You are on page 1of 12

Fires in waste to energy power

generation plants

A guide to loss prevention


Power generation from waste to energy plants is now commonplace, with electricity
being generated by mass burning of a variety of fuels derived from waste materials.
Waste fuel streams, however, can present a range of fire risks due to their
combustibility and other hazards.

Fires in waste to energy plants continue Other organisations, such as Factory Design Basis Document should be
to be a major cause of insurance loss. Mutual Global (FM), Underwriters produced. This document evaluates the
Commonly used fuels include waste Laboratories (UL) and the UK Loss plant-specific fire hazards, the fire
streams such as municipal solid waste Prevention Certification Board (LPCB), protection codes and standards that
from kerb-side collections, used tyres, provide testing, approval and apply and the methods proposed to
waste wood, dried sewage sludge and certification services for materials and control those hazards identified.
organic biomass. The risks from waste equipment used in fire protection
fuel streams can include dust, installations. These organisations also In general, the power plant’s overall
spontaneous combustion, poor deliver fire rating and performance design and layout should be based on
housekeeping, the delivery of already testing of materials and equipment used process systems that will prevent
smouldering loads, ignition in bulk in the construction of waste to energy inadvertent ignition in the fuel feed train.
storage bins or conveying systems, the power generation plants. This includes physical separation and
use of hydraulically actuated processing the use of non-combustible construction
equipment, flue gas filtration systems Insurers recognise FM, UL or LPCB materials that will prevent the spread of
and the use of combustion engine- approval and certification as the fire. The installation of fixed automatic
powered loading shovels. standard required for the fire resistance fire detection and protection systems to
rating of construction materials and for detect, control and extinguish a fire is an
This guide provides advice on best fire protection installations. essential element of the design.
practice engineering for fire prevention
control systems, fire detection and The layout of the buildings, plant and
firefighting arrangements within waste The hierarchy for control process equipment should allow
to energy facilities. unimpeded access by fire and rescue
of the fire risk should be:
service emergency response vehicles to
A list of common terms and definitions all areas.
is located at the end of this document. - Fire separation
- Fire prevention All construction and thermal insulation
Design and construction materials should hold a certified non-
- Fire detection
combustible or limited combustible
The energy and insurance industries - Fire extinguishing rating approved by the LPCB, FM or UL.
within the UK recognise and refer to the All interior surface materials used in the
USA’s National Fire Protection It is important that these floors, walls and ceilings should have
Association (NFPA) and other associated Class A fire spread ratings.
risk control measures are
NFPA organisation standards (NFPA
850, for example) for power plant design built into design and Where thermally insulated composite
and construction. The NFPA’s standards management procedures panels are used for the external side
are applied as the basis for best adopted by power walls and roofs of the building, the fill
engineering practice in the design and material should preferably be non-
generation plants.
installation of fire protection systems in combustible, such as mineral wool.
power plants, including waste to energy Composite panels using foamed fill
plants. The design, construction, operation and materials are acceptable, providing they
fire protection of waste to energy power have been tested and certified by LPCB
In many cases, British or European plants should meet the requirements of or FM to have a limited combustibility
standards for fire protection guidance on NFPA 850: Recommended Practice for rating.
specific items of plant and equipment fire Protection for Electrical Generating
used in the power industry do not exist. Plants and High Voltage Direct current Waterproofing membranes in the roof
Where British or European standards do Converter Stations. Chapter 9 is should have a Class A fire spread rating.
exist, these standards have been particularly relevant as it provides Torch-applied mineral felt or similar
referenced in this loss prevention guide. specific recommendations for the use of roofing materials are not recommended.
In many cases, British and European alternative fuels. This is because of the fire risk during
standards are often based on NFPA construction or repair, and the potential
standards. NFPA 850 requires that during the early to cause a fire to spread across the roof
stages of plant design, a Fire Protection to other areas of the plant.

2 Fires in waste to energy power generation plants


Lightning protection should meet the −−Material recovery and fuel processing water spray system or an approved
requirements of NFPA 780: Standard for area intumescent coating. This is to protect
the installation of Lightning Protection −−Fuel oil pumping and conditioning area against distortion and collapse in the
Systems. −−Plant rooms for air conditioning event of a reception bunker fire. The
systems structural steel protection should extend
In buildings where fuel is being handled, −−Hot-load unloading areas over full height of the column within the
the surfaces of equipment and structural −−Overflow fuel storage areas fuel reception area. The structural
members should be designed to prevent −−Plant vehicle garages steelwork protection system should
dust and combustible materials itself be protected from damage by plant
accumulating and to provide access for All fire barrier openings should have fire vehicles and fuel handling crane grabs.
cleaning. doors or fire shutters installed with the
same rating as the fire barrier. A designated bunker area should be
Fire area separation Ventilation ducts passing through the provided for unloading waste loads that
The installation of fire doors, fire fire barriers should be fitted with fire are smouldering on arrival. This area
dampers, fire shutters and windows dampers at the penetration point. should be at least 15m from any other
should meet the requirements of NFPA Where cables and pipes penetrate the structure or building and be provided
80: Standard for Fire Doors and Fire fire barrier, they should be sealed with a with fire extinguishing equipment.
Windows. Spatial separation distances fire resistant material with the same
should be in accordance with NFPA rating as the fire barrier. Containment and drainage
80A: Recommended Practice for To prevent flooding or damage to other
protection of Buildings from Exterior Viewing windows in designated fire areas and equipment, liquids and
Fire Exposure. barriers, such as the control room, crane firefighting water should be controlled
operator room and process observation and removed. Control and removal can
The fire areas within the plant should be areas, should be fitted with automatic be achieved by providing floor drains,
separated from each other by two-hour- fire shutters or automatic water curtains. trenches, curbs or bunds for containing
rated fire barriers or a minimum of 15m or directing liquids to drainage pits or
of spatial separation. The fire barriers The control room’s ventilation system sumps. Equipment can be protected by
must extend from the floor to the should be separate from other systems, elevating it on pedestals.
underside of a non-combustible roof. A and its fresh-air intake should be located
two-hour-rated fire barrier or sufficient in a position that avoids the ingestion of The curbing and drainage should be
spatial separation should be provided to smoke and airborne combustion designed to control the largest potential
separate the following areas: products. The control room’s ventilation spill of any flammable or combustible
system should operate at a positive liquids in the area. It should also
−−Receiving/tipping floor and refuse pit pressure to prevent smoke entry during accommodate the maximum design
−−Steam generator and turbine building a fire. discharge of the fire protection system
−−Auxiliary equipment rooms and hose streams operating for a
−−Auxiliary boiler room A fire damper is required where the minimum of 10 minutes. The water
−−Control room and DCS panel room boiler’s forced draft fan removes air from volumes used in wash-down should also
−−Electrical switchgear and motor the fuel tipping hall to reduce odour. The be considered.
control centres damper should be located where the
−−Cable spreading room and cable ductwork passes through the tipping To prevent the spread of burning liquids
tunnels hall fire barrier. There is a risk of boiler beyond the fire area, floor drainage from
−−Administrative areas and locker rooms implosion if the damper closes as a the areas containing flammable or
−−Emergency generator room result of a fire and the forced draft fan combustible liquids should be trapped
−−Fire pump room or pump house continues to operate. A bypass system or discharged to a sump.
−−Battery rooms or appropriate process interlocks should
−−Telecommunications and server rooms be considered to allow shutdown Lubricating and fuel oil bulk storage
−−Maintenance workshops and without damaging the boiler. tanks should be of double skin design or
warehouses bunded to contain 110% of the maximum
−−Flammable and combustible liquid Structural steel columns in the vicinity of tank capacity.
storage rooms the fuel reception bunker should be
−−Processed fuel storage area encased in concrete with a dedicated

Fires in waste to energy power generation plants 3


General requirements for fire A minimum of two 100% duty fire Portable fire extinguishers
detection and protection pumps should be installed. At least one Portable fire extinguishers should be
fire pump should be diesel engine-driven. provided in accordance with NFPA 10:
Fire protection systems should be The second pump may be electric motor Standard for Portable Fire Extinguishers,
designed and installed in accordance driven, provided the power supply is or BS5306 Part 8 Code of practice for
with NFPA 850: Recommended Practice from a secure source that is designed the Selection and Installation of Portable
for Fire Protection for Electric generating to supply site emergency services. The Fire Extinguishers.
Plants and High Voltage Current installation should also include
Converter Stations. Chapter 9 is provisions for routine flow testing of Fire detection and alarms
particularly relevant with its coverage of each pump. All rooms within all buildings should be
alternative fuels. fitted with an automatic fire detection
Fire main and hydrants and alarm system meeting the
All fire protection equipment must be A fire main and fire hydrants should be specifications given in BS 5839 Part 1.
approved and certified by either LPCB, installed that meet the requirements of The system should provide level P1
FM or UL. Fire protection systems and NFPA 24: Standard for the Installation coverage, or the equivalent, as set out in
equipment should only be designed, of Private Fire Services and Their NFPA 72: National Fire Alarm Code.
supplied and installed by companies Appurtenances or BS 5306-0: 1986
having LPCB Quality System Standard for fire extinguishing To avoid frequent false alarms, the
Certification. installations and equipment on specifications of the fire detection
premises: Guide for the selection of system selected should also
Water supplies installed systems and other fire accommodate the heat and dust
The fire protection system water supply equipment. conditions found in the protected zone.
should be provided from a reliable
source. Without making an allowance for A looped fire water supply main should The installation of very early smoke
reservoir filling, the water supply should be installed that encompasses the detection (VESDA) systems in electrical
be able to provide a minimum of two power block. Its capacity should meet rooms, motor control centres, DCS panel
hours of operation based on whichever is the flow requirements set out in NFPA and instrument rooms should be
greater of the following: 14: Standard for the Installation of considered.
Standpipes, Private Hydrants and Hose
a. The volume required for the largest Systems Fire Systems. The spacing of The operation of the fire detection and
fixed fire protection system demand, external hydrants should not exceed automatic fixed fire suppression
or 100m and they should not be greater systems should activate plant-wide
b. Two fixed fire protection systems that than 12.2m from the buildings they are audible and visual alarm signals. The
are expected to be operating designed to protect. systems should be supervised at a
simultaneously. master fire alarm panel located in the
The local fire and rescue service should control room.
In addition to the above, if the fire hose be consulted to ensure compliance with
hydrant system takes water from the its fire hydrant connection and pressure Internal and external manual fire alarm
same source, the supply must requirements. How to prevent hydrant call points should be provided inside all
simultaneously support a minimum of a damage as a result of vehicle impact buildings and all process plant areas.
1,890 litres per minute hose stream should also be considered.
demand. Fire protection for specific areas
Internal fire hoses of plant
Fire pumps Internal fire hose points should be
Fire pumps should be supplied and provided that meet the requirements Waste to energy power generating
installed meeting the specifications of NFPA 14. They should be provided plants operate using fuels and include
required by NFPA 20: Standard for the throughout the fuel handling and process and equipment areas that
Installation of Stationary Pumps and processing areas, hydraulic package require specific fire protection and
Fire protection. unit areas and the boiler firing and design to minimise fire risks.
charging floors.

4 Fires in waste to energy power generation plants


MSW and RDF tipping hall pit and Sprinkler systems should be designed explosion suppression system should
MRF areas to provide a minimum density of be fitted in accordance with NFPA 69:
Automatic sprinkler systems should be 10.2mm/min over the area protected. Standard for Explosion prevention
provided throughout the refuse Systems and ASTM E 1248 Standard
reception and tipping hall area, including Below belt sprinkler heads may be Practice for Shredder Explosion
the fuel tipping pit. The MRF processing required where areas below the belt are Systems.
building should also be provided with an shielded from other sprinkler
automatic sprinkler system that covers installations. Classifiers and rotating screens should
the whole floor area. Shielded areas, be fitted with automatic water spray
such as those below conveyors and Conveyors should be tripped or reversed, systems to prevent a fire from spreading
equipment, may require local sprinkler if it is safe to do so, on detection of a fire downstream.
heads. on or near the conveyor to prevent fire
spread. Alternatively, the conveying Boiler fuel feed system
These systems should be designed to a system should include a method of Boiler fuel feed bins, hoppers, conveyors,
minimum density of 10.2mm/min over diverting or dumping a burning load into chutes and ram feeders should be fitted
the floor area. The sprinkler systems a bin or safe area where the fire can be with automatic sprinklers providing a
should be designed and installed extinguished with fire hoses or monitors. minimum density of 8.1mm/min.
according to the requirements of NFPA In some instances, it may be appropriate
13 Standard for the installation of to run a burning load off the conveyor When designing fuel feed systems, the
Sprinkler systems. into the furnace. material and structural support strength
calculations should allow for the weight
In addition to sprinklers, oscillating Shredders and mills of the contents when saturated with fire
monitor nozzles with a manual override Shredders and mills have an elevated water. It may also be necessary to make
providing coverage of the whole tipping risk of fires and dust explosions. provision for additional emergency water
pit area should be installed. Monitor Undetected flammable or explosive drainage valves and systems.
nozzle protection should be designed to materials in the feed material increases
deliver a minimum of 946 litres per this risk. To control these risks, Hydraulic systems
minute at 6.9 bar at the nozzle tip with at shredders and mills should be fire Control and pressure systems used
least two streams operating segregated from each other, and from within hydraulically operated systems
simultaneously. other equipment, by physical distance or should be fitted with sprinkler or water
enclosures. spray protection systems designed to
It should be possible to operate the deliver a minimum of 10.2mm/min. This
monitor nozzles from the control room Shredder or mill enclosures, including is unless:
or crane operator’s pulpit. They should the intake and outfall chutes and vents,
be installed so that they do not interfere should be fitted with automatic sprinkler −−A listed fire resistant fluid is used
with operation of the grab crane and will protection designed for a minimum −−There is no normal ignition source
not be damaged by the waste grab. density of 10.2mm/min. The shredder or within 6m of any part of the hydraulic
mill should be automatically shut down system
Conveyors when the fire protection system is −−The system contains less than 380
Conveyor belts carrying combustible operated. litres of hydraulic oil.
materials should use fire retardant
conveyor belt material. Automatic water The shredder or mill enclosures should Tanks holding more than 380 litres of
spray or sprinkler systems should be be designed to withstand and safely vent petroleum-based oil should have an
provided on all enclosed conveyors and the worst case explosion. automatic oil pump and oil flow
for all conveyors carrying combustible shutdown. The oil pump should
materials located outside of a building If a shredder or mill has an open top feed automatically shut down when a fire or
with sprinklers. Open conveyors within hopper that will allow safe venting of an a temperature rise of more than 30°C
buildings should be covered by the internal explosion, additional explosion above the normally anticipated area
building sprinkler system. Sprinkler or protection is not required. However, if operating temperature is detected.
water spray coverage should be provided adequate explosion protection is not
at all transfer points. provided via the feed hopper, an

Fires in waste to energy power generation plants 5


Boiler and burner fronts Steam turbine and generator bearings instrument rooms, motor control
Boilers normally require a secondary fuel should be protected by closed head pre- centres, DCS panel rooms, UPS and
for light-off, and in some cases for use as action sprinklers that provide a battery rooms and the crane control
a secondary fuel. Secondary fuels may minimum density of 10.2mm/min. If room. Carbon dioxide or other clean
be either oil and or gas (natural or shaft or casing water damage is a agent gas flood systems should be
propane). concern, then NFPA 850 permits installed in accordance with the
shielding. An automatic activation appropriate standard. These include:
The burner operation and fuel controls system is preferable to manual NFPA 12 for a CO2 gas flood system,
must meet the requirements of NFPA operation. If the sprinklers are manually NFPA 2001 for a Clean Agent gas
85: Boiler and Combustion Systems operated, then activation should be from System and BSISO14520-1:2000 for
Hazards Code. a permanently manned control room or a gaseous Fire Extinguishing Systems.
safe but accessible place. A written
If a liquid fuel oil is used, the boiler procedure should describe how and Cable spreading rooms and tunnels
burner fronts should be protected by an when the system is activated, and Cable spreading and cable tunnels
automatic sprinkler, water spray, or operators should have approval to should be protected with automatic
foam-water sprinkler system installed in activate the system without first seeking sprinklers, water spray, foam water or an
accordance with NFPA 13, NFPA 15, or authorisation. automatic gaseous extinguishing
NFPA 16: Installation of Foam-water system. Sprinkler and water spray
sprinkler and Foam-water Spray system. If the steam turbine and generator are systems should be designed to provide a
installed within a separate enclosure, as minimum density of 12.2mm/min over
Indoor fuel oil pumping and/or heating an alternative to a sprinkler system, one the whole area,
facilities should be protected with a wet of the following systems may be used:
pipe foam-water automatic sprinkler Transformers
system. −−An automatic total flooding water mist For indoor installation, dry type
system meeting the requirements of transformers are preferred to oil-filled
If a gaseous secondary fuel is used, a NFPA 750 transformers. When oil-filled
fuel gas emergency shut off valve must −−A gaseous flooding system using transformers are used, less flammable or
be provided that automatically shuts-off Carbon Dioxide designed in non-flammable insulating oils are
the fuel gas supply when a fire or gas accordance with NFPA 12 recommended. Oil-filled transformers
leakage is detected. When the −−An approved clean agent gaseous fire should ideally be located outdoors.
emergency fuel gas shut-off valve is extinguishing system specified in
operated, it should also raise an alarm on accordance with NFPA 2001. NFPA 850 recommends a minimum
the central fire control panel. 15m line-of-sight separation distance
The turbine generator lubricating oil between individual oil-filled outdoor
Any auxiliary boiler burners and fuel reservoir, the seal oil system and the transformers that contain more than
systems should have the same level of control oil system, if separate, should 1,893 litres of insulating oil and any other
protection as the main boiler. each be protected by automatic structure or plant. Two-hour-rated fire
sprinkler or foam-water systems barriers can also be used as an
Turbine generator providing a minimum density of alternative to achieve the 15m line of
NFPA 850 recommendations should be 12.2mm/min. sight segregation.
applied for steam turbine generator fire
protection. If a listed fire resistant fluid is used for The outdoor transformer should be
the turbine-generator control oil system, protected by an automatic water spray
All areas beneath the steam turbine that and no ignition sources exist in the system if the 15m line of sight
may be subject to oil flow should be immediate area which could ignite fluid segregation distance cannot be
protected by an automatic sprinkler or in the event of a leak, then sprinkler achieved by the transformer’s location or
foam water system designed to a protection may not be necessary. fire barriers. The water spray system
minimum density of 12.2mm/min. must be designed and installed in
Lubricating and control oil lines above Electrical rooms accordance with NFPA 15, delivering a
the turbine operating floor should also A total gas flooding fire protection minimum density of 10.2mm/min on all
be protected by a sprinkler that provides system should be provided in all exposed surfaces of the transformer.
a minimum density of 12.2mm/min. electrical switch and distribution rooms,

6 Fires in waste to energy power generation plants


Oil-filled transformers holding more Vehicles separated by at least 15m from
than 379 litres of oil and installed Vehicles and mobile plant operators combustible or flammable materials.
indoors should be separated from all should be trained in their operation and
adjacent areas by fire barriers with a hold appropriate certificates of training To prevent the accumulation of
three-hour fire resistance rating. The fire for the vehicle(s) they are allowed to combustible materials on vehicles, a
barrier rating may be reduced to one operate. daily wash-down and cleaning
hour if the transformer is protected by programme should be established. This
an automatic water spray system. The engine bay of vehicles and mobile should also include the engine
plant, both owned or hired in, used for compartment.
Oil-filled transformers should be handling materials should be fitted with
installed within a bunded area fixed fire extinguishing systems of a type Flue gas emissions control equipment
surrounding each transformer. The approved for off-road vehicles. Each
bunded area should be designed so that vehicle should also be provided with a Fabric bag filters
the entire oil content of the transformer, portable fire extinguisher of an Automatic sprinkler protection is the
including the water volume due to appropriate type. The operators should preferred solution in fabric bag filter
operation of the fire protection system, be trained in the correct use of the enclosures. If sprinkler protection is
can be held in the bunded area. Ideally potable fire extinguisher. installed, there should be a method of
the bund should be rock filled so that the draining fire water from the hoppers.
leaking oil permeates below the rock Vehicle and mobile plant refuelling must
and does not present a combustible be undertaken in a designated area that Bag filter fabrics should be made of a
surface. is segregated from combustible and material with an operating temperature
flammable materials. limit exceeding 204°C. The filter
Warehouses and workshops enclosure should be divided into filter
Warehouse and workshops should be Bulk fuel storage must be held in double compartments by non-combustible
fitted with automatic wet pipe sprinkler skinned bunded tanks, segregated from partitions. The filter area provided in
protection systems. other plant and equipment and securely each compartment should be sufficient
locked when not in immediate use. so that a single compartment can be
Cooling towers isolated without limiting the boiler load.
Cooling towers constructed of Where vehicles and mobile plant are
combustible material or having a garaged within a building, it must be If no sprinkler protection is provided,
distribution pack or mist eliminator of constructed from certified non- collectors equipped with other types of
combustible material should be combustible or limited combustible filter bags should be subdivided into
protected by an automatic sprinkler or materials. The building should be kept compartments by partitions with 30–
water spray system that meets the free of combustible materials. If minutes-rated fire resistance. If sprinkler
requirements of NFPA 214: Standard on adjoining any other building, the building protection is provided, the partitions
Water-Cooling Towers. Using non- should have a two-hour-rated barrier, or should be of non-combustible design.
combustable construction materials should be separated by a minimum 15m. Partitions should extend from the
should be considered as an alternative. hopper through the bag area to the clean
Vehicles and mobile plant stored air chamber.
Diesel engines externally should be parked separated
Emergency diesel engine-driven by a minimum of 15m from other mobile Each filter compartment should be fitted
generators or other stationary diesel plant and any combustible materials or with temperature sensors that will
engines located within the main plant have appropriate separation provided by activate an alarm in the control room
buildings should be protected by an a two-hour-rated barrier. when the temperature exceeds 28°C
automatic sprinkler system, water spray, above the normal operating
foam-water or gaseous type fire Before starting work, vehicle and plant temperature.
extinguishing system. Sprinkler and operators should complete a prestart
water spray systems should be designed check on their vehicle in accordance
to a minimum density of 10.2mm/min with the manufacturer’s instructions.
over the fire area.
Vehicle repairs and maintenance should
be completed in a designated area

Fires in waste to energy power generation plants 7


To prevent damage to the filter bags by Outdoor stockpiles Site security
high temperature inlet flue gases, one of Stockpiles of combustible materials
the following should be provided: should be separated from buildings and Site security should be provided to
plant by a minimum distance of 15m restrict access by intruders who intend
−−Where permitted, an automated with a minimum of 5m clear separation to commit theft, arson or malicious
isolation damper and bypass duct from the site perimeter fence line. Where damage. Perimeter fence lines should be
should be installed to divert the inlet 15m separation is not possible, a two- at least 3m high with intruder control
gas stream around the bag filters hour-rated fire barrier is required to fixtures on the top.
during emergencies protect adjacent plant and buildings.
−−A flue gas water tempering spray The site main entrance should be
system in the duct between the boiler Fire rated barriers must extend a controlled at a manned gatehouse and
and the flue gas bag filter. minimum of 2m above the maximum only authorised personnel should be
stockpile height and the stockpile height allowed access to the facility. All visitors
Access doors/hatches and viewing must not exceed 4m. Stockpiles must should be accompanied by an
ports in all compartments should be not exceed 1,000m2 per pile. authorised person at all times.
provided with manual firefighting
equipment. A regime should be established to Intruder detection should be installed on
monitor the core temperature and all buildings and the intruder and fire
Flue gas desulphurisation scrubbers emissions from stockpiles. Stockpiles detection systems should be linked to a
NFPA 850, Section 7.6.5, provides should be regularly turned and damped remote monitoring location.
detailed guidance on the design, down to prevent spontaneous
construction and fire protection of combustion. Allowing longstanding Site security should include a
scrubbers, scrubber buildings and stockpiles to develop should be avoided. permanent security presence with
exhaust ducts. Guidance is also provided intermittent patrols or a remote
for fire protection and fire prevention Smoking, hot-work and open fires monitoring service using CCTV.
during maintenance. This guidance should be prohibited within 15m of the
should be followed for flue gas stockpile and signage should be Housekeeping
desulphurisation equipment installed on provided to this effect.
waste to energy power plants. To avoid the accumulation of
At all times, fire and rescue service combustible materials, dust and debris,
Electrostatic precipitators vehicles should have unobstructed good site housekeeping should be an
Electrostatic precipitators should be access and no portion of the stockpile ongoing process throughout the site.
equipped with temperature sensors in should be more than 45m from an
the inlet and outlet ducts. There should access road. There should be a programme in place
be alarms provided in the control room to regularly clear dust and debris
that indicate abnormal operating At least two public or private fire main accumulations from beneath and on top
temperatures. hydrant points should be provided within of all process equipment, conveyors,
90m of the stockpile perimeter. hoppers, hydraulic packages and ledges
Fuel stock piles Providing remote controlled oscillating at all levels. Mobile plant should also be
monitor nozzles covering the whole checked and cleared of debris
Fires in outdoor fuel stockpiles are a stockpile area should be considered. accumulations, particularly around
frequent cause of damage and loss in tracks, engine compartments and
waste to energy facilities. Due to the Bailed biomass fuels suspension components. Daily, weekly,
nature of the fuel, fires can be deep Covered warehouses for storing baled monthly and annual checklists should be
seated and difficult to extinguish quickly. fuels should be sprinklered in provided to monitor and confirm that the
accordance with NFPA 13. cleaning schedule is being followed.
Spontaneous combustion, smoking,
arson, the delivery of smouldering loads, Smoking, hot work and other sources of Fire incident pre-planning
adjacent hot-work and ignition by glass ignition must be prohibited within the
refracted sunlight are all common warehouse and signage must be The site should develop a fire action
causes of stockpile fires. provided to this effect. incident plan in coordination with the
fire and rescue service. The plan should

8 Fires in waste to energy power generation plants


consider the full range of potential fire −−A suitable portable fire extinguisher Regular thermal imaging inspections
scenarios and the type and level of available at the point of work of motors, bearings, transformers and
response required. −−A fire watchman, trained in firefighting, electrical equipment should be carried
to be stationed at the point of work out to detect possible overheating as a
An on-site incident controller should be −−The work area should be cleared of cause of fires.
designated to manage any fire incidents combustible materials before work
from start to finish. A dedicated radio commences To prevent the accumulation of
communication system or channel −−Fire retardant sheets or blankets combustible materials, equipment
should be allocated so that the incident should be used to prevent sparks should be regularly cleaned and
controller can receive information and and hot materials falling on washed down.
give directions. equipment below
−−Hot work should be carried out at least Electrical installations and portable
Fire and rescue service vehicles should 20m from any combustible materials equipment should be routinely checked
meet at a designated rendezvous point −−Hoses and bottle sets should be to confirm the continued safety of the
and escorted to the incident site. examined and be in good condition equipment, installation or system.
before work begins.
The plan should include the names of −−Flammable gas bottles and torches Storage of flammable liquids
responsible persons, their should be fitted with flash-back and gases
responsibilities and contact phone arrestors Flammable liquids should be stored in
numbers for people and services that −−The work area should be examined fire resistant steel cabinets specifically
may be required during an incident. periodically during the hour designed for the purpose. The volume of
immediately after work is completed stored flammable liquids should be
The fire incident plan document should to ensure there are no smouldering or maintained at the lowest possible level.
be held in the control room and at the incipient fires HSE Guidance Document: HSG 51 The
main gate. It should include drawings storage of flammable liquids in
showing the site layout, locations of key Smoking policy containers provides further information.
equipment and the location of fire Smoking should be banned within any
protection equipment and systems. building in accordance with legal LPG and flammable welding gases
requirements. should be stored and secured in the
A procedure should be established to upright position in locked and well-
immediately notify the facility’s insurers Ideally, there should also be a ban on ventilated cages outside. Full and empty
of any impairment of fire protection or smoking anywhere on site but if this flammable bottles should be kept in
detection systems. cannot be imposed, a limited number of separate cages and all oxygen bottles
designated outdoor smoking shelters must be stored separately. Gas bottle
Operational considerations may be provided which should be sited storage areas should be sited as far
at least 15m from buildings and any away as is reasonably practical from any
The following systems and procedures combustible materials. building or boundary fence. The use and
should be in place for operational plants: storage of acetylene is discouraged and
Smoking within site vehicles and mobile an alternative should be found.
Permit to work system plant should be prohibited.
The site should operate documented Note: Where the fire service is called to
permit to work system including lock- Maintenance and inspection attend a fire and acetylene gas bottles
out-tag-out (LOTO) of electrical and The site should establish a maintenance are involved, current fire service practice
mechanical systems before work is and inspection regime that covers all is to establish a 200m hazard exclusion
permitted on any process plant item. installed plant and equipment. zone around the incident and leave the
Maintenance and inspection should be cylinders involved undisturbed for 24
Control of hot work of a type and frequency recommended hours. All fire-fighting activity in the
The site should operate a permit system by the equipment supplier or designated hazard zone must cease and
for the control of hot work, such as flame manufacturer as a minimum the area must be evacuated.
cutting, welding and grinding. The fire requirement.
prevention requirements for any hot
work should include the following:

Fires in waste to energy power generation plants 9


Waste to energy plants – a summary of risk control measures

The hierarchy for control of the fire risk should be: fire separation, fire prevention, fire detection and fire extinguishing. It is
important that these risk control measures are built into design and management procedures adopted by the power generation
plant. The following table summarises the risk control measures:

Risks Controls to mitigate the risks

Fire separation

_
Design and construction  Design and construct the plant to provide appropriate fire separations, spacing,
compartmentation, fire barriers and fire resistance.
_
 Use construction materials with non-combustible or low combustibility fire ratings
certified by FM, LPCB or UL.

Fire prevention

_
Smouldering loads  Maintain close observation of delivered loads and provide a safe and suitably equipped
place to dump and extinguish the load.

_
Elimination of ignition sources  Prohibit smoking and control spark generation and hot work processes.
_
 Segregate high temperature areas.
_
Provide security provisions to prevent arson.
_
Select plant and equipment to minimise fire risks and limit ignition sources.
_
 Select approved non-combustible or limited combustible lubricating, hydraulic
and insulating oils.

_
Fuel stockpiles Monitor fuel stockpiles regularly to detect overheating or incipient fires.
_
Avoid long standing static stockpiles and turn the pile frequently.
_
 Provide local fire hose stations or monitors to extinguish burning areas before a small
fire gets out of control.

_
Education and training  Provide fire training to all staff in fire prevention, fire extinguishing and
emergency response.

_
Housekeeping Establish a continuous process of removing accumulations of dust and combustible
materials to reduce fire risks.

Fire detection

_
Installation of detection systems  Install approved and appropriate fire, smoke and heat detection systems throughout
the plant.
_
Install manual fire call points and audio-visual alarm systems throughout the plant.
_
Ensure regular patrols by operators and security staff to detect fires.

Fire extinguishing

_
Installation of fire control measures  Develop a major fire incident response plan.
_
 Seek advice and coordinate the major incident response plan with the fire and
rescue service.
_
 Complete a Fire Protection Design Basis Document to asses fire risks before
construction and install appropriate and approved fire control measures.

10 Fires in waste to energy power generation plants


Common terms and definitions

MSW Municipal Solid Waste. Unsorted refuse collected from the kerb-side by local authorities.

RDF Refuse Derived Fuel. Refuse which has been pre-sorted to remove the majority of recyclable and non-
combustible materials. It may be pelletised or mass burnt.

Biomass Biomass includes various types of bulk organic materials such as wood-chip, forestry waste, sugar cane,
chicken litter, straw, nut shells and olive kernels.

Used/old tyres Tyres that may be burnt whole or shredded into tyre chips.

Sewage sludge Effluent from a sewage treatment plant from which the majority of the liquid has been removed.

Mass burn Bulk burning of fuels in a furnace with a moving grate.

Waste to energy The conversion of waste materials into usable electrical energy.

MRF Materials Recycling Facility or Materials Recovery Facility. A processing area where delivered waste is sorted
to remove non-combustible or recyclable materials before mass burning.

References and guidance

BS5306 Part 8: Code of Practice for the Selection and Installation of Portable Fire Extinguishers
BS 5839 Part 1: Fire detection and fire alarm systems for buildings
BSISO14520-1: 2000: Gaseous Fire-Extinguishing Systems
HSG51: The storage of flammable liquids in containers (second edition, published 1998)
NFPA 10: Standard for Portable Fire Extinguishers
NFPA 12: Standard on Carbon Dioxide Extinguishing Systems
NFPA 13: Standard for the installation of Sprinkler systems
NFPA15: Standard for Water Spray Fixed Systems for Fire Protection
NFPA16: Standard for the Installation of Foam-water Sprinkler and Foam-Water Spray Systems
NFPA 20: Standard for the Installation of Stationary Pumps and Fire protection
NFPA 24: Standard for the Installation of Private Fire Services and Their Appurtenances
NFPA 69: Standard for Explosion prevention Systems and ASTM E 1248 Standard Practice for
Shredder Explosion Systems
NFPA 72: National Fire Alarm Code
NFPA 80: Standard for Fire Doors and Fire Windows
NFPA 80A: Recommended Practice for protection of Buildings from Exterior Fire Exposure
NFPA 85: Boiler and Combustion Systems Hazards Code
NFPA 214: Standard on Water-Cooling Towers
NFPA 780: Standard for the installation of Lightning Protection Systems
NFPA 850: Recommended Practice for fire Protection for Electrical Generating Plants and High
Voltage Direct current Converter Stations
NFPA 2001: Standard on Cleaning Agent Fire Extinguishing Systems

Disclaimer: The guidance in this document refers to industry best practice loss
control advice. Adoption of the advice contained within this document does not
imply compliance with industry, statutory or HSBEI guidelines, nor does it
guarantee that related losses will not occur.

HSB-LCE-RGN-010 Rev: 0 Date: 05/12/2014

Fires in waste to energy power generation plants 11


HSB Engineering Insurance Limited
Registered in England and Wales: 02396114,
New London House, 6 London Street,
London EC3R 7LP.
Registered as a branch in Ireland: 906020.
Authorised by the Prudential Regulation Authority
and regulated by the Financial Conduct Authority
and the Prudential Regulation Authority.

www.munichre.com/hsbeil

HSBEI-1368-0717-2

NOT IF, BUT HOW

You might also like