3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.

0 1
Introduction
SP4
Information about the library 2

Soft starter blocks 3


Industrial Controls
Module drivers of the soft
starter 4
Soft starter
3RW44 Soft Starter PCS 7 Library 3RW44 soft starter in the
5
Maintenance Station
V7-V9 Migration V8.0 SP4
CFC charts for 3RW44 soft
starter 6
Programming and Operating Manual

Technical data 7

List of abbreviations A

06/2019
A5E02845977020A/RS-AD/006
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.

DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.

WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.

CAUTION
indicates that minor personal injury can result if proper precautions are not taken.

NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:

WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.

Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.

Siemens Industry Inc. 3ZX1012-0CS16-1AC1 Copyright © Siemens AG 2010.


100 Technology Drive Ⓟ 06/2019 Subject to change All rights reserved
Alpharetta, GA 30005
UNITED STATES
Table of contents

1 Introduction ................................................................................................................................................ 7
1.1 Security information ..................................................................................................................7
1.2 Product specific security information ........................................................................................7
1.3 General .....................................................................................................................................8
1.4 Installing the library ...................................................................................................................8
1.5 Configuration steps ...................................................................................................................9
1.6 Handling the driver generator .................................................................................................10
1.7 Configuring in HW Config .......................................................................................................11
1.8 Parameterization softwares ....................................................................................................13
1.9 Further documentation ............................................................................................................13
2 Information about the library .................................................................................................................... 15
2.1 What's new?............................................................................................................................15
2.2 Faceplates ..............................................................................................................................15
2.2.1 Faceplates ..............................................................................................................................15
2.2.2 General Information ................................................................................................................16
2.3 Block icons ..............................................................................................................................21
3 Soft starter blocks .................................................................................................................................... 25
3.1 Overview of the blocks ............................................................................................................25
3.2 Error numbers .........................................................................................................................26
3.3 Quality codes ..........................................................................................................................27
3.4 SS_DIAG: Diagnostic block ....................................................................................................28
3.4.1 Description ..............................................................................................................................28
3.4.2 Calling OBs .............................................................................................................................29
3.4.3 Called blocks...........................................................................................................................29
3.4.4 Parameterization .....................................................................................................................30
3.4.5 Diagnostic functions ................................................................................................................30
3.4.5.1 Diagnostics of acyclic events ..................................................................................................31
3.4.5.2 Slave diagnostics of the 3RW44 .............................................................................................33
3.4.5.3 Diagnostics of upstream block ................................................................................................38
3.4.6 Message features ...................................................................................................................39
3.4.7 Start-up characteristics ...........................................................................................................41
3.4.8 Interconnection of function blocks ..........................................................................................42
3.4.9 Block parameters ....................................................................................................................43
3.5 SS_DIR: Signal block for direct starter control function ..........................................................45
3.5.1 Description ..............................................................................................................................45
3.5.2 Calling OBs .............................................................................................................................46
3.5.3 Called blocks...........................................................................................................................46

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 3
Table of contents

3.5.4 Parameterization .................................................................................................................... 46


3.5.5 Operating modes ................................................................................................................... 48
3.5.6 Functions................................................................................................................................ 51
3.5.6.1 Description ............................................................................................................................. 51
3.5.6.2 Control.................................................................................................................................... 52
3.5.6.3 Monitoring .............................................................................................................................. 53
3.5.6.4 Trip reset ................................................................................................................................ 54
3.5.6.5 Slow speed............................................................................................................................. 54
3.5.6.6 Emergency start ..................................................................................................................... 55
3.5.6.7 Lock ........................................................................................................................................ 55
3.5.6.8 Diagnostics............................................................................................................................. 57
3.5.6.9 QGRPERR: Group error ........................................................................................................ 60
3.5.6.10 QCURR: Current message .................................................................................................... 60
3.5.6.11 Process image input and process image output of 3RW44 soft starter................................. 61
3.5.6.12 Operator authorizations ......................................................................................................... 63
3.5.6.13 Output 1 and output 2 ............................................................................................................ 64
3.5.6.14 Disable Quick Stop ................................................................................................................ 64
3.5.6.15 Logbook ................................................................................................................................. 65
3.5.6.16 Substitute value...................................................................................................................... 72
3.5.6.17 Active parameter sets ............................................................................................................ 73
3.5.6.18 Reading and writing of data sets............................................................................................ 74
3.5.6.19 Enabling measurement and statistics .................................................................................... 75
3.5.7 Message features .................................................................................................................. 76
3.5.8 Start-up characteristics .......................................................................................................... 77
3.5.9 Block parameters for the inputs ............................................................................................. 78
3.5.10 Block parameters for inputs and outputs ............................................................................... 82
3.5.11 Block parameters for the outputs ........................................................................................... 91
3.5.12 Faceplates.............................................................................................................................. 95
3.5.12.1 General .................................................................................................................................. 95
3.5.12.2 Standard View ........................................................................................................................ 96
3.5.12.3 Maintenance View .................................................................................................................. 98
3.5.12.4 Process Image View ............................................................................................................ 100
3.5.12.5 Limits View ........................................................................................................................... 101
3.5.12.6 Parameters View .................................................................................................................. 102
3.5.12.7 Parameters View and views for Parameter set 1 to Parameter set 3 .................................. 104
3.5.12.8 Logbook View....................................................................................................................... 109
3.5.12.9 Views: Station Diagnostics, Control Diagnostics, Device Diagnostics, and Parameter
Diagnostics........................................................................................................................... 110
3.5.12.10 Block icon ............................................................................................................................. 114
3.6 SS_MEAS: Measurement block ........................................................................................... 115
3.6.1 Description ........................................................................................................................... 115
3.6.2 Calling OBs .......................................................................................................................... 116
3.6.3 Called blocks ........................................................................................................................ 116
3.6.4 Parameterization .................................................................................................................. 116
3.6.5 Operating modes ................................................................................................................. 117
3.6.6 Functions.............................................................................................................................. 117
3.6.7 Message features ................................................................................................................ 119
3.6.8 Start-up characteristics ........................................................................................................ 120
3.6.9 Block parameters ................................................................................................................. 121
3.6.10 Faceplates............................................................................................................................ 123
3.7 SS_STAT: Statistics block ................................................................................................... 128

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


4 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Table of contents

3.7.1 Description ............................................................................................................................128


3.7.2 Calling OBs ...........................................................................................................................129
3.7.3 Called blocks.........................................................................................................................129
3.7.4 Parameterization ...................................................................................................................129
3.7.5 Operating modes ..................................................................................................................130
3.7.6 Functions ..............................................................................................................................130
3.7.7 Block parameters ..................................................................................................................132
3.7.8 Faceplates ............................................................................................................................135
4 Module drivers of the soft starter ........................................................................................................... 139
4.1 Object lists and action lists ...................................................................................................139
4.2 Requirements for generating the module drivers .................................................................140
4.3 Driver blocks .........................................................................................................................141
5 3RW44 soft starter in the Maintenance Station ...................................................................................... 149
6 CFC charts for 3RW44 soft starter ......................................................................................................... 153
7 Technical data ....................................................................................................................................... 157
7.1 Technical data.......................................................................................................................157
A List of abbreviations ............................................................................................................................... 159
A.1 Abbreviations ........................................................................................................................159

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 5
Table of contents

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


6 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Introduction 1
1.1 Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be
connected to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or network
segmentation) are in place.
For additional information on industrial security measures that may be implemented, please
visit
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customer’s exposure
to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed under
https://www.siemens.com/industrialsecurity.

1.2 Product specific security information

Product specific security information


This library is designed to run under the PCS 7 environment. Therefore, it is recommended
to follow the security principles for PCS 7 to support a secure operation, such as:
● User rights
● Password protection of
– WinCC
– SIRIUS devices
For more information, click here
(https://support.industry.siemens.com/cs/document/60119725).

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 7
Introduction
1.3 General

1.3 General

Overview of available versions, manuals, read me and additional information


Please find an overview of all available versions, manuals, readme and additional
information on the internet (https://support.industry.siemens.com/cs/document/109760625).
● Getting Started:
Please check on the internet (https://support.industry.siemens.com/cs/document/41856498).

Validity of the documentation


This Programming and Operating Manual applies to the following version:
● 3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4.

Components of the software


The software contains the following components:
● Block library (function blocks and user interface) with:
– Diagnostic block SS_DIAG
– Signal blocks SS_DIR, SS_MEAS and SS_STAT
● A Programming and Operating Manual in German and English.
● Online help in German and English
● Installation program
● Readme file for installation

1.4 Installing the library

Starting the installation


1. Place the CD in the CD-ROM drive of your PG/PC.
2. Launch the "setup.exe" program.
All the other information you need will be provided during the installation process.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


8 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Introduction
1.5 Configuration steps

1.5 Configuration steps

Procedure
1. Configuring with HW Config
2. Make the necessary interconnections for the inputs and outputs in the CFC Editor In so
doing, all of the inputs used must be within the process image.
3. Compile the CFC chart using the "Generate Module Driver" function.

Reference
Additional information is available in the "Process Control System PCS 7 Compendium
Part A - Configuration Guidelines" Operating Manual on the Internet
(https://support.industry.siemens.com/cs/document/107196780).

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 9
Introduction
1.6 Handling the driver generator

1.6 Handling the driver generator


The "Generate Module Drivers" function is available for signal processing in PCS 7. Once
the hardware has been configured in HW Config and the technological functions have been
configured in the CFC, this function automatically generates, interconnects, and
parameterizes the required module drivers. These module drivers are responsible for
diagnosing and reporting errors during signal processing.
The Setup program installs XML files for the connection between the 3RW44 soft starter and
the driver generator.

Supported modules and configurations


The driver concept for the 3RW44 soft starter includes operation of the soft starter:
● As a DP slave directly on the DP master system.
The connection is made by means of Softstarter OM, GSD file or by an EDD object.
● As a DP slave following a Y link
DPV1 or DPV0 is possible depending on the version of the communication module used.
The connection has to made by means of the GSD file.

More information
Additional information regarding GSD files is available in the "SIRIUS 3RW44 Soft Starter"
System Manual > Chapter "Configuration with the GSD File".
GSD, GSDML & EDD files for Soft Starter can be found in the internet. Please follow this
link: http://support.industry.siemens.com and search for
● Soft Starter GSD or
● Soft Starter EDD

Purpose of the driver generator


A signal-processing block is inserted in the CFC for each soft starter, and the connection to
the hardware is established using symbolic addressing. You can retrieve this address from
HW Config of SIMATIC Manager. For detailed information on this, refer to the online help in
"Getting Started".
The "Generate Module Driver" option inserts the additionally required OB_DIAG1 and
SS_DIAG blocks and then connects and assigns the corresponding parameters.

See also
Object lists and action lists (Page 139)
Requirements for generating the module drivers (Page 140)
Driver blocks (Page 141)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


10 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Introduction
1.7 Configuring in HW Config

1.7 Configuring in HW Config


The 3RW44 soft starter along with its associated components, the GSD file, and the object
manager files are inserted and configured in HW Config.

Note
The following diagrams show example configurations to illustrate configuring in HW Config.

DP slave directly on the DP master system

Figure 1-1 DP slave directly on the DP master system

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 11
Introduction
1.7 Configuring in HW Config

DP slave following a Y link

Figure 1-2 DP slave following a Y link

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


12 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Introduction
1.8 Parameterization softwares

1.8 Parameterization softwares

Parameterization Softwares
For parametrizing the device following softwares are availible:
- Soft Starter ES (with OM intergration)
- PDM (with Soft Starter EDD)
- GSD

1.9 Further documentation

Overview
For additional information, refer to:
● "SIRIUS 3RW44 Soft Starter" System Manual
● "Getting Started" in the online help for this block library
● Online help for SIMATIC Process Control System PCS 7
● Manuals for SIMATIC Process Control System PCS 7

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 13
Introduction
1.9 Further documentation

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


14 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Information about the library 2
2.1 What's new?

What's new?
For more details please refer the respective library version Readme.
Please check whether an updated version of readme is available on the internet
(https://support.industry.siemens.com/cs/document/109760625/).

2.2 Faceplates

2.2.1 Faceplates
A faceplate displays all elements of a block graphically. The faceplate is displayed in a
separate window on the Operator Station (OS). You can call the faceplate:
● Using picture selection keys
● From the process tag list
● By clicking the specific block symbol

Tools
The following software and templates are available for configuring the faceplates:
● In WinCCExplorer: the Graphics Designer
● PCS 7-specific standard views
● Templates available from the Faceplate Designer
– Trend
– Batch
– Alarms
● Additionally required views, user objects, and functions
Additional information: You are recommended not to open the PCS 7 Soft Starter SP1
faceplate graphics files (*.pdl) in PCS 7 V7.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 15
Information about the library
2.2 Faceplates

2.2.2 General Information

Typical structure of a faceplate


The file name of the faceplate is structured as follows:
"@<PG>_<XXX>_<YYY>.pdl".

Table 2- 1 Meaning of tags

Tag Replaced with


<PG> • PG for block-specific elements
• PCS7 for elements provided by PCS 7
<XXX> Name of block, e.g., SS_DIR
<YYY> A specific element, e.g., STANDARD for the Standard View.

① Title + Name of starter


② Pinning the faceplate:
You can use this button to secure the faceplate when switching the range.
③ "Back to Process Picture" button:
This can be used to jump back to the original process picture
④ Name of block
⑤ "Open Loop" button:
Object for selecting the loop picture. The Faceplate Designer automatically hides this object, if
generation or update of the Loop View was not selected there.
⑥ Overview window
⑦ Dropdown menu for selecting the available views for the relevant block.
Right clicking on an icon opens the selected view in a separate window.
Left clicking on the icon opens the selected view in the same window.

Figure 2-1 Example of the header structure of a faceplate

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


16 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Information about the library
2.2 Faceplates

The Overview Window


The overview window is a constituent part of the root screen, such as a faceplate. It indicates
the overall status of the block, e.g.:
● Unacknowledged alarms
● Status of warnings
● LOCK status of messages
● Status of acknowledgement of messages
● …
The overview window is contained in the following file:
"@PG_<XXX>_OVERVIEW.pdl"

① EventState - Group display:


Indicates whether unacknowledged alarms and warnings are pending.
② EventState - Status LOCK of messages:
This function is available to users with authorization level 5 and higher
③ EventState - Message acknowledgment
This function is available to users with authorization level 5 and higher.
④ M_SUP_C - Message suppression
⑤ OCCUPIED:
This function indicates whether the block instance of SIMATIC BATCH is occupied.

Figure 2-2 Typical toolbar of a faceplate

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 17
Information about the library
2.2 Faceplates

The Trend View


The Trend View is available in all signal blocks in which parameter curves are generated in
online mode, e.g., for the current.

Figure 2-3 Example: Trend View

File name: @PCS7_SS_Trend.pdl


Integrating a curve in a faceplate:
Parameterize the ReturnPath and StandardTrend in properties of the block symbol.
To open the properties of the block, please right click on the block symbol in WinCC
GraphicsDesigner.

Property Inputs Example Meaning


ReturnPath .<ZZZ> .QCURR Name of structure element starting with a dot
: : Separator
<VVV> CO_GREEN Color of the curve
StandardTrend 2 — Online values with 5-minute time axis
>2 — Archive values with time axis of the entered value in min

Example:
.QCURR:CO_GREEN
Displaying multiple curves:
If multiple curves are to be displayed in the Trend View, parameterize the curves using the
following scheme:
.<Name of structure element 1>:< Color of the curve>,.<Name of structure element 2>:<
Color of the curve>,<Name of structure element 3>:< Color of the curve>
Example:
.QIL1:CO_DKRED,.QIL2:CO_DKBLUE,.QIL3:CO_DKGREEN

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


18 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Information about the library
2.2 Faceplates

The Alarm View


The Alarm View is available in all signal blocks in which a list of all alarms and warnings is
displayed. This view can be selected via the dropdown view list of the relevant block or by
right-clicking on the group representation of the associated block symbol. The list displays
the following for each alarm and warning:
● Date
● Time of day
● Status

Figure 2-4 Example: Alarm View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 19
Information about the library
2.2 Faceplates

Batch View
The Batch View is available in all signal blocks in which the status of batch parameters is
displayed.

① BA_EN Indicates the Enabled status


② OCCUPIED Indicates the Occupied status
③ BA_NA Shows the name of the batch.
④ STEP_NO Shows the step number of the batch.
⑤ BA_ID Shows the identification number of the batch.

Figure 2-5 Example: Batch View of a block

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


20 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Information about the library
2.3 Block icons

2.3 Block icons


The block symbols are contained in the following file:
"@PCS7Typicals_SS.pdl"

Structure
Each block has four assigned block symbols. The different block symbols of the soft starters
are displayed as follows:

If you click the block symbol, the associated faceplate opens. As long as the faceplate is
open, the block symbol is highlighted in color.
The user can configure the block symbol in CFC within the scope of the available selection
via the block symbol number in the object properties of the block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 21
Information about the library
2.3 Block icons

① Block symbol number


If you click the block symbol, the associated faceplate opens. As long as the faceplate is open,
the block symbol is highlighted in color
② Indicates the enable for the lock of the block.
"L" on white background: LOCK or LOCK_ON
③ Indicates the operating mode of the block:
"M" on white background = Manual
"A" on green background = Auto
④ Indicates the operating mode:
"L" on white background = Manual operation LOCAL
"R" on white background = Remote
⑤ Group error.
⑥ Indicates the status of the motor: VSTATUS.

e.g.: symbol RUN CW

Symbol RUN CCW

Symbol STOP

Symbol Error

The symbol flashes when the motor is in the startup or coast-down phase.
⑦ Group display
Reads the message configuration of the block and displays alarms and warnings.

Figure 2-6 Structure of a block symbol

Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


22 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Information about the library
2.3 Block icons

See also
General (Page 95)
Faceplates (Page 123)
Faceplates (Page 135)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 23
Information about the library
2.3 Block icons

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


24 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks 3
3.1 Overview of the blocks
The PCS 7 Library for SIRIUS Soft Starter 3RW44 contains the following blocks:

Table 3- 1 List of blocks

Block Name of block Block type and Description


number
Diagnostic block SS_DIAG FB 561 This block performs the diagnostics of the
3RW44 soft starter. In this processes, it acquires
all diagnostic information regarding controlling,
switching, parameters, and communication.
Signal block for direct starter SS_DIR FB 562 The block controls, monitors, and switches the
control function soft starter in the clockwise or counter-clockwise
direction.
This block supports:
• Various control functions
• Various faceplates with block icon for
operation and control
Statistics block SS_STAT FB 563 This block provides statistical information, e.g.,
regarding the operating hours of the device, fault
statistics, maximum pointer
Measurement block SS_MEAS FB 564 This block provides measurement information,
e.g., regarding phase currents, output power,
phase-to-phase voltages, line frequency

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 25
Soft starter blocks
3.2 Error numbers

3.2 Error numbers

Overview
The SIMOCODE pro PCS 7 Library blocks have an output parameter ErrorNum that can be
used to output internal error states of the block as error numbers. Each error number is
assigned to a specific error. The routine always displays the error number of the error most
recently detected in a block cycle.

Table 3- 2 Error numbers per block

Error number Error type Description SS_DIAG SS_DIR SS_MEAS SS_STAT


-1 — Default value X X X X
0 — No error X X X X
1 System error Rack failure X X X X

2 System error The module — X X X


does not
respond.
3 System error The module — — — —
has been
removed.
4 System error Error in X — — —
subnet 1 or in
subnet 2
11 Programming LOCK_ON / — X — —
error LOCK_DIR
command error

"X" = Error occurs in this block. "—" = Error does not occur in this block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


26 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.3 Quality codes

3.3 Quality codes


The process values of the function blocks are generated and transferred along with a signal
status as a structured variable. This contains a statement about the signal quality. The
function blocks determine the appropriate signal status for their process outputs depending
on the signal status of the process inputs. The signal status is formed from the input
parameters according to the priority table below (highest priority is 0). This group status is
displayed in the status bar of the faceplate and of the block icon. The signal status is
displayed for each individual parameter in the faceplate next to the process values.

Overview

Table 3- 3 Quality codes per block

Quality code Priority 1) Occurs in Description SS_DIAG SS_DIR SS_MEAS SS_STAT


16#00 3 • QRACKF • Rack failure — X X —

• QMODF • Module failure

• QBUSFLT • Failure of a
PROFIBUS DP
station
16#24 2 • QRACK1ERR • Incorrect quality — — — —
or code 2)
QRACK2ERR
• OB is not
loaded
16#60 1 QSIM Simulation — — — —
16#80 0 No error Correct quality code X X X X

"X" = Quality code occurs in this block. "—" = Quality code does not occur in this block.
1) "0" = high
2) Device-specific

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 27
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4 SS_DIAG: Diagnostic block

3.4.1 Description

Block type and number: FB 561


Product group: 3RW44

Purpose of block
The SS_DIAG block performs the diagnostics of the 3RW44 soft starter:
● It evaluates the acyclic events that are relevant for the 3RW44 soft starter:
– Startup
– DP station failure
– Module error
– Diagnostic interrupt
● It evaluates the diagnostics of the upstream block, e.g.:
– RACKF: Failure of the master system rack
– SUBN1ERR, SUBN2ERR: Subnet error
● It generates the associated quality codes.
● It reads all diagnostic information of the soft starter
● It transfers the diagnostic information to the SS_DIR and SS_MEAS blocks for display in
these blocks.

See also
Technical data (Page 157)
Error numbers (Page 26)
Quality codes (Page 27)
3RW44 soft starter in the Maintenance Station (Page 149)
Module drivers of the soft starter (Page 139)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


28 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.2 Calling OBs


The "Generate Module Driver" function inserts the block into the following organization
blocks:

Table 3- 4 Organization blocks that call the SS_DIAG block

Organization block Description


OB 1 Cyclic program
OB 82 Diagnostic interrupt
OB 83 Module Interrupt
OB 85 Priority class error
OB 86 Rack failure
OB 100 Warm restart

3.4.3 Called blocks


The block calls the following blocks:

Table 3- 5 Blocks called by the SS_DIAG block

Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a process data set
SFB 54 RALRM Receives the alarm data
SFC 13 DPNRM_DG Reads the diagnostic data of the DP slave
SFC 51 RDSYSST Reads the system status list or the sublist
SFC 6 RD_SINFO Reads the start information of the OB
SFC 64 TIME_TCK Reads the system time

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 29
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.4 Parameterization

Addressing
The "Generate Module Driver" function assigns all addresses to the SS_DIAG block, for
example:
● LADDR
● DADDR
● RACK_NO
● SLOT_NO
● SUBN1ID
● SUBN_TYP

3.4.5 Diagnostic functions

General
This block executes the following diagnostic functions:
● Acyclic events:
– Rack failure
– QMODF: Module error
– QERR: Priority class error - Malfunction when loading the organization blocks (OB)
● Slave diagnostics:
– QBUSFLT: Failure of a PROFIBUS DP station
● OB_DIAG1: Diagnostics of upstream block

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


30 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.5.1 Diagnostics of acyclic events

QRACK: Rack failure


The upstream OB_DIAG1 block detects the failure of the DP master or DP slave and
evaluates it by means of the following outputs:
● RACKF
● SUB1ERR
● SUB2ERR
Interrupt OB 86 detects the failure of the rack.

Table 3- 6 Conditions under which QRACK = 1 is set

Error Status at inputs and outputs


Failure of expansion rack OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C1
Supported I/O devices: OB86_EV_CLASS = B#16#39 AND
Failure of a DP master OB86_FLT_ID = B#16#C3
Failure of a PROFIBUS DP station OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C4
Fault on a PROFIBUS DP station OB86_EV_CLASS = B#16#39 AND
OB86_FLT_ID = B#16#C5

Table 3- 7 Conditions under which QRACK is reset

Error Status at inputs and outputs


Failure of expansion rack OB86_EV_CLASS = B#16#38 AND
(OB86_FLT_ID = B#16#C1 OR OB86_FLT_ID = B#16#C2)
Failure of a PROFIBUS DP station OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C4
Fault on a PROFIBUS DP station OB86_EV_CLASS = B#16#38 AND
OB86_FLT_ID = B#16#C5
Return of a PROFIBUS DP station, but error in assigning the OB86_EV_CLASS = B#16#38 AND
module parameters OB86_FLT_ID = B#16#C7
Return of a PROFIBUS DP station, but discrepancy OB86_EV_CLASS = B#16#38 AND
between the parameterized and current configuration OB86_FLT_ID = B#16#C8

When an error occurs, OMODE=16#40xxxxxx is assigned for the value of the OMODE
output.
If the "Rack failure" error QRACKF=1 occurs, the connection between the PROFIBUS and
the device is canceled. This is indicated as follows: QBUSFLT=1.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 31
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

QMODF: Module error


Module error is validated following the restart of PLC or if ACC_ID parameter is set to TRUE.
The system status list (SSL) ID xC91 is read out for this purpose. Temporary errors are
detected by reading the system status. These are listed in the following table. The
RDSYSST (SFC51) system function indicates this error as module error QMODF.

Table 3- 8 Temporary module errors

Error number Description


8085 No information currently available due to a problem in the system, e.g.,
lack of operating resources.
80A2 Temporary error in PROFIBUS DP protocol, layer 2
80A3 Temporary error in PROFIBUS DP protocol with user interface or user.
80A4 Communication problem on the communication bus:
The error occurs between the CPU and the external PROFIBUS DP
interface.
80A5 Temporary error: The distributed I/O is not available.

When an error occurs, OMODE=16#40xxxxxx is assigned for the value of the OMODE
output.

QERR: Priority class error - Malfunction when loading the OB


Interrupt OB 85 sets or resets the priority class error QERR - Malfunction when loading OBs
for the following events:

Table 3- 9 Events during which OB 85 QERR is reset

Description Status at inputs and outputs


Error when creating a start event for an OB. OB86_EV_CLASS = B#16#35AND
This is not loaded to the CPU. (OB86_FLT_ID = B#16#A1 OR A2)
Error when the operating system accesses a module. OB86_EV_CLASS = B#16#35 AND
(OB86_FLT_ID = B#16#A1 OR A3)

QERR is only triggered once for one execution cycle of the block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


32 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.5.2 Slave diagnostics of the 3RW44


The following system function and diagnostic interrupt calls read the diagnostic information
of the 3RW44 slave.

Block Description
SFC 13 DPNRM_DG Reads the diagnostic data of the PROFIBUS DP slave
SFB 52 RDREC If diagnostic interrupt 82 occurs, this block reads a process
data set.

Diagnostic messages that relate to communication and operation are read


● Acyclically when ReadData operation is triggered either from SS_DIR or SS_MEAS
blocks.
● If interrupt OB 82 occurs.
This diagnostic information is mapped onto the QDIAG_DIR and QDIAG_MEAS output
parameters. These parameters are interconnected with the SS_DIR and SS_MEAS blocks.
The information from the station diagnostics of the PROFIBUS DP slave is read out using
SFC 13 DPNRM_DG.

Table 3- 10 Status of the station

Byte Meaning
0 Station status 1
1 Station status 2
2 Station status 3
3 Master station number
4 Vendor ID (high byte)
5 Vendor ID (low byte)
6 Further slave-specific diagnostic information

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 33
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

DIAG_DIR
DIAG_DIR is a structured characteristic map that provides the following information.

Table 3- 11 Diagnostic information in DIAG_DIR.DIAG for each bit

DIAG_DIR.DIAG bit Diagnostic message


0 DP slave cannot be accessed by DP master. 1)
1 DP slave is not yet ready for data exchange.
2 Config data to DP slave from DP master does not match.
3 External diagnostics pending (Group diagnostics display)
4 Function not supported by DP slave e.g.: node address change by the
software
5 DP master cannot interpret DP slave response.
6 DP slave type does not match software config.
7 DP slave parameterized by a different DP master
8 DP slave parameters must be reassigned.
9 Static diagnostic message:
A diagnostics message is pending. DP slave will not function until the
error is corrected.
10 Bit is set to "1" as long as DP slave address exists.
11 Watchdog function activated for DP slave
12 DP slave has received "FREEZE" command.
13 DP slave has received "SYNC" command.
14 DP slave has been deactivated, e.g., it is not included in the current
processing.
15 More diagnostic messages than DP slave can store.
The DP master cannot write all diagnostic messages to its diagnostic
buffer that were sent by the DP slave.
16 … 31 Not used

1) The lost connection is signaled with QBUSFLT and as an alarm in WinCC. See also:

QBUSFLT: Failure of a PROFIBUS DP station (Page 38)


Various other diagnostic information are mapped onto DIAG_DIR, e.g., information on:
● Communication
● Parameters
● Switching
● Control

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


34 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

Table 3- 12 DIAG_DIR parameters

Parameter Data format Message Diagnostic type


DIAG 1) DWORD 3RW44 PROFIBUS DP slave diagnostics Station diagnostics
BUSERR BOOL Bus error
CPUMSTRSTOP BOOL CPU/master Stop
AUTOPLCCNTRL BOOL Automatic mode (CPU controls)
MANBUSCNTRL BOOL Manual operation bus, OCM controls
MANLOCCNTRL BOOL Manual operation LOCAL
CONNBRK BOOL Connection break in local mode
PIERROR BOOL Process image error Communication
NOEXTSTPAR BOOL No external startup parameters received
MANBUSPCCNT BOOL Manual operation bus, PC controls
MANLOCINCNT BOOL Manual operation LOCAL - input controls
MANLOCOMCNT BOOL Manual operation LOCAL - OCM controls
MANLOCPCNT BOOL Manual operation LOCAL - PC controls
READY BOOL Ready (automatic)
MOTCW BOOL Motor right (clock wise)
MOTCCW BOOL Motor left (counter clock wise)
EMGSTART BOOL Emergency start is active
GRPERR BOOL Group error
GRPWARN BOOL Group warning
BYPPRTTRP BOOL Bypass element protective tripping
CNTOVLD BOOL Contact block overload
CNTDMAG BOOL Contact block defective
NOMAINPWR BOOL No supply voltage
STRTMODACT BOOL Starting active Switching and controlling
STPMODACT BOOL Coast-down active
ELEBRKACT BOOL Electrical braking active
SLWSPDACT BOOL Slow speed active
CTRLINPUT BOOL Input control
QCKSTPACT BOOL Quick stop active
ELEVLTHI BOOL Electronics supply voltage too high
ELEVLTLO BOOL Electronics supply voltage too low
RDYMOTON BOOL Ready for motor ON
CNTSHRT BOOL Contact block short-circuited
BYPPRTFLT BOOL Bypass element defective
SWELE1FAIL BOOL Contact block 1 failed
SWELE2FAIL BOOL Contact block 2 failed
SWELE3FAIL BOOL Contact block 3 failed

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 35
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

Parameter Data format Message Diagnostic type


FACTSETRSTR BOOL Factory settings restored
FLTPARLB BYTE Incorrect parameter number
(least significant byte)
FLTPARHB BYTE Incorrect parameter number
(most significant byte)
IMPERCLASS BOOL Impermissible Ie / CLASS settings
PSACTIVE BOOL Parameter assignment active
PS1ACTIVE BOOL Parameter set 1 active
PS2ACTIVE BOOL Parameter set 2 active
PS3ACTIVE BOOL Parameter set 3 active
IMPCHNGPS BOOL Parameter set change impermissible
INCORPSVAL BOOL Invalid parameter value
PSPERMIT BOOL Parameter changes not permissible when
ON
PSDISCPUACT BOOL Parameters disabled CPU/master active
MOTHEATACT BOOL Motor heating active
DCBRKACT BOOL DC braking active Parameter
DYNDCBRK BOOL Dynamic braking active
CONSTDELT BOOL Motor connection type start/delta
CONINSDDELT BOOL Motor connection type inside delta
CONUNKWN BOOL Motor connection type unknown
NOLOAD BOOL No load
PHS1LOSS BOOL Phase failure L1
PHS2LOSS BOOL Phase failure L2
PHS3LOSS BOOL Phase failure L3
LIPHDIR BOOL Line phase direction right
LIPHREV BOOL Line phase direction left
OUT1ACT BOOL Output 1 active
OUT2ACT BOOL Output 2 active
OUT3ACT BOOL Output 3 active
OUT4ACT BOOL Output 4 active
TRPRSTCARID — Trip reset successful
TRPRSTNOTPOS BOOL Trip reset unsuccessful
MAXPNTRDEL BOOL Maximum pointer reset

1) This station diagnostics information is mapped onto the QDIAG.DIAG parameter as shown above.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


36 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

DIAG_MEAS
DIAG_MEAS is a structured characteristic map that provides the following information.

Table 3- 13 DIAG_MEAS parameters

Parameter Data format Meaning Diagnostic type


TMPSNSOVLD BOOL Temperature sensor overload
TMPSNSOPEN BOOL Temperature sensor wire break
TMPSNSSHORT BOOL Temperature sensor short-circuit
TMMOVLD BOOL Thermal motor model overload
OVLDSWOFF BOOL Overload switch off
IDLETMACT BOOL Idle time active
COOLDNTMACT BOOL Cooling time active
ASYMREC BOOL Asymmetry detected
ASYMSWOFF BOOL Asymmetry tripping
CURHI BOOL Current limit overshot
CURLO BOOL Current limit undershot
CURLMSWOFF BOOL Ie limit value tripping
Protective function
CURLMACT BOOL Current limiting active
motor/cable/short-circuited
MOTSTLSWOFF BOOL Motor block tripping
INPUT1 BOOL Input 1 active
INPUT2 BOOL Input 2 active
INPUT3 BOOL Input 3 active
INPUT4 BOOL Input 4 active
GNDFLT BOOL Ground fault
GNDFLTSWOFF BOOL Ground fault tripping
TMMDEACT BOOL Thermal motor model deactivated
PHANGCTRFLT BOOL Generalized phase error
COOLCNTACT BOOL Contact block cooling time active
CTNHOTSTART BOOL Contact block too hot for start
CUROVERFLOW BOOL Current measuring range exceeded
PREWRNUNDSHT BOOL Prewarning limit - prewarning time undershot
PREWRNHTEXED BOOL Prewarning limit - motor heating overshot

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 37
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

QBUSFLT: Failure of a PROFIBUS DP station

QBUSFLT
DIAG_DIR.DIAG Bit 0 indicates QBUSFLT.

Table 3- 14 Possible reasons for the connection error

Byte 0 Meaning Reason or remedy


Bit 0 1: DP slave cannot be accessed by DP master. • Is the station address of the DP slave set
correctly?
• Is the bus connector connected?
• Is voltage applied to the DP slave?
• Is the RS 485 Repeater secured correctly?
• Has a reset been performed on the DP
slave?

See also
Slave diagnostics of the 3RW44 (Page 33)

3.4.5.3 Diagnostics of upstream block

OB_DIAG1
The upstream OB_DIAG1 block detects the module failure. The module failure calls the
RACKF parameter and outputs QRACKF parameter sets.

See also
Handling the driver generator (Page 10)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


38 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.6 Message features

Messages
The diagnostic block outputs the messages via WinCC.

Table 3- 15 Output messages

Input Message Parameter Message Message


parameter no. class
MSG_EVID 2) 1 QRACK1ERR $$BlockComment$$Subnet1@1%d@:fault S
2 QRACK2ERR $$BlockComment$$Subnet2@2%d@:fault S
3 QRACKF $$BlockComment$$ DP Slave S
@1%d@/@5%d@/@3%d@: failure
4 QMODF $$BlockComment$$ DP Slave S
@1%d@/@5%d@/@3%d@: Module error
5 QBUSFLT $$BlockComment$$ DP Slave S
@1%d@/@5%d@/@3%d@: not reachable
6 MSG_6 1) $$BlockComment$$ Message Input 6 A
7 MSG_7 1) $$BlockComment$$ Message Input 7 A
8 MSG_8 1) $$BlockComment$$ Message Input 8 A

1) The MSG_6, MSG_7 and MSG_8 parameters represent messages that can be user-configured.
2) Parameters with message number for ALARM_8P.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 39
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

Table 3- 16 Structure of the related values in ALARM_8P

Message Related value Parameter Meaning


no.
1 1 SUBN1_ID Number of the DP master system (primary)
2 2 SUBN2_ID Number of the DP master system (redundant)
3 3 RACK_NO Rack/station number
4 4 SLOT_NO Slot number
5 5 SUBLNK_ID ID of Y-Link Subnet
6 6 AUX_PR06 1) Auxiliary value 6
7 7 AUX_PR07 1) Auxiliary value 7
8 8 AUX_PR08 1) Auxiliary value 8
9 9 AUX_PR09 1) Auxiliary value 9
10 10 AUX_PR010 1) Auxiliary value 10

1) The AUX_PR05 bis AUX_PR010 parameters represent auxiliary values for messages that can be user-configured.

The QMS_STAT, QMSG_ACK and QMSG_ERR parameters transfer the information found
in ALARM_8P:
● Status of messages
● Status of an alarm acknowledgement
● Status of errors during data transfer

See also
Block parameters (Page 43)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


40 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.7 Start-up characteristics

Description
The identifier for startup is OMODE=16#xx01xxxx. It is entered in OB 100 in the OMODE
output.
All alarm messages are suppressed in OB 100:
The user may define a value for the block parameter RUNUPCYC, different from the default
value of 10 cycles. This is assigned to OB 100 in order to suppress the messages for the
configured cycle count.
OB 100 resets the following errors:
● QERR
● QRACKF
● QMODE
● QRACK1ERR
● QRACK2ERR

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 41
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.8 Interconnection of function blocks

Figure 3-1 Interconnection of function blocks

See also
CFC charts for 3RW44 soft starter (Page 153)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


42 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

3.4.9 Block parameters

Table 3- 17 Parameters of the SS_DIAG block

Name of Data format Type Default value Meaning


parameter
AUX_PR06 ANY Input — Auxiliary value 6
AUX_PR07 ANY Input — Auxiliary value 7
AUX_PR08 ANY Input — Auxiliary value 8
AUX_PR09 ANY Input — Auxiliary value 9
DADDR INT Input 0 Diagnostic address of module
DPA_LINK BOOL Input FALSE Device connection:
1 = DP master
2 = Y link
EN_DIAG BOOL Input TRUE 1 = Enable: Reading of diagnostic data
MODE WORD Input 16#00 SS_DIAG OMODE
MSG_6 BOOL Input FALSE Message input 6
MSG_7 BOOL Input FALSE Message input 7
MSG_8 BOOL Input FALSE Message input 8
MSG_EVID DWORD Input 16#FF Number of the message event
RACK_NO INT Input 0 Address of DP slave
RACKF BOOL Input FALSE 1 = Rack failure
RD_DATA BOOL Input 0 1 = Read Device Diagnosis data set (DS92)
RSRV_IN WORD Input 16#00 Reserved
RUNUPCYC INT Input 3 Number of the cycle for which all messages are
suppressed
SLOT_NO INT Input 0 Slot number
SUBADDR INT Input 0 Subaddress
SUBN_TYP BOOL Input FALSE 1 = External DP interface
SUBN1_ID BYTE Input 16#FF Number of the primary DP master system
SUBN1ERR BOOL Input FALSE 1 = Slave
2 = Failure
SUBN2_ID BYTE Input 16#FF Number of the redundant DP master system
SUBN2ERR BOOL Input FALSE 1 = Slave
2 = Failure
SUBLNK_ID WORD Input 16#FFFF ID of Y Link Subnet
PA_DIAG DWORD Output 0 Diagnostic information for maintenance
SUBSLOT_NO INT Input 0 Signal module:
Address of channel
ACC_ID BOOL ON/OFF TRUE 1 = Accept new operating mode settings
LADDR WORD ON/OFF 16#0000 Logical address of soft starter
DIAG_DIR SSDIAGDIR* Outputs — Diagnostic information to SS_DIR block
DIAG_MEAS SSDIAGMEAS* Outputs — Diagnostic information to SS_MEAS block

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 43
Soft starter blocks
3.4 SS_DIAG: Diagnostic block

Name of Data format Type Default value Meaning


parameter
ERRORNUM INT Outputs -1 Error number
OMODE DWORD Outputs 16#00 Status
QBUSFLT BOOL Outputs FALSE 1 = The PROFIBUS connection to the DP slave
has failed
QEN_RD BOOL Outputs FALSE 1 = Enable: Reading of data sets
QERR BOOL Outputs FALSE 1 = Group error
QERR_RD BOOL Outputs FALSE 1 = Error while reading the data set
QMODF BOOL Outputs FALSE 1 = Module failure
QMSG_ACK WORD Outputs 16#00 ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Outputs FALSE 1 = Error during data transfer
QMSG_STAT WORD Outputs 16#00 ALARM_8P:
Status of outputs
QRACK1ERR BOOL Outputs FALSE 1 = Failure of DP slave system
(primary master)
QRACK2ERR BOOL Outputs FALSE 1 = Failure of DP slave system (redundant
master)
QRACKF BOOL Outputs FALSE 1 = Rack failure
QRSRV_OUT WORD Output 16#00 Reserved
QUALITY BYTE Outputs 16#80 Quality code

* = These parameters are structured labels that obtain information from data set 92.

Table 3- 18 Structure of OMODE

Byte Value Meaning


3 16#80 Valid data Primary error
16#40 Invalid data
16#20 Redundancy failure
2 16#01 Startup OB 100 —
1; 0 16#0000 —

See also
Message features (Page 39)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


44 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5 SS_DIR: Signal block for direct starter control function

3.5.1 Description

Block type and number: FB 562


Product group: 3RW44

Purpose of block
The SS_DIR block controls, monitors, and switches the soft starter in the clockwise or
counter-clockwise direction.
This block supports different control functions, such as:
● RUN / STOP
● Monitoring
● Slow speed
● Emergency start
● Lock
● Diagnostics
● Logbook
● Output function
● Trip reset
The SS_DIR block supports various faceplates with block icon for operation and control.

See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 139)
Interconnection of function blocks (Page 42)
CFC charts for 3RW44 soft starter (Page 153)
Technical data (Page 157)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 45
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.2 Calling OBs


The "Generate Module Driver" function inserts the block into the following organization
blocks:

Table 3- 19 Organization blocks that call the SS_DIR block

Organization block Description


OB 30 … OB 38 Cyclic interrupts
OB 100 Warm restart

3.5.3 Called blocks


The block calls the following blocks:

Table 3- 20 Blocks called by the SS_DIR block

Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a data set
SFB 53 WRREC Writes a data set
SFC 20 BLKMOV Copies variables
SFC 6 RD_SINFO Reads the start information of the OB

3.5.4 Parameterization

IN_01: Assigning the input address of the module


I-address:
2 bytes of input address of the module must be assigned to input parameter IN_01.

LADDR: Assigning the logical address


The module driver parameterizes the logical address LADDR of the soft starter
automatically.
The logical address is used to interconnect the IN_01 parameter of the function block.

DADDR: Diagnostic address


The module driver parameterizes the diagnostics address DADDR of the soft starter
automatically.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


46 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Assigning rated operational current


Parameterize the rated operational current of the soft starter in HW Config and in the block
parameters.
Call the following in HW Config:
1. Double-click to open the "Properties DP slave" dialog
2. Click "Parameterize". Set the parameters **), e.g., rated operational current
3. Click "OK". This completes the configuration.
Set input parameter PSx_IRATE as the rated operational current of the device.
"X" stands for 1, 2, or 3 based on the active parameter set.

Note
DPV0 in DP alarm mode
If the device is configured as DPV0 in DP alarm mode in HW Config, these parameters will
not be written to the soft starter.

Parameter sets
The three parameter sets PS1, PS2, and PS3 have been parameterized to specify the basic
parameters, such as:
● Rated operational current
● Velocity
● Torque
● Control functions:
– Startup mode
– Coast-down mode
– Current limits
– ...

See also
CFC charts for 3RW44 soft starter (Page 153)
Parameters View and views for Parameter set 1 to Parameter set 3 (Page 104)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 47
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.5 Operating modes

Operating mode LOCAL/REMOTE


Enabling switching between LOCAL and Remote control operations is not possible using the
library. Other software tools (Soft Starter ES, PDM, ...) have to be used for it. The process
image input 0.0 indicates whether the starter is running in REMOTE or LOCAL mode.
The specified operating mode is displayed at the QREMOTE output.
1 = Remote
0 = Manual operation LOCAL/Soft Starter ES
The device is controlled either locally or via other software tools (Soft Starter ES, PDM, ...).
When in the local mode, the following operations are available, such as:
● Motor CW
● Motor CCW

Note
Slow speed must be enabled in order for the Motor CCW operation to be active.

● Trip reset
● Emergency start
● Slow speed
● Output 1
● Output 2
● Disable Quick Stop
The same information is monitored in the faceplate views.
In Manual operation LOCAL mode, the OUT_01 output of the function block monitors the
process image output (PIQ; byte 1 and byte 2). This ensures that the status of the control
output does not change while the CPU switches back to Remote mode.
In Manual operation LOCAL mode, parameterize the parameter sets with Soft Starter ES or
directly in the hardware of the soft starter. These parameters are synchronized with the
parameters of the function block. This ensures that the status of the parameterized values
does not change while the CPU switches back to Remote mode.
The monitoring function does not monitor in Manual operation LOCAL mode.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


48 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Operating mode Auto/Manual


Requirement:
Use the Automatic mode command (remote control by the CPU) in Soft Starter ES. This
defines: Process image input 0.0 = 1.

Switch function block to Auto mode: Set LIOP_SEL = 1 and AUT_L =1 Interlinked parameters
Switch faceplate (OS) to Auto mode: Set LIOP_SEL = 0 and AUT_ON_OP = 1 Operating parameters

Switch function block to Manual mode: Set LIOP_SEL = 1 and AUT_L =0 Interlinked parameters
Switch faceplate (OS) to Auto mode: Set LIOP_SEL = 0 and set AUT_ON_OP = 0 Operating parameters

The specified operating mode is displayed at the QMAN_AUT output.


1 = Auto
0 = Manual

Figure 3-2 Mode switching

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 49
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Table 3- 21 Parameters that are active in Auto and Manual modes

Operating mode Auto Operating mode Manual Description


(interlinked parameters) LINK_MAN=0(operating LINK_MAN=1 (interlinked
parameters) parameters)
MOTCW_LI MOTCW_OP L_MOTCW Motor CW
MOTCCW_LI MOTCCW_OP L_MOTCCW Motor CCW
MOTOF_LI MOTOF_OP L_MOTOF Motor OFF
TRPRST_LI TRPRST_OP L_TRPRST Trip reset
EMRGST_LI EMRGST_OP L_EMRGST Emergency start
SLSPD_LI SLSPD_OP L_SLSPD Slow speed
OUT1_LI OUT1_OP L_OUT1 Output 1 function
OUT2_LI OUT2_OP L_OUT2 Output 2 function
DSQSTP_LI DSQSTP_OP L_DSQSTP Disable Quick Stop

Operating parameters are provided, operating permission is specified.


A signal with rising edge is pending at the XXX_LI parameters.

See also
Standard View (Page 96)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


50 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6 Functions

3.5.6.1 Description

General
The SS_DIR block has the following functions:
● Control
● Monitoring
● Trip reset
● Slow speed
● Emergency start
● Interlock
● Diagnostics
● QGRPERR: Group error
● QCURR: Current message
● Process image input and process image output
● Operator authorizations
● Output 1 and Output 2
● Disable Quick Stop
● Logbook
● Substitute value
● Active parameter sets
● Reading and writing of data sets
● Enabling measurement and statistics

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 51
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.2 Control

Functions for the motor start


The motor can be started in the clockwise or counter-clockwise direction in the following
operating modes:
● Manual operation LOCAL
● Auto
● Manual

Table 3- 22 Effectiveness of parameters for each operating mode

Operating mode Manual Operating mode Auto Operating mode Manual Description
operation LOCAL1)
PIQ 0.0 = 1 MOTCW_LI = 1 MOTCW_OP = 1 Motor CW
PIQ 0.1 = 1 MOTCCW_LI = 1 MOTCCW_OP = 1 Motor CCW 2)
PIQ 0.0 = 0 and PII 0.1 = 0 MOTOF_LI = 1 MOTOF_OP = 1 Motor OFF

1) Soft Starter ES
2) The following must be enabled for Motor CCW:
Slow speed SLSPD_LI = 1 in Auto mode, SLSPD_OP = 1 in Manual mode, and PIQ 0.6 = 1

A signal with rising edge is pending at the XXX_LI parameters.


Operation in LOCAL mode has priority. The function block and the faceplate cannot perform
any operations. However, the operation in LOCAL mode is monitored in the faceplate and in
the block icon.

Table 3- 23 General information for Auto and Manual modes: Parameters that indicate the ON/OFF status

Output parameter Related PIQ bits Description


QMOT_CW = 1 PIQ 0.0 Introductory command for starting the motor in
the clockwise direction
QMOT_CW = 0 PIQ 0.0 Introductory command for stopping the motor in
the clockwise direction
QMOT_CCW = 1 1) PIQ 0.1 Introductory command for starting the motor in
the counter-clockwise direction
QMOT_CCW = 0 PIQ 0.1 Introductory command for stopping the motor in
the counter-clockwise direction

1) The following must be enabled for Motor CCW:


Slow speed SLSPD_LI = 1 in Auto mode, SLSPD_OP = 1 in Manual mode, and PIQ 0.6 = 1

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


52 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.3 Monitoring

QMON_ERR, TIME_MON
This function monitors the consistency between the control command and the feedback
signal of the parameter within the specified TIME_MON monitoring time. Each discrepancy is
indicated with monitoring error QMON_ERR.

Table 3- 24 Parameters of control commands with the assigned PIQ and PII bits

Parameter of control Assigned PIQ bits 1) Assigned PII bits 2) Description


commands
QMOT_CW = 1 PIQ 0.0 PII 0.1 Each discrepancy is indicated with
monitoring error QMON_ERR. …
QMOT_CCW = 1 3) PIQ 0.1 PII 0.1 Each discrepancy is indicated with
monitoring error QMON_ERR. …

1) PIQ = Process image output


2) PII = Process image input, feedback parameters
3) For Motor CCW, the slow speed function must be enabled:
SLSPD_LI = 1 in Auto mode and PIQ 0.6 = 1

The MONITOR parameter indicates whether the monitoring function is enabled or disabled:
MONITOR = 1 enables the monitoring function.
MONITOR = 0 disables the monitoring function.
If the feedback signal of the process image input changes, the monitoring function performs
another check to determine whether a discrepancy exists between the feedback signal and
the process image output. Once the specified monitoring time elapses, any discrepancy is
indicated with monitoring error QMON_ERR.
If the block is in the LOCAL mode, monitoring errors are not checked. The process image
outputs 0.0 and 0.1 monitor the feedback signal of the process image input 0.1. This
prevents a bump from occurring when the operating mode is changed from LOCAL to Auto
or Manual mode.
The monitoring time is specified in seconds. If the monitoring time is less than the sampling
time, the monitoring time will be calibrated to the sampling time.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 53
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.4 Trip reset

Purpose and trigger of trip reset


Trip reset acknowledges all errors currently pending in the starter that require
acknowledgement. An error can be acknowledged once it has been resolved or if it no longer
exists.
Trip reset can be triggered as follows:
● Locally on the device
● By actuating TRPRST_OP in the Standard View (command reset), if this view has been
enabled for the Trip reset function:
TRPRSTOP_EN = 1
● By the TRPRST_LI link parameter. This is a signal with rising edge.
This sets the process image output DP bit 0.3.
Output parameter QTRPRSTOP indicates whether the Trip reset function is enabled for the
operator.

3.5.6.5 Slow speed

Purpose
This function allows you to temporarily operate an asynchronous motor in both directions of
rotation at a speed that is less than the rated speed.
The slow speed factor and the slow torque can be entered individually for both directions of
rotation in the Parameters View.
Various parameters are used in the different operating modes to set the slow speed.

Table 3- 25 Parameters for activation of slow speed for each operating mode

Operating mode Input parameter Assigned PIQ bits Operated via


LOCAL — PIQ 0.6 Other software
Auto SLSPD_LI = 1 1) PIQ 0.6 —
Manual SLSPD_OP = 1 PIQ 0.6 —

1) Precondition for Start Motor CCW is start command Slow speed on the starter.

QMOT_SLSPD = 1 indicates that slow speed is activated.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


54 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.6 Emergency start

Purpose and trigger of emergency start


The emergency start enables a restart in spite of an internal shutdown command.
The emergency start function can be triggered as follows:
● By enabling emergency startEMRGST_OP in the Maintenance View, if this view is
enabled on the operator side for the emergency start function:
EMSTOP_EN = 1
● By the EMRGST_LI link parameter, which is a signal with a rising edge
This sets the process image output DP bit 0.4.
Output parameter QEMSTOP indicates whether the emergency start function is enabled for
the operator.

3.5.6.7 Lock

LOCK, LOCK_ON
The LOCK and LOCK_ON functions are only available in Remote operating mode. An active
lock input prevents switching and disables control commands. LOCK always overwrites
LOCK_ON.
LOCK = 1: LOCK is set to OFF
The control commands are set in order to stop the motor.
QMOT_CW = 0
QMOT_CCW = 0
LOCK_ON = 1: LOCK is set to ON
LOCK_DIR = 0: Motor CW
LOCK_DIR = 1: Motor CCW
The control commands are set in order to start the motor based on the values set in
LOCK_ON and LOCK_DIR:
QMOT_CW = 1
QMOT_CCW = 1

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 55
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

For the LOCK and LOCK_ON functions, the following operating commands and linkable
control commands are disabled:
● MOTCW_OP
● MOTCW_LI
● MOTCCW_LI
The Standard View displays the "padlock" symbol to indicate whether the LOCK and
LOCK_ON functions are set.

Note
If slow speed has not been selected and LOCK_ON, LOCK_DIR command has been
initiated with CCW direction, an error number is generated as ERRORNUM. This status is
displayed in the Standard view in the faceplate as LOCK blinking in the status field.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


56 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.8 Diagnostics
The SS_DIR block receives diagnostic information from the SS_DIAG block. The SS_DIR
block displays this diagnostic information in various Diagnostics Views.

Note
The SS_DIAG block detects a rack failure and a module failure. These are interconnected
with the SS_DIR block and are indicated at the following outputs:
• QRACKF
• QMODF

QDIAG: PROFIBUS DP slave diagnostics

Table 3- 26 DIAG_DIR.DIAG: Bit assignment

Related structured QDIAG bit no. Description


characteristic map
DIAG_DIR.DIAG 0 DP slave cannot be accessed by DP master.
1 DP slave is not yet ready for data exchange.
2 Config data to DP slave from DP master does not match.
3 External diagnostics pending (Group diagnostics display)
4 Function is not supported by DP slave e.g.: station address change by the
software
5 DP master cannot interpret DP slave response.
6 DP slave type does not match software config.
7 DP slave parameterized by a different DP master
8 DP slave parameters must be reassigned.
9 Static diagnostic message:
A diagnostics message is pending. DP slave will not function until the error is
corrected. (Static diagnostic message)
10 Bit is set to "1" as long as DP slave address exists.
11 Watchdog function activated for DP slave
12 DP slave has received "FREEZE" command.
13 DP slave has received "SYNC" command.
14 DP slave has been deactivated, e.g.: it is not included in the current
processing.
15 More diagnostic messages than DP slave can store.The DP master cannot
write all diagnostic messages to its diagnostic buffer that were sent by the DP
slave. (Channel diagnostics)
— 16 … 31 Not used

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 57
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

QDIAGCM1: Diagnostics for communication, switching, and control

Table 3- 27 QDIAGCM1 Bit assignment of structured characteristic map DIAG_DIR

Related structured characteristic map QDIAGCM1 bit no. Description


DIAG_DIR
BUSERR 0 Bus error
CPUMSTRSTOP 1 CPU/master Stop
AUTOPLCCNTRL 2 Automatic mode (CPU controls)
MANBUSCNTRL 3 Manual operation bus, OCM controls
MANLOCCNTRL 4 Manual operation LOCAL
CONNBRK 5 Connection break in local mode
PIERROR 6 Process image error
MANBUSPCCNT 7 Manual operation bus, PC controls
MANLOCINCNT 8 Manual operation LOCAL - input controls
MANLOCOMCNT 9 Manual operation LOCAL - OCM controls
MANLOCPCNT 10 Manual operation LOCAL - PC controls
CNTOVLD 11 Contact block overload
CNTDMAG 12 Contact block defective
NOMAINPWR 13 No supply voltage
STRTMODACT 14 Starting active
STPMODACT 15 Coast-down active
ELEBRKACT 16 Electrical braking active
SLWSPDACT 17 Slow speed active
CTRLINPUT 18 Input control
QCKSTPACT 19 Quick Stop active
ELEVLTHI 20 Electronics supply voltage too high
ELEVLTLO 21 Electronics supply voltage too low
RDYMOTON 22 Ready for motor ON
CNTSHRT 23 Contact block short-circuited
BYPPRTFLT 24 Bypass element defective
SWELE1FAIL 25 Contact block 1 failed
SWELE2FAIL 26 Contact block 2 failed
SWELE3FAIL 27 Contact block 3 failed
NOEXTSTPAR 28 No external startup parameters received
BYPPRTTRP 29 Bypass element protective tripping
— 30 … 31 Reserved

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


58 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

QDIAGCM2: Bit assignment of structured characteristic map DIAG_DIR

Table 3- 28 QDIAGCM2 Bit assignment of structured characteristic map DIAG_DIR

Related structured characteristic map QDIAGCM2 bit no. Description


DIAG_DIR
READY 0 Ready (automatic)
MOTCW 1 Motor right
MOTCCW 2 Motor left
EMGSTART 3 Emergency start is active
GRPERR 4 Group error
GRPWARN 5 Group warning
-- 6...31 Reserved

QDIAGPAR: Diagnostics for parameters and device function

Table 3- 29 QDIAGPAR Bit assignment of structured characteristic map DIAG_DIR

Related structured characteristic map QDIAGPAR bit no. Description


DIAG_DIR
FACTSETRSTR 0 Factory settings restored
IMPERCLASS 1 Impermissible Ie / CLASS settings
PSACTIVE 2 Parameter assignment active
PS1ACTIVE 3 Parameter set 1 active
PS2ACTIVE 4 Parameter set 2 active
PS3ACTIVE 5 Parameter set 3 active
IMPCHNGPS 6 Parameter set change impermissible
INCORPSVAL 7 Invalid parameter value
PSPERMIT 8 Parameter changes not permissible when ON
PSDISCPUACT 9 Parameters disabled CPU/master active
MOTHEATACT 10 Motor heating active
DCBRKACT 11 DC braking active
DYNDCBRK 12 Dynamic braking active
CONSTDELT 13 Motor connection type start/delta
CONINSDDELT 14 Motor connection type inside delta
CONUNKWN 15 Motor connection type unknown
NOLOAD 16 No load
PHS1LOSS 17 Phase failure 1
PHS2LOSS 18 Phase failure 2
PHS3LOSS 19 Phase failure 3
LIPHDIR 20 Line phase direction right
OUT1ACT 21 Output 1 active
OUT2ACT 22 Output 2 active
OUT3ACT 23 Output 3 active

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 59
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Related structured characteristic map QDIAGPAR bit no. Description


DIAG_DIR
OUT4ACT 24 Output 4 active
TRPRSTCARID 25 Trip reset successful
TRPRSTNOTPOS 26 Trip reset unsuccessful
MAXPNTRDEL 27 Maximum pointer reset
LIPHREV 28 Line phase direction left
29 … 31 Reserved

QFLTPAR: Diagnostics for incorrect parameter numbers

Table 3- 30 QFLTPAR Byte assignment of structured characteristic map DIAG_DIR

Related structured characteristic map QFLTPAR byte no. Description


DIAG_DIR
FLTPARLB 0 Incorrect parameter number (least significant byte)
FLTPARHB 1 Incorrect parameter number (most significant byte)

See also
Slave diagnostics of the 3RW44 (Page 33)

3.5.6.9 QGRPERR: Group error

QGRPERR
The Group error parameter is set when one of the failures or errors listed below is detected.
The Standard View displays these errors as a group error.
● Group error: Process image bit 0.2:
● Module failure
● Rack failure
● Monitoring error

3.5.6.10 QCURR: Current message

QCURR
Bits 1.0 to 1.5 of the process image input write the current consumption when the motor is
connected. The QCURR output parameter indicates this information in amperes.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


60 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.11 Process image input and process image output of 3RW44 soft starter

Bit assignment

Table 3- 31 Process image input: Bit assignment of byte 0 and byte 1

Byte.Bit Meaning
DP 0.0 Ready to start (automatic)
DP 0.1 Motor ON
DP 0.2 Group error
DP 0.3 Group warning
DP 0.4 Input 1
DP 0.5 Input 2
DP 0.6 Input 3
DP 0.7 Input 4
Motor current
DP 1.0 Motor Current act-bit 0
DP 1.1 Motor Current act-bit 1
DP 1.2 Motor Current act-bit 2
DP 1.3 Motor Current act-bit 3
DP 1.4 Motor Current act-bit 4
DP 1.5 Motor Current act-bit 5
DP 1.6 Manual operation LOCAL mode
DP 1.7 Ramp operation

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 61
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Table 3- 32 Process image output: Bit assignment of byte 0 and byte 1

Byte.Bit Meaning
DP 0.0 Motor CW
DP 0.1 Motor CCW
DP 0.2 Brake
DP 0.3 Trip reset
DP 0.4 Emergency start
DP 0.5 Self-test
DP 0.6 Slow speed
DP 0.7 Reserved
DP 1.0 Output 1
DP 1.1 Output 2
DP 1.2 Active parameter sets 1, 2, 3
DP 1.3
DP 1.4 Reduction factor
DP 1.5
DP 1.6
DP 1.7 Disable Quick Stop

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


62 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.12 Operator authorizations

Operator authorizations
The enable parameters allow the operator to issue the desired commands. These
commands are interconnected to the corresponding outputs. This permits operation to be
enabled from the Standard View of the faceplate.
Example:
If the block is in Manual mode and AUTOP_EN = 0, the operator must not change the
operating mode of the block to Auto. He must not change the operating mode from the
Standard View of the faceplate or in the CFC. QAUTOP = FALSE is set in this process.
In a similar manner, every _EN parameter enables the corresponding operation.

Authorization ON Authorization OFF Description of _EN parameter Name of related


Name of parameter Name of parameter operating parameter
MANOP_EN QMANOP Enable: AUT_ON_OP
1 = Operator may enter Manual.
AUTOP_EN QAUTOP Enable:
1 = Operator may enter Auto.
MOTCWOP_EN QMOTCWOP Enable: MOTCW_OP
1 = Operator may enter Motor CW.
MOTCCWOP_EN QMOTCCWOP Enable: MOTCCW_OP
1 = Operator may enter Motor CCW.
MOTOFOP_EN QMOTOFOP Enable: MOTOF_OP
1 = Operator may enter Motor OFF.
TRPRSTOP_EN QTRPRSTOP Enable: TRPRST_OP
1 = Operator may enter Trip reset.
EMSTOP_EN QEMSTOP Enable: EMRGST_OP
1 = Operator may enter Emergency start.
SLSPD_EN SLSPDOP Enable: SLSPD_OP
1 = Operator may enter Slow speed.
OUT1_EN OUT1OP Enable: OUT1_OP
1 = Operator may enter OUT1.
OUT2_EN OUT2OP Enable: OUT2_OP
1 = Operator may enter OUT2.
DSQSTP_EN DSQSTPOP Enable: DSQSTP_OP
1 = Operator may enter Disable
Quick Stop.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 63
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.13 Output 1 and output 2

PS_OUT1, PS_OUT2
If the outputs device function is applied, the motor starter can carry out various
parameterizable actions. The integer values of PS_OUT1 and PS_OUT2 indicate the various
actions that can be parameterized.

Table 3- 33 Actions that can be parameterized for the outputs

Action Description PS_OUT1 / PS_OUT2 value


No action The output is deactivated. PS_OUT1=0
PS_OUT2=0
Control source (output 1) The output contact closes when bit 1.0 PS_OUT1=1
is set in the process image output.
Control source (output 2) The output contact closes when bit 1.1 PS_OUT2=1
is set in the process image output.

The following parameters are active when setting device functions for Output 1 and Output 2
in Auto or Manual mode.

Table 3- 34 Input parameters for each operating mode, output parameters and bit assignment of the process image for
OUT1 and OUT2

Operating mode Manual Operating mode Auto Output parameter Process image output
Input parameter Input parameter bits
OUT1_OP OUT1_LI QOUTPUT1 PIQ 1.0
OUT2_OP OUT2_LI QOUTPUT2 PIQ 1.1

A signal with rising edge is pending at the XXX_LI parameters.

3.5.6.14 Disable Quick Stop

Function Quick Stop


The Quick Stop function enables the motor and switches off the brake output without a group
error. This function can be disabled.
The following parameters are active in the various operating modes of the block.

Table 3- 35 Input parameters for each operating mode, output parameters and bit assignment of the process image

Operating mode Manual Operating mode Auto Output parameter Process image output
Input parameter Input parameter bit
DSQSTP_OP DSQSTP_LI — PIQ 1.7

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


64 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.15 Logbook

Content of the logbook


The logbook contains a reverse chronological list of tripping errors, device errors, and
events, which are provided with a time stamp. Each entry in the logbook has the following
attributes:
● LOGTIME1 to LOGTIME21: Time stamp
● LOGID1 to LOGID21: Number of message
● Text of message
This information is called from:
● Data set 72
● Data set 73
● Data set 75
A maximum of 63 messages can be logged with a time delay of 1 second. The LOGDS
parameter contains the values 1, 2, or 3. These indicate reading of data set 72, data set 73,
and data set 75.
The faceplate of the logbook function shows all entries to the log book.
The DEL_LOGTRP and DEL_LOGEVNT parameters can be used to delete the following
logged messages:
● Tripping errors
● Events

Table 3- 36 Messages regarding device errors received from the soft starter, including the related number

No. Message no. Device error message


1 452 Heat sink thermistor defective
2 1466 Contact block 1 failed
3 1467 Contact block 2 failed
4 1468 Contact block 3 failed
5 1417 Bypass element defective

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 65
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Table 3- 37 Messages regarding tripping errors received from the soft starter, including the related number

No. Message ID Tripping error message


1 309 Contact block overload
2 317 Electronics supply voltage too low
3 319 No supply voltage
4 324 Temperature sensor overload
5 325 Temperature sensor wire break
6 326 Temperature sensor short-circuit
7 327 Thermal motor model overload
8 334 Current limit overshot
9 335 Current limit undershot
10 339 Motor block tripping
11 341 Asymmetry tripping
12 343 Ground fault tripping
13 355 Process image error
14 365 Invalid parameter value:
Number of the invalid parameter
15 1407 Electronics supply voltage too high
16 1408 No load
17 1409 Phase failure L1
18 1410 Phase failure L2
19 1411 Phase failure L3
20 1421 Impermissible Ie / CLASS settings
21 1479 Generalized phase error
22 1481 Supply voltage too high
23 1482 Current measuring range exceeded

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


66 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Table 3- 38 Messages regarding events received from the soft starter, including the related number

No. Message ID Event error message


1 324 Overload
2 325 Temperature sensor wire break
3 326 Temperature sensor short-circuit
4 327 Thermal motor model overload
5 334 Current limit overshot
6 335 Current limit undershot
7 340 Asymmetry detected
8 342 Ground fault
9 310 Emergency start active
10 357 Automatic operating mode
11 358 Manual operation bus
12 359 Manual operation LOCAL mode
13 360 Manual operation connection abort
14 363 Maximum pointer reset
15 365 Invalid parameter value:
Number of the invalid parameter
16 366 Parameters cannot be changed in ON state:
Number of the invalid parameter
17 368 Parameters disabled CPU/master active
18 369 Factory settings restored
19 1302 Logbook - Triggering operations deleted
20 1303 Logbook - Events deleted
21 120 Device function_1
22 1 Device function_2
23 130 Rated operational current
24 3 Load type
25 4 Protection against voltage failure
26 5 Response to overload - thermal motor model
27 6 Tripping class
28 7 Recovery time
29 8 Idle time
30 137 Prewarning limit - remaining time for tripping
31 10 Response to overload - temperature sensor
32 9 Temperature sensor
33 12 Temperature sensor monitoring
34 15 Lower current limit
35 16 Upper current limit
36 14 Response to current limit value violation
37 140 Response to switching element overload

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 67
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

No. Message ID Event error message


38 21 Asymmetry limit
39 20 Response to asymmetry
40 22 Response to ground fault
41 47 Braking torque
42 40 Starting voltage
43 42 Current limiting value
44 167 Startup mode
45 168 Coasting method
46 35 Substitute value
47 36 Group diagnostics
48 34 Response to CPU/master stop
49 26 Input 1 - action
50 28 Input 2 - action
51 30 Input 3 - action
52 32 Input 4 - action
53 163 Output 1 - action
54 164 Output 2 - action
55 165 Output 3 - action
56 166 Output 4 - action
57 116 Breakaway time
58 117 Breakaway voltage
59 169 Max. starting time
60 170 Starting time
61 171 Coast-down time
62 172 Starting torque
63 118 Limiting torque
64 173 Stopping torque
65 119 Motor thermal capacity
66 178 Dynamic braking torque
67 43 Slow speed factor - CW rotation
68 198 Slow speed factor - CCW rotation
69 44 Slow torque - CW rotation
70 199 Slow torque - CCW rotation
71 104 Rated speed
72 113 Rated torque
73 308 Contact block defective
74 1414 Contact block short-circuited
75 1416 Contact block too hot for start
76 1418 Bypass element protective tripping
77 1422 Thermal motor model deactivated

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


68 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

No. Message ID Event error message


78 318 No contact block supply voltage
79 1419 Prewarning limit - remaining time for tripping undershot
80 1420 Prewarning limit - motor heating exceeded
81 1443 Manual operation bus; PC controls
82 1444 Manual operation local; input controls
83 1445 Manual operation local; HMI controls
84 1446 Manual operation local; PC controls
85 1453 Parameter set change impermissible
86 1473 Motor connection type unknown
87 17 Blocking current
88 18 Blocking time
89 19 Reponse to residual current detection
90 24 Input delay
91 25 Input 1 - level
92 27 Input 2 - level
93 29 Input 3 - level
94 31 Input 4 - level
95 37 Locking time
96 80 Input 1 - Signal
97 81 Input 2 - Signal
98 82 Input 3 - Signal
99 83 Input 4 - Signal
100 114 Response to switching element supply voltage cut-off
101 136 Pre-warning threshold - motor heating
102 139 Response to circuit breaker OFF
103 190 Input extension
104 208 Release delay time of brake on startup
105 209 Brake holding time on stopping
106 1520 Energy saving mode active
107 378 FW update unsuccessful
108 373 Memory module programming successful
109 376 FW update successful
110 1201 Blocking protection responded during startup
111 1202 Blocking protection responded during operation
112 1406 Cold start tripping
113 1423 Line protection short-circuit
114 1424 Short-circuit protector tripped
115 1425 Fuse defective
116 1426 Fuse L1 defective
117 1427 Fuse L2 defective

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 69
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

No. Message ID Event error message


118 1428 Fuse L3 defective
119 1429 Asymmetry prewarning
120 1430 Ground fault prewarning
121 1448 Setting elements not clearly defined
122 1454 TARGET =|= ACTUAL configuration
123 1455 Ie prewarning limit overshot
124 1456 Ie prewarning limit undershot
125 1474 Current limits are being determined
126 1475 Current limits transferred to PS1
127 1476 Current limits transferred to PS2
128 1477 Current limits transferred to PS3
129 1478 Current limits transferred to PS4
130 1480 Supply voltage too low
131 1490 Phase angle control failure
132 240 Prm message frame too short
133 241 Prm message frame too long
134 245 1st start-up dataset missing
135 246 2nd start-up dataset missing
136 247 3rd start-up dataset missing
137 248 4th start-up dataset missing
138 249 5th start-up dataset missing
139 250 6th start-up dataset missing
140 251 7th start-up dataset missing
141 252 8th start-up dataset missing
142 253 9th start-up dataset missing
143 254 10th start-up dataset missing
144 255 Start-up parameters incomplete
145 305 Safety-related disconnection
146 323 DC link voltage too high
147 331 Line protection overload
148 333 Circuit-breaker tripped
149 337 Residual current detected
150 338 Residual current tripping
151 348 Input tripping
152 351 Input warning
153 354 Sensor supply overload
154 371 Memory module defective
155 374 Memory module programming error
156 381 Self-test error
157 409 Commissioning error

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


70 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

No. Message ID Event error message


158 417 Stack overflow
159 418 Stack underflow
160 419 External interrupt
161 420 Undefined Opcode
162 421 Protection zone violation
163 422 Invalid operand
164 423 Invalid command
165 424 Address/data bus faulty
166 425 EEPROM power section: Memory defective
167 426 Impermissible parameter index
168 427 Function/parameter not implemented
169 428 Only read-access to function/information is permitted
170 430 Factory setting blocks parameter assignment
171 431 Internal parameter assignment value too high
172 432 Internal parameter assignment value too low
173 433 Option module is missing for this function/parameter
174 434 Error in system software
175 437 Watchdog overflow
176 439 Invalid internal parameter assignment value
177 441 EEPROM power section: Write error
178 442 Internal parameter assignment not possible in ON
179 443 Timeout RS485
180 445 EEPROM power section: Incorrect device parameters
181 451 Temperature sensor not ready for operation
182 453 Faulty interface to current detection
183 454 Faulty SSC interface
184 455 Faulty UART interface to power section
185 456 EEPROM: Memory defective
186 457 EEPROM: CRC error - Fixed-value parameter
187 458 EEPROM: CRC error - Device parameter
188 459 EEPROM: CRC error - Bus parameter
189 460 EEPROM: Contains invalid data
190 461 EEPROM: Invalid value for - Parameters disabled CPU/master
191 462 EEPROM: Invalid pointer for device parameter
192 463 EEPROM: Invalid pointer for bus parameter buffer
193 464 ROM failure
194 465 RAM failure
195 467 IFM: CRC error - Device naming
196 468 IFM: CRC error - Device parameter
197 469 IFM: CRC error - Bus parameter

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 71
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

No. Message ID Event error message


198 470 IFM: CRC error - Identification data
199 472 Heat sink thermistor - wire break
200 473 Heat sink thermistor - short-circuit
201 474 Adjuster defective
202 476 Current detection defective
203 477 Device naming not successful
204 478 Bypass element does not close
205 479 Bypass element does not open
206 480 Bypass element has opened accidentally during operation
207 486 Program execution check: Time-based program execution error
208 487 Program execution check: Logical program execution error
209 490 Incorrect power section detected
210 494 EEPROM power section: CRC error

3.5.6.16 Substitute value

SUB_VALUE
The operator parameterizes the substitute value. The SUB_VALUE parameter is 2 bytes
long. The data contained are written to the soft starter via data set 131. If the Response to
CPU/master stop event occurs, the soft starter is switched to the substitute value
parameterized in SUB_VALUE or it retains the last value.
This activation is parameterized at the START_OFF parameter:

START_OFF = 1: Switch substitute value


START_OFF = 0: Retain the last value
The SUB_VALUE parameter can only be written to the OUT_01 output of the block, if
START_OFF = 0:
● While a warm restart is performed on the CPU
● A rack error is detected
● A module error is detected

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


72 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.17 Active parameter sets

PS_SETACT
The process images of output bit PIQ 1.2 and PIQ 1.3 correspond to the settings that the
operator makes for the active parameter sets. These are based on the parameterization of
parameter PS_SETACT = 1, 2, or 3. The digits 1, 2, and 3 refer to the corresponding
parameter sets 1, 2, and 3.

PS_SETACT = 1 (Standard)
PIQ DP 1.2 = FALSE
PIQ DP 1.3 = FALSE

PS_SETACT = 2 (Standard)
PIQ DP 1.2 = TRUE
PIQ DP 1.3 = FALSE

PS_SETACT = 3 (Standard)
PIQ DP 1.2 = FALSE
PIQ DP 1.3 = TRUE

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 73
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.18 Reading and writing of data sets

RDREC, WRREC
For detailed information on data sets, refer to the "SIRIUS 3RW44 Soft Starter" System
Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets"

Table 3- 39 Data set table: Read access and/or write access for each data set

No. Data set no. Read access/ Number of Description of data set
write access bytes
1 68 R/W 8 Reading/Writing the Process Image of the Outputs
2 72 R 126 Log List - Reading device errors
3 73 R 126 Log List - Reading the trippings
4 75 R 126 Log List - Reading events
5 93 W 10 Writing a command
6 131 R/W 138 Technology parameter 2: Set 1
7 132 R/W 64 Technology parameter 3: Set 1
8 141 R/W 138 Technology parameter 2: Set 2
9 142 R/W 64 Technology parameter 3: Set 2
10 151 R/W 138 Technology parameter 2: Set 3
11 152 R/W 64 Technology parameter 3: Set 3

"R" = Read access; "W" = Write access

These data sets are based on the read authorization and/or write authorization. The
RDREC function is used to read the values and the WRREC function is used to write the
setting in the soft starter.
The Q_ENRDWR parameter indicates: The read function or write function is being executed.

Read function
Data sets are read with the following parameters:

RD_DATA = 1 : Operating parameters for reading values


L_RD_DATA = 1 : Linkable parameters for reading values.
EN_RDWR = 1
QERR_RD = 1 : Error when reading data sets.
The WRREC write function is supported in this case.

Write function
The WRREC function writes all values changed by the user to the device.
QERR_WR = 1 indicates errors when writing a data set.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


74 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.6.19 Enabling measurement and statistics

EN_MEAS, EN_STAT
A logical value "1" in the EN_MEAS and EN_STAT parameters activates the link for opening
the faceplates for the measurement block and the statistics block.

Faceplate for the EN_MEAS parameter


The user configures the faceplate that is opened with the EN_MEAS parameter in:
S7_string_1:='SSMEAS'
SSMEAS stands for the name of a function block of type SS_MEAS.

Faceplate for the EN_STAT parameter


The user configures the faceplate that is opened with the EN_STAT parameter in:
S7_string_1:=SSSTAT'
SSSTAT stands for the name of a function block of type SS_STAT.

Note
Configure the SS_MEAS function block for measurement and the SS_STAT function block
for statistics in the same CFC as the SS_DIR block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 75
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.7 Message features

Messages
The following messages are generated:

Table 3- 40 Output messages

Input parameter Message Parameter Message Message


no. class
MSG_EVID 3) 1 QMON_ERR $$BlockComment$$Monitoring Error or S
Starter tripped
2 CSF $$BlockComment$$Control System Fault S
3 MSG_3 1) $$BlockComment$$ Message Input 3 A
4 MSG_4 1) $$BlockComment$$ Message Input 4 A
5 MSG_5 1) $$BlockComment$$ Message Input 5 A
6 MSG_6 1) $$BlockComment$$ Message Input 6 A
7 MSG_7 2) $$BlockComment$$ Message Input 7 A
8 MSG_8 2) $$BlockComment$$ Message Input 8 A

1) The MSG_3 to MSG_6 parameters represent messages that can be user-configured.


2) The MSG_7 and MSG_8 messages as well as the associated values AUX_PR08 to AUX_PR010 are reserved.
3) Parameters with message number for ALARM_8P.

Table 3- 41 Structure of the related values in ALARM_8P

Message Related value Parameter Meaning


no.
1 1 BA_NA Name of batch
2 2 STEP_NO Step number
3 3 BA_ID Batch ID number
4 4 AUX_PR04 1) Auxiliary value 4
5 5 AUX_PR05 1) Auxiliary value 5
6 6 AUX_PR06 1) Auxiliary value 6
7 7 AUX_PR07 1) Auxiliary value 7
8 8 AUX_PR08 1) Auxiliary value 8
9 9 AUX_PR09 1) Auxiliary value 9
10 10 AUX_PR010 1) Auxiliary value 10

1) The AUX_PR04 bis AUX_PR07 parameters represent auxiliary values for messages that can be user-configured.

The M_SUP_C input can enable and disable the messages. The QMSG_STAT, QMSG_ACK
and QMSG_ERR parameters transfer the information found in ALARM_8P:
● Status of messages
● Status of an alarm acknowledgement
● Status of errors during data transfer

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


76 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.8 Start-up characteristics

Description
All alarm messages are suppressed in OB 100:
The user defines a value for RUNUPCY. This is assigned to OB 100 in order to suppress the
messages for the configured cycle count.
Depending on the value set for the START_OFF characteristic, the outputs contain either the
last valid value or the reset substitute value.

Table 3- 42 Outputs that are reset when START_OFF = 0

Output parameter Value of output


QREMOTE = TRUE
QMAN_AUT = FALSE
OUT_01 = SUB_VALUE
QMOT_CW = 1)

QMOT_CCW = 1)

QMOT_SLSPD = 1)

QOUTPUT1 = 1)

QOUTPUT2 = 1)

1) These parameters follow the value in OUT_01 PIQ 0.0 to PIQ 1.7.

If START_OFF = 1, all the outputs indicated above contain the last valid value.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 77
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.9 Block parameters for the inputs

Table 3- 43 Parameters of the SS_DIR block

Name of Data format Type Default Value Factor Meaning


parameter value range
IN_01* WORD Input 16#00 — — Value of process image
input DP 0.0 … 1.7
AUT_L BOOL Input FALSE — — Linkable input for
Auto/Manual mode
AUTOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Auto.
AUX_PR04 ANY Input — — — Auxiliary value 4
AUX_PR05 ANY Input — — — Auxiliary value 5
AUX_PR06 ANY Input — — — Auxiliary value 6
AUX_PR07 ANY Input — — — Auxiliary value 7
AUX_PR08 ANY Input Auxiliary value 8
AUX_PR09 ANY Input Auxiliary value 9
AUX_PR010 ANY Input Auxiliary value 10
BA_EN BOOL Input FALSE — — Enable batch
BA_ID DWORD Input 16#00 — — Batch ID number
BA_NA STRING[32] Input —’ — — Name of batch
CSF BOOL Input FALSE — — Control system error
DADDR INT Input 0 — — Diagnostic address of
module
DIAG_DIR SSDIAGDIR Input — — — Diagnostic information
from the SS_DIAG block
DSQSTP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Disable Quick Stop.
DSQSTP_LI BOOL Input FALSE — — Command in Auto mode:
1 = Disable Quick Stop
command active
EMRGST_LI BOOL Input FALSE — — Command in Auto mode:
1 = Emergency start
command active.
EMSTOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Emergency start.
EN_MEAS BOOL Input TRUE — — 1 = Measurement block
available
EN_RDWR BOOL Input TRUE — — Enable:1 =
Read and write data sets.
EN_STAT BOOL Input TRUE — — 1 = The statistics block is
available.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


78 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
L_DSQSTP BOOL Input FALSE — — 1=Disable Quick Stop
Active, Manual Linked
Command
L_EMRGST BOOL Input FALSE — — 1=Emergency Start Active,
Manual Linked Command
L_MOTCW BOOL Input FALSE — — 1=Motor CW Start, Manual
Linked command
L_MOTCCW BOOL Input FALSE — — 1=Motor CCW Start,
Manual Linked command
L_MOTOF BOOL Input FALSE — — 1=Motor OFF, Manual
Linked command
L_OUT1 BOOL Input FALSE — — 1=Out1 active, Manual
Linked Command
L_OUT2 BOOL Input FALSE — — 1=Out2 active, Manual
Linked Command
L_SLSPD BOOL Input FALSE — — 1=Slow Speed Active,
Manual Linked Command
L_TRPRST BOOL Input FALSE — — 1=Trip Reset Active,
Manual Linked Command
L_RD_DATA BOOL Input FALSE — — Linkable input 0 > 1:
Read data set
LADDR INT Input 0 — — Logical address of soft
starter
LINK_MAN BOOL Input FALSE — — Selection:
1 = Link
0 = Operator active
LIOP_SEL BOOL Input FALSE — — Selection:
1 = Link
0 = Operator active
LOCK BOOL Input FALSE — — 1 = Lock OFF
LOCK_DIR BOOL Input FALSE — — 0 = Clockwise
1 = Counter-clockwise
LOCK_ON BOOL Input FALSE — — According to the setting in
LOCK_DIR:
1 = Clockwise
rotation/counter-clockwise
rotation locked
M_SUP_C BOOL Input TRUE — — 1 = Suppress alarms
MANOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Manual.
MODF BOOL Input FALSE — — 1 = Module failure
MONITOR BOOL Input TRUE — — 1 = MONITOR ON
0 = MONITOR OFF:
"MONITOR" feedback
MOTCCW_LI BOOL Input FALSE — — Command in Auto mode:
1 = Motor start CCW

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 79
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
MOTCCWOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Motor CCW.
MOTCW_LI BOOL Input FALSE — — Command in Auto mode
1 = Motor start CW
MOTCWOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Motor CW.
MOTOF_LI BOOL Input FALSE — — Command in Auto mode:
1 = MOTOR OFF
MOTOFOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Motor OFF.
MSG_3 BOOL Input FALSE — — Message input 3
MSG_4 BOOL Input FALSE — — Message input 4
MSG_5 BOOL Input FALSE — — Message input 5
MSG_6 BOOL Input FALSE — — Message input 6
MSG_7 BOOL Input FALSE — — Message input 7
MSG_8 BOOL Input FALSE — — Message input 8
MSG_EVID DWORD Input 16#FF — — Number of the message
event
OCCUPIED BOOL Input FALSE — — Batch: Occupied
OUT1_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
OUT1.
OUT1_LI BOOL Input FALSE — — Command in Automode:
:1 = OUT1 active
OUT2_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
OUT2.
OUT2_LI BOOL Input FALSE — — Command in Auto mode:
1 = OUT2 active
RACKF BOOL Input FALSE — — 1 = Rack failure
RSRV_IN WORD Input 16#00 — — Reserved
RUNUPCYC INT Input 3 — — Number of the cycle for
which all messages are
suppressed.
SAMPLE_T REAL Input 0.1 — — Sampling time in s
SLSPD_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Slow speed.
SLSPD_LI BOOL Input FALSE — — Command in Auto mode:
1 = Slow speed active
STEP_NO DWORD Input 16#00 — — Step number of batch
TIME_MON REAL Input 3 — — Monitoring time in s

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


80 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
TRPRST_LI BOOL Input FALSE — — Command in Auto mode:
1 = Trip reset active
TRPRSTOP_EN BOOL Input TRUE — — Enable:
1 = Operator may enter
Trip reset.
PS2_IRATE** REAL Input 29 0 … 2000 0.01 A Parameter set 2:
Rated
operational current Ie
PS3_IRATE** REAL Input 29 0 … 200 0.01 A Parameter set 3:
Rated
operational current Ie

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 81
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.10 Block parameters for inputs and outputs

Table 3- 44 Parameters of the SS_DIR block

Name of Data format Type Default Value Factor Meaning


parameter value range
AUT_ON_OP BOOL Input/ FALSE — — Operator intervention in mode:
output 1 = Auto
0 = Manual
DSQSTP_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Disable Quick Stop command
active.
EMRGST_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Emergency start command active.
MOTCCW_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Motor start CCW
MOTCW_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Motor start CW
MOTOF_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Motor OFF
OUT1_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = OUT1 active
OUT2_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = OUT2 active
PS_IDLTM INT Input/ 0 0 … 255 1s Parameter set:
output Thermal motor model idle time
PS_MTRHT INT Input/ 80 0 … 95 5% Parameter set:
output Prewarning limit-motor heating
PS_OVLRES INT Input/ 0 — — Parameter set:
output Response to overload
0 =Trip without restart
1 = Trip with restart
2 = Warning
PS_OVLSEN INT Input/ 0 — — Parameter set:
output Response to overload - temperature
sensor
0 =Trip without restart
1 = Trip with restart
2 = Warning
PS_SETACT INT Input/ 1 — — Activates the parameter sets.
output
RD_DATA BOOL Input/ FALSE — — 1 = Read data from the data sets
output
SLSPD_OP BOOL Input/ FALSE — — Command in Manual mode:
output 1 = Slow speed active
START_OFF BOOL Input/ FALSE — — 0 = Switch substitute value
output 1 = Retain last value

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


82 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
SUB_VALUE*** WORD Input/ 16#00 — — Substitute value as Response to
output CPU/master stop
PS_RCRYTM REAL Input/ 1 60 30 s Parameter set:
output Recovery time
PS_TRPCLS INT Input/ 0 — — Parameter set:
output Thermal motor model
0 = CLASS 10
1 = CLASS 20
2 = CLASS 30
3 = CLASS 5(10a)
4 = CLASS 15
15 = CLASS OFF
PS_TRPTM INT Input/ 0 0 … 500 1s Parameter set:
output Remaining time for tripping
PS_TMPSNSR INT Input/ 0 — — Parameter set:
output Temperature sensor
PS_ASYLIM INT Input/ 30 30 … 60 10 % Parameter set:
output Asymmetry limit
PS_COMMON DWORD Input/ 16#13 — — Parameter set:
output General parameters
Bit 0: Protection against voltage failure
Bit 1: Response to current limit value
violation
0 = Warning
1 = Trip
Bit 2: Response to switching element
overload
0 =Trip without restart
1 = Trip with restart
Bit 3: Response to asymmetry
0 = Warning
1 = Trip
Bit 4: Response to ground fault
0 = Warning
1 = Trip
Bit 5: Group diagnostics
0 = Disabled
1 = Enabled
PS_IN1 INT Input/ 0 — — Parameter set: Input 1
output 0 = No action
5 = Group warning
6 = Manual operation LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 83
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS1_IRATE** REAL Input/ 29 0 … 2000 0.001 A Parameter set 1:
output Rated operational
current Ie
PS_IN2 INT Input/ 0 — — Parameter set: Input 2
output 0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
PS_IN3 INT Input/ 0 — — Parameter set: Input 3
output 0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3
PS_IN4 INT Input/ 0 — — Parameter set: Input 4
output 0 = No action
5 = Group warning
6 = Manual LOCAL mode
7 = Emergency start
10 = Slow speed
11 = Quick Stop
12 = Trip reset
16 = Motor CW with PS1
17 = Motor CCW with PS1
18 = Motor CW with PS2
19 = Motor CCW with PS2
20 = Motor CW with PS3

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


84 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS_OUT1 INT Input/ 0 — — Parameter set:
output Output 1 - action
0 = No action
1 = Control source (Output 1)
2 = Control source (Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON
PS_OUT2 INT Input/ 0 — — Parameter set:
output Output 2 - action
0 = No action
1 = Control source (Output 1)
2 = Control source (Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 85
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS_OUT3 INT Input/ 0 — — Parameter set:
output Output 3 - action
0 = No action
1 = Control source (Output 1)
2 = Control source (Output 2)
6 = Control source input 1
7 = Control source input 2
8 = Control source input 3
9 = Control source input 4
10 = Ramp-up
11 = Operation / Bypass
12 = Coast-down
13 = On time motor (RUN)
14 = Control command motor ON
16 = Brake contactor
18 = Device ON
31 = Group warning
32 = Group error
33 = Bus error
34 = Device error
38 = Ready for motor ON
PS1_BR_U INT Input/ 80 40 … 100 5% Parameter set 1:
output Breakaway voltage
PS1_BRKTQ INT Input/ 50 20 … 100 5% Parameter set 1:
output Braking torque
PS1_CURLM REAL Input/ 450 125 … 550 3,13 % Parameter set 1:
output Current limiting value
PS1_DYNTQ INT Input/ 50 20 … 100 5% Parameter set 1:
output Dynamic braking torque
PS1_LMTQ INT Input/ 150 20 … 200 5% Parameter set 1:
output Limiting torque
PS1_SPDRATE INT Input/ 1500 500 … 3600 1 rpm Parameter set 1:
output Rated speed
PS1_SPTQ INT Input/ 10 10 … 100 5% Parameter set 1:
output Stopping torque
PS1_ST_U INT Input/ 30 20 … 100 5% Parameter set 1:
output Starting voltage
PS1_BRTM REAL Input/ 0 0…2 — Parameter set 1:
output Breakaway time
PS1_STOP INT Input/ 0 — — Parameter set 1:
output Coasting method
0 = Coast-down without load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


86 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS1_STMD INT Input/ 5 — — Parameter set 1:
output Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr limiting
6 = Trq ctrl + curr limiting
PS1_STPTM REAL Input/ 10 0 … 360 0.1 s Parameter set 1:
output Coast-down time
PS1_STTM REAL Input/ 20 0 … 360 0.1 s Parameter set 1:
output Starting time
PS1_STTQ INT Input/ 50 10 … 100 5% Parameter set 1:
output Starting torque
PS1_THMCAP INT Input/ 20 1 … 100 1% Parameter set 1:
output Motor thermal capacity
PS1_CCWSSPD INT Input/ 7 3 … 21 1 Parameter set 1:
output Slow speed factor CCW
PS1_CCWSTQ INT Input/ 50 20 … 100 5% Parameter set 1:
output Slow torque CCW
PS1_CURH REAL Input/ 112.5 50 … 150 3,13 % Parameter set 1:
output Upper current limit (warn/trip)
PS1_CURL REAL Input/ 18.75 18,75 … 100 3,13 % Parameter set 1:
output Lower current limit (warn/trip)
PS1_CWSSPD INT Input/ 7 3 … 21 1 Parameter set 1:
output Slow speed factor CW
PS1_CWSTQ INT Input/ 50 20 … 100 5% Parameter set 1:
output Slow torque CW
PS1_TM_MAX REAL Input/ 0 0 … 1000 0.1 s Parameter set 1:
output Max. starting time
PS1_TQRATE DINT Input/ 0 0 … 65535 1 nm Parameter set 1:
output Rated torque
PS2_SPDRATE INT Input/ 1500 500 … 3600 1 rpm Parameter set 2:
output Rated speed
PS2_STMD INT Input/ 5 — 1 nm Parameter set 2:
output Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr limiting
6 = Trq ctrl + curr limiting
PS2_BRKTQ INT Input/ 50 20 … 100 5% Parameter set 2:
output Braking torque
PS2_DYNTQ INT Input/ 50 20 … 100 5% Parameter set 2:
output Dynamic braking torque

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 87
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS2_BR_U INT Input/ 80 40 … 100 5% Parameter set 2:
output Breakaway voltage
PS2_BRTM REAL Input/ 0 0…2 0.01 s Parameter set 2:
output Breakaway time
PS2_CURLM REAL Input/ 450 12 … 550 3,13 % Parameter set 2:
output Current limiting value
PS2_LMTQ INT Input/ 150 20 … 200 5% Parameter set 2:
output Limiting torque
PS2_SPTQ INT Input/ 10 10 … 100 5% Parameter set 2:
output Stopping torque
PS2_ST_U INT Input/ 30 20 … 100 5% Parameter set 2:
output Starting voltage
PS2_STTM REAL Input/ 20 0 … 360 0.1 s Parameter set 2:
output Starting time
PS2_STTQ INT Input/ 50 10 … 100 5% Parameter set 2:
output Starting torque
PS2_TM_MAX REAL Input/ 0 0 … 1000 01 s Parameter set 2:
output Max. starting time
PS2_TQRATE DINT Input/ 0 0 … 65535 — Parameter set 2:
output Rated torque
PS2_CCWSSPD INT Input/ 7 3 … 21 1 Parameter set 2:
output Slow speed factor CCW
PS2_CCWSTQ INT Input/ 50 20 … 100 5% Parameter set 2:
output Slow torque CCW
PS2_CURH REAL Input/ 112.5 50 … 150 3,10 % Parameter set 2:
output Upper current limit (warn/trip)
PS2_CURL REAL Input/ 18.75 18.75 … 100 3,13 % Parameter set 2:
output Lower current limit (warn/trip)
PS2_CWSSPD INT Input/ 7 3 … 21 1 Parameter set 2:
output Slow speed factor CW
PS2_CWSTQ INT Input/ 50 20 … 100 5% Parameter set 2:
output Slow torque CW
PS2_STOP INT Input/ 0 — — Parameter set 2:
output Coasting method
0 = Coast-down without load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking
PS2_STPTM REAL Input/ 10 0 … 360 0.1 s Parameter set 2:
output Coast-down time
PS2_THMCAP INT Input/ 20 1 … 100 1% Parameter set 2:
output Motor thermal capacity
PS3_BR_U INT Input/ 80 40 … 100 5% Parameter set 3:
output Breakaway voltage

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


88 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS3_BRKTQ INT Input/ 50 20 … 100 5% Parameter set 3:
output Braking torque
PS3_CURLM REAL Input/ 450 125 … 550 3,13 % Parameter set 3:
output Current limiting value
PS3_DYNTQ INT Input/ 50 20 … 100 5% Parameter set 3:
output Dynamic braking torque
PS3_LMTQ INT Input/ 150 20 … 200 5% Parameter set 3:
output Limiting torque
PS3_SPDRATE INT Input/ 1500 500 … 3600 1 rpm Parameter set 3:
output Rated speed
PS3_SPTQ INT Input/ 10 10 … 100 5% Parameter set 3:
output Stopping torque
PS3_ST_U INT Input/ 30 20 … 100 5% Parameter set 3:
output Starting voltage
PS3_STMD INT Input/ 5 — — Parameter set 3
output Startup mode
0 = Direct
1 = Voltage ramp
2 = Torque control
3 = Motor heating
5 = Voltage ramp + curr limiting
6 = Trq ctrl + curr limiting
PS3_STTM REAL Input/ 20 0 … 360 0.1 s Parameter set 3:
output Starting time
DEL_LOGEVNT BOOL Input/ FALSE — — Delete Logbook - Events
output
DEL_LOGTRP BOOL Input/ FALSE — — Delete Logbook - Triggering operations
output
PS3_BRTM REAL Input/ 0 0…2 0.01 s Parameter set 3:
output Breakaway time
PS3_CCWSSPD INT Input/ 7 3 … 21 1 Parameter set 3:
output Slow speed factor CCW
PS3_CCWSTQ INT Input/ 50 20 … 100 5% Parameter set 3:
output Slow torque CCW
PS3_CURH REAL Input/ 112.5 50 … 150 3,13 % Parameter set 3:
output Upper current limit (warn/trip)
PS3_CURL REAL Input/ 18.75 18,75 … 100 3,13 % Parameter set 3:
output Lower current limit (warn/trip)
PS3_CWSSPD INT Input/ 7 3 … 21 1 Parameter set 3:
output Slow speed factorCW
PS3_STTQ INT Input/ 50 10 … 100 5% Parameter set 3:
output Starting torque
PS3_TM_MAX REAL Input/ 0 0 … 1000 0.1 s Parameter set 3:
output Max. starting time
PS3_TQRATE DINT Input/ 0 0 … 65535 1 nm Parameter set 3:
output Rated torque

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 89
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
PS3_CWSTQ INT Input/ 50 20 … 100 5% Parameter set 3:
output Slow torque CW
PS3_STOP INT Input/ 0 — — Parameter set 3:
output Coasting method
0 = Coast-down without load
2 = Torque control
3 = Pump Stop
4 = DC braking
5 = Combined braking
PS3_STPTM REAL Input/ 10 0 … 360 0.1 s Parameter set 3:
output Coast-down time
PS3_THMCAP INT Input/ 20 1 … 100 1% Parameter set 3:
output Motor thermal capacity

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


90 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.11 Block parameters for the outputs

Table 3- 45 Parameters of the SS_DIR block

Name of Data format Type Default Value Factor Meaning


parameter value range
OUT_01* WORD Output 16#00 — — Value of process image
output DP 0.0 … 1.7
ERRORNUM INT Output -1 — — Error number
LOGDS INT Output 0 — — Logbook:
Record
LOGID1 INT Output 0 — — Logbook:
Message no. 1
LOGID10 INT Output 0 — — Logbook:
Message no. 10
LOGID11 INT Output 0 — — Logbook:
Message no. 11
LOGID12 INT Output 0 — — Logbook:
Message no. 12
LOGID13 INT Output 0 — — Logbook:
Message no. 13
LOGID14 INT Output 0 — — Logbook:
Message no. 14
LOGID15 INT Output 0 — — Logbook:
Message no. 15
LOGID16 INT Output 0 — — Logbook:
Message no. 16
LOGID17 INT Output 0 — — Logbook:
Message no. 17
LOGID18 INT Output 0 — — Logbook:
Message no. 18
LOGID19 INT Output 0 — — Logbook:
Message no. 19
LOGID2 INT Output 0 — — Logbook:
Message no. 2
LOGID20 INT Output 0 — — Logbook:
Message no. 20
LOGID21 INT Output 0 — — Logbook:
Message no. 21
LOGID3 INT Output 0 — — Logbook:
Message no. 3
LOGID4 INT Output 0 — — Logbook:
Message no. 4
LOGID5 INT Output 0 — — Logbook:
Message no. 5
LOGID6 INT Output 0 — — Logbook:
Message no. 6
LOGID7 INT Output 0 — — Logbook:
Message no. 7

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 91
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
LOGID8 INT Output 0 — — Logbook:
Message no. 8
LOGID9 INT Output 0 — — Logbook:
Message no. 9
LOGTIME1 DWORD Output 16#00 — — Logbook:
Time 1
LOGTIME10 DWORD Output 16#00 — — Logbook:
Time 10
LOGTIME11 DWORD Output 16#00 — — Logbook:
Time 11
LOGTIME12 DWORD Output 16#00 — — Logbook:
Time 12
LOGTIME13 DWORD Output 16#00 — — Logbook:
Time 13
LOGTIME14 DWORD Output 16#00 — — Logbook:
Time 14
LOGTIME15 DWORD Output 16#00 — — Logbook:
Time 15
LOGTIME16 DWORD Output 16#00 — — Logbook:
Time 16
LOGTIME17 DWORD Output 16#00 — — Logbook:
Time 17
LOGTIME18 DWORD Output 16#00 — — Logbook:
Time 18
LOGTIME19 DWORD Output 16#00 — — Logbook:
Time 19
LOGTIME2 DWORD Output 16#00 — — Logbook:
Time 2
LOGTIME20 DWORD Output 16#00 — — Logbook:
Time 20
LOGTIME21 DWORD Output 16#00 — — Logbook:
Time 21
LOGTIME3 DWORD Output 16#00 — — Logbook:
Time 3
LOGTIME4 DWORD Output 16#00 — — Logbook:
Time 4
LOGTIME5 DWORD Output 16#00 — — Logbook:
Time 5
LOGTIME6 DWORD Output 16#00 — — Logbook:
Time 6
LOGTIME7 DWORD Output 16#00 — — Logbook:
Time 7
LOGTIME8 DWORD Output 16#00 — — Logbook:
Time 8
LOGTIME9 DWORD Output 16#00 — — Logbook:
Time 9

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


92 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
QAUTOP BOOL Output FALSE — — Status:
1 = Operator may enter
Auto.
QCURR REAL Output 0 — — Actual motor current
QDIAG DWORD Output 16#00 — — 3RW44 PROFIBUS DP
slave diagnostics
QDIAGCOM DWORD Output 16#00 — — Diagnostics:
Communication, switching,
and controlling
QDIAGPAR DWORD Output 16#00 — — Diagnostics:
Parameters and device
function
QDSQSTP BOOL Output 0 — — 1= disable quick stop
active
QDSQSTPOP BOOL Output TRUE — — Status:
1 = Operator may enter
Disable Quick Stop.
QEMRGST BOOL Output 0 — — 1= Emergency Start active
QEMSTOP BOOL Output TRUE — — Status:
1 = Operator may enter
Emergency start.
QEN_RDWR BOOL Output FALSE — — 1 = Enable read and write
data sets
QERR_RD BOOL Output FALSE — — 1 = Error while reading a
data set
QERR_WR BOOL Output FALSE — — 1 = Error while writing a
data set
QFLTPAR WORD Output 16#00 — — Diagnostics for invalid
parameter numbers
QGRPERR BOOL Output FALSE — — 1 = Group error
QMAN_AUT BOOL Output FALSE — — 0 = Manual mode
1 = Auto mode
QMANOP BOOL Output FALSE — — Status 1:
Operator may enter
Manual.
QMODF BOOL Output FALSE — — 1 = Module failure
QMON_ERR BOOL Output FALSE — — 1 = Monitoring error
QMOT_CCW BOOL Output FALSE — — Motor CCW active
QMOT_CW BOOL Output FALSE — — Motor CW active
QMOT_SLSPD BOOL Output FALSE — — Motor in slow speed active
QMOTCCWOP BOOL Output TRUE — — Status 1:
Operator may enter Motor
CCW.
QMOTCWOP BOOL Output TRUE — — Status 1:
Operator may enter Motor
CW.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 93
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Name of Data format Type Default Value Factor Meaning


parameter value range
QMOTOFOP BOOL Output TRUE — — Status 1:
Operator may enter Motor
OFF.
QMSG_ACK WORD Output 16#00 — — ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Output FALSE — — 1 = Error during data
transfer
QMSG_STAT WORD Output 16#00 — — ALARM_8P:
Status output
QOUT1OP BOOL Output TRUE — — Status 1:
Operator may enter OUT1.
QOUT2OP BOOL Output TRUE — — Status 1:
Operator may enter OUT2.
QOUTPUT1 BOOL Output FALSE — — Value of process image
output 1 DP 1.0
QOUTPUT2 BOOL Output FALSE — — Value of process image
output 2 DP 1.1
QRACKF BOOL Output FALSE — — 1 = Rack failure
QRAMP_ON BOOL Output FALSE — — Ramp operation active
QRD_OUT BOOL Output 0 — — 1= trigger read operation of
device diagnosis data set
(DS92) at SS_DIAG
QREMOTE BOOL Output FALSE — — 1 = Remote
0 = Manual LOCAL
QRSRV_OUT WORD Output 16#00 — — Reserved
QSLSPDOP BOOL Output TRUE — — Status 1:
Operator may enter Slow
speed.
QTRPRSTOP BOOL Output TRUE — — Status 1:
Operator may enter Trip
reset.
QUALITY BYTE Output 16#80 — — Quality code
VSTATUS DWORD Output 16#00000000 — — Status information

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


94 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12 Faceplates

3.5.12.1 General

Table 3- 46 Signal block for direct starter control function SS_DIR: Faceplates with their associated
PDL file names

Faceplate PDL file name


Standard @PG_SS_DIR_STANDARD.pdl
Maintenance @PG_SS_DIR_MAINTENANCE.pdl
Process image @PG_SS_DIR_PROCESSIMAGE.pdl
Limits @PG_SS_DIR_LIMITS.pdl
Parameter @PG_SS_DIR_PARAMETER.pdl
Parameter set 1 @PG_SS_DIR_PARAMETERSET1.pdl
Parameter set 2 @PG_SS_DIR_PARAMETERSET2.pdl
Parameter set 3 @PG_SS_DIR_PARAMETERSET3.pdl
Logbook @PG_SS_DIR_LOGBOOK.pdl
Station diagnostics @PG_SS_DIR_STATION_DIAG.pdl
Control diagnostics: @PG_SS_DIR_CONTROL_DIAG.pdl
Controlling, switching, and
communication
Device diagnostics @PG_SS_DIR_DEVICE_DIAG.pdl
Parameter diagnostics @PG_SS_DIR_PARAMETER_DIAG.pdl
Alarms @PCS7_SS_ALARM.pdl
Trend @PCS7_SS_TREND.pdl
Batch @PCS7_SS_BATCH.pdl
Block icon @PCS7Typicals_SS.pdl.

See also
Block icons (Page 21)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 95
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.2 Standard View

① AUT_ON_OP , QMAN_AUT, Changes the operating mode of the block.


QMANOP, QAUTOP This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_0 and String_1 attribute of AUT_ON_OP.
② MOTCW_OP, QMOTCWOP, Buttons used to start the motor in the clockwise or counter-
MOTCCW_OP, QMOTCCWOP, clockwise direction.
MOTOF_OP, QMOTOFOP Slow speed must be activated in order to start the motor in the
counter-clockwise direction.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of MOTCCW_OP, MOTOF_OP,
MOTCW_OP.
③ LOCK, LOCK_ON, LOCK_DIR The symbols indicate the enable for the lock of the block
according to the direction of rotation.
④ SLSPD_OP, QSLSPDOP Activates or deactivates the slow speed function.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of SLSPD_OP.
⑤ TRPRST_OP, QTRPRSTOP Executes a Trip reset.
This control function is available to users with authorization
level 5 and higher. The user can define the text on the button:
String_1 attributes of TRPRST_OP.
⑥ VSTATUS Indicates the status of the block.
⑦ QCURR Motor current

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


96 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

⑧ VSTATUS Indicates the status of the motor:

Symbol RUN CW

Symbol RUN CCW

Symbol STOP

Symbol Error

Figure 3-3 SS_DIR: Standard View

See also
Operating modes (Page 48)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 97
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.3 Maintenance View

① EN_STAT This button opens the faceplate for the statistics block.
This control function is available to users with authorization level 5 and higher.
② SUB_VALUE Activates or deactivates substitute values and sets the active parameter set.
This control function is available to users with authorization level 6 and higher.
③ START_OFF Sets the Response to CPU/master stop.
This control function is available to users with authorization level 6 and higher.
④ OUT1_O2 Activates or deactivates the Output2 function.
This control function is available to users with authorization level 6 and higher.
⑤ OUT1_OP Activates or deactivates the Output1 function.
This control function is available to users with authorization level 6 and higher.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


98 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

⑥ DSQSTP_OP Activates or deactivates the Disable Quick Stop function.


This control function is available to users with authorization level 6 and higher.
⑦ EMRGST_OP Activates or deactivates the Emergency start function.
This control function is available to users with authorization level 6 and higher.
⑧ TIME_MON Entry for Monitoring time.
⑨ MONITOR Activates or deactivates the Monitoring function.

Figure 3-4 SS_DIR: Maintenance View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 99
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.4 Process Image View

① VSTATUS Process image input


② VSTATUS Process image output

Figure 3-5 SS_DIR: Process Image View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


100 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.5 Limits View

① QCURR, PS_COMMON, Displays the current as a bar diagram for parameter sets 1, 2, and 3.
PS1_IRATE, PS1_CURH, Based on the setting in the "Response to current limit value violation" field of
PS1_CURL, PS2_IRATE, the Parameters View, the colors of the limits in the columns change from
PS2_CURH, PS2_CURL, yellow (= warning) to red (= trip).
PS3_IRATE, PS3_CURH,
PS3_CURL
② QCURR Indicates the motor current for the selected parameter set. The selected
parameter set is highlighted in a different color.
③ PS1_CURH, PS1_CURL Parameter set 1 current limits
This control function is available to users with authorization level 6 and higher.
④ PS2_CURH, PS2_CURL Parameter set 2 current limits
This control function is available to users with authorization level 6 and higher.
⑤ PS3_CURH, PS3_CURL Parameter set 3 current limits
This control function is available to users with authorization level 6 and higher.
⑥ ReadData Button for enabling reading of data.
This control function is available to users with authorization level 5 and higher.
The user can define the text on the button: String_1 attribute of RD_DATA
Figure 3-6 SS_DIR: Limits View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 101
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.6 Parameters View

① PS_COMMON Activates or deactivates the Group diagnostics.


This control function is available to users with authorization level 6 and higher.
② PS_COMMON Activates or deactivates the Protection against voltage failure.
This control function is available to users with authorization level 6 and higher.
③ PS_COMMON Sets the Response to ground fault
This control function is available to users with authorization level 6 and higher.
④ PS_TMPSNSR, PS_OVLSEN Parameters for Motor temperature sensor
This control function is available to users with authorization level 6 and higher.
⑤ PS_COMMON, PS_ASYLIM Parameters for Asymmetry
This control function is available to users with authorization level 6 and higher.
⑥ PS_COMMON Parameters for Current limiting
This control function is available to users with authorization level 6 and higher.
⑦ PS_OUT1, PS_OUT2, Specifies actions for the various outputs.
PS_OUT3 This control function is available to users with authorization level 6 and higher.
⑧ EN_MEAS This button opens the faceplate for the SS_MEAS block.
This control function is available to users with authorization level 5 and higher.
⑨ ReadData Button for enabling reading of data.
This control function is available to users with authorization level 5 and higher.
The user can define the text on the button: String_1 attribute of RD_DATA
⑩ PS_IN1, PS_IN2, PS_IN3, Specifies actions for the various inputs.
PS_IN4 This control function is available to users with authorization level 6 and higher.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


102 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

⑪ PS_COMMON Parameters for Contact block


This control function is available to users with authorization level 6 and higher.
⑫ PS_OVLRES, PS_RCRYTM Parameters for Motor overload
This control function is available to users with authorization level 6 and higher.
⑬ PS_MTRHT, PS_TRPTM Parameters for Prewarning limit
This control function is available to users with authorization level 6 and higher.
⑭ PS_TRPCLS, PS_IDLTM Parameters for Thermal motor model
This control function is available to users with authorization level 6 and higher.
⑮ PS_SETACT Selection of active parameter set
This control function is available to users with authorization level 5 and higher.
Figure 3-7 SS_DIR: Parameters View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 103
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.7 Parameters View and views for Parameter set 1 to Parameter set 3

Note
Parameter set 1, Parameter set 2, Parameter set 3
The settings in the "Startup mode" and "Coasting method" fields determine whether or not
the field for assigning settings for the soft starter is enabled.

Parameter Set 1 View

① PS1_IRATE, PS1_SPDRATE, Basic parameters of Parameter set 1


PS1_TQRATE This control function is available to users with
authorization level 6 and higher.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


104 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

② PS1_STMD, PS1_ST_U, PS1_STTQ, Control functions of Parameter set 1


PS1_LMTQ, PS1_CURLM, PS1_STTM, This control function is available to users with
PS1_TM_MAX, PS1_BR_U, authorization level 6 and higher.
PS1_BRTM, PS1_THMCAP,
PS1_STOP, PS1_STPTM, PS1_SPTQ,
PS1_CWSSPD, PS1_CCWSSPD,
PS1_CWSTQ, PS1_CCWSTQ,
PS1_BRKTQ, PS1_DYNTQ
③ RD_DATA Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA

Figure 3-8 SS_DIR: Parameter Set 1 View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 105
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Parameter Set 2 View

① PS2_IRATE, PS2_SPDRATE, PS2_TQRATE Basic parameters of Parameter set 2


This control function is available to users
with authorization level 6 and higher.
② PS2_STMD, PS2_ST_U, PS2_STTQ, PS2_LMTQ, Control functions of Parameter set 2
PS2_CURLM, PS2_STTM, PS2_TM_MAX, This control function is available to users
PS2_BR_U, PS2_BRTM, PS2_THMCAP, with authorization level 6 and higher.
PS2_STOP, PS2_STPTM, PS2_SPTQ,
PS2_CWSSPD, PS2_CCWSSPD, PS2_CWSTQ,
PS2_CCWSTQ, PS2_BRKTQ, PS2_DYNTQ
③ RD_DATA Button for enabling reading of data.
This control function is available to users
with authorization level 5 and higher.
The user can define the text on the button:
String_1 attribute of RD_DATA

Figure 3-9 SS_DIR: Parameter Set 2 View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


106 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Parameter Set 3 View

① PS3_IRATE, PS3_SPDRATE, Basic parameters of Parameter set 3


PS3_TQRATE This control function is available to users with
authorization level 6 and higher.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 107
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

② PS3_STMD, PS3_ST_U, PS3_STTQ, Control functions of Parameter set 3


PS3_LMTQ, PS3_CURLM, PS3_STTM, This control function is available to users with
PS3_TM_MAX, PS3_BR_U, authorization level 6 and higher.
PS3_BRTM, PS3_THMCAP,
PS3_STOP, PS3_STPTM, PS3_SPTQ,
PS3_CWSSPD, PS3_CCWSSPD,
PS3_CWSTQ, PS3_CCWSTQ,
PS3_BRKTQ, PS3_DYNTQ)
PS3_STMD, PS3_ST_U, PS3_STTQ,
PS3_LMTQ, PS3_CURLM, PS3_STTM,
PS3_TM_MAX, PS3_BR_U,
PS3_BRTM, PS3_THMCAP,
PS3_STOP, PS3_STPTM, PS3_SPTQ,
PS3_CWSSPD, PS3_CCWSSPD,
PS3_CWSTQ, PS3_CCWSTQ,
PS3_BRKTQ, PS3_DYNTQ
③ RD_DATA Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA

Figure 3-10 SS_DIR: Parameter Set 3 View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


108 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.8 Logbook View

① DEL_LOGEVNT This control function is available to users with authorization level 5 and higher. The user can
define the text on the button:
String_1 attribute of DEL_LOGEVNT
② DEL_LOGTRP This control function is available to users with authorization level 5 and higher. The user can
define the text on the button:
String_1 attribute of DEL_LOGTRP
③ RD_DATA Button for enabling reading of data. This control function is available to users with authorization
level 5 and higher. The user can define the text on the button: String_1 attribute of RD_DATA.
Figure 3-11 SS_DIR: Logbook View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 109
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.9 Views: Station Diagnostics, Control Diagnostics, Device Diagnostics, and Parameter
Diagnostics

Station Diagnostics View

Figure 3-12 SS_DIR: View: Station diagnostics

QDIAG - For a list of parameters, refer to Chapter:


Diagnostics (Page 57)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


110 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Control Diagnostics View - Switching, controlling, and communication

Figure 3-13 SS_DIR: Control Diagnostics View - Switching, controlling, and communication

QDIAGCOM - For a list of parameters, refer to Chapter:


Diagnostics (Page 57)

Read_Data Button for enabling reading of data. This control function is


available to users with authorization level 5 and higher. The
user can define the text on the button: String_1 attribute of
RD_DATA.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 111
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Device Diagnostics View

Figure 3-14 SS_DIR: Device Diagnostics View

QDIAGPAR - For a list of parameters, refer to Chapter:


Diagnostics (Page 57)

Read_Data Button for enabling reading of data. This control function is


available to users with authorization level 5 and higher. The
user can define the text on the button: String_1 attribute of
RD_DATA.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


112 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

Parameter Diagnostics View

Figure 3-15 SS_DIR: Parameter Diagnostics View

QDIAGPAR, QFLTPAR - For a list of parameters, refer to Chapter:


Diagnostics (Page 57)

Read_Data Button for enabling reading of data. This control function is


available to users with authorization level 5 and higher. The
user can define the text on the button: String_1 attribute of
RD_DATA.

See also
Slave diagnostics of the 3RW44 (Page 33)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 113
Soft starter blocks
3.5 SS_DIR: Signal block for direct starter control function

3.5.12.10 Block icon

Structure of block symbol

① "G" on white background = Group error


② Indicates the operating mode:
"L" on white background = Manual operation LOCAL
"R" on white background = Remote
③ Indicates the operating mode of the block:
"M" on white background = Manual
"A" on green background = Auto
④ Indicates the enable for the lock of the block.
"L" on white background: LOCK or LOCK_ON
⑤ Header: displays the name of the tag
⑥ Indicates the status of the motor: VSTATUS.
e.g.:

Symbol RUN CW

Symbol RUN CCW

Symbol STOP

Symbol Error

The symbol flashes when the motor is in the startup or coast-down phase.
⑦ Group display
Reads the message configuration of the block and displays alarms and warnings.

Figure 3-16 SS_DIR: Block symbol

Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


114 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6 SS_MEAS: Measurement block

3.6.1 Description

Block type and number: FB 564


Product group: 3RW44

Purpose of block
The SS_MEAS block provides:
● Measurement information regarding:
– Phase currents
– Thermal motor model
– Output power
– Phase-to-phase voltages
– Line frequency
– Asymmetry
– ...
● Information regarding diagnostics of measurement parameters
The block receives information from the SS_DIAG and SS_DIR blocks.

See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 139)
Interconnection of function blocks (Page 42)
CFC charts for 3RW44 soft starter (Page 153)
Technical data (Page 157)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 115
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6.2 Calling OBs


The "Generate Module Driver" function inserts the block into the following organization
blocks:

Table 3- 47 Organization blocks that call the SS_MEAS block

Organization block Description


OB 30 … OB 38 Cyclic interrupts
OB 100 Warm restart

Recommendation:
You are recommended to insert the block SS_MEAS into OB 32 for cyclic operation.
See also the CFC manual.

3.6.3 Called blocks


The block calls the following blocks:

Table 3- 48 Blocks called by the SS_MEAS block

Block Description
SFB 35 ALARM_8P Generates block-specific messages with values for eight
signals
SFB 52 RDREC Reads a data set
SFC 6 RD_SINFO Reads the OB start information
SFC 20 BLKMOV Move block

3.6.4 Parameterization

LADDR, DADDR: Assigning the logical address


The module driver parameterizes the logical address LADDR and the diagnostics address
DADDR of the soft starter automatically.

Interconnection
In addition, set: IN_01 = PII address (logical address).

See also
CFC charts for 3RW44 soft starter (Page 153)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


116 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6.5 Operating modes

Manual operation LOCAL/REMOTE


The specified operating mode is displayed at the QREMOTE output.
0 = Manual operation LOCAL/Soft Starter ES
1 = Remote

3.6.6 Functions

Reading measured values


All measured values are read from:
● Data set 94:
The "call RDREC()" function reads data set 94.
● Data set 92:
The SS_DIAG block reads data set 92. The related measurement information is passed
to the SS_MEAS block.

EN_RD = TRUE : Read data set


RD_DATA = 1 : Operating parameter for reading measured values
L_RD_DATA = 1 : Linkable parameter for reading measured values. This is a signal
with rising edge.
QERR_RD = 1 : Error when reading data sets.

Measurement functions
For detailed information on measured values, refer to the "SIRIUS Soft Starter 3RW44"
System Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets" > "Data
Set 94 - Reading the Measured Values".
These values are displayed in the faceplate in the Standard View and Standard 2 View.

Table 3- 49 Data set 94: Access

No. Data set no. Read/write Number of Data set description


bytes
1 94 R 64 Read measured values

"R" = Read access

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 117
Soft starter blocks
3.6 SS_MEAS: Measurement block

Measurement functions of device diagnostics


The SS_DIAG block reads data set 92 "Read device diagnostics". The measured values of
the device diagnostics are passed to the SS_MEAS block. They are displayed there in the
Protection Diagnostics View.

Table 3- 50 List of measured values of device diagnostics

Name of output parameter Structured characteristic map QDIAGMEAS bit no. Description
DIAG_MEAS
QDIAGMEAS: TMPSNSOVLD 0 Temperature sensor overload
Measurement parameter TMPSNSOPEN 1 Temperature sensor open
diagnostics
TMPSNSSHORT 2 Temperature sensor short
TMMOVLD 3 Thermal motor model overload
OVLDSWOFF 4 Overload switch off
IDLETMACT 5 Idle time active
COOLDNTMACT 6 Cooldown time active
ASYMREC 7 Asymmetry recognized
ASYMSWOFF 8 Asymmetry switch-off
CURLMACT 9 Current limiting active
CURHI 10 Current limit exceeded
CURLO 11 Current limit undershot
CURLMSWOFF 12 Current limit switch-off
MOTSTLSWOFF 13 Motor stalled-switched off
INPUT1 14 Input1 active
INPUT2 15 Input2 active
INPUT3 16 Input3 active
INPUT4 17 Input4 active
GNDFLT 18 Ground fault
GNDFLTSWOFF 19 Ground fault switch off
TMMDEACT 20 Thermal motor model deactivated
PHANGCTRFLT 21 Phase angle control failure
COOLCNTACT 22 Cooldown time contact block active
CTNHOTSTART 23 Contact element too hot for starting
CUROVERFLOW 24 Current range overflow
PREWRNUNDSHT 25 Prewarning limit-prewarning time
undershot
PREWRNHTEXED 26 Prewarning limit-motor heat build-
upexceeded
-- 27...31 Reserved

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


118 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6.7 Message features

Messages
The following messages are generated:

Table 3- 51 Output messages

Input parameter Message no. Parameter Message Message


class
MSG_EVID 3) 1 DIAG_MEAS.TMPSNSOVLD $$BlockComment$$Temperature Sensor S
Overload
2 DIAG_MEAS.TMMOVLD $$BlockComment$$ Thermal motor model S
overload
3 DIAG_MEAS.CURHI $$BlockComment$$ Current limit S
exceeded
4 DIAG_MEAS.CURLO $$BlockComment$$ Current limit S
undershot
5 MSG_5 1) $$BlockComment$$ Message Input 5 A
6 MSG_6 1) $$BlockComment$$ Message Input 6 A
7 MSG_7 1) $$BlockComment$$ Message Input 7 A
8 MSG_8 2) $$BlockComment$$ Message Input 8 A

1) The MSG_5 to MSG_8 can be user-configured.


2) Parameters with message number for ALARM_8P.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 119
Soft starter blocks
3.6 SS_MEAS: Measurement block

Table 3- 52 Structure of the related values in ALARM_8P

Message Related value Parameter Meaning


no.
1 1 BA_NA Name of batch
2 2 STEP_NO Step number
3 3 BA_ID Name of batch
4 4 AUX_PR04 1) Auxiliary value 4
5 5 AUX_PR05 1) Auxiliary value 5
6 6 AUX_PR06 1) Auxiliary value 6
7 7 AUX_PR07 1) Auxiliary value 7
8 8 AUX_PR08 1) Auxiliary value 8
9 9 AUX_PR09 1) Auxiliary value 9
10 10 AUX_PR010 1) Auxiliary value 10

1) The AUX_PR04 to AUX_PR010 parameters represent auxiliary values for messages that can be user-configured.

The M_SUP_C input can enable and disable the messages. The QMS_STAT, QMSG_ACK
and QMSG_ERR parameters transfer the information found in ALARM_8P:
● Status of messages
● Status of an alarm acknowledgement
● Status of errors during data transfer

3.6.8 Start-up characteristics

OB 100: Suppress all alarm messages


All alarm messages are suppressed in OB 100:
The user defines a value for RUNUPCY. This is assigned to OB 100 in order to suppress the
messages for the configured cycle count.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


120 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6.9 Block parameters

Table 3- 53 Parameters of the SS_MEAS block

Name of Data format Type Default value Meaning


parameter
AUX_PR04 ANY Input — Auxiliary value 4
AUX_PR05 ANY Input — Auxiliary value 5
AUX_PR06 ANY Input — Auxiliary value 6
AUX_PR07 ANY Input — Auxiliary value 7
AUX_PR08 ANY Input — Auxiliary value 8
AUX_PR09 ANY Input — Auxiliary value 9
AUX_PR010 ANY Input — Auxiliary value 10
BA_EN BOOL Input FALSE Enable batch
BA_ID DWORD Input 16#00 Batch ID
BA_NA STRING[32] Input — Batch Name
DADDR INT Input 0 Diagnostic address of module
DIAG_MEAS SSDIAGMEAS* Input — Diagnostic information of SS_DIAG block
EN_RD BOOL Input FALSE 1 = Enable reading of data set
IN_01 WORD Input 16#00 Value of process image input DP 0.0 … 1.7
L_RD_DATA BOOL Input FALSE Linkable input 0 → 1:
Read data set
LADDR INT Input 0 Logical address of soft starter
M_SUP_C BOOL Input TRUE 1 = Suppress alarm
MODF BOOL Input FALSE 1 = Module failure
MSG_5 BOOL Input FALSE Message input 5
MSG_6 BOOL Input FALSE Message input 6
MSG_7 BOOL Input FALSE Message input 7
MSG_8 BOOL Input FALSE Message input 8
MSG_EVID DWORD Input 16#FF Number of the message event
OCCUPIED BOOL Input FALSE Batch: Occupied
RACKF BOOL Input FALSE 1 = Rack failure
RSRV_IN WORD Input 16#00 Reserved
RUNUPCYC INT Input 3 Number of cycles for which all messages are
suppressed.
SAMPLE_T REAL Input 0.1 Sampling time in s
STEP_NO DWORD Input 16#00 Step number of batch
RD_DATA BOOL Input/ output FALSE 1 = Read data from data set
ERRORNUM INT Output -1 Error number
QASYMTRY INT Output 0 Asymmetry
QASYMTYEN BOOL Output FALSE 0 = No asymmetry
1 = Asymmetry ≥ 40%
QCNTCOLTM REAL Output 0 Remaining contact block cooling time
QCNTCT_HT INT Output 0 Contact block heating

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 121
Soft starter blocks
3.6 SS_MEAS: Measurement block

Name of Data format Type Default value Meaning


parameter
QCURHI BOOL Output FALSE Current limit overshot
QCURLO BOOL Output FALSE Current limit undershot
QDIAGMEAS DWORD Output 16#00 Current diagnostics and thermal diagnostics
QEN_RD BOOL Output FALSE 1 = Enable reading of data set
QERR_RD BOOL Output FALSE 1 = Error while reading a data set
QGRPERR BOOL Output FALSE 1 = Group error
QHTSNK_TMP INT Output 0 Contact block heating
QIL1 REAL Output 0 Phase current IL1 in %
QIL1E REAL Output 0 Effective phase current IL1 in amperes
QIL2 REAL Output 0 Phase current IL2 in %
QIL2E REAL Output 0 Effective phase current IL2 in amperes
QIL3 REAL Output 0 Phase current IL3 in %
QIL3E REAL Output 0 Effective phase current IL3 in amperes
QKW_OUT REAL Output 0 Output power in KW
QL_FREQ REAL Output 0 Line frequency
QMODF BOOL Output FALSE 1 = Module failure
QMOTCOLTM REAL Output 0 Remaining motor cooling time
QMOTHTBLD INT Output 0 Motor heating
QMSG_ACK WORD Output 16#00 ALARM_8P:
ACK_STATE output
QMSG_ERR BOOL Output FALSE 1 = Error during data transfer
QMSG_STAT WORD Output 16#00 ALARM_8P:
Status output
QOUT_FREQ REAL Output 0 Output frequency
QRACKF BOOL Output FALSE 1 = Rack failure
QRD_OUT BOOL Output 0 1= Enable Read operation of DS92 at
SS_DIAG
QREMOTE BOOL Output FALSE 1 = Remote
0 = Manual LOCAL
QRSRV_OUT WORD Output 16#00 Reserved
QTRPTM INT Output 0 Remaining time for tripping the thermal motor
model
QU_ELESUP REAL Output 0 Electronics supply voltage
QU_L1L2 REAL Output 0 Effective phase-to-phase voltage UL1-L2 in
volts
QU_L2L3 REAL Output 0 Effective phase-to-phase voltage UL2-L3 in
volts
QU_L3L1 REAL Output 0 Effective phase-to-phase voltage UL3-L1 in
volts
QUALITY BYTE Output 16#80 Quality code
VSTATUS DWORD Output 16#00 Status information

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


122 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

3.6.10 Faceplates

Table 3- 54 Measurement block SS_MEAS Faceplates with their associated PDL file names

Faceplate PDL file name


Standard @PG_SS_MEAS_STANDARD.pdl
Standard 2 @PG_SS_MEAS_STANDARD2.pdl
Protection diagnostics @PG_SS_MEAS_PROTECTION_DIAG.pdl
Alarms @PCS7_SS_ALARM.pdl
Trend @PCS7_SS_TREND.pdl
Batch @PCS7_SS_BATCH.pdl

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 123
Soft starter blocks
3.6 SS_MEAS: Measurement block

Standard View

① QIL1, QIL1E, QIL2, Phase current in % and A


QIL2E, QIL3, QIL3E
② QMOTHTBLD Motor heating
③ QTRPTM: Remaining time for tripping thermal motor model
④ QMOTCOLTM Remaining motor cooling time
⑤ QKW_OUT Output power
⑥ Read_Data Button for enabling reading of data.
This control function is available to users with authorization level 5
and higher.
The user can define the text on the button: String_1 attribute of
RD_DATA

Figure 3-17 SS_MEAS: Standard View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


124 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

Standard 2 View

① QU_ELESUP Electronic supply voltage of 3RW44


② QU_L1L2, QU_L2L3, QU_L3L1 Phase-to-phase voltage
③ QL_FREQ Line frequency
④ QOUT_FREQ Output Frequency
⑤ QASYMTYEN Asymmetry ≥ 40%
⑥ QASYMTRY Asymmetry
⑦ QHTSNK_TMP Heat sink temperature
⑧ QCNTCT_HT Contact block heating
⑨ QCNTCOLTM Remaining contact block cooling time
⑩ Read_Data Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA

Figure 3-18 SS_MEAS: Standard 2 View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 125
Soft starter blocks
3.6 SS_MEAS: Measurement block

Protection Diagnostics View


QDIAGMEAS - This view displays a maximum of 10 diagnostic messages.

Figure 3-19 SS_MEAS: Protection Diagnostics View

For a list of parameters, refer to Chapter:


Functions (Page 117)

Read_Data Button for enabling reading of data. This control function is


available to users with authorization level 5 and higher. The
user can define the text on the button: String_1 attribute of
RD_DATA.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


126 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.6 SS_MEAS: Measurement block

Block symbol of the SS_MEAS measurement block

① Title with name of block


② Phase current 1
③ Phase current 2
④ Phase current 3
⑤ Group display:
• Indicates the status of alarms and warnings.
• Reads the message configuration of the block for this view.

Figure 3-20 SS_MEAS: Block symbol

Right-clicking on the group representation of the block symbol opens the Alarm View of the
block.

See also
Block icons (Page 21)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 127
Soft starter blocks
3.7 SS_STAT: Statistics block

3.7 SS_STAT: Statistics block

3.7.1 Description

Block type and number: FB 563


Product group: 3RW44

Purpose of block
The SS_STAT block provides statistical information related to:
● Operating hours
● Operating cycles
● Error statistics
● Current measurement
● Maximum pointer
● ...
The block receives information from the SS_DIAG and SS_DIR blocks.

See also
Error numbers (Page 26)
Quality codes (Page 27)
Module drivers of the soft starter (Page 139)
Interconnection of function blocks (Page 42)
CFC charts for 3RW44 soft starter (Page 153)
Technical data (Page 157)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


128 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.7 SS_STAT: Statistics block

3.7.2 Calling OBs


The "Generate Module Driver" function inserts the block into the following organization
blocks:

Table 3- 55 Organization blocks that call the SS_STAT block

Organization block Description


OB 30 … OB 38 Cyclic interrupts
OB 100 Warm restart

Recommendation:
You are recommended to insert the SS_STAT block into OB 32 for cyclic operation.
See also the CFC manual.

3.7.3 Called blocks


The block calls the following blocks:

Table 3- 56 Blocks called by the SS_STAT block

Block Description
SFB 52 RDREC Reads a data set
SFB 53 WRREC Writes a data set
SFC 6 RD_SINFO Reads the start information of the OB

3.7.4 Parameterization

IN_01: Assigning the input address of the module


I-address:
2 bytes of input address of the module must be assigned to input parameter IN_01.

LADDR: Assigning the logical address


The module driver parameterizes the logical address LADDR of the soft starter
automatically.

L DADDR: Diagnostic address


The module driver parameterizes the diagnostics address DADDR of the soft starter
automatically

See also
CFC charts for 3RW44 soft starter (Page 153)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 129
Soft starter blocks
3.7 SS_STAT: Statistics block

3.7.5 Operating modes

Operating mode Manual operation LOCAL/REMOTE


The specified operating mode is displayed at the QREMOTE output.
0 = Manual operation LOCAL/Soft Starter ES
1 = Remote

3.7.6 Functions

Statistical values
For detailed information on statistical values, refer to the "SIRIUS Soft Starter 3RW44"
System Manual > Chapter "Communication Module PROFIBUS DP" > "Data Sets":
● > Data Set 93 - "Writing a Command"
● > Data Set 95 - "Reading the Statistics Data"
● > Data Set 96 - "Reading the Maximum Pointer"

Table 3- 57 Data set 93, Data set 95, and Data set 96: Read access and/or write access

SI No. Data set no. Read/write Number of Data set description


bytes
1 93 RW 10 Writing a command
2 95 R 90 Read statistics data
3 96 R 86 Read maximum pointer

"R" = Read access; "W" = Write access

The following parameters are active:

EN_RD = TRUE : Read data set


RD_DATA = 1 : Operating parameter for reading measured values
L_RD_DATA = 1 : Linkable parameter for reading measured values. This is a signal
with rising edge.
DEL_MXPTR = 1 : Delete maximum pointer values
QERR_RDWR = 1 : The reading/writing of the data set is finished.
QERR_RD = 1 : Error when reading data sets.
QERR_WR = 1 : Error when writing data sets.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


130 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.7 SS_STAT: Statistics block

Statistics function
Data set 95 reads the statistics data. These are displayed in the faceplate in Standard View.

Maximum pointer function


Data set 96 reads the maximum pointer information. These are displayed in the faceplate in
Maximum Pointer View.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 131
Soft starter blocks
3.7 SS_STAT: Statistics block

3.7.7 Block parameters

Table 3- 58 Parameters of the SS_STAT block

Name of Data format Type Default value Meaning


parameter
DADDR INT Input 0 Diagnostic address of module
EN_RDWR BOOL Input TRUE 1 = Enable reading/writing of data set
IN_01 WORD Input 16#00 Value of process image input DP 0.0 … 1.7
L_RD_DATA BOOL Input FALSE Linkable input 0 → 1:
Read data set
LADDR INT Input 0 Logical address of soft starter
MODF BOOL Input FALSE 1 = Module failure
RACKF BOOL Input FALSE 1 = Rack failure
RSRV_IN WORD Input 16#00 Reserved
SAMPLE_T REAL Input 0.1 Sampling time in s
DEL_MXPTR BOOL Input/ output FALSE Maximum pointer reset
RD_DATA BOOL Input/ output FALSE 1 = Read data from data set
ERRORNUM INT Output -1 Error number
QCNTCTMP INT Output 0 Maximum contact block heating
QEN_RDWR BOOL Output FALSE 1 = Enable read and write data sets
QERR_RD BOOL Output FALSE 1 = Error while reading a data set
QERR_WR BOOL Output FALSE 1 = Error while writing a data set
QGRPERR BOOL Output FALSE 1 = Group error
QHTSKMP INT Output 0 Maximum heat sink temperature
QIL1MAX REAL Output 0 Phase current IL1max in %
QIL1MAXE REAL Output 0 Effective phase current IL1max
QIL1MIN REAL Output 0 Phase current IL1min in %
QIL1MINE REAL Output 0 RMS phase current IL1min
QIL2MAX REAL Output 0 Phase current IL2max in %
QIL2MAXE REAL Output 0 RMS phase current IL2max
QIL3MAX REAL Output 0 Phase current IL3max in %
QIL3MAXE REAL Output 0 RMS phase current IL3max
QIL3MIN REAL Output 0 Phase current IL3min in %
QIL3MINE REAL Output 0 RMS phase current IL3min
QILTRPEMX REAL Output 0 RMS maximum tripping current
QILTRPMX REAL Output 0 Maximum tripping current in %
QL2MIN REAL Output 0 Phase current IL2min in %
QL2MINE REAL Output 0 RMS phase current IL2min
QLFREQMAX REAL Output 0 Maximum line frequency
QLFREQMIN REAL Output 0 Minimum line frequency
QM_IMAX REAL Output 0 Motor current Imax in %
QM_IMAXE REAL Output 0 RMS motor current Imax

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


132 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.7 SS_STAT: Statistics block

Name of Data format Type Default value Meaning


parameter
QM_OPH DWORD Output 16#00000000 Motor operating hours
QMODF BOOL Output FALSE 1 = Module failure
QN_BRKSTP DINT Output 0 Number of stops with electrical braking
QN_CNTTRP DINT Output 0 Number of contact block overload trips
QN_OVLTRP INT Output 0 Number of overload trips
QN_ST_CCW DINT Output 0 Number of motor starts CCW
QN_ST_CW DINT Output 0 Number of motor starts CW
QOHIL120MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 120 … 1000% x Ie(max)
QOHIL18MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 18 … 49.9% x Ie(max)
QOHIL50MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 50 … 89.9% x Ie(max)
QOHIL90MP DWORD Output 16#00000000 Maximum pointer:
Operating hours - motor current
= 90 … 1199.9% x Ie(max)
QOPHIL120 DWORD Output 16#00000000 Operating hours - motor current
= 120 … 1000% x Ie(max)
QOPHIL18 DWORD Output 16#00000000 Operating hours - motor current
= 18 … 49.9% x Ie(max)
QOPHIL50 DWORD Output 16#00000000 Operating hours - motor current
= 50 … 89.9% x Ie(max)
QOPHIL90 DWORD Output 16#00000000 Operating hours - motor current
= 90 … 1199.9 % x Ie(max)
QOUTPUT1 DINT Output 0 Number of starts - output 1
QOUTPUT2 DINT Output 0 Number of starts - output 2
QOUTPUT3 DINT Output 0 Number of starts - output 3
QOUTPUT4 DINT Output 0 Number of starts - output 4
QOVLTRPMP INT Output 0 Number of motor overload trips, e.g., motor
protection, temperature sensor, blocking
QRACKF BOOL Output FALSE 1 = Rack failure
QREMOTE BOOL Output FALSE 1 = Remote
0 = Manual LOCAL
QRSRV_OUT WORD Output 16#00 Reserved
QS_OPH DWORD Output 16#00000000 Starter operating hours
QS_OPHMP DWORD Output 16#00000000 Operating hours - Device:
Maximum pointer
QTRG_I REAL Output 0 Last tripping current IA in %
QTRG_IE REAL Output 0 Last tripping current IA RMS
QUALITY BYTE Output 16#80 Quality code

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 133
Soft starter blocks
3.7 SS_STAT: Statistics block

Name of Data format Type Default value Meaning


parameter
QUEL_MAX REAL Output 0 Max. electronics power supply
QUEL_MIN REAL Output 0 Min. electronics power supply
QUL1L2MAX REAL Output 0 RMS phase-to-phase voltage UL1-L2max
QUL1L2MIN REAL Output 0 RMS phase-to-phase voltage UL1-L2min
QUL2L3MAX REAL Output 0 RMS phase-to-phase voltage UL2-L3max
QUL2L3MIN REAL Output 0 RMS phase-to-phase voltage UL2-L3min
QUL3L1MAX REAL Output 0 RMS phase-to-phase voltage UL3-L1max
QUL3L1MIN REAL Output 0 RMS phase-to-phase voltage UL3-L1min
VSTATUS DWORD Output 16#00000000 Status information

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


134 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.7 SS_STAT: Statistics block

3.7.8 Faceplates

Table 3- 59 Statistics block SS_STAT: Faceplates with their associated PDL file names

Name of view PDL file name


Standard @PG_SS_STAT_STANDARD.pdl
Maximum pointer @PG_SS_STAT_MAX_POINTER.pdl

Standard View

① QS_OPH, QM_OPH Operating hours


QOPHIL18, QOPHIL50, QOPHIL90, QOPHIL120 Operating hours – motor current
② QN_CNTTRP, QN_OVLTRP Fault statistics
③ QM_IMAX, QM_IMAXE, QTRG_I, QTRG_IE Current measuring
④ QN_ST_CW, QN_ST_CCW, QN_BRKSTP, Operating cycles
QOUTPUT1, QOUTPUT2, QOUTPUT3, QOUTPUT4
⑤ Read_Data: Button for enabling reading of data.
This control function is available to users with
authorization level 5 and higher.
The user can define the text on the button: String_1
attribute of RD_DATA
Figure 3-21 SS_STAT: Standard View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 135
Soft starter blocks
3.7 SS_STAT: Statistics block

Maximum Pointer View

① QS_OPHMP Operating hours - device


QOHIL18MP, QOHIL50MP, QOHIL90MP, QOHIL120MP Motor operating hours
② QUEL_MIN, QUEL_MAX Electronics supply voltage
③ QLFREQMIN, QLFREQMAX Main energy monitoring
④ QUL1L2MIN, QUL1L2MAX, QUL2L3MIN, QUL2L3MAX Voltage measurement
⑤ QIL1MIN, QIL1MAX, QIL1MINE, QIL1MAXE,QIL2MIN, QIL2MAX, Current measuring
QIL2MINE, QIL2MAXE,QIL3MIN, QIL3MAX, QIL3MINE, QIL3MAXE
⑥ DeleteMaxPntr Delete maximum pointer button
This button is only available in Remote
mode.
This control function is available to users
with authorization level 5 and higher.
The user can define the text on the button:
String_1 attribute of DEL_MXPTR

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


136 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Soft starter blocks
3.7 SS_STAT: Statistics block

⑦ Read_Data Button for enabling reading of data.


This control function is available to users
with authorization level 5 and higher.
The user can define the text on the button:
String_1 attribute of RD_DATA
⑧ QILTRPMX, QILTRPEMX Current measuring - maximum tripping
current
⑨ QOVLTRPMP Fault statistics
⑩ QCNTCTMP Thermal contact block model
⑪ QHTSKMP Solid-state switching
Figure 3-22 SS_STAT: Maximum Pointer View

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 137
Soft starter blocks
3.7 SS_STAT: Statistics block

Block icon of the SS_STAT statistics block

① Title with name of block


② Operating hours of soft starter
③ Number of motor starts
④ Manual operation LOCAL or REMOTE:
"L" = Manual operation LOCAL
"R" = Remote

Figure 3-23 SS_STAT: Block icon

See also
Block icons (Page 21)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


138 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Module drivers of the soft starter 4
4.1 Object lists and action lists
Hardware modules, among other things, are configured in HW Config.

Description
The object lists and the action lists are used to generate the module drivers for these
hardware modules.
The object list contains a unique object identification number for each of these hardware
modules. Each object list is assigned to a particular hardware configuration.
The action list contains a list of actions. These actions must be executed for the object
identification numbers that appear in the object list Examples of such actions include:
● Assigning the device address
● Interconnecting the input and output parameters of the driver block
The "Generate Module Driver" function generates the module drivers when the CFC is
compiled.

See also
Handling the driver generator (Page 10)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 139
Module drivers of the soft starter
4.2 Requirements for generating the module drivers

4.2 Requirements for generating the module drivers

Requirements
After generating an instance for a signal block, ensure that the following requirements are
met:
● IN_01 and IN_02 are parameterized.
● The driver blocks have been generated in the CFC with the "Generate module driver"
function when compiling the CFC chart.

Generate module driver settings


These options can be used to disable / enable all diagnostic alarm messages at the
MOD_SWT block.
● Default setting at the blocks : Enabled
● Set the "Leave unchanged" option (default) to retain current settings

Note
To have similar behavior between this library and the PCS 7 Basis Library, a PCS 7 Basis
Library version supporting this functionality needs to be installed as well.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


140 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Module drivers of the soft starter
4.3 Driver blocks

4.3 Driver blocks


Following successful compilation of the signal blocks, specific driver blocks are generated
depending on the configuration.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 141
Module drivers of the soft starter
4.3 Driver blocks

Circuit diagrams

Figure 4-1 Circuit diagram: 3RW44 soft starter directly on the DP master system

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


142 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Module drivers of the soft starter
4.3 Driver blocks

Note
The blocks highlighted in yellow are inserted by module driver generator. The blocks
highlighted in white are inserted in CFC charts as part of template.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 143
Module drivers of the soft starter
4.3 Driver blocks

Figure 4-2 Circuit diagram: 3RW44 soft starter following a Y link

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


144 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Module drivers of the soft starter
4.3 Driver blocks

Note
The blocks highlighted in yellow are inserted by module driver generator. The blocks
highlighted in white are inserted in CFC charts as part of template.

3RW44 soft starter directly on the DP master system - Configuration using the hardware catalog or a
GSD file
The following driver blocks and interconnections are generated when the CFC is compiled:
1. SS_DIAG - Diagnostics for the SIRIUS 3RW44 soft starter
2. OB_DIAG1 - OB diagnostic function
3. OB_BEGIN - CPU function block
4. MOD_SWT - Message diagnostic for slave connected to the DP master system

Table 4- 1 Interconnections generated when CFC is compiled

OB_DIAG1 OB_BEGIN MOD_SWT SS_DIAG SS_DIR SS_STAT SS_MEAS


QRACKF — — RACKF — — —
EN_F — EN EN — — —
EN_DIAG — — EN_DIAG — — —
SUBN1ERR — — SUBN1ERR — — —
SUBN2ERR — — SUBN2ERR — — —
RAC_DIAG — RAC_DIAG — — — —
CPU_DIAG CPU_DIAG CPU_DIAG — — — —
CPU_OB_5 CPU_OB_5 —
— — — QRACKF RACKF RACKF RACKF
— — — QMODF MODF MODF —MODF
— — — — — — —
— — — — — — —
— — — QEN_RD EN_RDWR EN_RDWR EN_RD
— — — DIAG_DIR DIAG_DIR — —
— — — DIAG_MEAS — — DIAG_MEAS
— — OMODE_00 — MODE MODE MODE

1) 3RW44 soft starter directly on the DP master system: DP alarm mode is set to DPV1.
2) The driver blocks for PCS 7 V6.1 do not support interconnection of the CPU_DIAG parameter with MOD_SWT.

Note
This table specifies the interconnections between the blocks. For e.g. the first line eplains
that the QRACKF pin of OB_DIAG1 block is interconnected to RACKF pin of SS_DIAG
Block.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 145
Module drivers of the soft starter
4.3 Driver blocks

3RW44 soft starter following a Y link - Configuration using OM supplied by Soft Starter ES
This configuration cannot be applied.

3RW44 soft starter following a Y link - Configuration using GSD file


The following driver blocks and interconnections are generated when the CFC is compiled:
1. SS_DIAG - Diagnostics for the SIRIUS 3RW44 soft starter
2. OB_DIAG1 - OB diagnostic function
3. OB_BEGIN - CPU function block
4. MOD_SWT - Message diagnostic for slave connected to the DP master system

Table 4- 2 Interconnections generated when CFC is compiled

OB_DIAG1 OB_BEGIN MOD_SWT SS_DIAG SS_DIR SS_STAT SS_MEAS


QRACKF — — RACKF — — —
EN_F — EN EN — — —
EN_DIAG — — EN_DIAG — — —
SUBN1ERR — — SUBN1ERR — — —
SUBN2ERR — — SUBN2ERR — — —
RAC_DIAG — RAC_DIAG — — — —
CPU_DIAG CPU_DIAG CPU_DIAG — — — —
CPU_OB_5 CPU_OB_5 —
— — — QRACKF RACKF RACKF RACKF
— — — QMODF MODF MODF —MODF
— — — — — — —
— — — — — — —
— — — QEN_RD EN_RDWR EN_RDWR EN_RD
— — — DIAG_DIR DIAG_DIR — —
— — — DIAG_MEAS — — DIAG_MEAS
— — OMODE_00 — MODE MODE MODE

The driver blocks for PCS 7 V6.1 do not support interconnection of the CPU_DIAG parameter with MOD_SWT.

Note
3RW44 soft starter following a Y link - Configuration using GSD file
If you are using the communication module with firmware version < E*04, a DPV1 following
the Y link is not possible.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


146 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Module drivers of the soft starter
4.3 Driver blocks

More information
Additional information regarding GSD files is available in the "SIRIUS 3RW44 Soft Starter"
System Manual > Chapter "Configuration with the GSD File".
Additional information on:
DPV1 functionality for SIRIUS 3RW44 soft starter following a Y link
(https://support.industry.siemens.com)
1. Enter the following search term in the "Product Name or Part Number" field: y link 3rw44
2. Select the entry.

See also
Handling the driver generator (Page 10)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 147
Module drivers of the soft starter
4.3 Driver blocks

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


148 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
3RW44 soft starter in the Maintenance Station 5
Description
The Maintenance Station is a node in the network control. It displays the status of all devices
that are configured in the network. The Maintenance Station is primarily connected to the
Plant Asset Management System.
The Maintenance Station supports the following basic functions:
● Collecting online information:
– For evaluation of the system
– For evaluation of the status of components
– For evaluation of system errors
● Decisions regarding service activities, such as
– Customer service for system
– Inspection
– Maintenance
– Eliminating faults
● Maintenance request and status management
The "Generate Module Driver" function generates the module drivers when the CFC is
compiled.
The softstarter device is equipped with the following driver blocks:
● RACK
● OB_DIAG1
● MOD_SWT
● SS_DIAG
The type of driver block depends on the configuration.
These blocks function as an interface for writing the status of service activities to the
Maintenance Station.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 149
3RW44 soft starter in the Maintenance Station

Figure 5-1 Message diagnostics for PA slave DP V0 linked to the DP master system

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


150 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
3RW44 soft starter in the Maintenance Station

Figure 5-2 Maintenance Station

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 151
3RW44 soft starter in the Maintenance Station

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


152 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
CFC charts for 3RW44 soft starter 6
Description
The CFC charts are a ready-made reference for using blocks from the block library. They
reduce the engineering effort required to configure the various blocks that support the proper
functioning of the signal blocks.
The charts are available in the block library under:
"PCS7 SS Library V8.0 SP4 > Blocks+Templates\Templates > SoftStarter"
Generate instances of the charts stored in the block library for incorporation in the CFC
charts. These are stored in the "Templates" directory of the SIMATIC project S7_program.

Figure 6-1 Path of directory where the CFC charts are stored

Soft Starter CFC chart


The "Soft Starter" CFC chart contains one instance each of the following blocks:
● SS_DIR
● SS_MEAS
● SS_STAT
Use this CFC chart for the following:
● For operating
● For measuring
● For providing statistical information on the 3RW44 soft starter

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 153
CFC charts for 3RW44 soft starter

The parameters have a textual interconnection that mentions the parameters to be


interconnected.
The following parameters must be assigned:
● IN_01 = Logical address of the starter block.

Figure 6-2 "Soft Starter" CFC chart

Note:
To facilitate the symbolic interconnection of the block inputs and outputs IN_01 and OUT_01
with the inputs and outputs of the device, symbols can be created in the symbol table.
You can find the symbol table in the HW Config Options > Symbol Table.
The inputs and outputs for the device are created here. Since the addresses are available in
BYTE, and the blocks are interconnected with WORD, the data type must be stored
accordingly in the symbol table.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


154 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
CFC charts for 3RW44 soft starter

In this example, the symbols In01 and Out01 are assigned for the addresses IW 2 and QW 2
in data type WORD.
The suitable symbol can now be selected when interconnecting.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 155
CFC charts for 3RW44 soft starter

Alternatively, editing can be carried out without the symbol table. Then a direct
interconnection is made with, for example, IW 2.

See also
Parameterization (Page 46)
Parameterization (Page 116)
Parameterization (Page 129)
Interconnection of function blocks (Page 42)

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


156 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
Technical data 7
7.1 Technical data

Table 7- 1 Memory requirement, FB number, and called blocks, per block type

Name of FB no. 2) Length of block Length of block Length of instance Length of instance Temporary Blocks
block 1) in the load in the work data in the load data in the work memory, in called 6)
memory, in memory, in memory, in memory, in bytes 5)
bytes 3) bytes 3) bytes 4) bytes 4)
SS_DIAG 561 5680 4756 1178 418 422 SFB 35
SFB 52
SFB 54
SFC 13
SFC 51
SFC 6
SS_DIR 562 46538 43038 4506 2520 106 SFB 35
SFB 52
SFB 53
SFC 20
SFC 6
SFC 64
SS_STAT 563 5052 4564 906 530 56 SFB 52
SFB 53
SFC 6
SS_MEAS 564 3524 2988 1044 590 62 SFB 35
SFB 52
SFB 6
SFC 20
1) The symbolic designator in the symbol table of the library for the respective function block (FB). It must be unique within
the project.
2) Composed of the block type, e.g., FB for function block and the number.
3) Memory requirement of program code, once per block type.
4) Memory requirement for an instance data block.
5) The memory required for the local data when the block is called in an execution level. This is limited according to the
specific CPU. If this amount is exceeded, you must check the setting in the CPU configuration and redistribute it among
the organization blocks based on the actual requirement.
6) The relevant driver block uses these blocks. They are now located in the user program They are stored in the same
library.

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 157
Technical data
7.1 Technical data

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


158 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006
List of abbreviations A
A.1 Abbreviations

Overview

Table A- 1 Meaning of abbreviations

Abbreviation Meaning
AS Automation station
HMI Human Machine Interface
CFC Continuous Function Chart
CCW Counter-clockwise
CW Clockwise
DC Direct-current voltage
DP Distributed Peripherals
ES Engineering system
FB Function block
GSD Generic Station Description
HW Config "Hardware configuration" module in SIMATIC Manager
ID Identification number
OB Organization block
OS Operator station
PCS 7 Process Control System 7
PIQ Process image output
PII Process image input
PG Programming device
PS Parameter set
RS Formerly: Radio Selector; now usually: Recommended Standard
SFB System function block
SFC Sequential function chart
PLC Programmable logic controller
SS Soft starter
SSL System status list
TIA Totally Integrated Automation

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006 159
List of abbreviations
A.1 Abbreviations

3RW44 Soft Starter PCS 7 Library V7-V9 Migration V8.0 SP4


160 Programming and Operating Manual, 06/2019, A5E02845977020A/RS-AD/006