaust
(0.85)
21.5
31
Unclassified
Maxseal
Air Operated Valve
Description
A general purpose
direct-acting valve for
liquid and gas
management in industrial
applications.
A B A
C B A B A B
D C
E
32
Unclassified
Maxseal
Air Operated Valve
Technical Specification
Response times 60 - 100 ms
Operating pressure ranges
Main valve 0 - 10 bar(g) (0 - 145 psi) 2/2 port 1/2" - 4" (option)
3/2 port 1/2" - 3" (option)
5/2 port 1/2" - 2" (option)
0 - 20 bar(g) (0 - 290 psi) 2/2 port 1/2" - 4" (standard)
3/2 port 1/2" - 3" (standard)
5/2 port 1/2" - 2" (standard)
0 - 50 bar(g) (0 - 725 psi) 2/2 port 1/2" to 2" (option)
3/2 port 1/2" to 11/2" (option)
0 - 103 bar(g) (0 - 1494 psi) 2/2 port 1/2" to 11/2" (option)
3/2 port 1/2" to 1" (option)
0 - 138 bar(g) (0 - 2001 psi) 2/2 port 1/2" - 11/2" (option)
3/2 port 1/2" to 1" (option)
0 - 207 bar(g) (0 - 3000 psi) 2/2 port 1/2" - 11/2" (option)
3/2 port 1/2" - 1" (option)
Pilot signal 2 - 10 bar(g) (29-145 psi) 2/2, 3/2 and 5/2 ports
Dimensions in mm (inches)
(2/2 EO 4" configuration illustrated)
20 3 (8.0)
I nlet - pilot
)5
7. 6 ( 5.1 7 1
)0.
)5
)52.8( 01
7 .21( 4 2 3
4 ( 6 .101 ø
2
Closed
Open
For your convenience,
1 63.5 (6.43)
Operation and Maintenance
327 (12.875) instructions are included
with each valve.
33
Maxseal Solenoid Valves.
Optional Valve Features.
34
Special Valve Features.
1 2 3 4 5 6 7 8 9 10 11 12
Horizontal Mounting.
35
Intrinsic Safety.
36
Hazardous Area Installation Guidelines.
A simplified appreciation of hazardous area types
and risk levels involved.
The ultimate decision as design engineer is to Most countries or trade recognized authorizing
to what constitutes a ensure that emergency areas have their own body, such as BASEEFA
hazardous area (or zone) shutdown apparatus certifying authorities. in the UK, and enjoy
rests with the company (ESD), e.g. Maxseal Hazardous area instal- wide global acceptance,
chemist, usually in solenoid valves, lation standards in force except in the USA and
consultation with health complies with operating in the EU are written by dollar areas where
and safety executives or speed and zoning CENELEC1/IEC2. They American standards
an authorizing body. The requirements. can be certified by any prevail.
role of the instrument or
1 2
International Electrotechnical Commission European Committee for Electrotechnical Standards.
Both the risk level and zoning definition are affected by ventilation, quantity and
type of gas (heavier/lighter than air), as well as the need for a heat source to
prompt ignition.
37
Hazardous Area Coding System.
Solenoids should be
selected according to
the standard
identification code for
E Exd IIC T6
hazardous area
equipment.
Other protection methods such as oil immersion (‘o’) or powder filling (‘q’) are
usually associated with products other than solenoid valves.
2. Apparatus or There are 2 main gas Group IIA includes the It should be noted that
Gas Groups. groups: least incendive gases American incendivity
and IIC the most groups go in reverse, A
Group I relates incendive. For being the most
specifically to mining standardization and incendive and D the
applications. safety reasons, valve least.
manufacturers usually fit
Group II applies to all solenoids certified for
applications other than group IIC gases.
mining and is
subdivided into:
Group IIA - Propane
Group IIB - Ethylene
Group IIC - Hydrogen
PHOTOGRAPH COURTESY OF BAE SYSTEMS MARINE LIMITED
38
3. Surface Most gases will not Apparatus
Temperature. ignite without a heat Temperature
source. This could be Classification
any heated object, not
Class Maximum
necessarily a naked
(T)4 Surface
flame, approaching the
Temperature (°C/ºF)5
gas flash point.
T1 450°C/842ºF
T2 300°C/572ºF
Hazardous area
T3 200°C/392ºF
equipment is therefore
T4 135°C/275ºF
designed to limit surface
T5 100°C/212ºF
temperature in
T6 85°C/185ºF
continuous or
intermittent operation,
Maxseal solenoid valves
so as to minimize the
4
‘G’ in Germany. can be installed in
risk of ignition of
5
Based on an ambient ambient temperatures of
surrounding gases.
of 40°C (104ºF). up to 90°C (194ºF)
while still retaining a
T4 rating.
General Note. Hazardous areas standards for dust and fibres (zones 10 and 11) are not covered
here, nor are the USA standards. Please contact FCX Thompson Valves regarding
these types of hazardous areas, and any other matter where installation guidance
or valve selection information is needed.
PHOTOGRAPH COURTESY OF SHELL
39
Maxseal Solenoid Valves.
Valve Flow Characteristics.
Table 1
Flow Coefficients
C • p1 T0
Q = •
√G T1
Critical
Choked
pressure
flow
ratio
Non-choked
flow
Varying
Flow rate
inlet
pressure
p2
41
Maxseal Solenoid Valves.
Valve Flow Characteristics.
As p2/p1 = 0.56, the flow is choked. As p2/p1 = 0.18, the flow is choked.
42
Valve Flow Performance.
Chart 1.
Air Flow, ICO4 1/4", Low Pressure
20 bar max., universal
C = 3.7, B = 0.3, Cv = 0.8 USgpm
90
80
60 20
18
50 16
14
40
Ex. 2 12
30
10
8
20 6
4
10
0
0 5 10 15 20 25
Ex. 1
Outlet pressure (bar g)
Example 1: What is the flow rate at 20 bar inlet and
18 bar outlet pressures (i.e. 2 bar ∆p)?
Answer: 40 N l/s.
Example 2: What is the ∆p at inlet 10 bar and 32 l/s flow?
Answer: 10 - 7 = 3 bar.
Chart 2.
Air Flow, ICO4 1/2", Low Pressure
20 bar max., universal
C = 15, B = 0.35, Cv = 4.2 USgpm
350
300
20
18
200
16
14
150
12
10
100 8
6
50 4
0
0 5 10 15 20 25
Outlet pressure (bar g)
43
Maxseal Solenoid Valves.
Valve Flow Performance.
Chart 3.
Liquid Flow, ICO4 1/4", Low Pressure
20 bar max., Cv = 0.8 USgpm
Fluid water at density 1 kg/l
70.0
60.0
50.0
Flow rate (N l/min) water
40.0
30.0
Inlet pressure (bar g)
20.0 20
18
16
14
12
10.0 10
8
4 6
2
0.0
0 5 10 15 20 25
Outlet pressure (bar g)
Chart 4.
Liquid Flow, ICO4 1/4", High Pressure
207 bar max., Cv = 0.28 USgpm
160.0
140.0
120.0
Flow rate (N l/min) water
100.0
80.0
207 220
40.0 160 180
120 140
80 100
40 60
20.0 20
0.0
0 50 100 150 200 250
Outlet pressure (bar g)
44
Chart 5.
Flow Test, ICO4 1/4"
90
80
70
R
Q
60
N
P
Flow rate (N l/s)
M
O
50
I L
J K
40
H
30
D G
20
B C F
A E
10
0
0 5 10 15 20 25
Outlet pressure (bar g)
45
Maxseal Solenoid Valves.
Valve Flow Performance.
Chart 6.
Flow Test, ICO4 1/2"
At 10 bar inlet pressure for lift of 0.055"
200
120
100
80
60
40
20
0
0 2 4 6 8 10 12
Outlet pressure (bar g)
Chart 7.
Flow Test, ICO4 1/2"
At 20 bar inlet pressure for lift of 0.055"
400
Actual flow rate
350
250
200
150
100
50
0
0 5 10 15 20 25
Outlet pressure (bar g)
46
Maxseal Solenoid Valves.
Conversion Chart.
To convert into
Unit (Symbol) Unit (Symbol) Multiply by
To convert from
Unit (Symbol) Unit (Symbol) Divide by
47
FCX Thompson Valves designs and
manufactures exclusive valve products
for the most demanding applications.
We offer cost-effective integrated
product packages, supported by the
resources of the FCX Flow Control
division.
Maxseal Solenoid Ashford Bellows-
Valves Sealed and Gland
Packed Needle Valves
Resilient, low power and Manifolds
consumption, fast
acting instrument Compact, lightweight
changeover and and robust, widely used
solenoid valves. in nuclear applications.