Three Phase Transformer selection

Distribution transformers (upto and


Sr. No. Selection Criteria including 2500 KVA) Power transformers (above 2500 KVA) Generator transformers

The secondary no-load voltage should be The MVA rating of the generator
specified 5 percent more than the nominal transformer should be at least equal to
voltage to compensate the transformer the full generator output without
regulation partly. considering reduction
for unit auxiliary requirements. The no-
load voltage of the secondary winding
Voltage & KVA rating as per IS 1180 should be specified about 5 % more
1 Ratings
(Part 1 & Part 3). than the nominal value to compensate
the transformer regulation partly.

Normally provided Generally OLTC provided for HV. For Normally provided with off circuit tap
with off-circuit taps on HV side interconnecting autotransformers with OLTC, changers except in cases where the
except in special cases when OLTC system conditions may warrant tapping on LV system conditions warrant use of OLTC.
are specified. The standard range for side. In case of OLTC, the taps may be + 10% in The standard range for off-circuit tap
off-circuit taps which are provided on steps of 1.25 % with 16 steps. The distribution on changer is 2.5 % to 7.5 % in steps of 2.5
HV side should be +2.5 % and +5.0 positive and negative taps shall be decided to- %. For 400 kV transformers, on-load/off-
%. In case of OLTC, the taps may be + suit the system conditions. Off-circuit taps, when circuit taps should have tapping range
10% in steps of 1.25 % with 16 steps. specified, should be in the range of + 2.5 % and of + 5 % in steps of & 2.5 percent.
2 Taps The positive and negative taps shall +5 % provided on the HV side.
be specified to suit the system
conditions in which the transformer
is to be operated.

To be specified as per annexure E of IS 2026 (Part The preferred connection symbol for
1). For transformers of ratings up to 50 MVA, two winding transformers is YNd 11 or
three limb ( Yyo ) construction, no stabilizing YNd 1 with the star neutral solidly
winding is required unless the tertiary winding is earthed.
required for auxiliary loads. In case of unloaded
3 Connection symbol Usually Delta / star. (Dyn11 or Dyn1)
tertiary winding, one terminal should be brought
out for testing purposes.

The typical impedance values are The typical impedance values are given in Table 1 The standard impedances are
given in table 3 & table 6 of IS : 2026 ( Part 5 )- 12.5 to 14 % with tolerance as given in
4 Impedance of IS : 1180 (Part 1) IS: 2026

Primary and secondary terminals may Primary and secondary terminals may be bare The generator side LV terminals should
be bare bushings, cable boxes or bus bushings, cable boxes or bus trunking depending be suitable for bus duct or cable
trunking depending upon the method upon the connection. The HV side should have
of installation. method of installation. Wherever compound bare bushings suitable for outdoor
Wherever compound filled cable filled cable boxes are used, it is preferable to installation. For 66 kV and above, oil-
boxes are used, it is preferable to specify disconnecting filled condenser type bushings should
specify disconnecting chamber chamber between transformer terminals and be specified. For
between transformer terminals and cable box to facilitate disconnection of installation in polluted atmospheres,
cable box to facilitate disconnection transformer terminals without dismantling the the bushings shall be specified with
of transformer terminals without cable connections. In case of extruded insulation extra creepage distance as given in IS :
Termination
5 dismantling the cable connections. In cable connections in air, a separate 2099
arrangements
case of extruded insulation cable disconnecting chamber is not necessary. For
connections in air, a separate transformers up to 33 kV, porcelain bushings and
disconnecting chamber is not for transformers of 66 kV and above, oil-filled
necessary condenser type bushings should be specified.
Distribution transformers (upto and
Sr. No. Selection Criteria including 2500 KVA) Power transformers (above 2500 KVA) Generator transformers

ONAN, ONAN/ONAF, ONAN/ONAF/OFAF or


6 Cooling ONAN,AN,ANAN. OFWF. ONAN, OFAF or OFWF.

Standard fittings along with explosion Standard fittings along with skids and hauling Standard fittings and acccessories along
vent specified for all 11 kV lugs; with Magnetic oil level gauge; Gas and
transformers above 400 kVA rating Magnetic oil level gauge with low level alarm oil actuated relay; Explosion vent;
and all 33 kV transformers. When contacts; Winding temperature indicator with
radiators are required to be detached Rollers ( bidirectional, if required ). If flanged electrical contacts for alram/trip and
for transportation, isolating valves rollers are controlling fans and pumps; Skids and
should be specified. Alarm and trip required, rail gauge should be specified; Winding hauling lugs; Rollers ( bidirectional, if
contacts for oil temperature temperature indicator with electrical contacts for required ). If flanged rollers are
indicator, winding temperature alarm/trip and controlling fans and pumps; Gas required, rail gauge should be specified;
indicator and gas actuated relay may and oil actuated relay with alarm and trip accessories for cooling arrangement.
Fittings and
7 be specified when monitoring and contacts. For OLTC tank, a separate relay or other
Accessories
control suitable protective device may be specified;
devices are available for the Explosion vent;
transformer application. Accessories for cooling arrangement; Oil
Standard accessories to be provided. temperature indicator with alarm and trip
contacts; and Two sampling valves at tap and
bottom of the main tank.

References - IS 10028 (Part 1)


IS 2026 (Part 1 & Part 5)
IS 1180 (Part 1)