You are on page 1of 2

PBH Series

POWER LINE FILTER 16/20A HIGH CURRENT, SNAP-IN/FLANGE MOUNT FILTER


WITH IEC 60320 AC INLET SOCKET.

MECHANICAL DIMENSIONS (Unit: mm)


CASE F
52.8 42.0
42.0 35.0

R3 TYP.
30.1 27.0

2x 3.5

3.6

(79.5)
67.4

6.35 0.8
34.0 26

CASE U
FEATURES 38.0 36.0

The PBH series offers filters for application that have high 30.0 R3 TYP.
27.0
current (16/20A) requirements. The filters are available
with different configurations of components and termination SUGGESTED PANEL CUTOUT
(MOUNTING FROM FRONT)
styles. These filters are available in flange mount and THICKNESS OF PANEL IS FROM
1.00mm to 1.6mm
snap-in type. The medical grade filters offer excellent 27.6
performance with maximum leakage current of 2µA at
120VAC, 60Hz. 3.8

A ground choke can be added to enhance the grounding (79.5)


67.4
ability of the circuit. A bleeder resistor can also be added
to prevent excessive voltages from developing across the
filter capacitors when there is no load.
6.35 0.8
APPLICATIONS 34.0 26.0

Computer & networking equipment, Measuring & control


equipment, Data processing equipment, laboratory instruments, CASE O
43.0+-- 0.1
Switching power supplies, other electronic equipment. 2x 6#32 34.5+ 0.5

10.0+-- 0.1

TECHNICAL DATA
+ 0.5
30.0 6.0 +-- 0.1 26.5--

• Rated Voltage: 115/250VAC 43.0


R3.0
RECOMMENDED 2x 3.5
• Rated Current: 16A, 20A 52.0 PANEL CUTOUT
• Power Line Frequency: 50/60Hz (MOUNTING FROM REAR)

• Max. Leakage Current each


Line to Ground:
@ 115VAC 60Hz: 0.25mA
@ 250VAC 50Hz: 0.50mA 79.5
75.7

@ 115VAC 60Hz: 2µA*


@ 250VAC 50Hz: 5µA*
• Hipot Rating (one minute)
Line to Ground: 2250VDC 6.35 0.8
34 26
Line to Line: 1450VDC
• Temperature Range: -25C to +85C
✛ SEMKO, VDE approved to 16A
* Medical application Specifications subject to change without notice. Dimensions (mm). See Appendix A for
recommended power cord. See PDI full line catalog for detailed specifications on power cords.

145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076


e-mail: filtersales@powerdynamics.com • www.powerdynamics.com 13
PBH Series Example & Ordering Code
SCHEMATICS
PBH 20 Q - 60 - 1 C U
1
L mH
L L'
Cy

LOAD
CURRENT RATING (A):

LINE
R
= 16 CX L G'
Cy
= 20 N N'
L mH
G
Lg
TERMINAL: 3.0 -3.6L
8.0
6.3/0.25 QUICK CONNECT =Q 2
L mH
2.0 -3.0L
L L'
4.0/0.187 6.6 SOLDER =S Cy

LOAD
LINE
R L G'
Cy
UL 1015, 18AWG WIRE =W N N'
STRANDED, 4” L mH
G
Lg

OPTIONS: NO BLEEDER RESISTOR & NO GROUND CHOKE = 00


BLEEDER RESISTOR (1W, 1M)
3
= 60 L mH
BLEEDER RESISTOR (1W, 1M) & GROUND CHOKE L'
= 80 L
Cy

LOAD
LINE
GROUND CHOKE (100µH) = 90 R L CX G'
Cy
N N'
COMPONENT LOCATIONS: STANDARD TYPE = 1 L mH
G
WITHOUT C(X); C(Y) ONLY = 2✢ Lg
C(X) & C(Y) BEHIND L = 3✢
WITHOUT C(Y); C(X) ONLY = 1M
WITHOUT C(Y); C(X) BEHIND L = 2M✢ MEDICAL
SCHEMATICS
ATTENUATION CODE TABLE:
Non-Medical applications, select Attenuation code with corresponding component values from the table.
1M
Case Code Cap. Cx (µF) Cap. Cy (pF) 20A (mH) L mH
F,O,U 0.1 2200 0.5 =A L L'
=B

LOAD
F,O,U 0.1 3300 0.5

LINE
R CX L
F,O,U 0.33 2200 0.5 =C
N N'
L mH
Medical applications, select Attenuation code with corresponding component values from the table. G G'
Lg
Case Code Cap. Cx (µF) 16/20A (mH)
F,O,U 0.1 0.5 = M1
F,O,U 0.33 0.5 = M2
2M
L mH
L L'

LOAD
CASE CODE: = F
LINE

FLANGE MOUNT R L CX
SNAP-IN TABS - SIDE =U N N'
REAR PANEL MOUNT =O G
L mH
G'
Lg
Contact PDI for attenuation numbers

Non-Medical Applications Medical Applications


❖ ✧

Insertion loss in dB (50 Ohm circuit) Insertion loss in dB (50 Ohm circuit)

Attenuation Comm. Mode(L-G) in MHz Diff. Mode(L-L) in MHz Attenuation Comm. Mode(L-G) in MHz Diff. Mode(L-L) in MHz
Code .15 .5 1 5 10 30 .15 .5 1 5 10 30 Code .15 .5 1 5 10 30 .15 .5 1 5 10 30
A 17 22 26 43 51 43 8 18 24 45 43 35 M1 16 21 22 24 25 20 8 18 25 42 43 30
B 17 23 28 47 57 45 8 18 23 51 54 34 M2 16 20 22 24 25 20 17 28 33 41 40 31
C 17 22 26 43 51 43 18 28 33 46 53 35 ✧
This table applies to schematic 1M only.

This table applies to schematic 1 only. Visit our website or contact PDI for other schematic attenuation numbers.
Visit our website or contact PDI for other schematic attenuation numbers.

145 Algonquin Parkway, Whippany, NJ 07981 • 973-560-0019 • FAX: 973-560-0076


14 e-mail: filtersales@powerdynamics.com • www.powerdynamics.com

You might also like