You are on page 1of 3

3799371500

Outdoor cabinet
ODPS 2900-48-6 2.0VA VA/C [NSN IQ]
OutD V series

Description
The Delta OutD cabinet is the choice from the tropics to the arctic when space is scarce or site density needs to be
increased cost-effectively.

The Delta OutD series offers several size options, ensuring right dimensions for telecom equipment. A flexible
configuration is the way to tailor solutions for your demand, and our OutD cabinets offer an option to build the whole
base station inside. Wall options are with multi- or single-layer, and multi lock mechanism completes the protection of
installed equipment.

The flexible rectifier system and aluminium outdoor cabinet configuration is the tailored solution for your base station
demand. The 4 point door lock mechanism completes the protection of installed equipment.
Advanced thermal cooling and system control enables remarkable savings both in capital and operational expendi-
tures.

Main features
Cabinet:

 Resistant outdoor enclosure made from non-corrosive


aluminum sheets
 IP 55 protection class
 Single (common) compartment
 Hybrid cooling system – air ventilation (AV) and active
cooling (Air Conditioner)
 Space for battery backup system up to 380Ah
 Multilayer wall design
 Thermal insulation of the walls
 Bottom cable entry with specific cable glands
configuration
 Option for enhanced monitoring and controlling

Rectifier System:

 Delta modular CellD system DPS 2900B-48-6


Space for up to 6x high efficient rectifier modules
DPR 2900B-48 (96.2% Efficiency)
High power density (17.4kW @ 5U)
 Initially installed rectifier module power 8.7kW
 Advanced system monitoring and controlling
 Space saving AC distribution on cabinet side wall

Applications
Network base stations
Wireless applications
Fixed line applications, data communications
3799371500

Outdoor cabinet
ODPS 2900-48-6 2.0VA VA/C [NSN IQ]
OutD V series

Technical specifications
1. General 3. Thermal management
Multi-layer aluminum/ galva- Hybrid cooling system AV + AC
Construction
nized steel cabinet
Fans + Air Filter
Overall with plinth, without Air ventilation (AV)
250 W/K; 48 Vdc
Dimensions external, cooling units
H2050 x W800 x D865 mm
Air conditioner (DC) 1600W DC

Internal rack dimension 16 / 22 / 38 HU Air filter G4 class (EN 779)


Without external cooling
Weight
units ~110 kg 4. Equipment
Materials: 2 rows of cable glands
AlMg for external surface
Cabinet skins, internal Left side:
HDG for internal components
frames, plinth 3xPG36, 1xPG29, 3xPG21
Thermal insulation EPS closed cells Cable entry bottom access 2xPG16, 2xPG11
Polyester Powder Paint Right side:
Finish 3xPG42, 1xPG29, 3xPG21
RAL7035
2xPG16, 2xPG11
Safety IEC/EN 60950
4 points , Key and inserts -
EMC EN 300 386 Door locking
configurable, Door stopper
Maintenance cycle 12 months 2 x 23’ for front terminals
Battery shelves
batteries
Screw terminals:
PE grounding bar 10 x 16 mm2
4 x 35 mm2
2. Environment
Lifting eye bolts 4 points under roof cover
-33 to +50 °C
Operating temperature Service light 1 W / 48 Vdc
(ETS 300 019-1-4)
Optional equipment Box for documentation
1120 W/m2 Open door sensor
Solar radiation
(ETS 300 019-1-4)
IP 54 (EN 60529)
Protection class
IP 55 (EN 60529) option
Noise
AV - max. 55 dB(A)
(sound pressure 1 m
DC 1600W - max. 65 dBA)
distance, free field)
Humidity (relative) Max. 100 %

Delta Energy Systems (Poland) Sp. z o.o.


23 Poleczki Str. 02-822 Warsaw, Poland
Phone: +48 22 335 26 00, Fax: +48 22 335 26 01

www.deltapowersolutions.com
3799371500 Fact_sheet_OutD_NSN_IRAQ.docx / Rev. 06 / RPä
3791545300

Outdoor cabinet
ODPS 2900B-48-6 OUTD 2000
OutD V series

Rectifier system and AC distribution technical


specifications
1. Input 6 alarm relays,
WEB interface,
AC connection 3L + N + PE Remote monitoring SNMP protocol,
Nominal voltage 3 x 230 VRMS (L-N) Converter board RS232 to
RS485 (Modbus protocol)
Voltage range 88 – 300 VRMS
Frequency range 45 – 66 Hz 4. General
Current nominal / phase 26,2 ARMS Rectifiers Max 6 x DPR 2900B-48
Mains terminal 3L + N + PE; 230/400 V Efficiency 96,2 %
Input protection 3 x 40 A MCB (1P) Height, overall 489 mm (3 + 3 + 5 U)
AC OVP (SPD) Phoenix (3 + 1), Class C Width, body 444 mm (19”)
Depth, overall 310 mm
2. Output
Sliding mechanism Yes (on rectifier system)
Voltage range 42 – 58 VDC; 54 VDC nom
Ambient temperature -4 C
Power, nominal 17,4 kW
Relative humidity 95 % max, non cond.
Output current (max.) 300 A
Safety IEC/EN 60950
Load breakers Max 40 x MCB (up to 63 A)
EMC EN 300 386
Battery breakers Max 6 x MCB (up tp 100 A)
Protection IP20
LVD (battery) 300 A
PLD (non critical loads) 250 A 5. Equipment
2 x Battery cable sets (35
mm2)
3. Control / Monitoring Standard equipment 3 x DPR2900B-48 (not
included)
Controller PSC 3
3 x Rectifier slot cover plates
Display,
Menu structure, Subject to change without notice
Local interface
Keypads,
LEDs

You might also like