You are on page 1of 9

Pump Electric

NA-HSC

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 1 of 3


www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 2 of 3
www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 3 of 3
Submittal Ref. #: SQJLX000606_1

Series: NA-HSC
Model: NA-HSC NA6x5x15L
Project name: UIN Mataram - NTB Representative: Cindy Kusnadi
Location: Phone number:
Date submitted: 5/15/2020 6:35 AM e-mail: cik_ryan@yahoo.com
Engineer: Submitted by: Kusnadi, Cindy

PROJECT DETAILS
Tag Num: 1. EFP Qty: 1
Service: Electric Fire Pump Location: Pump Room

PUMP DESIGN DATA


Pump Size NA6x5x15L Flange Rating ANSI 125lb Suction/250lb
Discharge
Fire Pump Listing Non-approved Design Head 120 m
Design Flow 1250 USgpm Maximum Working 190.34 psi
Pressure
Maximum Suction Pressure 2m 150% Design Flow BHP 206 hp
NPSHR @ Design Flow 4.28 m Design BHP 172.35 hp
NPSHR @ 150% Design Flow 4.28 m Peak Power BHP 220.63 hp
Pump Construction BF250 Motor Service Factor 1.15

PUMP Weight (lb) NOT for CONSTRUCTION


525 lb [238.14 kg]

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 1 of 2


----Duty Points—-
Design: 1250 USgpm @ 120 m
NPSHR @ Rated flow: 4.28 m
NPSHR @ 150% Rated Flow: 4.28
m

----Pump Data----
Impeller: 12.33 in
Design BHP: 172.35 hp
BHP@ 150 Design Flow: 206 hp
Peak Power: 220.63 hp
Closed Valve Pressure: 187.5 psi

---Operating Data----
Design Flow: 1250 USgpm
Motor Speed: 3000 rpm

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 2 of 2


Pump Diesel

NA-HSC

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 1 of 2


www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 2 of 2
Submittal Ref. #: SQJLX000606_1

Series: NA-HSC
Model: NA-HSC NA6x5x15L
Project name: UIN Mataram - NTB Representative: Cindy Kusnadi
Location: Phone number:
Date submitted: 5/15/2020 6:35 AM e-mail: cik_ryan@yahoo.com
Engineer: Submitted by: Kusnadi, Cindy

PROJECT DETAILS
Tag Num: 2. DFP Qty: 1
Service: Diesel Fire Pump Location: Pump Room

PUMP DESIGN DATA


Pump Size NA6x5x15L Flange Rating ANSI 125lb Suction/250lb
Discharge
Fire Pump Listing Non-approved Design Head 120 m
Design Flow 1250 USgpm Maximum Working 189.34 psi
Pressure
Maximum Suction Pressure 2m 150% Design Flow BHP 205 hp
NPSHR @ Design Flow 2.94 m Design BHP 169.29 hp
NPSHR @ 150% Design Flow 2.94 m Peak Power BHP 219.07 hp
Pump Construction BF250 Motor Service Factor n/a

PUMP Weight (lb) NOT for CONSTRUCTION


525 lb [238.14 kg]

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 1 of 2


----Duty Points—-
Design: 1250 USgpm @ 120 m
NPSHR @ Rated flow: 2.94 m
NPSHR @ 150% Rated Flow: 2.94
m

----Pump Data----
Impeller: 15.05 in
Design BHP: 169.29 hp
BHP@ 150 Design Flow: 205 hp
Peak Power: 219.07 hp
Closed Valve Pressure: 186.5 psi

---Operating Data----
Design Flow: 1250 USgpm
Motor Speed: 2350 rpm

www.armstrongfluidtechnology.com 5/15/2020 6:35:55 AM, Ref. #SQJLX000606_1 Page 2 of 2