You are on page 1of 34

MAIN

Gas Engines
Application and
Installation
Guide

G3500–G3300
● Ignition Systems

● Starting Systems

● Engine Protection Systems

LEKQ7257 1-98
G3500-G3300
Ignition Systems
Variable Timing for Dual Fuel
Ignition Systems in Hazardous Locations
Engine Shutdown
Power for Auxiliary Panels
Spark Plugs
Ignition Systems Gas Engines with EIS incorporate a control
system that senses and reacts to combustion
detonation by controlling ignition timing. An
Caterpillar Gas Engines use a low tension
accelerometer and electronic buffer unit is
ignition system. Individual ignition
mounted on each side of the cylinder block,
transformers are mounted near the spark plug
and is used to sense the detonation level (if
for each cylinder. Each engine is equipped
any). When a level of detonation is reached
with a solid-state magneto or an Electronic
that might damage the engine, the electronic
Ignition System (EIS) to provide a flexible
timing control retards the ignition timing six
ignition system requiring less maintenance
degrees. If the engine continues to detonate,
and more reliability than older breaker-point
the control will provide a signal to shut the
magnetos.
engine down. If the retarded timing
Figure 1 is a diagram showing the major successfully stops the detonation, the timing
components of the Caterpillar Electronic control will begin advancing the timing at a
Ignition System (EIS). The EIS system rate of 1 degree per minute up to the original
monitors engine operation and distributes timing. The timing control will stop advancing
power to the cylinder transformers, to provide if detonation begins again. This allows the
the best engine performance at all engine engine to obtain optimum fuel consumption
speeds. It provides detonation protection and by running close to detonation without
precision spark control for each cylinder. damaging the engine.

Inlet Manifold
Pressure Sensor

G3516
(top view)

Ignition RB Detonation Terminal


Transformers Sensor Box

Digital Diagnostic Tool


(DDT)

Figure 1.

5
The EIS control module sets engine timing The timing is automatically changed by an
according to desired engine timing, customer electrical signal, usually generated by falling
specified parameters, and the conditions in pressure in the primary fuel. The customer
which the engine operates. Timing is must provide the external contacts to signal
automatically adjusted according to EIS or the magneto. See the “Fuel Systems”
speed/timing maps, manifold air pressure, section of this guide for additional
and any detonation. The control module also information.
creates diagnostic codes if a problem
develops in a component or harness.

EIS ignition transformers are located under Ignition Systems in Hazardous


the cylinder valve cover. The EIS control Locations
module sends a pulse to the primary coil of Engines installed in hazardous locations
the ignition transformer to initiate combustion generally fall under the Class I Division 2
in each cylinder. The transformer steps up the category of Article 500 of the National
voltage to create an arc across the spark plug Electrical Code. It reads:
gap. The cylinder valve cover acts as the
ground for the ignition transformer. “A Class I, Division 2 location is a location:

Engine sensors provide information to the 1. in which volatile flammable liquids or


EIS control module. Detonation sensors are flammable gases are handled, processed, or
located on each side of the engine and used, but in which the liquids, vapors, or
continually monitor the engine for gases will normally be confined within
combustion detonation. A speed/timing closed containers or closed systems from
sensor provides accurate spark timing and which they can escape only in case of
engine speed information. A special accidental rupture or breakdown of such
speed/timing ring is located on the rear, left containers or systems, or in case of
camshaft on G3500 engines or on the front of abnormal operation of the ventilation
G3400 camshafts. An intake manifold air equipment; or
pressure sensor provides engine load
2. in which ignitable concentrations of gases
information.
or vapors are normally prevented by
The timing is set by connecting the positive mechanical ventilation, and which
Caterpillar Digital Diagnostic Tool (DDT) to might become hazardous through failure or
the engine to electronically set the timing. abnormal operation of the ventilation
The DDT is available through the price list. equipment; or
The DDT is also used to monitor engine
3. that is adjacent to a Class I, Division 1
speed, detonation level (if any), and
location, and to which ignitible
diagnostic codes.
concentrations of gases or vapors might
occasionally be communicated unless such
communication is prevented by adequate
Variable Timing for Dual Fuel positive-pressure ventilation from a source
The recommended timing varies with fuel of clean air, and effective safeguards
composition. Serious engine damage could against ventilation failure are provided.”
result if the timing is not changed when the
fuel is switched for example, from natural gas
Basic difference between Division 1 and
to propane or digester to natural gas. To allow
Division 2 is:
automatic timing adjustment when the fuel is
changed, EIS offers a dual timing switch. • Division 1 – flammable gases are always
A dual timing magneto is available as well. present.

• Division 2 – flammable gases may be


present.

6
When an engine is installed in such a location, of normally closed switches in the primary
shielding of the ignition system wiring or wiring is one method of temporarily
usage of approved ignition system interrupting ignition to identify a misfiring
components may be required. Many cylinder. If devices are incorporated in the
Caterpillar Gas Engines have attachments shielded system for troubleshooting purposes, the
providing an ignition system that is CSA primary of the magneto must never be
approved for Class I, Division 2,GpD, grounded to interrupt the ignition. This would
locations. CSA approval is a Canadian most likely cause failure of solid-state
requirement for engines operating in components within the magneto.
hazardous locations in Canada. CSA approval
is also recognized in Division 2 locations
outside Canada. Consult factory for
Engine Shutdown
availability.
Accomplish normal shutdown by shutting off
The basis for the CSA attachment design is to the fuel supply. This allows the engine to
either prevent hazardous atmosphere from consume the fuel trapped between the shutoff
coming in contact with arcing or sparking valve and cylinder. It also prevents raw fuel
devices or to contain an explosion, within the from being pumped into the exhaust system.
engine itself. This is accomplished on Raw fuel in a hot exhaust system presents the
Caterpillar Gas Engines by special metal potential for explosion. Stopping the ignition
conduit harness assemblies for the ignition system to cause engine shutdown should be
system and engine wiring harnesses. Special utilized only for emergencies.
explosion-proof transformers and cylinder
head components have been developed to
contain any potential explosion in the head. Power for Auxiliar y Panels
Applications not having a 24 VCD electrical
The Caterpillar EIS system is available in a
power source, such as gas compressors at
CSA approved configuration. This system
remote sights, must find some source of
varies from the standard EIS system by
electricity to power auxiliary panels. The
offering special ignition coils and a terminal
power source has often been magneto.
box located on top of the EIS control module.
Unlike most other engines, no pin is provided
With the CSA system, no shutoffs, monitoring
on the G3500 LE magneto for auxiliary power.
systems, start/stop logic or gas shutoff valves
This engine requires all the magneto power
are provided. The functions must be provided
available in order to operate the ignition
by the customer. The required shutoffs are
system. The electronic nature of its control
jacket water temperature (104°C, 220°F), oil
system requires that a 24 VDC power source
pressure (15 psig at low idle, 40 psig above
be available for engine operation. The power
1000 rpm), and overspeed (lesser of 10%
source provided for the engine's control
above maximum engine speed or maximum
system can also be used to operate auxiliary
driven equipment speed).
panels.
The CSA terminal box contains warning,
Stoichiometric engines have a pin available on
shutdown, and power lamps and a diagnostic
the magneto that can be used to provide
reset switch. All of these may be remote
power for auxiliary panels. This pin provides
mounted by the customer.
180 VDC with a maximum current draw of
For magneto systems with the CSA 20mA. As with the low emission engine, spark
attachment, troubleshooting can be more plug life will be decreased if the magneto is
difficult. A standard transformer can be used to power auxiliary panels.
installed temporarily so that a timing light can
For all engines with Caterpillar EIS, a 24 VDC
be triggered from the exposed high tension
power source is necessary.
lead. Detecting a misfiring cylinder is more of
a problem with a shielded system. Installation

7
Spark Plugs
Spark plugs for Caterpillar Gas Engines have
been specifically developed to meet the
ignition needs of a given engine. Failure to
use proper spark plugs, or failure to properly
maintain the park plugs will affect the
engine's fuel consumption, emissions, and
stability. This is why the spark plugs must be
maintained according to the specified
maintenance schedule. Good maintenance
practices can be found in Systems Operation
Testing and Adjusting Manual for your
engine.

Note: The maximum ambient air temperature


for magneto operation is 85°C (185°F).

8
G3500-G3300 Starting Systems
General Starting Information (Electric, Air, and Gas
Driven Starters)
Cranking Torque
Breakaway Torque
Variables that Affect Length of Engine Start and
the Cranking Torque
Types of Starting Systems
Minimum Requirements for Sizing Support
Equipment
Air or Gas Starting Systems
System Description
System Operation
General Installation Guidelines
Ferrous Starting Systems (Natural Gas as the
Starting Media)
Maximum Starter Exhaust Back Pressure
Exhaust Shields for Vane Starters
Selecting the Proper Starter: Size, Type and
Quantity
Free Air Consumption for Bare Engine
Sizing Support Equipment

CONTINUED
Electric Starting Systems
Batteries
Battery Charger
Cable Size
Breakaway Torque
Cranking Torque
Ratio of Engine to Starter Speed
Ratio of Engine and Starter Torque
Automatic Start Stop
Ten Second Starting
Starting Aids
Jacket Water Heaters
Oil Heaters
Starting Systems How to use the starter performance
information for cranking and breakaway
torque will be discussed in the section,
Selecting the Proper Starter: Size Type and
General Starting System Quality.
Information (Electric, Air, and
Breakaway Torque
Gas Driven Starters) Engine breakaway torque refers to the torque
There are two major types of starting systems required to begin rotating the crankshaft.
available for Caterpillar Engines - air and
electric. Starter breakaway torque refers to the
maximum torque a starter can generate at or
The choice of the starting system depends on near zero rpm. It is important to ensure that
the availability of the starting energy - ie. the starter breakaway torque is larger than
batteries and a method to charge them versus the sum of the engine and auxiliary load
air or gas of sufficient pressure and flow. breakaway torque. Since breakaway torque
Another criteria may be additional parasitic can vary widely, it is best to include a
starting load from the driven equipment. Air breakaway torque margin when handling
starters can generally provide more starting auxiliary loads. The following equation should
torque and are typically used when parasitic be used as a guideline to assure proper
driven loads are encountered. breakaway torque margin. The values used
The first sections of this module will describe for Teng brk and Taux brk should be values
the formulas to size an air starting system. representing worst case conditions under
The second section will discuss electric which an engine is expected to start.
motors and their performance. Even though Tstart brk > (1.4)[Teng brk +Taux brk]
the examples given are for sizing the air
system of a G3512 engine, the principles are where,
the same to size the air system for any
gas engine. Tstart brk = starter breakaway torque output

Cranking Torque Teng brk = engine breakaway torque req


Table 1 shows the torque requirements to
Taux brk = auxiliary breakaway torque req
crank an unloaded gas engine.

Cranking
Torque (ft-lbs @ 100 or 150 rpm)
Variables that Affect Length of Engine
Breakaway SAE 30 Wt Oil Start and the Cranking Torque
Engine Model Torque (ft-lbs) 0°C (32°F) 10°C (50°F) Size the starting system for an engine to meet
G3304 110 160 110 the most demanding conditions under which
G3306 180 205 150 a specific engine is expected to start. To
G3406 270 375 225 account for the variability, consider the
G3408 310 440 260 following guidelines:
G3412 475 600 385
1) Engine Size: As the number of cylinders
G3508 750 800 630
increases, the torque requirements to
G3512 920 1160 765
crank the engine increases. The crank
G3516 1140 1400 950
torque curves for each engine must be
Note: Oil Temperature and Viscosity are major contributors to
the actual amount of torque needed to crank the engine at consulted when sizing a starting system.
the specific speed. Breakaway torque is independent of oil
viscosity or temperature. 2) Engine Application: Various applications
Table 1. Engine Breakaway and Cranking Torques. have different auxiliary loads during the
start up. The auxiliary load torque curve
Note: The temperature and oil viscosity are the will affect the time to accelerate the engine
largest factors that affect the cranking torque to the minimum recommended cranking
needed to start an engine. Higher oil rpm.
temperatures and less viscous oil require less
torque to turn the engine. 11
3) Fuel Composition: Fuel composition 1) The starting system must accelerate the
varies widely from site to site. Fuels with engine and its auxiliary load to the
low energy content will lengthen the Minimum Cranking RPM in five seconds.
cranking time as these fuels burn slower
and cylinder firing during start-up is more 2) The starter(s) must be able to sustain the
erratic than when using natural gas. Minimum Cranking RPM for a minimum of
twenty-five seconds.
4) Cold Ambient Conditions: Cold
temperature increases the viscosity of the Note: Electric starter engagements longer than
engine oil. The torque demand of the 30 seconds or repeat 30 second start attempts
cranking engine increases as oil will overheat starters. Start attempts longer
temperature decreases. Start length will than 30 seconds may indicate engine problems.
increase due to cold temperatures. Note:
Some applications may require multiple, back
The breakaway torque is not influenced by
to-back start capability. In this case, multiply
oil temperature.
the above one-start minimum
Types of Starting Systems requirements by the total number of
There are two types of starting systems required start attempts. Thus, if a site must
available on most gas engines. Air or natural be capable of three back-to-back start
gas driven starters may be selected for any attempts, the support equipment should be
gas engine model. An electric motor starting capable of three, five second acceleration
system is also available on all engine models intervals and three, twenty-five second
of the G3500, G3400 and G3300 families. intervals of sustained engine speed equal to
or greater than the Minimum Starting RPM.
Minimum Requirements for Sizing
Support Equipment
When sizing a facility’s support equipment for
a starting system (i.e. air tank volume, air
Air or Gas Starting Systems
tank location, pipe diameter, pipe length, System Description
compressor size, battery quantity and Figure 2 shows a typical air starting system.
capacity), the equipment must be capable of Table 2 contains component descriptions.
meeting the following minimum
requirements for one start attempt:

Air Starting System Schematic

Plant
Air Supply

Check Valve Starting Air

Engine

Starting
Generator Motor
Engine Motor
Compressor

Oiler Solenoid Strainer Regulator Manual Pressure


Valve Shutoff Valve Shutoff Valve

Figure 2. Air Starting System


12
Component Name Function/Description
engine. The 7C0330 air start control is
Pressure Regulator A pressure regulator maintains
necessary to interface with a Caterpillar
constant pressure to the air starter. supplied control panel and air starter and air
Manual Shutoff Allows starting system to be isolated prelube group. The following describes the
Valve from air supply during maintenance or events that occur with the Engine Status
no use periods.
Control (ESC). A similar sequence should
Strainer Removes particles/contaminants from
air stream. A 40 mesh is recommended occur if a customer supplied panel is used.
for vane starters; a 150 mesh is When the engine is signaled to start either by
recommended for turbine starters.
placing the Cat four-position engine panel
Relay Valve Controls flow of air to starter
switch to the manual position or by activating
Lubricator Used only with a vane starter.
Lubricates internal components of a remote start switch (Cat switch in the auto
vane starter. Turbine starters are position), the following cycle occurs:
internally lubricated.
Solenoid Valve Valve controls start pinion engagement 1. A solenoid controlled valve (part of
and main air supply to starter. Valve is
three way normally-closed solenoid. 7C0330) is activated by the ESC to initiate
Pressure Relief Protects starters and relay valve from the prelube cycle. If there is no prelube
pressure spikes in system that may system, this valve will engage the air
cause damage to components.
starter.
Table 2. Start System Schematic, Component
Description 2. After prelube is complete (measured by an
oil pressure switch), the ESC initiates a
There are two main air paths in the starting
system: cranking cycle.

1) The main air supply line supplies the air 3. After cranking begins, the engine status
starter motor with pressurized air that control opens the gas shutoff valve
serves as the source of power for the (GSOV).
starter. 4. When the speed of the engine increases to
2) The control air supply line supplies air to 400 rpm, the ESC disengages the prelube
engage the starter pinion into the flywheel, group.
and opens the relay valve to allow air to 5. An overcrank timer will terminate cranking
pass through the main air line to the if the engine does not start in a preset
starter. Some engines smaller than the amount of time (programmable).
G3516 have a manually operated control
valve to permit supply air to the starter. Start Cycle with Continuous Prelube
System — G3500 Engines
System Operation
For factory supplied electric motor driven by
Start Cycle for the G3516 Engine continuous prelube systems, power to the
with Intermittent Air Prelube System prelube pump is removed by a signal from the
The Engine Status Control (ESC) panel or control panel when a start is initiated. See
generator control or customer supplied Figure 3. The schematic for the prelube
control panel will provide the logic to start the
Oiler (used with vane starters)
Engine
Oil
Pressure
Relay
Valve
Starter SV

+ Electric Air Start-Solenoid

Air or Prelube Pump


Gas
Supply SV

Slave Valve

Figure 3.

13
system is similar to the G3516 with 7) Air cranking systems may freeze at low
Intermittent Air Prelube except the following ambients. Water vapor in compressed air
components are deleted: prelube pump, freezes during expansion in temperatures
engine oil pressure relay valve, and the lower below 0°C (32°F). A dryer at the
slave valve. compressor outlet or a small quantity of
alcohol in the air receiver tank prevents
Start Cycle — G3300 and G3400 freezing. In addition to this precaution it is
Most G3400 and G3300 air starters are also recommended that traps to contain oil-
supplied with a shipped loose manual starting water be built into the lines with small
valve. The G3412 C LE Industrial engine has slopes toward these traps. These traps
an optional Engine Status Control Panel and should be drained periodically or have
air start control (7C0330) which is similar to automatic drain systems.
the G3500 system without prelube.
8) Tandem or compound engines use at least
General Installation Guidelines
two starters and solenoid valves. Valves
1) A leak in the air system may cause the
should be spaced equal distances from
system to lose pressure over a period of
their respective motors for coordinated
time. To avoid air receiver pressure loss,
motor engagement. When a single solenoid
ensure all connection points do not leak air.
controls the air to both motors, piping
A check valve between the plant air supply
between the valves and each motor must be
and receiver assures that failure of the
of equal length.
plant air supply will not deplete the backup
supply. 9) Air receivers should meet appropriate
building and construction codes. Generally
2) Use proper sealant on all threaded
ASME specifications should be used.
connections throughout the system.
Proper gauges and safety valves are also
3) Always run air supply lines from the top of needed and should be checked periodically.
the air receiver, never at or near the Ferrous Starting Systems (Natural
bottom. Damage to the starting system
Gas as the Starting Media)
could result if piping is routed from the
Typically in the gas compression industry
bottom of the air receiver tank due to the
compressed wellhead (natural) gas is used to
collection of water in the bottom of the
power the starter. Since wellhead gas is less
receiver tank.
dense than air, approximately 40% more gas is
4) The typical diameter of pipe to the factory needed at the same pressure to have the
connection of the G3500-G3300 air starters same starting power as air.
is 1 1/2 inches. If the air receiver is a
Standard starter supply and control lines may
substantial distance from the engine, larger
be constructed with rubber hoses, brass
lines should be used to minimize pressure
fittings, and aluminum valves. These
drop. When applicable, use the largest pipe
components may need to be replaced to meet
diameter practical to route exhaust air away
local and/or API codes. Consult the local
from the starter.
Caterpillar dealer.
5) Whenever using natural gas to operate the
Starters can emit considerable noise if not
starters, there must be no leaks in the inlet
muffled. For natural gas operation, the
or exhaust piping. All starter exhaust must
exhaust must always be piped away from the
be piped away to a safe area.
engine. The drive housing vent plug must be
6) Use a flexible connection between engine replaced with a suitable tube that is connected
piping and installation piping to isolate from to the air start exhaust system. Venting the
engine vibration. drive housing reduces the possibility of
trapping natural gas in the starter housing.

14
Maximum Starter Exhaust Back starting rpm rather quickly. A 5 second
Pressure acceleration time is considered adequate. This
The maximum recommended starter exhaust may need to be shortened for standby
back pressure is 5 psig. Back pressure larger applications.
than 5 psig may significantly decrease starter
performance. Several methods may be used Generally one starter is adequate to start any
to minimize exhaust back pressure: G3500 through G3300 engine. A two starter
option is available on the G3500 engines and
1) Use an adequate pipe size to carry exhaust may be necessary in cold weather or when
gases. high parasitic loads are encountered.

2) Minimize the number of restrictions Step 1: Determine Engine


(bends, expansions, and contractions) in Breakaway Torque and Parasitic
the starter exhaust piping. Breakaway Torque Requirements
Add the auxiliary (driven) breakaway
3) Keep the starter exhaust pipe as short as requirements to the base engine breakaway
possible. torque shown in Table 1. This value will
determine the total breakaway torque that the
4) If a silencer is used, either factory installed starter must provide to begin to turn the
or after-market, ensure the pressure drop is engine and auxiliary load.
low. The pressure drop across a silencer
may significantly increase over time due to Step 2: Determine Starter
the accumulation of oil and must be Breakaway Torque
cleaned or replaced periodically. The starter breakaway torque must be larger
than the total of the engine and auxiliary
Exhaust Shields for Vane Starters equipment to begin the crank cycle. Use the
Vane starters are lubricated by atomizing oil following equation as a guideline to ensure
in the pressure side air stream. As the air proper breakaway torque margin for the
exhausts through the starter’s silencer, the oil G3500 to G3300 engine.
mist can cause an undesirable oil spray on the
engine and surrounding area. To minimize Tstart brk>(1.4)[Teng brk +Taux brk ]
the oil spray, starter exhaust covers are
available from the factory. Periodically inspect where,
and clean the covers to ensure proper starter Tstart brk = starter breakaway torque output
performance.
Teng brk = engine breakaway torque req
Selecting the Proper Starter: Size,
Type, and Quantity Taux brk = auxiliary breakaway torque req
Choosing the starter type is many times a
decision based on the starting media The breakaway torque for G3500 air starters
available, such as an existing air supply in a is given in Figure 4 and G3400 and G3300 are
building or wellhead gas available at the job given in Figure 5. These performance curves
site. Economics and reliability are important will be discussed in the section entitled
factors in choosing an air or electric starter Starter Inlet Pressure.
especially if no air supply is available. The
parasitic (auxiliary) driven equipment will The relationship of the starter torque to the
also be a major factor in the choice of air or torque applied to the engine (and auxiliary
electric starters. equipment if direct coupled) is:
Starter Torque = Torque to Engine & Driven Eq 3
The size of the starter is critical. The starter
Number of Pinion Teeth/ Flywheel Teeth.
must have enough breakaway torque to begin
rotating the engine and driven parasitic load. This formula will work for determining either
Once the engine and driven equipment begin the breakaway torque needs or the cranking
to turn, the starter must accelerate the engine torque needs of the starter.
and driven components to the minimum

15
300 100
Torque
Flow
Torque at 90 2000
150 psig Flow at 150 psig
BHP at 150 psig
250
80

120
70
200 1500
120 120
Torque (ft-lb)

Horsepower

Flow (scfm)
60
Breakaway 90
Torque
150 50
90 90 1000
40

100
30

500
20
50

Slowest Example 2, 10
Speed Step #3
0 0 0
0 1000 2000 3000 4000 5000 6000 7000
Speed (rpm)

LEGEND Pinion Teeth =12


_________ Torque (3500 Flywheel Teeth = 183)
- - - - - - - - - Flow

Figure 4. G3500 Air Starter (Vane Type) Performance Curve

200 50 1500
Torque
Flow

Torque at
150 psig Flow at 150 psig 40
BHP at 150 psig
150

1000
120
120
30
Torque (ft-lb)

Flow (scfm)
Horsepower

120
100
90
90
20
90
500

50
10

0 0 0
0 1000 2000 3000 4000 5000
Speed (rpm)

LEGEND Pinion Teeth =11


_________ Torque (3408 Flywheel Teeth = 156)
- - - - - - - - - Flow (3406 Flywheel Teeth = 136)
(3300 Flywheel Teeth = 113)

Figure 5. G3400, G3300 Air Starter (Vane Type) Performance Curve

16
Example 1. Starter Sizing for Step # 3: Sizing Starter for Engine
Breakaway Torque Crank Speed
An air supply source of 90 psi is available to The starter must be able to crank the engine
start a G3512 engine. The lowest ambient to a minimum of 150 rpm for G3500 to G3300
temperature will be 50°F and 30 wt oil will be engines with magneto ignition systems.
used. The engine will drive a water pump Engines with the Caterpillar Electronic
through a clutch so the breakaway torque is Ignition System should be designed for a
negligible. The customer prefers an air minimum cranking speed of 100 rpm. Speeds
starter. What is the breakaway torque much larger than these design minimums will
required for this application? Does a single result in excessive air consumption and
vane starter with 90 psi inlet air pressure have reduce the life of the starters.
sufficient energy to rotate the G3512 engine?
The final engine crank speed is the
Consulting the Engine Breakaway and intersection of the necessary engine and
Cranking Torque Chart, Table 1. The auxiliary crank torque with the starter
breakaway torque for the G3512 engine is cranking torque capability for a given air flow
920 lb ft. The auxiliary equipment has and pressure. For simplicity we should design
negligible breakaway torque. The starter a starter system designed for the above
should be able to produce 1.4 times 920 lb ft = minimum cranking speed. In actuality the
1288 lb ft. for torque. final cranking speed may be slightly higher or
lower than the design speed. Examples are
The starter torque = 1288 3 12 (pinion teeth)/ 183
given below to help illustrate the flow and
(number of flywheel teeth)
pressure needed for the application at hand.
The starter torque = 85 lb ft.

Next consult the Air Starter Torque Chart


Figure 4, for the starter’s capability at 90 psig.
Use the torque of the slowest listed speed of
the starter as the breakaway torque. The
G3500 air starter (vane type) is 145 lb ft. Thus
one air starter for the G3512 engine will
provide sufficient breakaway torque.

Free Air Consumption m3/s (ft3/s ) For a Bare Engine at 10¡C (50¡F)
690 kPa (100 psig) 862 kPa (125 psig) 1034 kPa (150 psig)
Engine Model To Starter Starter Starter P min kPa (psig*)
G3304 .16 (5.8) .19 (6.8) .22 (7.7) 242 (35)
G3306 .17 (5.9) .20 (6.9) .22 (7.8) 248 (36)
G3406 .18 (6.2) .21 (7.3) .23 (8.3) 276 (40)
G3408 .18 (6.4) .21 (7.5) .24 (8.6) 269 (39)
G3412 .25 (9.0) .30 (10.3) .33 (11.8) 207 (30)
G3508 .26 (9.3) .31 (10.8) .36 (12.6) 310 (45)
G3512 .28 (9.8) .32 (11.4) .38 (13.3) 344 (50)
G3516 .30 (10.5) .34 (12.1) .40 (14.1) 448 (65)
G353 .19 (6.6) .22 (7.8) .25 (8.9) 276 (40)
G379 .26 (9.3) .31 (10.8) .36 (12.6) 207 (30)
G398 .28 (9.8) .32 (11.4) .38 (13.3) 242 (35)
G399 .30 (10.5) .34 (12.1) .40 (14.1) 345 (50)
Note: 1. Add to the G399 and G3516 .0283 m3/sec
(1 cu ft/sec) of air consumption for the air operated oil prelubrication pump.
This pump will normally operate 2 to 10 seconds before the engine begins to crank.
2. For start control systems with a purge cycle, include the time of the purge sequence to estimate starting time to obtain total
estimated starting time.
*Minimum air storage tank pressure required to sustain cranking at 100 rpm.
Table 3.

17
Free Air Consumption for a Bare G3512 at 50°F and 100 psig air pressure to
Engine the starter, the G3512 will need 9.8 cu ft/sec
Quantity of free air required per start depends of air to turn the engine at 100 rpm. Thus for
on: 30 seconds the air supply will be 30 times 9.8
or 294 cu ft of air at 100 psig. If the pressure
Time Required to Start – Time per start drops below the minimum pressure shown in
depends on engine model, condition, the rightmost column, the engine cranking
ambient air temperature, oil viscosity, fuel speed will most likely fall below a speed
type, condition of fuel system, purge cycle, which will allow the engine to start.
and cranking speed. Ten to fifteen seconds
is typical for gas engines at 25°C (80°F), Note: The flow and pressure to maintain
but restart of hot engines normally takes cranking speed is drastically impacted by the
less than four seconds. engine oil temperature and viscosity.
Significantly more pressure and flow would be
Free air consumption – Free air needed to start an engine at lower oil
consumption depends to some extent on temperatures or with higher viscosity oil. Since
these same variables and also on the the values for combinations of these two factors
pressure regulator setting. The correct increase starter needs dramatically , it is
setting is 620 to 690 kPa (90 to 100 psi), recommended that if at all possible 50°F be the
with the higher pressure used to improve minimum oil temperature and 30 wt oil be the
starting under adverse conditions. 0.14 to heaviest (thickest) oil when starting a gas
0.42 m3/s (5 to 15 cu ft) is typical for engine.
engines from 37 kW to 1194 kW (50 hp to
1600 hp). Sizing Support Equipment
Starter Inlet Pressure, Pstarter inlet
Purge Cycle To crank the engine and its auxiliary load to
Some start/stop controls call for a “purge” the recommended minimum speed, the initial
cycle. Units are purged to remove gas which and final starter inlet pressure during the
may have become trapped in the exhaust and start cycle must be determined. These
could be ignited if hot combustion gases pressures and the accompanying flow will
entered the exhaust system. During purging, determine the size of the receiver tank. For
the engine is cranked but the gas shutoff these examples, a 30 second start cycle will
valve is not open. Only fresh air enters and be used. Use the following procedure to
exits the engine to clean the exhaust system determine the required initial and final starter
of any possible gas. The purge cycle time inlet pressure and volume of air to start an
must be added to the seconds of starting time engine.
to obtain the total starting time and proper
starter air consumption needed. Generally the pressures and flow determined
during cranking will create sufficient starter
Example 1. Free Air Consumption of
breakaway torque to begin rotating the
Bare Engine engine. After the cranking pressure and flow
Using the 90 psig air pressure to the G3512 is determined, the starter’s breakaway torque
with EIS vane type starter, what is the will be compared to the engine and auxiliary
necessary flow to sustain a 30 second start load breakaway torque to be sure the starter
sequence? is adequate.
A fast method to determine the air flow is to Example 2.
look at the Free Air Consumption for a Bare Application: G3512 with EIS driving a direct
Engine (Table 3). This chart will permit a fast coupled water pump. The minimum ambient
approximation of the necessary air is 50°F and 30 wt oil will be used. The
consumption. Note: Seldom does air pressure breakaway torque of the water pump is
remain constant during a start cycle , thus the negligible but the cranking torque of the
values from this method will be slightly water pump is 50 ft lbs at 100 engine rpm.
lowered than calculated later using air tanks
which have limited size and for which
pressure drops occur during cranking. For a
18
Example 2, Step 1: Determine The starter’s torque is multiplied by the ratio
Starter Speed of the flywheel teeth to the pinion teeth on the
starter. The formula is:
Consult the Engine Breakaway and Cranking
Torque, Table 1. The G3512 EIS will require Starter Torque/Pinion Teeth = Cranking Torque/
765 ft lbs of torque at 100 rpm cranking speed Flywheel Teeth OR Starter Torque = Cranking
and 50°F with 30 wt oil. Torque 3 Pinion Teeth /Flywheel Teeth

The starter speed = Engine Speed 3 Flywheel Thus Starter Torque Required =
Teeth/Pinion Teeth 840 lb ft. 3 12/183

Starter Speed = 100 rpm 3 183/12 (Flywheel Starter Torque Req = 55 ft lbs
Teeth and Pinion Teeth are found in Air Starter
Performance Information Figure 4.) Example 2, Step 3: Starter Inlet
Pressure Required
Starter Speed =1525 rpm See Figure 7 for a diagram of an air starter
This is the speed of the starter to turn the engine
system both customer and factory
at 100 rpm.
components.

Example 2, Step 2: Starter Cranking Consult Figure 4, G3500 Air Starter (Vane
Torque Required Type) Performance Curves. Look across the
horizontal axis to the starter speed of
Now it is necessary to determine the torque 1500 rpm. The necessary pressure for the
required by the starter to be able to provide starter will be the intersection of the line
1525 rpm to continue cranking the engine at drawn straight up from the 1500 rpm speed
100 rpm. and a horizontal line drawn across from the
55 ft lbs torque point on the left vertical axis.
Consult the Engine Breakaway and Cranking The intersection of these two points is less
Torques, Table 1. than 90 psig. Since only 3 pressures: 90, 120
and 150 are listed, use the 90 psig curve.
The cranking torque for the G3512 at 100 rpm
with an oil temperature of 50°F and 30 wt oil
is 765 ft lbs of torque. Add the driven
equipment torque of 75 ft lbs and the total is
840 ft lbs of torque.

Air Receiver Customer Connection Air Starter

Pstarter exhaust

Facility Piping Factory Piping

Preceiver Punion Pstarter inlet


Figure 7.

19
Example 2, Step 4: Air Flow 1) Preceiver = Pstarter inlet + (pressure drop of factor y
Required piping) + (pressure drop of facility piping)
Once again consult Figure 4, G3500 Air
Starter (Vane Type) Performance, to where:
determine the air flow required. It is known pressure drop of factory piping = pressure
that 90 psig air pressure is needed to crank drop from customer connection to the
the G3512 EIS engine with a direct driven starter inlet at full flow conditions.
water pump. Follow a line upward from the pressure drop of facility piping = pressure
1500 rpm speed on the horizontal axis of the drop from the air receiver to the starting
90 psig Flow Curve (note the “Flow at system’s customer connection at full flow
150 psig” in the upper right hand corner and conditions.
use the 2nd curve below it marked “90”). The
2) Some restriction to air flow across the
flow of air at 90 psig will be approximately
lubricator (used on vane starters) and to
800 scfm.
pipe fittings and bends be encountered at
Example 2, Step 5: Breakaway the customer connection to the starter.
Torque Check Because of the high flow rate in the region
Using the rule of 1.4 times the engine and between Ppipe union to Pstarter inlet, the
driven load breakaway torque, the starter pressure drop in this area should be
must provide a minimum of 920 ft lbs of included. To approximate the pressure
torque (Breakaway Torque of G3512 from drop of the factory piping at full flow
Table 1) 3 1.4 = 1288 ft lbs of torque. conditions let: pressure drop of factory
piping = 103 kPa (15 psig)
Consult the G3500 Air Starter Performance
Curves, Figure 4. The starter is capable of a 3) To calculate the pressure drop associated
maximum torque of 140 ft lbs at 90 psig. with the facility’s piping one must know the
pipe size, number of bends, and location of
Note: Since the breakaway torque of the air the air receiver. After this is known, the
starter is mostly a function of pressure and not pressure drop using Qfacility piping can be
speed, simply look at the lowest speed and calculated. Use this method if exact
highest torque given for the pressure being pressure drop information is necessary.
considered. This is the breakaway torque of the
starter. The maximum allowable pressure at the inlet
to a vane starter is 150 psig (dynamic) for
The necessary starter torque is determined starters used on G3500-G3300 engines.
by the following formula:
For a vane starter system without an air
Necessary Starter Breakaway Torque= Breakaway pressure regulator, the air receiver can not be
Torque 3 Pinion/Flywheel Teeth above 150 psig. During the initial instance of
start-up, Preceiver and Pstarter inlet are equal as
Necessary Starter Torque =
there is no dynamic pressure loss. An air
1288 3 12/183 = 85 ft lb
receiver pressure above 150 psig would
overpressurize the vane starter.
Since the starter is capable of 140 ft lbs of
If an air pressure regulator is used in
breakaway torque and only 85 ft lbs is
conjunction with a pressure relief valve, the
necessary, only one air starter is sufficient.
air receiver pressure can be increased beyond
Air Receiver Pressure, Preceiver 150 psig. The pressure regulator reduces the
Prior to determining the air receiver pressure, pressure of the incoming air while the
the air pressure at the starter inlet, pressure relief valve protects the starters
Pstarter inlet, must be calculated. Refer to from overpressurizing. Higher tank pressure
section titled Starter Inlet Pressure, Pstarter inlet is desirable as it reduces the receiver’s size.
and Figure 6. See examples below in the section Air
Receiver Volume.
Use the following procedure to determine the
required air receiver pressure.
20
Example 2, Tank Receiver Sizing pressure regulator and facility piping yield
Given: For the G3512 application used in less than 150 psig at the customer connection.
Example 2 using a vane starter, the required Thus, a safe tank pressure for the receiver
starter inlet pressure, over 150 psig could be chosen as long as
pressure to the starter inlet does not exceed
Pinlet, is 90 psig and Qfacility piping = 800 scfm.
150 psig. Since there is a drop of 15 psig after
Find: Determine the pressure of the receiver, the customer connection point in the factory
Preceiver, if no pressure regulator is used. piping and lubricator, the regulator must
Determine the pressure of the receiver if a control the pressure to the starter inlet to less
pressure regulator is used in conjunction with than 150 psig or 165 lbs before the customer
a relief valve. connection point.

Solution: No pressure regulator Air Receiver Volume, Vreceiver


From the previous section Air Receiver The air receiver volume is a function of the
Pressure: number of start attempts required and the
length of starts. Based on the section titled
Preceiver = Pstarter inlet + (pressure drop of factor y piping) General Starting Criteria the minimum
+(pressure drop of facility piping) recommended air tank volume needs to be
sized for at least one, thirty-second crank
cycle. The equation to calculate the tank
Preceiver = 90 psig + 15 psig + (pressure drop of volume follows:
facility piping)
Tank vol (m3) =
The maximum pressure of the receiver air flow(m3/s) x crank time (sec) x atm pressure (kPa)
without a pressure regulator is 150 psig, thus, Prcvr,initial(kPa) – Prcvr,final(kPa)
pressure drop of facility piping must be less
than or equal to 45 psig. The pressure drop Tank vol (ft3) =
associated with the customer’s supply pipe air flow(scfm) x crank time (sec) x atm pressure (psig)
(pipe from the air receiver to the engine’s 60 x [Prcvr,initial(psig) – Prcvr,final(psig)]
connection point) should be calculated with
where:
Qfacility piping = 800 scfm. If the result is, say, 20
psig, then a 125 psig tank pressure may be Prcvr,initial is air receiver initial pressure
used. If the result is larger than 45 psig, then
the supply lines will have to be upsized, line Prcvr,final is air receiver final pressure
lengths reduce, or bends removed to lower
the pressure drop to keep pressure to the It is important to note that Prcvr,final must be
starter inlet less than 150 psig. sufficient to crank the engine at the end of the
crank cycle.
Solution: With pressure regulator and
pressure relief valve Prcvr, final = Pstarter inlet + (pressure drop of factor y
Receiver Pressure: piping) + (pressure drop of facility piping) – (allowable tank
pressure drop)
Preceiver = Pstarter inlet + (pressure drop of factor y piping) +
(pressure drop of facility piping) Note: The receiver volume will need to be
larger if an air prelube motor is used. For an
approximate usage of air for the prelube motor
Preceiver = 90 psig + 15 psig + (pressure drop of consult the Free Air Consumption for a Bare
facility piping) Engine, Table 3. For applications where
commercial power is available a continuous
When using a pressure regulator, the air prelube system can be used to reduce the air
receiver pressure is not limited to the supply needs.
starter’s maximum pressure rating of
150 psig. The air receiver pressure can be at
any desired, safe pressure as long as the
combination of the air receiver pressure,

21
Example 2, Air Receiver Sizing shorter start cycle. Caterpillar Electronic
Given: The G3512 EIS engine with direct Ignition may also allow the shorter start cycle
driven water pump using one vane starter. to become commonplace in the future.
The required starter inlet pressure, Pstarter inlet
is 90 psig and the flow is 800 scfm. The Tank vol (ft3)=
customer has chosen a receiver such that 800 scfm 3 30 sec 3 14.7 psig
Prcvr, initial = 160 psig. The pressure drop of 60 sec/min 3 ( 160 psig – 125 psig)
the facility’s piping is estimated at 20 psig.
Tank vol = 168 ft3 (1257 gal)
Find: Determine the minimum tank volume
If a 200 psig tank was chosen:
using a pressure regulator and pressure relief
valve. Tank vol (ft3)=
800 scfm 3 30 sec 3 14.7 psig
Solution: Since only 90 psi to the starter inlet
60 sec/min 3 ( 200 psig – 125 psig)
is sufficient to crank this engine and driven
equipment at 100 rpm (the minimum cranking Tank vol = 78 ft3 (583 gal)
speed), higher pressures to the starter are
not necessary (this will increase cranking
speed but will create inefficient air usage).
Thus installing a pressure regulator upstream
Electric Starting Systems
Electric starting (Figure 8) is the most
of the starter to maintain 90 psi to the starter
convenient to use especially for small gas
inlet is recommended. The pressure regulator
generator sets. It is least expensive and is
should be installed ahead of the lubricator
most adaptable for remote control and
and factory piping.
automation.
Regulator Pressure = 15 psig (factory air Batteries
piping) + 90 psig (air pressure required at Batteries provide sufficient power to crank
starter inlet) engines long and fast enough to start. Lead-
Earlier the air flow for this example was acid types are common, have high output
calculated at 800 scfm at 90 psi. capabilities, and lowest first cost. Nickel-
cadmium batteries are costly, but have long
crank time = 30 sec shelf life and require minimum maintenance.
Prcvr,initial = 160 psig Nickel-cadmium types are designed for long
life and may incorporate thick plates which
Prcvr, final = Pstarter inlet + (pressure drop of factor y decrease high discharge capability. Consult
piping) + (pressure drop of facility piping) - (allowable tank the battery supplier for specific
pressure drop) recommendations.
Prcvr,final = 90 psig + 15 psig + 20 psig Two considerations in selecting proper
Prcvr,final = 125 psig battery capacity are:

Tank vol (ft3)= • The lowest temperature at which the


air flow(scfm) 3 crank time (sec) 3 atm pressure (psig) engine might be cranked.
60 3 [Pinlet,max (psig) - Pinlet,min(psig)]
• The parasitic load imposed on the engine.
Based on the section Minimum Requirements A good rule of thumb is to select a battery
for Sizing Support Equipment, crank time = package which will provide at least four,
30 secs. 30 second cranking periods (total of
2 minutes cranking). An engine should not
Note: A lower crank time of 20 seconds may be be cranked continuously for more than
sufficient if the compressor is capable of a 30 seconds or starter motors may overheat.
reasonably quick fill the receiver tank, the
purge cycle is 5 secs or less, and the fuel is Ambient temperatures drastically affect
natural gas. Field experience will dictate this battery performance and charging
efficiencies. Maintain 32°C (90°F) maximum

22
Suggested Minimum Battery Cold Cranking Amps
12 24-32 1-motor 30-32 2-motor
Battery Voltage
Minimum ¡F -20 30 60 -20 0 60 -20 0 60
G3304 1450 1225 925 725
G3306 1450 1225 925 725
G3406 1225 925
G3408 1300 1225 925
G3412 1300 1225 925
G3508 1300 1225 925
G3512 1300 910 725
G3516 1300 910 725
Note: Use aids below -18¡C (0¡F)
Table 5.

temperature to assure rated output. Impact of Batter y Charger


colder temperatures is described in Tables 4 Various chargers are available to replenish a
and 5. battery. Trickle chargers are designed for
continuous service on unloaded batteries.
They automatically shut down to milliampere
current when batteries are fully charged.

Overcharging shortens battery life and is


recognized by excessive water loss.
Conventional batteries require less than
59.2 mL (2 oz) make-up water during 30 hours
of operation.

Float-equalize chargers are more expensive


than trickle chargers and are used in
Figure 8. applications demanding maximum battery life.
These chargers include line and load
Temperature vs. Output regulation, and current limiting devices,
27°C (80°F) which permit continuous loads at rated
Ampere Hours output.
°C °F Output Rating
28 80 100
Both trickle chargers and float equalize
0 32 65
chargers require a source of A/C power while
-18 0 40
the engine is not running. Chargers must be
Table 4. capable of limiting peak currents during
cranking cycles or have a relay to disconnect
Locate cranking batteries for easy visual during cranking cycles. Where engine-driven
inspection and maintenance. They must be alternators and battery chargers are both
away from flame or spark sources and used, the disconnect relay usually disconnects
isolated from vibration. Mount level on the battery charger during engine cranking
nonconducting material and protect from and running.
splash and dirt. Use short slack cable lengths
Engine-driven generators or alternators can
and minimize voltage drops by positioning
be used, but have the disadvantage of
batteries near the starting motor.
charging batteries only while the engine runs.
Disconnect the battery charger when Where generator sets are subject to many
removing or connecting battery leads. Solid- starts, insufficient battery capacity could
state equipment, i.e., electronic governor, threaten dependability.
speed switches, can be harmed if subjected
to charger’s full output.

23
Cable Size Solution: Cable size must be No. 1 to meet
The start circuit between battery and starting cable length and resistance requirements. To
motor, and control circuit between battery, determine fixed resistance in a parallel circuit,
switch, and motor solenoid, must be within only series connections in one leg of the
maximum resistance limits shown in Table 6. parallel circuit are counted.

Maximum Allowable Resistance .00300 #4 #2 #1 #0 #00 #000

Magnetic Switch and Solenoid Starting .00280

L
LE
Series-Parallel Circuit Switch Circuit Motor Circuit .00260

AL
12 Volt System, 0.048 Ohm 0.0067 Ohm 0.0012 Ohm

R
.00240

PA

L
LE
24 Volt System, 0.10 Ohm 0.030 Ohm 0.002 Ohm

IN
.00220

AL
#0

R
32 Volt System, 0.124 Ohm 0.070 Ohm 0.002 Ohm

PA
.00200

2-
L

OR
LE

IN
.00180 L

0
RA

#0
Table 6. Resistance
PA

2-
in Ohms at .00160
80˚F (27˚C) IN
.00140 00 EL
Not all this resistance is allowed for cables. #0 LL
.00120 2- RA
PA
Connections and contactors, except the motor .00100 00
IN
00
solenoid contactor, are included in the total .00080 2-
#

allowable resistance. .00060


.00040
• Contactors (relays, solenoid, switches) .00020
0.0002 Ohm .00000
0 100 200 300 400 500 600
INCHES
• Connections (each series connectors) 0 2.54 5.08 7.62 10.16 12.70 15.24
0.0001 Ohm METERS

Cable Size vs. Resistance


The fixed resistance of connections and
Figure 10.
contactors is determined by the cable routing.
Fixed resistance (Rf) subtracted from total Breakaway Torque
resistance (Rt) equal allowable cable The electric starter must be able to exceed
resistance (Rc): Rt - Rf = Rc. the torque of the engine and auxiliary in
order to begin rotating the engine. With an
electric starter the voltage and amperage is
important, so that the electric starter can
reach its full potential which is listed in
Table 7. As discussed in the General Starting
System Information section, the starter should
have 1.4 times the sum of the engine and
auxiliary equipment.
Cranking Torque
Table 8 gives the cranking performance of the
electric starters used on the G3500-G3300
engines. Consult these charts to determine
System ......................................................... 24-volt starter speed, volts and amps to the starter
Starting Motor Type.................................... Heavy Duty and the starters torque capability at 100 rpm
Maximum Allowable Resistance ............... .00200
Minus Fixed Resistance — and 1500 rpm engine rpm (150 rpm should be
6 Connections @ .00001...................... .00006 Ohm used for magneto engines and 100 rpm for
Resistance Remaining for Cable .............. .00194
Battery Cable Length ................................. 144 in.
Caterpillar Electronic Ignition System
equipped engines). Compare the capability of
Figure 9. the electric starter to the total of your
particular engine model and auxiliary
Problem: With cable length and fixed equipment cranking torque needs.
resistance determined (Figure 12), select
cable using the following chart (Figure 10).
Use only full-stranded copper wire.
24
Electric Starter Breakaway Performance
Speed Starter/ Potential Torque Potential Torque
Eng Cranking of Starter on Flywheel
Volts at Starter Amps to Starter (rpm) (lb ft) (lb ft)
G3304, G3306
(156 flywheel teeth) Starter Part No. — 1W5516 (12 pinion teeth)
Breakaway* 17 1400 0/0 95 1235
G3406
(113 flywheel teeth) Starter Part No. — 2S7227 and 6V0927 (11 pinion teeth)
Breakaway* 12.5 1400 0/0 100 1027
G3408, G3412
(136 flywheel teeth) Starter Part No. — 4N1062 (11 pinion teeth)
Breakaway* 12.5 1400 0/0 100 1236
G3508, 12, 16
(183 flywheel teeth) Starter Part No. — 7C0527, 6V4246 (11 pinion teeth)
13 1400 0/0 92 1530
Breakaway* Starter Part No. — 6V0927 (11 pinion teeth)
12.5 1400 0/0 100/1660 100/1660

*Breakaway torque is theoretically 0 starter and engine rpm. However, the starter amperage limit is approximately
1400 amps. Thus the breakaway torque shown is reduced somewhat from actual to accommodate the amperage limit.

Table 7.

Electric Starter Cranking Performance


Potential Torque Potential Torque
of Starter on Flywheel
Volts at Starter Amps to Starter (lb ft) (lb ft)
G3304, G3306
(156 flywheel teeth) Starter Part No. — 1W5516 (12 pinion teeth)
Cranking*
@ 100 engine rpm 19 800 52 676
@ 150 engine rpm 22 500 22 286
G3406
(113 flywheel teeth) Starter Part No. — 2S7227 and 6V0927 (11 pinion teeth)
Cranking*
@ 100 engine rpm 17 900 54 550
@ 150 engine rpm 19 600 36 370
G3408, G3412
(136 flywheel teeth) Starter Part No. — 4N1062 (11 pinion teeth)
Cranking*
@ 100 engine rpm 17 860 52 640
@ 150 engine rpm 19 580 30 360
G3508, 12, 16
(183 flywheel teeth) Starter Part No. — 7C0527, 6V4246 (11 pinion teeth) [Values for 1 starter]

Cranking* 19 600 30 500


@ 100 engine rpm Starter Part No. — 6V0927 (11 pinion teeth) [Values for 1 starter]

18.5 600 36 600

*Cranking torque is at 100 engine rpm. Cranking torque is very dependent on oil viscosity and temperature. When
solving a cranking issue, increasing the temperature of the engine and oil plus lowering the viscosity of the oil will
dramatically improve cranking performance.

Table 8.

25
Ratio of Engine to Starter Speed systems may be required. The on-site tuning
Engine speed and starter speed can be will require additional start-up costs and must
determined by the following ratio: be considered when estimating start-up costs.
Starter rpm/Engine rpm = Pinion Teeth of Requirements for 10-second automatic
Starter/Engine Flywheel Teeth starting:
Ratio of Engine and Starter Torque • Combustion air must be a minimum of
Engine and starter torque can be determined 21°C (70°F).
by the following ratio:
• Jacket water heaters maintain a minimum
Torque on Engine Flywheel/Starter Torque =
Engine Flywheel Teeth/Starter Pinion Teeth
of 32°C (90°F) water temperature.

• Fully charged batteries to provide


60 seconds of continuous cranking, or full
Automatic Start-Stop air supply.
Automatic start-stop systems are primarily for
unattended engines which must start • Readily available fuel.
automatically, pick up the load, operate the
load, and stop automatically when demand • G3500 and G3600 must have a continuous
ceases. For example, a standby generator set pre-lube pump.
must start automatically when commercial
power fails and stop automatically when it is
reinstated. Starting Aids
Caterpillar offers both electric and air- Jacket Water Heaters
powered systems. The engine control switch Jacket Water heaters are electrical heaters
determines the panel status. The automatic which maintain the jacket water at a
position (3 o’clock), enables the engine to temperature high enough to allow easy
start automatically. engine starting.

Ten Second Starting More heaters of higher ratings may be


Ten second starting is often required either required in areas of extremely cold
by application or local regulation. For temperature.
instance, National Fire Protection Association
(NFPA) 99, Health Care Facilities 1987 Recommended jacket water heater kW ratings
Edition, states, “The generator set(s) shall are listed in the Cooling section.
have sufficient capacity to pick up the load Oil Heaters
and meet the minimum frequency and voltage Heating elements in direct contact with non-
stability requirements of the emergency circulating lubricating oil are usually not
system within 10 seconds after loss of normal recommended due to the danger of oil coking.
power.” However, the 10 second starting If specified, heater skin temperatures should
requirement is greatly dependent on the site not exceed 150°C (300°F) and have
gas supply, starting system, and if a purge maximum heat densities of .02 Watts/mm2
cycle is necessary or recommended. (13 Watts/in2).
Caterpillar will not guarantee 10 second
starting capability, and suggests that dealers On G3500 and G3600 engines continuous pre-
influence the specifications to allow a lube pumps are available and are a preferred
minimum starting time of 20 seconds that can method for heating engine oil. The oil is
be accomplished without additional circulated through the engine when the
installation costs or start-up expense. engine is stopped and is heated by the jacket
water heater. The jacket water heater should
Ten second starting is routinely obtained by be sized to have adequate capacity to heat the
dealers with careful attention to the various jacket water and engine oil.
systems such as starting and the gas supply.
On-site adjustment and tuning of those

26
G3500 – G3300
Engine Protection Systems
G3500 Engine Protection System
G3400 and G3300 Engine Protection System
Remote Control Panel
Alarm Modules
Customer Interface Module
Recommended Alarms and Shutdowns
Engine Protection attended, alarms can be provided before actual
engine shutdown that warn of approaching
Systems shutdown limits in each monitored system.
This allows the attendant to decide the
urgency of the fault and schedule repairs
All engines require a protection system. The before a shutdown. Protection equipment for
protection system is a basic requirement of unattended applications can be tailored to the
any engine installation and provides protection specific requirements.
to the engine as well as to the facility and
operation personnel. This guide provides Although most Caterpillar Gas Engines come
basic information about the Caterpillar with a standard set of shutoffs, some engine
G3500-G3300 engine protection systems. configurations come with additional shutoffs
and alarms. They may also use different
Engine protection is required for the strategies for shutdowns, annunciation, etc.
lubrication, cooling, and combustion systems. Consult the Gas Engine General Dimension &
These systems in turn interact with fuel and Wiring Diagrams on CD LERQ2015 or paper
ignition systems and in some cases, with the LEBQ5111, for additional information on how
customer’s switchgear. The lubrication to connect to a specific engine’s safety system.
system must maintain the oil pressure within
a certain range; oil temperature is internally Gas generator set engines are normally
controlled via a thermostat for most equipped with Energize-To-Run (ETR) gas
arrangements. The cooling system must shutoff valves. The diesel offers both ETR
maintain the cooling water below a certain and Energize-To-Shutoff (ETS). The gas
temperature. Some engines have a protection engine differs because there is not a
system for the combustion chamber; commercially available gas shutoff valve that
detonation sensing that can adjust or even is energize-to-shutoff with an automatic reset.
shutdown the engine. Overspeed protection is For manual start-stop operations, ETS gas
also very important. A listing of standard and valves are available as an option for G3400
optional protection systems can be found with and G3300 with a manual reset.
each engine pricing arrangement in the price
list. The details of these offerings will be
expanded upon in the following sections. G3500 Engine Protection System
The G3500 Generator Set and Industrial
When problems occur that do not engines offer an electronic protection system
immediately endanger the condition of the that requires a 24 volt power source. The fuel
engine or the operator, the fuel gas valve is shutoff valve is included and is energized to
closed as soon as a fault is detected and the run. The control panel for protection system
ignition system remains on for 10 seconds. hardware will be one of three offerings:
This allows all the gas downstream of the
shutoff valve and in the intake manifold to be 1. Remote Control Panel (Status), remote
consumed by the engine and not dumped into mounted with optional harness lengths up to
the exhaust stack. When a problem occurs 24.4 m (80 ft), offered on all G3500 EIS
that can cause immediate damage to the genset and industrial engines except G3500
engine or operator, such as overspeed, the package gensets for COSA. A description of
gas valve is closed and the ignition system is the Status Control panel is located below.
immediately shut off. When starting again,
the engine should be cranked for 10 seconds 2. Customer supplied control panel, safeties,
with the gas valve closed and the ignition shutdowns, and start/stop logic, standard
system off. This purges the engine of any on G3500 Package Gensets for COSA.
unburned air/fuel mixture.
3. Electronic Modular Control Panel (EMCP II),
When designing an installation, consider if the mounted on the generator, standard for the
engines will be attended or unattended when 1800 rpm genset standby package, optional
selecting protection equipment. When

29
for G3500 package gensets for COSA, and Low Oil Pressure @ Alarm Shutdown
available via SER for other genset engines. Below Low Idle Speed 103 kPa 15 psig 69 kPa 10 psig
Above Low Idle Speed 241 kPa 35 psig 207 kPa 30 psig
Customer supplied shutoffs must meet all High Oil Temperature 102¡C 215¡F 104¡C 220¡F
Caterpillar and other local requirements. High Coolant Temperature
Caterpillar requires at a minimum a
Low Coolant Temperature 21¡C 70¡F
duplication of the safeties and shutdowns that
Overspeed 118% Rated
would have been provided by Caterpillar for
Overcrank Time 360 Seconds
the particular engine. These safeties and their
High Intake
limiting values are shown for each engine in Manifold Air Temp
71¡C 160¡F

the product description section of the price


list and in Tables 9 and 10. For a typical Table 10.
standard cooling G3500 LE, the Caterpillar
system provides:
For engines operating above a jacket water
• Emergency stop button temperature of 110°C (230°F), a Caterpillar
pump may not be used. When using a customer
• Energized to run gas shutoff valve supplied pump, Caterpillar requires that a
• Power, warning, and shutdown lights shutdown be provided for low jacket water flow.
This can be done with a pressure switch or a
• Detonation delta-pressure switch across the engine block,
triggering below 27 kPa (4 psig) delta.
• Start, stop, run switch
The third system offered on G3500 genset
Low Oil Pressure @ Alarm Shutdown engines is the EMCP II. The EMCP II
Below Low Idle Speed 103 kPa 15 psig 69 kPa 10 psig contains a genset control (GSC) and several
Above Low Idle Speed 241 kPa 35 psig 207 kPa 30 psig instrument panel switches plus optional alarm
High Coolant Temperature 103¡C 217¡F 109¡C 228¡F modules and customer interface module. The
Low Coolant Temperature 21¡C 70¡F GSC monitors and controls:
Overspeed 118% Rated
Overcrank Time 360 Seconds • Starting and stopping of the engine

• Shows engine condition and generator


Table 9.
output display

• Engine faults, displays fault codes


When the high temperature cooling option is
selected, the following are used: • Displays GSC programming information
• Emergency stop button The safeties and shutdowns listed above are
all contained in the EMCP II. The setpoints
• Energized to run gas shutoff valve
are programmed into the EMCP II using a
• Power, warning, and shutdown lights keypad on the GSC.

• Detonation

• Start, stop, run switch

30
G3400 and G3300 Engine Powered Shutoffs – These shutoffs are for
magneto engines and require an external
Protection Systems
power supply of 24 volts. The power to an
The G3400 and G3300 engines offer several
energized to run gas valve (optional) is
protection system options. In the price list,
interrupted to stop the engine. The shutoffs
the desired protection system is selected from
provided are listed in Table 12.
a list of mandatory options. Not all options are
available for each engine, consult the use
G3400 G3300
codes for compatibility. EMCP II is standard Shutoff Point Shutoff Point
on the G3406 package and SER on other Low Oil Pressure 60 kPa 10 psig 55 kPa 8 psig
engines at this time. The following is a High Coolant Temperature 104¡C 220¡F 98¡C 208¡F
description of the options. Overspeed (use the lesser of 10% over rated engine speed
or the maximum safe speed of driven equipment)
Self Powered Shutoffs – These shutoffs are Emergency Stop
Push Button
powered by the magneto; no external power
is required. An energized to shut off gas valve
(manual reset) is activated to stop the engine. Table 12.
The shutoffs provided are listed in Table 11.

G3400 G3300
Automatic Start/Stop Shutoff – These
Shutoff Point Shutoff Point shutoffs are for magneto engines and require
Low Oil Pressure 60 kPa 10 psig 55 kPa 8 psig an external power supply of 24 volts. The
High Coolant Temperature 104¡C 220¡F 98¡C 208¡F customer is required to supply automatic
Overspeed (use the lesser of 10% over rated engine speed or start/stop logic. The shutoffs provided are
the maximum safe speed of driven equipment)
also listed in Table 12.
Emergency Stop
Push Button (manually activated)
Customer Supplied Shutoff – This
Table 11.
selection provides no wiring groups or
shutoffs. It is the customer’s responsibility to
provide the minimum protection listed in
Table 13.

Shutoff Points
G3306 G3406 G3408 G3412
Standard LE
Low Oil Pressure 55kPa (8 psig) 60kPa (10 psig)
High Coolant Temperature 98¡C (208¡F) 104¡C(220¡F)
Overspeed (Use the lesser of 10% over rated engine speed or the maximum safe of driven equipment.)
High Intake Manifold Air
Temperature
32¡C (90¡F) SCAC

Pre-alarm 41¡C (106¡F) 42¡C (108¡F) 54¡C (129¡F) 47¡C (117¡F) 47¡C (117¡F)
Shutdown 45¡C (113¡F) 46¡C (115¡F) 58¡C (136¡F) 51¡C (124¡F) 51¡C (124¡F)
54¡C (130¡F) SCAC
Pre-alarm 60¡C (140¡F) 60¡C (140¡F) 66¡C (151¡F) 66¡C (151¡F) 66¡C (151¡F)
Shutdown 64¡C (147¡F) 64¡C (147¡F) 70¡C (158¡F) 70¡C (158¡F) 70¡C (158¡F)
Emergency Stop Push
Button
Gas Shutoff Valve

Table 13.

31
Protection System – These shutoffs are for • Lights for power, warning, and shutdown
Caterpillar EIS engines and require an • Diagnostic reset switch
external 24 volt power supply. This system • Emergency stop push-button (ESPB)
contains a Remote Status Control Panel (immediately shuts off fuel and ignition)
(SCP), identical to that used on G3500. A • Control for gas valve, energized to run
description of the panel is located later in this • Engine control switch (ECS)- start, run,
manual. The panel is connected to the engine stop switch
mounted junction box with an interconnect • SI Engine Status Control Module (SCM),
wiring harness that is 3 m (10 ft) to 24 m which contains:
(80 ft) long, depending on the length selected • Engine protection system with two
in the price list. The shutoffs provided are: stage shutdown
• Emergency stop button • Start/stop functions
• Energized to run gas shutoff valve • Shutdown for low oil pressure at low
• Power, warning, and shutdown lights idle (69 kPa, 10 psig)
• Detonation • Shutdown for low oil pressure at
• Start, stop, run switch high idle (207 kPa, 30 psig)
• Shutdown for high coolant
Low Oil Pressure @ Alarm Shutdown temperature (99°C, 210°F)
Below Low Idle Speed 103 kPa 15 psig 69 kPa 10 psig • Shutdown for overspeed (118 %)
Above Low Idle Speed 241 kPa 35 psig 207 kPa 30 psig • Shutdown for detonation
High Coolant Temperature 103¡C 217¡F 109¡C 228¡F • Overcranking control
Low Coolant Temperature 21¡C 70¡F
The following describes functions of controls
Overspeed 118% Rated
on the Remote Control Panel. When the ESPB
Overcrank Time 360 Seconds
is depressed, the gas shutoff valve is de-
energized, stopping the fuel supply to the
Table 14.
engine. A relay is also energized to turn the
ignition off. To restart the engine, the ESPB
EMCP II- The EMCP II contains a genset
must be reset.
control (GSC) and several instrument panel
switches plus optional alarm modules and
customer interface module. The GSC
monitors and controls:
• Starting and stopping of the engine
• Shows engine condition and generator
output display
• Shows engine condition and generator
output display
• Engine faults, displays fault codes
• Displays GSC programming information

The safeties and shutdowns listed above are


all contained in the EMCP II. The setpoints
are programmed into the EMCP II using a
keypad on the GSC.

Remote Control Panel


The Remote Control Panel (Status Control
Panel) is used on most engines with
Caterpillar EIS (Figure 11). Alternatives are
the EMCP II or a customer supplied system.
The Remote Control Panel (Status) contains:

32
The ECS determines the status of Remote
Control Panel. When set for automatic, the
engine will start when a remote initiating
contact (IC) is closed and stops when the IC
is opened. A cool down timer can be adjusted
between 0 and 30 minutes. In the manual
position, the engine will start and run as long
as the ECS is in this position. In the
cooldown/stop position, the fuel solenoid
shuts the engine down after cooldown. In the
off/reset position, the fault lights are reset
and the engine shuts down. Power is removed
from the SCM and Electronic Ignition System
when the engine is shut down.

The Status Control Module displays fault


conditions and key engine parameters.
Information is received from the operator,
Figure 11. Engine Status Control Module (SCM).
magnetic speed pickup, (1) Display LCD. (2) Switch (display hold switch).
pressure/temperature module, and the EIS (3) Overcrank LED. (4) Low oil pressure LED.
control. This information is in turn used to (5) Overspeed LED. (6) Emergency stop LED. (7) High
control the position of the fuel shutoff valve, coolant temperature LED. (8) Auxiliary shutoff.
starting system, and relay information back to
the ignition system. Cooldown – Upon receiving a signal to
perform a normal shut down, the SCM will
The SCM has the following features: wait a preprogrammed amount of time before
shutting the engine off by means of the gas
Cycle Crank – The SCM can be shut-off valve.
programmed to crank-rest-crank for
adjustable time periods (see Service Automatic Operation – While in the
Procedure A for adjusting). automatic mode, the SCM can be started by a
remote initiate signal [when initiate contact
2301A Speed Control – When the engine (IC) closes]. Upon loss of the signal, the SCM
oil pressure increases past the low oil will perform a normal shut down.
pressure set point, the SCM will indicate to a
2301A Speed Control that it should increase Alarm Module Communication – The
the engine speed from idle to rated. SCM can transmit fault and alarm conditions
to an alarm module.

Power Down – The Remote Control Panel


(Status) system is designed to remove power
from the SCM and EIS when in the off/reset
mode. The SCM will not allow the power
down until the Crank Termination Relay and
the Fuel Control Relay are both “off” (both
relays turn off two seconds after zero rpm).

Fuel Solenoid Type – The SCM can be


programmed to work with either an Energize-
To-Run (ETR) fuel system or an Energize-To-
Shutdown (ETS) fuel system.

LED Display – Six LEDs are located on front


of the SCM to annunciate overcrank
shutdown, overspeed shutdown, low oil
pressure shutdown, high coolant temperature
33
shutdown, emergency stop and auxiliary circuit to be tested while the engine is
shutdown. operating at rated speed. See Service
Procedure G for testing.
Emergency Stop – If the SCM detects an
emergency stop, the engine will shut down by Low Oil Pressure Protection – If the
means of ignition and fuel control. LED (6) engine oil pressure drops below the low oil
will flash. pressure set point, it will be shut down by
means of the fuel control. LED (4) will flash.
Pressure/Temperature Module There are two low oil pressure set points, one
Malfunction – If the signal from the engine for when the engine speed is below the oil
mounted oil pressure/temperature transducer step speed and another for when the engine
module is lost or unreadable, the engine will speed is above the oil step speed. See Service
be shut down by means of the fuel control and Procedure I for testing.
a diagnostic code will be displayed. The SCM
can be programmed to ignore the transducer High Coolant Temperature Protection – If
module malfunction. the engine coolant temperature exceeds the
high coolant temperature setpoint, the engine
Speed Pickup Malfunction – If the SCM will shut down by means of the fuel control.
loses its magnetic pickup signal, the engine LED (7) will flash. See Service Procedure H
will be shut down by means of the ignition for testing.
system and fuel control and a diagnostic code
will be displayed. Note: For all fault conditions, if the fuel
control fails to shut down the engine, the
Overcrank Protection – If the engine fails to ignition system is shut off five seconds after the
start in a preprogrammed amount of time, the fault occurs.
SCM will halt the starting sequence and flash
an LED (3). Another attempt at starting the
engine cannot be made without first going
into the off/reset position on the ECS.

Liquid Cr ystal Display (1) – Service hours,


engine speed, system battery voltage, engine
oil pressure and engine coolant temperature
are sequentially displayed in either English or
metric units. Pressing switch (2) on the front
of the SCM will cause the display to lock
(stop) on one of the engine parameters.
Pressing the switch again will resume the
display to normal sequencing. When a fault
signal is detected, the display is also used to
indicate diagnostic codes, to aid in
troubleshooting. In the Troubleshooting
Section, see Diagnosed Problems.

Note: All diagnostic lights should turn on


briefly when the panel is powered up. This is a
lamp test.

Overspeed Protection – If the engine speed


exceeds the overspeed set point, it will be
shut down by means of ignition and fuel
control. LED (5) will flash. The overspeed set
point is lowered to 75 percent of its original
value while the overspeed verify switch is
depressed. This will allow the overspeed

34
Alarm Modules Customer Interface Module
Alarm modules are optional equipment, The Customer Interface Module (CIM)
available as an attachment to the Electro- provides an interface (separate relay contacts)
Mechanical Control Panel (EMCP) or between the GSC for EMCP II or the SCM for
Electronic Modular Control Panel (EMCP II). the Remote Control Panel and the switch
These provide red and amber LED’s plus an gear. The two major components of the CIM
audible indicator. Two versions are available: are the relay board and the electronic control.
NFPA 99 alarm module and NFPA 110 alarm The electronic control connects to the serial
module. NFPA 99 provides alarms for low oil data link and decodes the information into
pressure, low coolant temperature and high discrete outputs. The output drives relays to
coolant temperature. NFPA 110 provides sound a horn, flash a lamp, or trigger some
alarms for low oil pressure, low coolant other action. Information available from the
temperature and high coolant temperature, serial data link is:
low battery voltage, battery charge
• High coolant temperature alarm
malfunction and system not in auto.
• High coolant temperature shutdown
The alarm module has a serial connection to • Low coolant temperature alarm
the SCM and must be located within 305 m • Low coolant temperature shutdown
(1000 feet). • Low oil pressure alarm
• Low oil pressure shutdown
When using non-Caterpillar alarm modules • Overcrank
and panels, Caterpillar recommends the • Overspeed
following features: • Engine control switch not in auto
• Diagnostic failure
• Fault light lock-in circuitry - keeps fault
light on when intermittent faults occur. The CIM is normally shipped loose for
installation in a convent location, such as the
• Lockout of additional alarm lights - switch gear. The CIM must be located within
prevents subsequent alarm lights from 305 m (1000 ft) of the GSC or SCM.
going on after the activated engine shutoff
stops the engine. This aids in
troubleshooting.

• Alarm silence - allows engine man to


acknowledge the alarm without having to
continually listen to the alarm horn. Alarm
light is left on.

• If more than one engine is connected to an


alarm panel, a fault in a second engine
should activate the alarm, even though the
alarm horn may have been silenced after a
fault on another engine.

• Circuit Test - provides for periodic


checking of alarm panel functions

35
Recommended Alarms and
Shutdowns
The engine shutoff systems discussed above
are the standard systems. Customers
routinely add alarms and shutdowns to meet
the needs of the application. Table 15
suggests various alarms and shutdowns to be
considered and how they might be applied.
This chart is frequently modified to fit the
site, application, and maintenance personnel
preferences.

Controls and Safety Devices

Malfunction Unattended Attended Recommended Values


Low Oil Pressure S S 69 kPa low idle 207 kPa
High Oil Temperature S A
Excessive Vibration S S
Overspeed I I 10% - Driven

High Inlet Air Temperature S S


Alarm Shut Down S S

Detonation I I
Overcrank S S
High Jacket Water Temperature S S 210¡ F for non co-gen Application
High Water Level A A

Low Water Level S A


Loss of Power S A
Reverse Power S S

Overcurrent S S

High Steam Pressure A A

Overload S A

Under Frequency S S
Over/Under Voltage S S

Battery Charger Failure (AC) A A

Battery Failure (DC) A A


Low Condensate Level S S
Low Tower Water Level S A

I – Immediate shutdown - close gas valve and terminate ignition immediately


S – Staged shutdown - close gas valve immediately and terminate ignition after 10 second time delay
A – Alarm only

Table 15.

36
Materials and specifications are
subject to change without notice.

© 1998 Caterpillar Inc.

Printed in U.S.A.

You might also like