You are on page 1of 12

Safety, Protection, and Modification of the Product *1:


*2:
English, German, French, and Spanish are available for the guide display.
The /LP option can be specified in the combination of Type 2 code (any of “0” or “1”) and 3. How to Install
Operation UT35A, UT32A
(1) In order to protect the system controlled by this product and the product itself,
Type 3 code (any of “0” or “1”.)

Guide Digital Indicating Controller (Panel Mounting Type) and to ensure safe operation, observe the safety precautions described in the
*3:
*4:
The /HA option can be specified only when the Type 1 code is “-0” or “-2.”
When the /CT option is specified, the UT35A does not conform to the safety standards (UL ■ Installation Location
Operation Guide tiona
l operation guide. Use of the instrument in a manner not prescribed herein may and CSA) and CE marking (Products with /CT option are not intended for EEA-market).
Func ment The instrument should be installed in indoor locations meeting the following
compromise the product's functions and the protection features inherent in the
IM 05P01D31-11EN Installation and Wiring Enha
nce
device. We assume no liability for safety, or responsibility for the product's quality, ■ UT32A «Standard Code Model» conditions:
performance or functionality should users fail to observe these instructions when • Instrumented panel
«Standard Code Model» 5th Edition : Mar. 2016 operating the product. Model Suffix code
Option
Description This instrument is designed to be mounted in an instrumented panel. Mount the
code
(2) Installation of protection and/or safety circuits with respect to a lightning instrument in a location where its terminals will not inadvertently be touched.
Digital Indicating Controller (Power supply: 100-240
protector; protective equipment for the system controlled by the product and the UT32A V AC) (provided with retransmission output or 15 V • Well ventilated locations
This operation guide describes installation, wiring, and other tasks required to make the product itself; foolproof or fail-safe design of a process or line using the system DC loop power supply, 2 DIs, and 3 DOs)
Mount the instrument in well ventilated locations to prevent the instrument’s inter-
controller ready for operation. controlled by the product or the product itself; and/or the design and installation -0 Standard type
of other protective and safety circuits are to be appropriately implemented as the nal temperature from rising.
For details of the each function, refer to the electronic manual. Manuals can be -1 Position proportional type
downloaded or viewed at the following URL. customer deems necessary. -2 Heating/cooling type
However, make sure that the terminal portions are not exposed to wind. Exposure
(3) Be sure to use the spare parts approved by YOKOGAWA when replacing parts Type 1:
Dual-loop type (please see the Operation Guide IM to wind may cause the temperature sensor accuracy to deteriorate. To mount mul-
http://www.yokogawa.com/ns/ut/im/ or consumables. Basic -D
05P08D31-11EN.) tiple indicating controllers, see the external dimensions/panel cutout dimensions
control
(4) This product is not designed or manufactured to be used in critical applications -V which follow. If mounting other instruments adjacent to the instrument, comply with
Contents
UT32A Digital Indicating Controller (Entry model)
that directly affect or threaten human lives. Such applications include nuclear -C (please see the Operation Guide IM 05P01F31- these panel cutout dimensions to provide sufficient clearance between the instruments.
power equipment, devices using radioactivity, railway facilities, aviation -R 11EN.)
• Locations with little mechanical vibration
1. Safety Precautions equipment, air navigation facilities, aviation facilities, and medical equipment. 0 None Install the instrument in a location subject to little mechanical vibration.
2. Model and Suffix Codes If so used, it is the user’s responsibility to include in the system additional Type 2:
1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*1)
equipment and devices that ensure personnel safety. Functions • Horizontal location
3. How to Install 2 2 additional DIs and 2 additional DOs
Mount the instrument horizontally and ensure that it is level, with no inclination to
4. Hardware Specifications (5) Modification of the product is strictly prohibited. 0 None
Type 3:
(6) This product is intended to be handled by skilled/trained personnel for electric devices. Open networks
the right or left.
5. How to Connect Wires 3 CC-Link communication (with Modbus master function) (*2)
(7) This product is UL Recognized Component. In order to comply with UL standards,
6. Terminal Wiring Diagrams -1 English (Default. Can be switched to other language by the setting.)
end-products are necessary to be designed by those who have knowledge of the
-2 German (Default. Can be switched to other language by the setting.) Front panel
requirements. Display language (*3) Keep this angle
Introduction
-3 French (Default. Can be switched to other language by the setting.) of controller within 30°
-4 Spanish (Default. Can be switched to other language by the setting.)
0 White (Light gray)
Thank you for purchasing the UT35A, UT32A Digital Indicating Controller. Case color
l Power Supply 1 Black (Light charcoal gray) 30° Rear of
This operation guide describes the basic operations of the UT35A and UT32A. The Ensure that the instrument’s supply voltage matches the voltage Fixed code -00 Always "-00" (for Standard Code Model) controller
guide should be provided to the end user of this product. of the power supply before turning ON the power. /LP 24 V DC loop power supply (*4)
Be sure to read this operation guide before using the product in order to ensure WARNING l Do Not Use in an Explosive Atmosphere
correct operation. Do not operate the instrument in locations with combustible
/HA Heater break alarm (*5) Note
/DC Power supply 24 V AC/DC
For details of each function, refer to the electronic manual. Before using the product, or explosive gases or steam. Operation in such environments If the instrument is moved from a location with low temperature and low humidity
/CT Coating (*6)
refer to the table of Model and Suffix Codes to make sure that the delivered product constitutes an extreme safety hazard. Use of the instrument in /CV Terminal cover to a place with high temperature and high humidity, or if the temperature changes
is consistent with the model and suffix codes you ordered. Also make sure that the environments with high concentrations of corrosive gas (H2S,
following items are included in the package. Option codes
Mount on DIN rail (without the display parts and keys) rapidly, condensation will result. Moreover, in the case of thermocouple inputs,
SOX, etc.) for extended periods of time may cause a failure. (In case of the Standard type, the Position proportion-
l Do Not Remove Internal Unit al type, or the Heating/cooling type, please see the
measurement errors will result. To avoid such a situation, leave the instrument in the
/MDL new environment under ambient conditions for more than 1 hour prior to using it.
• Digital Indicating Controller (the model you ordered)...............................x1 The internal unit should not be removed by anyone other than Operation Guide IM 05P01D81-11EN. In case of the
Dual-loop type, please see the Operation Guide IM
• Set of Brackets.........................................................................................x1 YOKOGAWA's service personnel. There are dangerous high voltage
05P08D81-11EN.)
• Unit Label (L4502VZ)...............................................................................x1 parts inside. Additionally, do not replace the fuse by yourself. Do not mount the instrument in the following locations:
Non-isolated remote input (please see the Operation
• Tag Label (L4502VE)...............................................................................x1 l Damage to the Protective Construction /RSP
Guide IM 05P01D31-81EN.) • Outdoors
(Only when ordered.) Operation of the instrument in a manner not specified in the
operation guide may damage its protective construction. *1: When the /LP option is specified, the RS-485 communication of the Type 2 code “1” is 2-wire system. • Locations subject to direct sunlight or close to a heater
• Operation Guide (this document).............................................................x6 (A3 size) Install the instrument in a location with stable temperatures that remain close to an
*2: The type 3 code “3” can be specified only when the Type 1 code is “-0” and the Type 2 code is “0.”
(Installation and Wiring, Initial Settings, Operations, and Parameters) *3: English, German, French, and Spanish are available for the guide display. average temperature of 23°C. Do not mount it in locations subject to direct sunlight
*4: The /LP option can be specified in the combination of Type 1 code (any of “-0” or “-1”), Type
or close to a heater. Doing so adversely affects the instrument.
l Target Readers 2 code (any of “0” or “1”) and Type 3 code “0.”
*5: The /HA option can be specified in the combination of Type1 code “-0” or “-2.” and Type 3 code “0.” • Locations with substantial amounts of oily fumes, steam, moisture, dust, or
This guide is intended for the following personnel; This instrument is an EMC class A product. In a domestic environ- *6: When the /CT option is specified, the UT32A does not conform to the safety standards (UL corrosive gases
• Engineers responsible for installation, wiring, and maintenance of the equipment. ment this product may cause radio interference in which case the and CSA) and CE marking (Products with /CT option are not intended for EEA-market). The presence of oily fumes, steam, moisture, dust, or corrosive gases adversely
• Personnel responsible for normal daily operation of the equipment. user needs to take adequate measures.
affects the instrument. Do not mount the instrument in locations subject to any of
CAUTION ■ Accessories (sold separately) these substances.
1. Safety Precautions The following is an accessory sold separately. • Areas near electromagnetic field generating sources
Do not place magnets or tools that generate magnetism near the instrument. If the
The following symbol is used on the instrument. It indicates the possibility of injury
to the user or damage to the instrument, and signifies that the user must refer to the
2. Model and Suffix Codes • LL50A Parameter Setting Software instrument is used in locations close to a strong electromagnetic field generating
Model Suffix code Description source, the magnetic field may cause measurement errors.
operation guide or user’s manual for special instructions. The same symbol is used in
the operation guide and user’s manual on pages that the user needs to refer to, together
LL50A -00 Parameter Setting Software • Locations where the display is difficult to see
with the term “WARNING” or “CAUTION.” ■ UT35A «Standard Code Model» • External Precision Resistor
The instrument uses an LCD for the display unit, and this can be difficult to see
Option from extremely oblique angles. Mount the instrument in a location where it can be
Model Suffix code Description Model Suffix code Description
code seen as much as possible from the front.
Digital Indicating Controller (Power supply: 100-240 V X010 See the General Specifications (*) Resistance Module
Calls attention to actions or conditions that could cause serious • Areas close to flammable articles
UT35A AC) (provided with retransmission output or 15 V DC
or fatal injury to the user, and indicates precautions that should be loop power supply, 2 DIs, and 3 DOs) *: Necessary to input the current signal to the voltage input terminal. Absolutely do not place the instrument directly on flam-
taken to prevent such occurrences. Type 1: -0 Standard type • Terminal Cover mable surfaces. If such a circumstance is unavoidable 150 mm
WARNING Basic -1 Position proportional type For UT35A: Model UTAP001; For UT32A: Model UTAP002 and the instrument must be placed close to a flammable
control -2 Heating/cooling type • Manuals item, provide a shield for it made of 1.43 mm thick plated 150 mm 150 mm
0 None Note: Manuals can be downloaded from a website. URL: http://www.yokogawa.com/ns/ut/im/ steel or 1.6 mm thick unplated steel with a space of at 150 mm
Type 2: • Brackets
Calls attention to actions or conditions that could cause injury to 1 2 additional DIs, 2 additional DOs least 150 mm between it and the instrument on the top,
Functions
the user or damage to the instrument or property and indicates pre- 2 5 additional DIs, 5 additional DOs Part number: L4502TP (2 pcs for upper and lower sides) bottom, and sides.
cautions that should be taken to prevent such occurrences. 0 None • Areas subject to being splashed with water
CAUTION 1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)

AC Type 3: Open
networks
2 Ethernet communication (with serial gateway function)
3 CC-Link communication (with Modbus master function) Be sure to turn OFF the power supply to the controller before in-
AC/DC 4 PROFIBUS-DP communication (with Modbus master function) stalling it on the panel to avoid an electric shock.
5 DeviceNet communication (with Modbus master function)
WARNING
The equipment wholly protected by double insulation or reinforced insulation. -1 English (Default. Can be switched to other language by the setting.)
-2 German (Default. Can be switched to other language by the setting.)
Display language (*1)
-3 French (Default. Can be switched to other language by the setting.)
Functional grounding terminals -4 Spanish (Default. Can be switched to other language by the setting.)
(Do not use this terminal as a protective grounding terminal). 0 White (Light gray) YOKOGAWA ELECTRIC CORPORATION
Case color
1 Black (Light charcoal gray) Network Solutions Business Division
Note Fixed code -00 Always "-00" (for Standard Code Model) 2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPAN
Identifies important information required to operate the instrument. /LP 24 V DC loop power supply (*2) YOKOGAWA CORPORATION OF AMERICA
/HA Heater break alarm (*3) Head office and for product sales
/DC Power supply 24 V AC/DC 2 Dart Road, Newnan, Georgia 30265, USA
■ Warning and Disclaimer /CT Coating (*4) YOKOGAWA EUROPE B.V.
Option codes /CV Terminal cover Headquarters
(1) YOKOGAWA makes no warranties regarding the product except those stated in Mount on DIN rail (without the display parts and keys) Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
the WARRANTY that is provided separately. /MDL (please see the Operation Guide IM 05P01D81-
(2) The product is provided on an "as is" basis. YOKOGAWA assumes no liability to 11EN.) www.yokogawa.com/ns
any person or entity for any loss or damage, direct or indirect, arising from the /RSP
Non-isolated remote input (please see the Operation
use of the product or from any unpredictable defect of the product. Guide IM 05P01D31-81EN.) All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation
IM 05P01D31-11EN page 1/12
■ Mounting the Instrument Main Unit 4. Hardware Specifications • Allowable signal source resistance: Note: The control output should always be used with a load of 10 mA or more.
The alarm output should always be used with a load of 1 mA or more.
TC or mV input: 250 Ω or less
Provide an instrumented panel steel sheet of 1 to 10 mm thickness. Effects of signal source resistance: 0.1 µV/Ω or less
After opening the mounting hole on the panel, follow the procedures below to install DC voltage input: 2 kΩ or less
■ Transistor Contact Output Specifications
the controller: Effects of signal source resistance: About 0.01%/100 Ω • Number of outputs: See the table of Model and Suffix Codes.
This instrument is for Measurement Category No.1.
1) Insert the controller into the opening from the front of the panel so that the • Allowable wiring resistance: • Output type: Open collector (SINK current)
Do not use it for measurements in locations falling under Measure-
terminal board on the rear is at the far side. RTD input: Max. 150 Ω/wire (The conductor resistance between the three wires • Output contact rating: Max. 24 V DC, 50 mA
ment Categories No.2, No.3, and No.4.
2) Set the brackets in place on the top and bottom of the controller as shown in the figure WARNING shall be equal.) • Output time resolution: Min. 200 ms
below, then tighten the screws of the brackets. Take care not to overtighten them. Wiring resistance effect: ±0.1ºC/10 Ω • Use: Alarm output, FAIL output, etc.
• Allowable input voltage/current:
Panel Bracket Internal Wiring TC, mV, mA and RTD input: ±10 V DC ■ Position Proportional Output Specifications
(top mounting hardware) II
V input: ±20 V DC
III T
Entrance IV O( I )
mA input: ±40 mA • Position signal input:
Cable
Outlet • Noise rejection ratio: Slide resistance: 100 Ω to 2.5 kΩ of total resistance
Direction to insert the
controller Normal mode: 40 dB or more (at 50/60 Hz) 100% side and slide line: with disconnection detection
Terminal board
Insert the controller Common mode: 120 dB or more (at 50/60 Hz) 0% side: without disconnection detection
into the opening at IEC/EN/CSA/UL
Category
61010-1
EN 61010-2-030 Remarks
For 100-240 V AC, the power frequency can be set manually. Automatic Current input: 4 to 20 mA (with disconnection detection)
the front of the panel.
Measurement For measurements performed on circuits not direct- detection is also available. • Sampling period: 50 ms
Insert a screwdriver into the No.1 O (Other)
Category I ly connected to MAINS.
For 24 V AC/DC, the power frequency can be set manually. • Measurement resolution: 0.1% of input span
brackets to tighten the screws.
No.2
Measurement Measurement For measurements performed on circuits directly • Reference junction compensation error: • Position proportional relay output:
Category II Category II connected to the low-voltage installation. UT35A: contact point 1a; 2 points, 250 V AC, 3 A or 30 V DC, 3 A (resistance load)
Appropriate ±1.0ºC (15 to 35ºC), ±1.5ºC (-10 to 15ºC and 35 to 50ºC)
Measurement Measurement For measurements performed in the building instal- UT32A: contact point 1a; 2 points, 240 V AC, 3 A or 30 V DC, 3 A (resistance load)
Bracket tightening torque: No.3
Category III Category III lation. • Applicable standards: JIS/IEC/DIN (ITS-90) for TC and RTD
(bottom mounting hardware) 0.25 N•m Note: This should always be used with a load of 10 mA or more.
Measurement Measurement For measurements performed at the source of the
No.4
Category IV Category IV low-voltage installation. ■ Contact Input Specifications
■ Heater Break Alarm Specifications
■ Input Specifications • Number of inputs: See the table of Model and Suffix Codes.
• Number of inputs: 2
• Tighten the screws with appropriate tightening torque within 0.25 N•m. • Input type: No-voltage contact input or transistor contact input
• Number of outputs: 2 (transistor contact output)
Otherwise it may cause the case deformation or the bracket damage. • Input contact rating: 12 V DC, 10 mA or more
●Universal Input (Equipped as standard) • Use: Measures the heater current using an external current transformer (CT) and
• Make sure that foreign materials do not enter the inside of the Use a contact with a minimum on-current of 1 mA or less.
CAUTION instrument through the case’s slit holes. • Number of inputs: 1 generates a heater break alarm when the measured value is less than the break
• ON/OFF detection:
• Input type, instrument range, and measurement accuracy: See the table below, detection value.
No-voltage contact input:
Instrument Range • Current transformer input resistance: About 9.4 Ω
Input Type Accuracy
Contact resistance of 1 kΩ or less is determined as “ON” and contact
• Current transformer input range: 0.0 to 0.1 Arms (0.12 Arms or more cannot be applied.)
■ External Dimensions and Panel Cutout Dimensions ºC
-270.0 to 1370.0ºC
ºF
-450.0 to 2500.0ºF ±0.1% of instrument range ±1 digit for
resistance of 50 kΩ or more as “OFF.”
• Heater current setting range: OFF, 0.1 to 300.0 Arms
Transistor contact input:
K -270.0 to 1000.0ºC -450.0 to 2300.0ºF 0°C or more Heater current measured value display range: 0.0 to 360.0 Arms
UT35A 11 Unit: mm (approx. inch) ±0.2% of instrument range ±1 digit for Input voltage of 2 V or less is determined as “ON” and leakage current must
(0.43) -200.0 to 500.0ºC -200.0 to 1000.0ºF Note: The CT ratio can be set. CT ratio setting range: 1 to 3300
96 (3.78) 65 (2.56) Bracket less than 0°C not exceed 100 µA when “OFF.” • Recommended CT: CT from U.R.D., Ltd.
Terminal cover J -200.0 to 1200.0ºC -300.0 to 2300.0ºF ±2% of instrument range ±1 digit for
20 (0.79) • Minimum status detection hold time: Control period +50 ms CTL-6-S-H: CT ratio 800, measurable current range: 0.1 to 80.0 Arms
-270.0 to 400.0ºC -450.0 to 750.0ºF less than -200.0°C of thermocouple K
T ±1% of instrument range ±1 digit for • Use: SP switch, operation mode switch, and event input CTL-12L-30: CT ratio 3000, measurable current range: 0.1 to 180.0 Arms
0.0 to 400.0ºC -200.0 to 750.0ºF less than -200.0°C of thermocouple T
• Heater current measurement period: 200 ms
±0.15% of instrument range ±1 digit ■ Analog Output Specifications
105.2 (4.14)

• Heater current measurement accuracy: ±5% of current transformer input range


91.6 (3.61)
94.6 (3.72)

for 400°C or more


96 (3.78)

B 0.0 to 1800.0ºC 32 to 3300ºF


±5% of instrument range ±1 digit for • Number of outputs: span ± 1digit (CT error is not included.)
less than 400°C
Control output: 1 • Heater current detection resolution: Within 1/250 of current transformer input range span
S 0.0 to 1700.0ºC 32 to 3100ºF
±0.15% of instrument range ±1 digit Cooling-side control output of Heating/cooling type (Retransmission output • Break detection On-time: Min. 0.2 second (for time proportional output)
R 0.0 to 1700.0ºC 32 to 3100ºF
±0.1% of instrument range ±1 digit terminal): 1
Bracket Thermo- N -200.0 to 1300.0ºC -300.0 to 2400.0ºF ±0.25% of instrument range ±1 digit • Output type: Current output or voltage pulse output ■ 24 V DC Loop Power Supply Specifications
couple for less than 0°C
1 to 10 mm (0.04 to 0.39 inch) (panel thickness) • Current output: 4 to 20 mA DC or 0 to 20 mA DC/load resistance of 600 Ω or less
E -270.0 to 1000.0ºC -450.0 to 1800.0ºF ±0.1% of instrument range ±1 digit for • Use: Power is supplied to a 2-wire transmitter.
• General mounting • Side-by-side close mounting • Current output accuracy: ±0.1% of span (±5% of span for 1 mA or less)
+0.8 L -200.0 to 900.0ºC -300.0 to 1600.0ºF 0°C or more • Power supply: 21.6 to 28.0 V DC
117 (4.61) min. [(N-1)×96+92] 0 ±0.2% of instrument range ±1 digit for The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH,
-200.0 to 400.0ºC -300.0 to 750.0ºF
less than 0°C • Rated current: 4 to 20 mA DC
([(N-1)×3.78+3.62] +0.03 ) and power frequency at 50/60 Hz.
0 U ±1.5% of instrument range ±1 digit for • Maximum supply current: About 30 mA (with short-circuit current limiting circuit.)
0.0 to 400.0ºC -200.0 to 1000.0ºF
less than -200.0°C of thermocouple E. • Voltage pulse output:
+0.8 Use: Time proportional output
92 0
+0.03 W 0.0 to 2300.0ºC 32 to 4200ºF
±0.2% of instrument range ±1 digit
(Note 2) On-voltage: 12 V or more/load resistance of 600 Ω or more
■ Safety and EMC Standards
(3.62 0 )
Platinel 2 0.0 to 1390.0ºC 32.0 to 2500.0ºF ±0.1% of instrument range ±1 digit Off-voltage: 0.1 V DC or less • Safety:
(53) (2.09) 145 (5.71)
min. ±0.5% of instrument range ±1 digit for Time resolution: 10 ms or 0.1% of output, whichever is larger Compliant with IEC/EN 61010-1 (CE), IEC/EN 61010-2-201 (CE), IEC/EN 61010-
“N” stands for the number of controllers to be 800°C or more 2-030 (CE), approved by CAN/CSA C22.2 No. 61010-1 (CSA), approved by UL
+0.8 PR20-40 0.0 to 1900.0ºC 32 to 3400ºF
92 0 installed. Accuracy is not guaranteed for less
+0.03
(3.62 0 ) However, the measured value applies if N≥5. than 800°C. ■ Retransmission Output Specifications 61010-1.
Installation category: II
W97Re3- 0.0 to 2000.0ºC 32 to 3600ºF ±0.2% of instrument range ±1 digit
+0.8
Normal tolerance: W75Re25 • Number of outputs: Retransmission output; 1, shared with 15 V DC loop power Pollution degree: 2
92 0 (25) ±(value of JIS B 0401-1998 tolerance class IT18)/2 Measurement category: I (CAT I) (UL, CSA)
±0.1% of instrument range ±1 digit supply or Cooling-side control output.
+0.03 (0.98) -200.0 to 500.0ºC -300.0 to 1000.0ºF
(3.62 0 ) JPt100 (Note 1) O (Other) (CE)
• Current output: 4 to 20 mA DC or 0 to 20 mA DC/ load resistance of 600 Ω or less
-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit Rated measurement input voltage: Max. 10 V DC
RTD
-200.0 to 850.0ºC -300.0 to 1560.0ºF ±0.1% of instrument range ±1 digit
• Current output accuracy (conversion accuracy from PV display on the set scale): Rated transient overvoltage: 1500 V (*)
UT32A Unit: mm (approx. inch) ±0.1% of span (±5% of span for 1 mA or less) * This is a reference safety standard value for measurement category I of CSA/UL 61010-
48 (1.89) Pt100 -200.0 to 500.0ºC -300.0 to 1000.0ºF (Note 1)
11 (0.43) 65 (2.56) Bracket Terminal cover The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, 1, and for measurement category O of IEC/EN 61010-2-030. This value is not necessarily a
-150.00 to 150.00ºC -200.0 to 300.0ºF ±0.1% of instrument range ±1 digit
20 (0.79) and power frequency at 50/60 Hz. guarantee of instrument performance.
0.400 to 2.000 V
This is not conversion accuracy through input and output but the performance of • EMC standards:
Standard signal 1.000 to 5.000 V
transmission output itself. Compliant with CE marking
4.00 to 20.00 mA
EN 61326-1 Class A, Table 2 (For use in industrial locations),
0.000 to 2.000 V
■ 15 V DC Loop Power Supply Specifications
105.2 (4.14)

EN 61326-2-3
91.6 (3.61)
94.6 (3.72)
96 (3.78)

±0.1% of instrument range ±1 digit


0.00 to 10.00 V * The instrument continues to operate at a measurement accuracy of within ±20% of the
DC voltage/current 0.00 to 20.00 mA
(Shared with retransmission output or Cooling-side control output.) range during testing.
-10.00 to 20.00 mV • Power supply: 14.5 to 18.0 V DC EN 55011 Class A, Group 1
0.0 to 100.0 mV • Maximum supply current: About 21 mA (with short-circuit current limiting circuit) EN 61000-3-2 Class A
The accuracy is that in the standard operating conditions: 23±2°C, 55±10%RH, and power
EN 61000-3-3
Bracket frequency at 50/60 Hz. ■ Step Response Time Specifications EMC Regulatory Arrangement in Australia and New Zealand (for all model includ-
1 to 10 mm (0.04 to 0.39 inch) (panel thickness) Note 1: ±0.3°C ±1 digit in the range between 0 and 100°C, ±0.5°C ±1 digit in the range ing LL50A)
between -100 and 200°C. Within 1 s (63% of analog output response time when a step change of 10 to 90% of EN 55011 Class A, Group 1
• General mounting • Side-by-side close mounting
+0.6 Note 2: W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988 input span is applied) • KC marking:
70 (2.76) [(N-1)×48+45] 0
Electromagnetic wave interference prevention standard, electromagnetic wave
min.
([(N-1)×1.89+1.77] 0
+0.02
) • Input sampling (control) period: 200 ms ■ Relay Contact Output Specifications protection standard compliance
• Burnout detection:
92 +0.8
0 Functions at TC, RTD, and standard signal. • Contact type and number of outputs: ■ Construction, Installation, and Wiring
(3.62+0.03 Upscale, downscale, and off can be specified. Control output: contact point 1c; 1 point
0 ) • Dust-proof and drip-proof: IP66 (for front panel) (Not available for side-by-side
145 (5.71) For standard signal, burnout is determined to have occurred if it is 0.1 V or 0.4 Heating/cooling type: contact point 1a; 2 points for both heating and cooling sides
(53) (2.09) min. mA or less. Alarm output: contact point 1a; 3 points (common is independent) close mounting.)
“N” stands for the number of controllers to be • Input bias current: 0.05 µA (for TC or RTD) • Contact rating: • Material: Polycarbonate (Flame retardancy: UL94V-0)
92 +0.8
0 installed. • Measured current (RTD): About 0.16 mA Contact point 1c (control output): 250 V AC, 3 A or 30 V DC, 3A (resistance load) • Case color: White (Light gray) or Black (Light charcoal gray)
(3.62+0.03
0 ) However, the measured value applies if N≥5. • Input resistance: Contact point 1a (control output): 240 V AC, 3A or 30 V DC, 3A (resistance load) • Weight: 0.5 kg or less
Normal tolerance: TC or mV input: 1 MΩ or more Contact point 1a (alarm output): 240 V AC, 1A or 30 V DC, 1 A (resistance load) • External dimensions (mm):
+0.6
45 0 (25) ±(value of JIS B 0401-1998 tolerance class IT18)/2 V input: About 1 MΩ • Use: Time proportional output, alarm output, FAIL output, etc. UT35A: 96 (W) × 96 (H) × 65 (depth from the panel face)
+0.02
(1.77 0 )
(0.98) mA input: About 250 Ω • Time resolution of control output: 10 ms or 0.1% of output, whichever is larger UT32A: 48 (W) × 96 (H) × 65 (depth from the panel face)
(Depth except the projection on the rear panel)
IM 05P01D31-11EN page 2/12
• Installation: Direct panel mounting; mounting bracket, one each for upper and
lower mounting
5. How to Connect Wires ● Cable Specifications and Recommended Cables DC Relay Wiring
Purpose Name and Manufacturer
• Panel cutout dimensions (mm): UT35A, UT32A
Power supply, relay contact outputs 600 V Grade heat-resistant PVC insulated wires, JIS C
UT35A: 92+0.8/0 (W) × 92+0.8/0 (H) External DC power supply
• Wiring work must be carried out by a person with basic electrical 3317(HIV), 0.9 to 2.0 mm2 Relay
UT32A: 45+0.6/0 (W) × 92+0.8/0 (H) knowledge and practical experience. Thermocouple Shielded compensating lead wires, JIS C 1610
• Mounting attitude: Up to 30 degrees above the horizontal. No downward titling allowed. For thermocouple input (PV input and remote input with direct
• Be sure to turn OFF the power supply to the controller before R
• Wiring: M3 screw terminal with square washer (for signal wiring and power wiring) WARNING wiring to avoid an electric shock. Use a tester or similar device to
input), shielded compensating lead wire of cross-sectional area
less than or equal to 0.75 mm2 is recommended. If the cross-
ensure that no power is being supplied to a cable to be connected. sectional area is wide, the reference junction compensation
Diode
■ Power Supply Specifications and Isolation • For the wiring cable, the temperature rating is 75 °C or more. error may be large.
(Mount it directly
RTD Shielded wires (three/four conductors), UL2482 (Hitachi Cable)
• As a safety measure, always install a circuit breaker (an IEC UT’s contact Relay
• Power supply: Other signals (other than contact input/output) Shielded wires to the relay coil
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily (Use one with a relay coil rating terminal (socket).)
Rated voltage: 100-240 V AC (+10%/-15%), 50/60 Hz Other signals (contact input/output) Unshielded wires
accessible location near the instrument. Moreover, provide less than the UT’s contact rating.)
24 V AC/DC (+10%/-15%) (for /DC option) RS-485 communication Shielded wires
indication that the switch is a device for turning off the power to
• Power consumption: UT35A: 18 VA (DC:9 VA, AC: 14 VA if /DC option is specified) the instrument. Ethernet communication 100 BASE-TX (CAT-5)/10 BASE-T
UT32A: 15 VA (DC:7 VA, AC: 11 VA if /DC option is specified) • Install the power cable keeping a distance of more than 1 cm PROFIBUS-DP communication Dedicated cable for PROFIBUS-DP (Shielded two-wires) AC Relay Wiring
• Data backup: Nonvolatile memory from other signal wires. DeviceNet communication Dedicated cable for DeviceNet (Shielded five-wires)
• Power holdup time: 20 ms (for 100 V AC drive) CC-Link communication Dedicated cable for CC-Link (Shielded three-wires) External AC power supply
• The power cable is required to meet the IEC standards concerned or UT35A, UT32A
• Withstanding voltage the requirements of the area in which the instrument is being installed. PROFIBUS-DP/CC-Link Connector (wiring side) (Part number: A1987JT)
Between primary terminals and secondary terminals: 2300 V AC for 1 minute (UL, CSA) • Wiring should be installed to conform to NEC (National Electrical DeviceNet Connector (wiring side) (Part number: L4502BW)
Between primary terminals and secondary terminals: 3000 V AC for 1 minute (CE) Code: ANSI/NFPA-70) or the wiring construction standards in Recommended tightening torque: 0.5 to 0.6 N·m
Between primary terminals: 1500 V AC for 1 minute countries or regions where wiring will be installed. R
Between secondary terminals: 500 V AC for 1 minute • Since the insulation provided to each relay output terminal is
(Primary terminals: Power* and relay output terminals; Secondary terminals: Functional insulation, provide Reinforced insulation to the
Analog I/O signal terminals, contact input terminals, communication terminals external of the device as necessary. (Refer to the drawing below.)
UT’s contact Relay CR filter
and functional grounding terminals.)
This product (Use one with a relay coil (Mount it directly
*: Power terminals for 24V AC/DC models are the secondary terminals. This product
A safety A safety rating less than the UT’s to the relay coil
• Insulation resistance: Between power supply terminals and a grounding terminal A safety
voltage circuit voltage circuit voltage circuit contact rating.) terminal (socket).)
20 MΩ or more at 500 V DC
Functional
• Isolation specifications Functional Reinforced insulation
insulation insulation
PV (universal ) input terminals A hazardous A hazardous Transistor Output Wiring
A safety
voltage circuit voltage circuit voltage circuit
Control, retransmission (analog) output terminals UT
(not isolated between the analog output terminals) Reinforced insulation DO
Valve position (feedback) input terminals 6. Terminal Wiring Diagrams Load
Control relay (contact point c/contact point a x 2) output terminals This product COM
A hazardous A hazardous + –
Alarm-1 relay (contact point a) output terminals Internal Power voltage circuit voltage circuit • Do not use an unassigned terminal as the relay terminal. power

Alarm-2 relay (contact point a) output terminals circuits supply Functional Do not use a 100-240 V AC power supply for the 24 V AC/DC
insulation Reinforced insulation model; otherwise, the instrument will malfunction.
Alarm-3 relay (contact point a) output terminals A hazardous A hazardous CAUTION
voltage circuit voltage circuit
Position proportional relay output terminals

Reinforced insulation
■ UT35A
Contact input terminals (all)
RS-485 communication terminals (2 ports)
(Equipped
Control output OUT PV input PV as standard) Retransmission output RET (Equipped as standard)
24 V DC loop power supply terminals (Suffix code: Type1=-0)
Relay contact output Factory default: PV input TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
• When connecting two or more crimp-on terminal lugs to the Terminal wiring differs in Heating/cooling type is undefined. power supply when not used for
Contact output (transistor) terminals 101
Default: PV
retransmission output.
single terminal block, bend the crimp-on terminal lugs before NC
control and Position proportional control.
+ 202
A 201 retransmission
+ 205 + 205
Refer to the terminals of Position
Ethernet communication terminal tightening the screw. NO 102 proportional control output and
b 202 4-20 mA DC or
0-20 mA DC
14.5-18.0 V DC
(Max. 21 mA DC)

PROFIBUS-DP/DeviceNet/CC-Link communication terminals


CAUTION • Note that the wiring of two or more crimp-on terminal lugs to the Heating/cooling control output below.
- 203 - 206 - 206
COM 103 B 203 Load resistance 600 Ω or less
single high-voltage terminal of the power supply and relay, etc. Factory default: Control output is relay. Default: 4-20 mA DC
Current transformer input terminals does not comply with the safety standard. Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
30 V DC, 3 A (resistance load)
Cooling-side control output RET/OUT2
The circuits divided by lines are insulated mutually. - 203 + 202 Current/voltage pulse output
(Suffix code: Type 1=-2)
Can not be used for retransmission output or
• Provide electricity from a single-phase power supply. If the Heating/cooling control output + 204 - 203
+ 205 15 V DC loop power supply when
■ Environmental Conditions power is noisy, install an isolation transformer on the primary Heating/cooling relay contact output (Suffix code: Type 1=-2)
0-20 mA DC,
4-20 mA DC,
current/voltage pulse output is used.
Can be used for retransmission output or 15 V
Voltage pulse (12V)
side, and use a line filter on the secondary side. When measures OUT2 Cooling NO
-side 101 E4-terminal area E1-terminal area - 206 DC loop power supply when control output is
Normal Operating Conditions: CAUTION against noise are taken, do not install the primary and secondary Heating NO
101 501 401 301 201 not used.
Current output range can be changed.
OUT -side 102 -112 -512 -412 -306 -212
• Ambient temperature: -10 to 50°C (side-by-side mounting: -10 to 40 °C) power cables close to each other.
101 501 401 301 201
• If there is a risk of external lightning surges, use a lightning COM 103
If the CC-Link option is specified, 0 to 50 °C for UT35A; 0 to 40 °C for UT32A.
arrester etc. 102 502 302 202
(side-by-side mounting: 0 to 40 °C for UT35A and UT32A with CC-Link option) Contact rating: 240 V AC, 3 A
30 V DC, 3 A (resistance load) Control output OUT (Suffix code: Type1=-0, -1 or -2)
• Ambient humidity: 20 to 90% RH (no condensation allowed) • For TC input, use shielded compensating lead wires for wiring. 103 503 303 203
Current/voltage pulse output Retransmission output 15 V DC loop power supply
• Magnetic field: 400 A/m or less For RTD input, use shielded wires that have low conductor 104 504 304 204
Default: Undefined
Wiring direction
• Continuous vibration at 5 to 9 Hz: Half amplitude of 1.5 mm or less, 1oct/min for 90 resistance and cause no significant differences in resistance 105 505 305 205 + 207
0-20 mA DC, + 207 + 207
minutes each in the three axis directions between the three wires. 106 506 306 206
4-20 mA DC, 0-20 mA DC,
4-20 mA DC
14.5-18.0 V DC
(Max. 21 mA DC)
Voltage pulse (12 V)
Continuous vibration at 9 to 150 Hz: 4.9 m/s2 or less, 1oct/min for 90 minutes each • Since the control output relay has a life span (resistance load of - 208 - 208 - 208
107 507 407 207
in the three axis directions 100,000 times), use the auxiliary relay to perform ON/OFF control. Default: 4-20 mA DC
108 508 408 208
• Short-period vibration: 14.7 m/s2, 15 seconds or less • The use of inductance (L) loads such as auxiliary relays, motors (Equipped Can be used for retransmission output or 15 V DC loop power supply when
and solenoid valves causes malfunction or relay failure; always Contact output ALM as standard) 109 509 409 current/voltage pulse output is not used for control output.
• Shock: 98 m/s2 or less, 11 ms Current output range can be changed.
insert a CR filter for use with alternating current or a diode for External contact output (relay) 110 510 410 210 In Position proportional type, can be used for retransmission output or 15 V
• Altitude: 2000 m or less above sea level DC loop power supply.
use with direct current, as a spark-removal surge suppression Alarm-3 output
104
UT
111 511 411 211
• Warm-up time: 30 minutes or more after the power is turned on (PV high limit)
circuit, into the line in parallel with the load. AL3
112 512 412 212
• Startup time: Within 10 seconds • After completing the wiring, the terminal cover is recommended
Common 105 Contact input DI (Equipped as standard)
*: The LCD (a liquid crystal display) is used for a display portion of this product. Alarm-2 output
to use for the instrument. ( PV low limit)
106 External contact input
The LCD has a characteristic that the display action becomes late at the low
temperature. However, the control function is not affected.
AL2 E3-terminal area No-voltage
contact UT Transistor UT
+5V
Common 107 contact DI2
STOP when DI2=ON 210 DI2 210
Transportation and Storage Conditions: ● Recommended Crimp-on Terminal Lugs
Alarm-1 output
(PV high limit) 108 RUN when DI2=OFF
DI1
+5V
AL1 AUTO when DI1=ON 211 DI1 211
• Temperature: -25 to 70ºC Common 109 MAN when DI1=OFF
COM
• Temperature change rate: 20ºC/h or less (ød ) Relay contact rating: 240 V AC, 1 A
Position proportional control output VALV Common
212 COM 212
• Humidity: 5 to 95% RH (no condensation allowed) 30 V DC, 1 A (resistance load) Relay contact output Feedback input (Suffix code: Type1=-1) Contact rating: 12 V DC, 10 mA or more
HIGH 100% Function can be assigned to the terminals with no function.
Effects of Operating Conditions (A) 5.5 3.3 (direct) 507 510

• Effect of ambient temperature: Power supply LOW


(reverse) 508 511

Voltage or TC input: ±1 µV/ºC or ±0.01% of F.S./ºC, whichever is larger (F) 100-240 V AC power supply 24 V AC/DC power supply 509 Heater break alarm HBA (Option code /HA)
0% 512
COM

Current input: ±0.01% of F.S./ºC N


110
N
- 110 Contact rating: 250 V AC, 3A Resistance: 100 Ω to 2.5 kΩ External contact output (transistor) Heater current detection input
RTD input: ±0.05ºC/ºC (ambient temperature) or less Recommended tightening torque: 0.6 N·m L L
30 V DC, 3 A
(resistance load) Feedback input
UT
510
111 + 111 Heater break alarm-1 HAL1 507
Analog output: ±0.02% of F.S./ºC or less Applicable wire size: Power supply wiring 1.25 mm2 or more Current (mA)
output CT1
+ 510 511
• Effect of power supply voltage fluctuation Applicable terminal lug Applicable wire size mm2 (AWG#) (φ d) (A) (F)
112 112 input Heater break alarm-2
output
HAL2 508 CT2
Analog input: ±0.05% of F.S. or less 511 512
M3 0.25 to 1.65 (22 to 16) 3.3 5.5 4.2 Allowable range: (24 V AC/DC power supply: Option code /DC) Common COM 509 COM
100-240VAC (+10%/-15%)
Analog output: ±0.05% of F.S. or less (free voltage) - 512
50/60 Hz shared Transistor contact rating: 24 V DC, 50 mA
(Each within rated voltage range) When feedback input is current
IM 05P01D31-11EN page 3/12
■ UT35A (Continued from page 3) ■ UT32A
Control output OUT PV input PV (Equipped
as standard) Retransmission output RET (Equipped as standard)
E4-terminal area E1-terminal area 301-306 E1-Terminal Area 501-506 E4-Terminal Area Relay contact output
(Suffix code: Type1=-0) Factory default:
PV input type is
TC input RTD input Retransmission output 15 V DC loop power supply Can be used for 15 V DC loop
Terminal wiring differs in Heating/cooling Default:
power supply when not used for
NC 101 control and Position proportional control. undefined. A 201 PV retransmission retransmission output.
Refer to the terminals of Position + 202 + 205 + 205
101 501 401 301 201 Contact input 4-20 mA DC or 14.5-18.0 V DC
DI (Suffix code: Type 2=2) Contact output DO (Suffix code: Type 2=2) NO 102 proportional control output and
b 202
0-20 mA DC (Max. 21 mA DC)
-112 -512 -412 -306 -212 Heating/cooling control output below.
- 203 - 206 - 206
External contact input External contact output COM 103 B 203 Load resistance 600 Ω or less
101 501 401 301 201 Factory default: Control output is relay. Default: 4-20 mA DC
No-voltage UT Transistor contact UT UT
contact Contact rating: 250 V AC, 3 A Current (mA) input Voltage (mV, V) input
COM Factory default: No function DO45 501 30 V DC, 3 A (resistance load)
102 502 302 202 Common 301 COM 301
+5V Cooling-side control output RET/OUT2
103 503 303 203 DI11 Factory default: No function DO44 502 - 203 + 202
Factory default: No function 302 DI11 302 Current/voltage pulse output (Suffix code: Type 1=-2)
+5V
104 504 304 204 DI12 Factory default: No function DO43 503 + 204 - 203 Can not be used for retransmission output or 15 V
Factory default: No function 303 DI12 303
+5V + 205 DC loop power suppy when current/voltage pulse
DI13 0-20 mA DC,
105 505 305 205 304 Factory default: No function DO42 504 4-20 mA DC, output is used for control output.
Factory default: No function 304 DI13
+5V Heating/cooling control output E1-terminal area Voltage pulse (12 V) Can be used for retransmission output or 15 V DC
106 506 306 206 DI14 - 206 loop power suppy when control output is not used.
Factory default: No function 305 DI14 305 Factory default: No function DO41 505
Heating/cooling relay contact output (Suffix code: Type 1=-2) 101 301 201
+5V Current output range can be changed.
107 507 407 207 DI15 Cooling NO -112 -312 -212
Factory default: No function 306 DI15 306 Common COM 506 OUT2 -side 101
108 508 408 208 101 301 201
Heating NO
Contact rating: 12 V DC, 10 mA or more Function can be assigned to the Transistor contact rating: 24 V DC, 50 mA OUT -side 102
102 302 202
109 509 409 terminals with no function. Function can be assigned
110 510 410 210 to the terminals with no COM 103 103 303 203 Control output OUT (Suffix code: Type1=-0, -1 or -2)
function. Contact rating: 240 V AC, 3 A 104 304 204 Current/voltage pulse output Retransmission output 15 V DC loop power supply
111 511 411 211 30 V DC, 3 A (resistance load) Wiring direction
Contact input / Contact output DI/DO (Suffix code: Type 2=1) 105 305 205
Default: Undefined
112 512 412 212 + 207
External contact input 0-20 mA DC, + 207 + 207
106 306 206 4-20 mA DC, 0-20 mA DC, 14.5-18.0 V DC
No-voltage
contact
UT Transistor contact UT 24 V DC loop power supply Voltage pulse (12 V) 4-20 mA DC
- 208
(Max. 21 mA DC)
- 208
COM 107 307 207 - 208

E3-terminal area Common 301 COM 301


+5V
24 V DC loop power supply
LPS24 108 208
Default: 4-20 mA DC
308
DI11 (Option code /LP) Can be used for retransmission output or 15 V DC loop power suppy when
302
ALM (Equipped
Factory default: No function 302 DI11
DI12
+5V
21.6-28.0 V DC
+ 505 Contact output as standard)
109 309 current/voltage pulse output is not used for control output.
Factory default: No function 303 DI12 303 (Max. 30 mA DC) Current output range can be changed.
- 506 External contact output (relay) 110 310 210
In Position proportional type, can be used for retransmission output or 15 V DC
Contact rating: 12 V DC, 10 mA or more Alarm-3 output UT 111 311 211 loop power supply.
(PV high limit) 104
External contact output Function can be AL3 312
112 212
assigned to the Common 105
UT terminals with no
Factory default: No function DO12 304
function. Alarm-2 output Contact input DI (Equipped as standard)
(PV low limit) 106
AL2 External contact input
Factory default: No function DO11 305 107 No-voltage UT
Common
contact UT Transistor
contact +5V
Alarm-1 output STOP when DI2=ON DI2
Common COM 306 108 210 DI2 210
(PV high limit) RUN when DI2=OFF +5V
AL1 DI1
AUTO when DI1=ON 211 DI1 211
Transistor contact rating: 24 V DC, 50 mA Common 109 Position proportional control output VALV MAN when DI1=OFF
COM
Relay contact rating: 240 V AC, 1 A Relay contact output Feedback input (Suffix code: Type1=-1) 212 COM 212
30 V DC, 1 A (resistance load) Common
HIGH 100%
(direct) 101 310
Contact rating: 12 V DC, 10 mA or more
Power supply LOW
(reverse) 102 311 Function can be assigned to the terminals with no function.

100-240 V AC power supply 24 V AC/DC power supply (24 V AC/DC power supply: COM 103 0% 312
N N
Option code /DC) Heater break alarm HBA (Option code /HA)
- 110 Contact rating: 240 V AC, 3A Resistance: 100 Ω to 2.5 kΩ
110
30 V DC, 3 A External contact output (transistor) Heater current detection input
L L (resistance load)
111 + 111 Feedback input UT
Current (mA) Heater break alarm-1 HAL1 307 310
input + 310 output CT1
112 112
Heater break alarm-2
311
HAL2 308 CT2
Allowable range: 311 output
100-240VAC (+10%/-15%) 312
(free voltage) Common COM 309 COM
- 312
50/60 Hz shared
When feedback input is current Transistor contact rating: 24 V DC, 50 mA

401-412 E3-Terminal Area 301-306 E1-Terminal Area


RS-485 communication RS485 Ethernet communication (with gateway function) PROFIBUS-DP communication (with Modbus master)
RS-485 (Suffix code: RS-485 communication RS485 24 V DC loop power supply CC-Link communication (with Modbus master)
10BASE-T/100BASE-TX ETHR VP
PROF
Type 3=1) 1 Data 390Ω
(Suffix code: Type 3=4) RS-485 (Suffix code: 24 V DC loop power supply CC-L
SDB(+) 407
RJ45 connector (Suffix code: Type 3=2)
2
CHK line
RxD/TxD-P LPS24 If the UT is located at the end of a FG: Flame ground 301
RDY
Data 220Ω
Type 2=1) (Suffix code: Type 2=0 and segment for the CC-Link (Suffix code: Type 3=3)
SDA(-) 408 3 If the UT is located at the end SDB(+) 301 communication wiring,terminating
ERR line + 305 SLD: Shield 302
Upper side LED (baud rate) 4 RxD/TxD-N of a segment for the
21.6-28.0 V DC option code /LP) resistors are separately needed.
SG 409 Color Amber 390Ω PROFIBUS SDA(-) 302 (Max. 30 mA DC) These are to be prepared by
5 - 306 DG: TX/RX signal ground 303
DGND communication wiring,
Lit 100M bps users. (110 Ω: 1 pc.)
RS-485 terminating resistors are 303
RDB(+) 410 Unlit 10M bps Pin Signal name Description SG
separately needed. DB: RX/TX signal - signal 304
Lower side LED (link activity) 1 VP +5V bus power These are to be prepared by DB
RDA(-) 411 RSB(+) 407 RDB(+) 304
Color Green Data signal users. (390 Ω: 2 pcs. 220 Ω: DA: RX/TX signal + signal 305
2 RxD/TxD-P 110Ω
Lit Linked (positive data receive/transmit) 1 pc., or an active
RSA(-) 408 RDA(-) 305
Data signal terminator.)
Blink Active 3 RxD/TxD-N DA Not used 306 RS-485
(negative data recive/transmit)
Unlit Link failure SG 409
4 DGND Signal ground CHK(red)
307 RSB(+) 310
5 SHIELD Shield ground (Lit: User profile error/Adress error, Unlit: Normal)

LED Lit Unlit


RS-485
Contact input / Contact output DI/DO (Suffix code: Type 2=2) L ERR(red)
(Lit: Communication failure(CRC error), Unlit: Normal)
308 RSA(-) 311
CHK
(red) User profile error Normal External contact input L RUN(green)
309
RSB(+) 407 (Lit: Normal, Unlit: No carrier detected/Communication timeout) SG 312
Normal
RDY Communicating
No power, or No-voltage UT Transistor
contact
UT
Communication contact
(green) successfully RSA(-) 408 COM
failure Common 301 COM 301
Not connected, or +5V
ERR DI11
(red) communication
failure (flashing)
Normal SG 409
Factory default: No function 302 DI11 302 RS-485 communication/24 V DC loop power supply
+5V
DI12 RS-485
Factory default: No function 303 DI12 303
24 V DC loop power supply RS485/LPS24
Contact rating: 12 V DC, 10 mA or more RSB(+) 301
(Suffix code: Type 2=1 and
CC-Link communication (with Modbus master) DeviceNet communication (with Modbus master) + 305 option code /LP)
External contact output Function can be 21.6-28.0 V DC
RSA(-) 302 (Max. 30 mA DC)
DA CC-L CAN_H DNET assigned to the - 306
1
CHK 110Ω (Suffix code: Type 3=3) 1 121Ω (Suffix code: Type 3=5, UT terminals with no
2 2
Factory default: No function DO12 304
function. SG 303
DB CHK CAN_L except Type 2=3)
3 If the UT is located at 3
L ERR the end of a segment If the UT is located at the Factory default: No function DO11 305
4 4
L RUN for the CC-Link MNS end of a segment for the
5 5 DeviceNet
communication wiring,
communication wiring, Common COM 306
terminating resistors
Pin Signal name Description Pin Signal name Description terminating resistors are
are separately needed.
1 FG Flame ground These are to be 1 V+ DeviceNet power supply 24V separately needed. Transistor contact rating: 24 V DC, 50 mA
2 SLD Shield prepared by users. 2 CAN_H RX/TX + signal These are to be
3 DG RX/TX signal ground (110 Ω: 1 pc.) 3 DRAIN Shield/Drain wire
prepared by users. (121
4 DB RX/TX - signal
Ω: 1 pc.)
4 CAN_L RX/TX - signal
5 DA RX/TX + signal 5 V- DeviceNet power supply common

LED Lit Unlit LED Lit/flashing Unlit


CHK User profile error/ CHK
(red) Address error Normal User profile error Normal
(red)
RS-485 RS-485
Normal. Communicating
L ERR Communication failure successfully (green, lit).
Normal RSB(+) 407 RSB(+) 407
(red) (CRC error) Not connected (green, flashing).
MNS Critical link failure (red, lit).
RSA(-) 408 (green/ Communication timeout (red, No electricity
No carrier RSA(-) 408
L RUN Normal detected/ red) flashing)
(green) Communicating successfully Communication SG 409 At power-on/Communication SG 409
timeout faulted (green/red, flashing)

IM 05P01D31-11EN page 4/12


3. Quick Setting Function (Setting of Input and Output) · To change and set the parameter setting, press the SET/ENTER key to start the
Operation UT35A, UT32A setpoint blinking. The blinking state allows you to make changes (setting mode).
Use the Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/EN-
Guide Digital Indicating Controller (Panel Mounting Type) The Quick setting function is a function to easily set the basic function of the control-
TER key to register the setting.
Operation Guide nal
ler.
tio Turn on the controller to start the Quick setting function.
Func ment
Initial Settings Enha
nce
This function allows you to easily set the control type, input, and output, and quickly
■ Making Settings Using Quick Setting Function
start the control action. Example: Setting to PID control, thermocouple type K (range of 0.0 to
«Standard Code Model» The items (parameters) to be set by Quick setting function are as follows. 500.00C), and current control output
(1) Control type (PID control, Heating/cooling control, etc.) For the detailed procedure and switching of displays, see "Flow of Quick Setting
(6) (2) Input function (PV input type, range, scale (at voltage input), etc.) Function" below. For the parameters to set, see the next page.
This operation guide describes basic settings and operations of the UT35A and UT32A. (4) (1) (4) (1) (3) Output function (control output type and cycle time)
For details of each function, see User’s manual (IM 05P01D31-01EN). (2)
The scrolling guide is displayed on PV display in the Parameter Setting Display. (1) Press the SET/ENTER key while YES for QSM (Quick setting mode) is displayed.
This guide can be turned on/off with the Fn key. (5) (2) After turning on the controller, first decide whether or not to use the Quick setting func-
(5) (2) Set the control type parameter (CNT) to PID (PID control).
For details of the each function, refer to the electronic manual. Manuals can be (6) (3) tion. (3) Set the PV input type parameter (IN) to K1 (-270.0 to 1370.0 0C).
downloaded or viewed at the following URL.
Operation in Initial Display (4) Set the PV input unit parameter (UNIT) to C (Degree Celsius).
http://www.yokogawa.com/ns/ut/im/ No. in figure Name Description
(5) Set the maximum value of PV input range parameter (RH) to 500.0.
Used to switch the Operation Displays. · Press the SET/ENTER key while YES is displayed to start the Quick setting function. (6) Set the minimum value of PV input range parameter (RL) to 0.0.
Press the key in the Operation Display to switch the provided
Contents (1)
UT35A: DISPLAY key
UT32A: DISP key
Operation Displays.
· If you change YES to NO and press the SET/ENTER key, Operation Display will
appear without starting the Quick setting function.
(7) Set the output type selection parameter (OT) to OUT terminals (current=00.02).
Press the key in the Menu Display or Parameter Setting Display (8) Finally, EXIT is displayed. Change NO to YES and press the SET/ENTER key to
to return to the Operation Display.
1. Names and Functions of Display Parts
Hold down the key for 3 seconds to move to the Operation
Operation for Setting complete the setup. Operation Display appears.
2. Setup Procedure Parameter Setting Display. · To select the parameter setting displayed as the initial value, press the Down arrow
3. Quick Setting Function (Setting of Input and Output) UT35A: Hold down the key and the Left arrow key simultaneously for 3
(2) PARAMETER key seconds to move to the Setup Parameter Setting Display. key to move to the next parameter.
4. Adjusting Valve Position Automatically (for a Position Proportional Type Controller Only)
UT32A: PARA key Press the key in the Parameter Setting Display to return to the
5. Setting Alarm Type Menu Display. Press the key once to cancel the parameter set-
6. Setting Alarm Setpoint ting (setpoint is blinking).
SET/ENTER key
■ Flow of Quick Setting Function
1. Names and Functions of Display Parts Press the key in the Menu Display to move to the Parameter
Setting Display of the Menu. Press the key in the Parameter
Setting Display to transfer to the parameter setting mode In Quick setting mode, the parameter guide appears on PV display.
(setpoint is blinking), and the parameter can be changed. This guide can be turned on/off with the Fn key.
Press the key during parameter setting mode to register the
setpoint.
(1) SET/ENTER key
(3) Up/Down/Left/Right
Up/Down/Left/Right arrow keys
Press the Left/Right arrow keys in the Menu Display to switch
Power-on 7. The PV input unit parameter (UNIT) is displayed.
(2) arrow keys Initial value: C (Degree Celsius)
(3) the Displays.
(8) Press the Up/Down/Left/Right arrow keys in the Parameter
(2) (11)
(4) Setting Display to switch the Displays.
(4) Quick setting starts Press the Down arrow key.
(3) Press the Up/Down arrow keys during parameter setting mode
(9)
(5)
(9) (5) (setpoint is blinking) to change a setpoint.
1. 8.
(6)
Press the Left/Right arrow keys during parameter setting mode The upper limit value of the setting range is displayed
(10) (setpoint is blinking) to move between digits according to the parameter.
(6) for the parameter RH (maximum value of PV input range).
It is the communication interface for the adapter cable used when
(10)
(11) (4) Light-loader interface setting and storing parameters from a PC. The LL50A Parameter [NO]
(7)
Setting Software (sold separately) is required. Press the SET/ENTER key.
(8) Used to switch between AUTO and MAN modes. [YES]
(5) A/M key The setting is switched between AUTO and MAN each time the 9.
key is pressed.
(2) + (3) + (4) : Setpoint display Press the SET/ENTER key while YES Select NO with the Down The last digit of the upper limit value blinks.
The UT35A has F1, F2, and Fn keys.
(6) User function keys The UT32A has only the Fn key. The user can assign a function is displayed to start the Quick setting. arrow key and press the
No. in figure Name Description SET/ENTER key. Change the setpoint using the Up/Down arrow keys
to the key. The function is set by the parameter.
Displays PV. 2. First, the control type to increase and decrease the value and the Left/Right arrow
PV display Displays an error code if an error occurs. Note: The communication connector (maintenance port) for LL50A Parameter Setting Software is
(1) on the top of the unit. parameter (CNT) keys to move between digits.
(white or red) Displays the scrolling guide in the Menu Display and Parameter
is displayed.
Setting Display when the guide display ON/OFF is set to ON.
Initial value: PID (PID control)
10.
(2) Group display (green)
Displays a group number (1 to 4 or R) and terminal area (E1 to E4).
1 to 4 represent SP numbers in the Operation Display.
2. Setup Procedure  Press the Down arrow key.
The parameter RH (maximum value of PV input range)
has been changed to 500.0.
R and E1 to E4 are displayed in the Parameter Setting Display.
(3) Symbol display (orange) Displays a parameter symbol. The following flowchart shows the setup procedure for UT35A and UT32A. Press the SET/ENTER key.
(4) Data display (orange) Displays a parameter setpoint and menu symbol. 3. The PV input type
Installation parameter (IN) is
Displays control output value (OUT) and measured input value (PV). and wiring Install and wire a controller.
displayed. 11.
Bar-graph display The data to be displayed can be set by the parameter.
(5) Initial value: OFF
(orange) Initial value: Deviation, Heating-side control output (in Heating/ The setpoint for the parameter RH has been registered.
cooling control)
Power ON
Lit when the alarms 1 to 4 occur. Press the SET/ENTER key.
Event indicator
(6) Event displays other than alarms can be set by the parameter.
(orange)

Key navigation indica- Lit or blinks when the Up/Down or Left/Right arrow key operation Use NO
4.
(7)
tor (green) is possible. Quick setting OFF blinks. Press the Down arrow key.
Displays the setting conditions of the parameter display level func- function? Blinking allows you to
tion. change the setting. Follow the same procedure to set RL
YES to 0.0 and OT to 00.02.
Parameter display level Parameter display level EASY PRO
(8) Control type setup  Press the Up arrow key. Set other parameters as needed.
indicator (green) Easy setting mode Lit Unlit
Standard setting mode Unlit Unlit
Professional setting mode Unlit Lit
5. Select NO to return to Finally, EXIT is displayed.
Control type setup
Displays the operating conditions and control status. Input setup the Operation Display. Press the SET/ENTER key to swtich to the setting mode.
Input/output setup
Indicator Description
Change NO to YES and press the SET/ENTER key
K1 is displayed. 12.
REM Lit when in remote mode (REM).
to complete the setup of the basic function.
Status indicator
(9) STOP Lit when in stop mode (STOP).
Operation Display appears.
(green and red)
Lit when in manual mode (MAN). Position Position Press the SET/ENTER key. The Quick setting function continues in the NO state.
MAN YES YES
Blinks during auto-tuning. proportional proportional
type? type?
6.
(10) Security indicator (red) Lit if a password is set. The setup parameter settings are locked. NO For Position proportional type NO
Ladder operation Lit while the ladder operation is executed.
(11) Valve position Output setup K1 has been registered.
indicator (green) adjustment
Operation Display
Displays the measured
input value (PV).
Displays the target
Other setup Set the other parameters as needed.  Press the Down arrow key. setpoint (SP).

PID tuning Adjust PID using auto-tuning or manually for PID control.

Operation Monitoring and control of regular operations

IM 05P01D31-11EN page 5/12


OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
displayed.
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Press the SET/ENTER key. Note 2: Positive setpoint, Negative setpoint

■ Parameters to be set 1. 5. Setting Display of Alarm Type Stand-by Action

Control Type Show the Operation Display. The last digit of the setpoint blinks. ºC
Treated
Normal Abnormal

Parameter Symbol Name of Parameter Setting Range MAN as normal The alarm output

is lit Change the setpoint using the Up/Down arrow keys turns on.
PID: PID control PV low limit
to increase and decrease the value and alarm setpoint
ONOF: ON/OFF control (1 point of hysteresis) Alarm type
CNT Control type ONOF2: ON/OFF control (2 points of hysteresis) the Left/Right arrow keys to move between digits. Without (0) or With (1) The alarm output does not turn on
2P2L: Two-position two-level control Stand-by action
+ in this region even if the PV valule
H/C: Heating/cooling control
Hold down the keys for 3 seconds. Press the SET/ENTER key. Energized (0) / De-energized (1) is below PV low limit alarm setpoint.
Latch action (0/1/2/3/4)
Note: Some setpoints may not be displayed depending on the model and suffix codes.
2. * When a password is set, PASS is displayed. 6. The alarm-1 type setpoint 02 (PV low limit) See User’s Manual (IM 05P01D31-01EN).
Input Function If the correct password is not entered, setup is registered. Power-on Time
parameters cannot be changed. After the setup is completed, press the DISPLAY key
Parameter Symbol Name of Parameter Setting Range
CTL menu is displayed. or DISP key once to return to the Operation Display.
OFF: Disable
K1: -270.0 to 1370.0 0C / -450.0 to 2500.0 0F  Press the Right arrow key until OUT menu appears. Symbol Stand-by action
K2: -270.0 to 1000.0 0C / -450.0 to 2300.0 0F
K3: -200.0 to 500.0 0C / -200.0 to 1000.0 0F
3.
Energized/De-energized
Latch action 6. Setting Alarm Setpoint
J: -200.0 to 1200.0 0C / -300.0 to 2300.0 0F
T1: -270.0 to 400.0 0C / -450.0 to 750.0 0F The following operating procedure shows an example of setting the alarm-1 setpoint
T2: 0.0 to 400.0 0C / -200.0 to 750.0 0F OUT menu is displayed. ● To change the alarm type, change the last 2 digits of the
of group 1 to 180.0.
B: 0.0 to 1800.0 0C / 32 to 3300 0F 5-digit value.
S: 0.0 to 1700.0 0C / 32 to 3100 0F
● Stand-by action and excitation are turned on or off by Before setting the alarm setpoint, check the alarm type.
R: 0.0 to 1700.0 0C / 32 to 3100 0F Press the SET/ENTER key. To change the alarm type, see “5. Setting Alarm Type.”
N: -200.0 to 1300.0 0C / -300.0 to 2400.0 0F selecting 1 or 0. (See “Setting Display of Alarm Type.”)
E: -270.0 to 1000.0 0C / -450.0 to 1800.0 0F
4. ● For the latch action, see User ’s Manual (IM 05P01D31-01EN). 1. Show the Operation Display.
L: -200.0 to 900.0 0C / -300.0 to 1600.0 0F
U1: -200.0 to 400.0 0C / -300.0 to 750.0 0F The parameter V.AT (automatic valve
U2: 0.0 to 400.0 0C / -200.0 to 1000.0 0F
position adjustment) is displayed. 2. Display MODE menu with the same procedure as described in
IN PV input type
W: 0.0 to 2300.0 0C / 32 to 4200 0F Setting Alarm Type.
PL2: 0.0 to 1390.0 0C / 32.0 to 2500.0 0F Alarm Type (Alarm Setpoint) Alarm Action (Energized) Alarm Action (De-energized)
P2040: 0.0 to 1900.0 0C / 32 to 3400 0F Press the SET/ENTER key. - - Press the Right arrow key.
WRE: 0.0 to 2000.0 0C / 32 to 3600 0F No alarm (00)
JPT1: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
JPT2: -150.00 to 150.00 0C / -200.0 to 300.0 0F 5. Hysteresis Hysteresis
PT1: -200.0 to 850.0 0C / -300.0 to 1560.0 0F
OFF blinks. PV high limit (01) Open Closed Closed Open
3.
PT2: -200.0 to 500.0 0C / -300.0 to 1000.0 0F (unlit) (lit) (unlit) (lit)
PT3: -150.00 to 150.00 0C / -200.0 to 300.0 0F Analog input PV high limit (19)
0.4-2V: 0.400 to 2.000 V PV Alarm setpoint PV Alarm setpoint
1-5V: 1.000 to 5.000 V SP menu is displayed.
4-20: 4.00 to 20.00 mA
 Press the Up arrow key.
0-2V: 0.000 to 2.000 V Hysteresis Hysteresis
0-10V: 0.00 to 10.00 V 6.
0-20: 0.00 to 20.00 mA ON is displayed. PV low limit (02) Closed
(lit)
Open
(unlit)
Open
(lit)
Closed
(unlit)
-1020: -10.00 to 20.00 mV Blinks during the change. Analog input PV low limit (20)
0-100: 0.0 to 100.0 mV Alarm setpoint PV Alarm setpoint PV
-: No unit, C: Degree Celsius Press the SET/ENTER key.
UNIT PV input unit
-: No unit, - -: No unit, - - -: No unit, F: Degree Fahrenheit
Press the SET/ENTER key. Hysteresis
Depends on the input type. Hysteresis Press the Down arrow key until A1 appears.
Maximum value of - For temperature input -
7. SP high limit (03) Open Closed Closed Open
RH
PV input range Set the temperature range that is actually controlled.
(RL<RH) ON has been registered and the automatic Target SP high limit (09)
(unlit) (lit) (unlit) (lit) 4.
SP or Alarm setpoint
- For voltage / current input - adjustment of the valve position starts. Target SP
SP or Alarm setpoint
The parameter A1 is displayed.
Target SP
Set the range of a voltage / current signal that is applied. V.AT blinks during the automatic adjustment. A1 to A4 represent the alarm-1 to -4 setpoints.
The scale across which the voltage / current signal is
RL
Minimum value of
actually controlled should be set using the maximum value After the adjustment is completed, press Hysteresis Hysteresis
PV input range
of input scale (SH) and minimum value of input scale (SL). the DISPLAY key or DISP key once to return SP low limit (04) Closed Open Open Closed Group
(Input is always 0% when RL = RH.) (lit) (unlit) (lit) (unlit)
to the Operation Display. Target SP low limit (10)
PV input scale 0: No decimal place 3: Three decimal places Alarm setpoint SP or Alarm setpoint SP or
SDP decimal point 1: One decimal place 4: Four decimal places Each parameter and group can be changed
Target SP Target SP
position 2: Two decimal places ● When the adjustment is completed normally, the indication in the Parameter Setting Displays of alarms
SH
Maximum value of automatically returns to OFF. Hysteresis Hysteresis using arrow keys.
PV input scale
-19999 to 30000, (SL<SH), | SH - SL | ≤ 30000 ● When VAT.E appears on PV display, it indicates an error. Deviation high limit (05) Open Closed Closed Open Up/Down arrow keys: parameters
Minimum value of
SL
PV input scale Check the wiring for feedback input and perform the Target SP deviation high (unlit) (lit) (unlit) (lit) Left/Right arrow keys: groups
limit (11)
automatic adjustment again. To perform a valve adjustment PV Deviation setpoint PV Deviation setpoint
Note 1: SDP, SH, and SL are displayed only for voltage/current input.
Note 2: W: W-5%Re/W-26%Re (Hoskins Mfg.Co.), ASTM E988 manually, see User’s Manual (IM 05P01D31-01EN). SP or Target SP SP or Target SP Display the parameter and group
Hysteresis Hysteresis that need to be changed.
Output Function
Closed Open Open Closed
Deviation low limit (06) (lit) (unlit)
Parameter Symbol Name of Parameter Setting Range Target SP deviation low limit (12)
(lit) (unlit)
Press the SET/ENTER key.
Control output or Heating-
side control output (Lower
Cooling-side control output
(Upper two digits) 5. Setting Alarm Type Deviation setpoint PV Deviation setpoint PV

two digits)
SP or Target SP SP or Target SP 5.
00: OFF 00: OFF The following operating procedure shows an example of changing the alarm-1 type Hysteresis Hysteresis Hysteresis Hysteresis Blinks during the change.
Output type selection
01: OUT terminals 01: OUT terminals
(voltage pulse) (voltage pulse)
(factory default: PV high limit alarm) to PV low limit alarm (setpoint: 02). Deviation high and low Closed Open Closed Open Closed Open
limits (07) (lit) (unlit) (lit) (lit) (unlit) (lit)
OT 02: OUT terminals (current)
03: OUT terminals (relay)
02: OUT terminals (current)
03: OUT terminals (relay)
1. Target SP deviation high and
Deviation PV
Upper two digits low limits (13) Deviation PV
setpoint setpoint
Lower two digits 06: OUT2 terminals (relay) 06: OUT2 terminals (relay)
SP or Target SP SP or Target SP Change the setpoint using the Up/Down arrow
07: RET/OUT2 terminals 07: RET/OUT2 terminals Show the Operation Display.
(voltage pulse) (voltage pulse) Hysteresis Hysteresis Hysteresis Hysteresis keys to increase and decrease the value and
08: RET/OUT2 terminals 08: RET/OUT2 terminals
Deviation within high and low the Left/Right arrow keys to move between digits.
(current) (current) Open Closed Open Closed Open Closed
limits (08) (unlit) (lit) (unlit) (unlit) (lit) (unlit)
Control output cycle Target SP deviation within high
time and low limits (14) Deviation PV Deviation PV Press the SET/ENTER key.
Heating-side control setpoint setpoint
CT SP or Target SP SP or Target SP
output cycle time
(in Heating/cooling Hold down the key for 3 seconds. Hysteresis Hysteresis
0.5 to 1000.0 s
control)
6. The setpoint has been registered.
Cooling-side control 2. Control output high limit (15)
Open Closed Closed Open
After the setup is completed, press
Cooling-side control output (unlit) (lit) (unlit) (lit)
output cycle time
CTc
(in Heating/cooling
high limit (17)
Output Alarm setpoint Output Alarm setpoint the DISPLAY key or DISP key once
control) MODE menu is displayed. to return to the Operation Display.
 Press the Right arrow key until ALRM menu appears. Hysteresis
4. Adjusting Valve Position Automatically
Hysteresis
Control output low limit (16)
3. Closed Open Open
(for a Position Proportional Type Controller Only)
Closed
Cooling-side control output (lit) (unlit)
Initializing parameter values
(lit) (unlit)
low limit (18)
Alarm setpoint Output Alarm setpoint Output
The following operating procedure describes how to input feedback signals from the ALRM menu is displayed.
control valve and adjust the fully-open and fully-closed positions of the control valve Parameters that you have changed can be initialized to factory default values or user default
Feedback input high limit (27) Fault diagnosis alarm (30)
automatically. The fully-open and fully-closed positions of the valve can be adjusted Press the SET/ENTER key. Burnout of PV input, ADC failure, RJC error. values. For details, see “Parameter Initialization” in the User’s Manual (IM 05P01D31-01EN).
automatically by inputting feedback signals from the valve. To adjust the valve posi-
Feedback input low limit (28)
tion, you need to carry out the connection and bring the controller into manual mode.
For the connection, see “6. Terminal Wiring Diagrams” in "Installation and Wiring",
4. FAIL (31) Changing the parameter display levels
For the factory default, the contact output is turned ON in normal operation,
and for the manual mode, see “5. Switching between AUTO and MAN” in "Opera- The parameter AL1 (alarm-1 type) is PV velocity (29) OFF at the time of FAIL. Control output: OFF or 0%, Alarm output: OFF
tions." displayed. This operation guide does not explain all the parameters. To display all the parame-
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
ters, you need to change the parameter display level to professional setting mode. For
Note 2: Positive setpoint, Negative setpoint
Press the SET/ENTER key. details, see “Setting Security Functions” in the User’s Manual (IM 05P01D31-01EN).

Setting Display of Alarm Type Stand-by Action IM 05P01D31-11EN page 6/12


5.
ºC Normal Abnormal
Treated
2. Setting Target Setpoint (SP) 5. 5. Switching between AUTO and MAN
Operation UT35A, UT32A
OFF blinks.
Guide Digital Indicating Controller (Panel Mounting Type) AUTO and MAN switching can be performed using any of the following: (1) A/M key,
Operation Guide nal
(2) Contact input, (3) Communication, and (4) User function key.
tio The figure below shows a direct operation using the A/M key.
Func ment Press the Up/Down arrow keys to display the required setpoint.
Operations nce
Enha When AUTO and MAN switching function is assigned to the contact input, and the

«Standard Code Model»


6. contact input is ON, the switching by key operation cannot be performed.
For details, see User’s Manual (IM 05P01D31-01EN).
Blinks during the change.

This operation guide describes key entries for operating the UT35A and UT32A.
Although the display of UT35A is used in this guide, UT32A can be operated similarly. The setting range is 1 to 4 (represent group numbers) or R.
For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams”
in “Installation and Wiring.” 1. Show the SP Display (Operation Display).
To perform auto-tuning for the PID of group 1, set the parameter AT to 1.
To quit the auto-tuning, set the parameter to OFF.
If you cannot remember how to carry out an operation during setting, press the (This is an example of setting the target
MAN lamp is lit in MAN mode.
DISPLAY key or DISP key once. This brings you to the display (Operation Display) that setpoint to 150.0).
appears at power-on. Press the SET/ENTER key.
The scrolling guide is displayed on PV display in the Parameter Setting Display.
This guide can be turned on/off with the Fn key. 2. Press the SET/ENTER key to start the
For details of the each function, refer to the electronic manual. Manuals can be last digit of the setpoint blinking. 7. The setpoint has been registered.
This starts auto-tuning.
downloaded or viewed at the following URL. Blinking allows you to change the value.
The limiter can be set to the output during auto-tuning. Each time you press the key,
http://www.yokogawa.com/ns/ut/im/ For details, see User’s Manual (IM 05P01D31-01EN).
3. To set the setpoint, use the AUTO and MAN is switched alternately.
Left/Right arrow keys to move During auto-tuning,
Contents between digits and the Up/Down • The MAN lamp blinks. When AUTO is switched into MAN, the control output value in AUTO mode is held.
arrow keys to increase and • The OUT symbol appears. The controller can be operated manually from the hold value.
1. Monitoring-purpose Operation Displays Available during Operation decrease the value. • The output values at 100.0% and If the manual preset output is set (MPON parameter ≠ OFF), the controller can be
2. Setting Target Setpoint (SP) 4. When the required value is displayed, 0% appear alternately. operated manually from the arbitrary output value (MPO1 to MPO5 parameters).
3. Performing/Canceling Auto-tuning press the SET/ENTER key to register
4. Selecting Target Setpoint Numbers (SPNO.) 8.
5. Switching between AUTO and MAN
the setpoint.
6. Switching between RUN and STOP
6. Switching between RUN and STOP
7. Switching between REM (Remote) and LCL (Local) RUN and STOP switching can be performed using any of the following: (1) Contact
The MAN lamp goes off, which means that
8. Manipulating Control Output in Manual Mode input, (2) Parameter, (3) Communication, and (4) User function key.
the auto-tuning completed normally.
9. Troubleshooting The following shows an example of switching using the contact input.
(The switching function is assigned to DI2 contact for the factory default.)
1. Monitoring-purpose Operation Displays Available during Operation For details of other switching methods and the display appearing when the operation
is started, see User’s Manual (IM 05P01D31-01EN).
■ Operation Display Switching Diagram for Standard and Posi- 3. Performing/Canceling Auto-tuning When the controller is stopped, input and outputs are as follows:
tion Proportional Types 4. Selecting Target Setpoint Numbers (SPNO.) PV input
Control output
Displays the PV value.
Displays the preset output value.
• SP Display Auto-tuning should be performed after setting a target setpoint.
The preset output value is set for each PID group.
Displays the measured input value on PV display. Make sure that the controller is in automatic mode (AUTO) and in run mode (RUN) The following operating procedure shows an example of changing the target setpoint Alarm output Turns the output on in case of an alarm.
Displays the target setpoint (SP) on Setpoint display (SP can be changed). before auto-tuning. For setting to AUTO, see “5. Switching between AUTO and number (SPNO.) from 1 to 2. Each SP has its PID group. The PID group set for the
• OUT Display MAN,” and for setting to RUN, see “6. Switching between RUN and STOP.” parameter PIDN (PID number selection) is used.
Display in STOP mode
Displays the measured input value on PV display.
Displays the control output value (OUT) on Setpoint display (OUT can be changed
If the setpoint is known in advance or auto-tuning does not find any appropriate PID 1. Show the Operation Display. “STOP” is displayed on Symbol display and "preset output value" is displayed on
constants, set the PID manually. For setting the PID manually, see User’s Manual (IM
in manual mode). Data display.
05P01D31-01EN).
Displays the valve’s feedback input value (at 0 to 100% valve opening) in Position 2.
proportional control. Display in STOP mode
210

Do not perform auto-tuning for the following processes. Hold down the PARAMETER key or PARA key for DI2 OFF: Operation RUN
Tune PID manually. 3 seconds to display MODE menu. 212

• Processes with fast response such as flow rate control and pres-
CAUTION sure control.
• Processes which do not allow the output to be turned on and off 210
even temporarily. DI2 ON: Operation STOP
Press the SET/ENTER key.
• Processes which prohibit severe output changes at control 212
valves (or other actuators).
• Processes in which product quality can be adversely affected if
3.
In cases where the communication is
SP Display OUT Display PV values fluctuate beyond their allowable ranges. specified, the parameter R.L Preset output (PO)
(SP can be changed.) (OUT can be changed.) (REMOTE/LOCAL switch) is displayed. Valve opening (0-100%) for
Position proportional type
Press the Down arrow key until the parameter SPNO.
■ Operation Display Switching Diagram for Heating/Cooling Type 1. Show the Operation Display. appears. STOP lamp is lit.
• SP Display
Displays the measured input value on PV display. 4.
Displays the target setpoint (SP) on Setpoint display (SP can be changed). 2. The parameter SPNO. (SP number selection)
• OUT Display Display in STOP mode in Heating/cooling control
is displayed.
Displays the measured input value on PV display. “Cooling-side preset output value” is displayed on the left side of the “ST” symbol,
Hold down the PARAMETER key or PARA key for
Displays the control output values (C.H.) of heating and cooling sides on Setpoint and “Heating-side preset output value” is on the right side.
3 seconds to display MODE menu. Press the SET/ENTER key.
display (C.H. can be changed in manual mode).
Display in STOP mode
210
5. Change the setpoint using DI2 OFF: Operation RUN
the Up/Down arrow keys. 212
Press the SET/ENTER key. Blinks during the change.

3. Press the SET/ENTER key. 210


In cases where the communication is DI2 ON: Operation STOP
specified, the parameter R.L
(REMOTE/LOCAL switch) is displayed. 6. The setpoint has been registered. 212

SP Display Heating/cooling OUT Display Press the DISPLAY key or DISP key once
(SP can be changed.) (OUT can be changed.) to return to the Operation Display.
Press the Down arrow key until the parameter AT appears.
After showing the OUT Display, press the DISPLAY key or DISP key to show the fol- Heating-side preset output (PO)
lowing displays conditionally. For details, see User’s Manual (IM 05P01D31-01EN).
4. Cooling-side preset output (POc)
Standard, Position Proportional, and Heating/Cooling Types 7. STOP lamp is lit .
The parameter AT (auto-tuning switch) is displayed.
• SELECT Displays 1 to 5 (which appear when registered)
• Analog Input Display (display only) (factory default: non-display) SPNO. has been changed to 2.
• Position Proportional Computation Output Display (display only) (factory default: Press the SET/ENTER key.
non-display)
• PID Number Display (display only) (factory default: non-display)
• Heater Break Alarm-1 Current Display (display only) (for heater break alarm option only)
• Heater Break Alarm-2 Current Display (display only) (for heater break alarm option only) IM 05P01D31-11EN page 7/12
7. Switching between REM (Remote) and LCL (Local) 8. Manipulating Control Output in Manual Mode ■ Errors at Power On
The errors shown below may occur in the fault diagnosis when the power is turned on. (For details of Setpoint display and input/output action when each error occurs, see User’s Manual (IM
Remote and local switching can be performed using any of the following: 05P01D31-01EN).)
(1) Contact input, (2) Parameter, (3) Communication, and (4) User function key. NOTE PV display
Setpoint display Status indicator Parameter that displays error
(Operation Error description Cause and diagnosis Remedy
(Operation Display) (Operation Display) details
LCL (Local) In manual mode, control output is manipulated by operating the keys (the value is Display)
Control is performed using the target setpoint set on the controller. changed using the Up/Down arrow keys, then outputted as it is). Indication off Indication off — — Faulty MCU RAM / MCU ROM MCU RAM / MCU ROM are failed.
Faulty.
Even if the SET/ENTER key is not pressed, the control output value changes ac- Contact us for repair.
REM (Remote) cording to the displayed value. SYS - - - - - — System data error System data is corrupted.
Faulty.
Contact us for repair.
Control is performed using a setpoint via communication for the target setpoint. The In stop mode (when the STOP lamp is lit), control output cannot be manipulated.
following shows an example of switching from local to remote using the parameter. PAR 0004 User (parameter) default value User parameter is corrupted.
(for user default value error
(Only in cases where the communication is specified.) error Initialized to factory default value.
only) Check and reconfigure the initialized
For details of other switching methods, see User’s Manual (IM 05P01D31-01EN). Up arrow key: increases control output.
PAR 0010 setting parameters. Error indication is
Down arrow key: decreases control output. Setup parameter (PA.ER) Setup parameter data is corrupted.
• The PID group for the local SP number is used as PID in remote mode. (for setup parameter error Setup parameter error
Initialized to user default value.
erased when the power is turned on
ERR only) — again.
NOTE PAR 0020 Operation parameter data is corrupted.
Operation parameter error
(for operation parameter error only) Initialized to user default value.
When the contact input is ON, operation cannot be performed using the parameter, Inconsistence of system data and
communication, or key. When the contact input is OFF and the setting is switched SLOT 0015 Nonresponding hardware of hardware of extended function.
MAN lamp is lit. (0015: Error occurs to all Faulty.
using the parameter, communication, or key, the last switching operation is per- hardware of E1 to E4-terminal
Setup parameter (OP.ER) extended function (E1 to E4- Nonresponding communication between
Contact us for repair.
formed. terminal areas) hardware of extended function (E1 to E4-
In Position proportional control: areas.)
terminal areas).
Up arrow key; opens the valve.
Rightmost decimal point Initialized to calibrated default value because
Down arrow key; closes the valve. Calibration value error
Normal on PV display blinks. of corrupted factory default value. Faulty.
1. Show the Operation Display. Output; only while pressing a key.
OUT; valve opening (0-100%) indication
Normal indication
Rightmost decimal point
Setup parameter (PA.ER)
Faulty FRAM Data writing (storing) to FRAM is impossible.
Contact us for repair.
on Symbol display blinks.
2. Output manipulation in Position proportional control
is not restricted from output limiters (OH, OL).
Normal
indication
Normal indication LADDER lamp blinks Setup parameter (LA.ER) Corrupted ladder program
Ladder program is corrupted.
Operates without ladder program.
Download the ladder program again.

Normal 0.000 00000


Hold down the PARAMETER key or PARA key Manual operation in Heating/cooling control (Decimal point on the left of — Setup parameter (OP.ER) User profile error User profile is corrupted. Download the user profile again.
indication
for 3 seconds to display MODE menu. the Symbol display blinks)

■ Errors during Operation


Heating-side control output The errors shown below may occur during operation. (For input/output action when each error occurs, see User’s Manual (IM 05P01D31-01EN).)
Press the SET/ENTER key. Symbol of heating side PV display
Setpoint display Status indicator Parameter that displays
(Operation Error description Cause and diagnosis Remedy
Cooling-side control output Display)
(Operation Display) (Operation Display) error details
3. Symbol of cooling side Analog input terminal ADC error Faulty.
The parameter R.L (REMOTE/LOCAL switch)
AD.ERR Normal indication (Note) — Setup parameter (AD1.E)
•PV input
Analog input terminal AD value error
Contact us for repair.
Target setpoint (SP) number
is displayed. RJC.E Faulty.
(Displays RJC. Normal indication (Note) Universal input terminal RJC error Contact us for repair.
— Setup parameter (AD1.E) Universal input terminal RJC error
Up arrow key: concurrently decreases cooling-side control output and increases E and PV •PV input Set the parameter RJC to OFF to erase
heating-side control output. alternately.) error indication.
Press the SET/ENTER key.
Down arrow key: concurrently increases cooling-side control output and decreases Check wiring and sensor.
Analog input terminal burnout error
4. Change the operation mode using heating-side control output.
Setup parameter (AD1.E)
•PV input
Analog input terminal sensor burnout Error indication is erased in normal
operation.
the Up/Down arrow keys. (Either none of the heating-side and cooling-side outputs are presented, or both of B.OUT Normal indication (Note) — Check wiring and sensor of connected
Blinks during the change. them are presented according to the dead band setting.) analog input terminals.
Setup parameter (PV1.E) PV input burnout error Burnout of analog input connected to PV
Error indication is erased in normal
Actual output (%) Actual output (%)
operation.
100 100
Press the SET/ENTER key. PV input over-scale PV input is out of -5 to 105%. Also occurs
Cooling-side Heating-side OVER Normal indication — Setup parameter (PV1.E) PV input under-scale when the data out of range which is the
Check analog input value or ladder
5. manipulated output manipulated output
Cooling-side Heating-side -OVER (PV values out of -5 to 105%) ladder calculation result is input.
program.
manipulated output manipulated output
Check wiring of feedback input resistor/
Normal Feedback input resistor/current
The REM lamp is lit. indication OUT - - - - - — Setup parameter (AD2.E)
burnout
Feedback input burnout current. Error indication is erased in
normal operation.
-12.4 0 12.4 -12.4 0 12.4
Floating point computation for ladder
Control computation output Control computation output Ladder calculation overflow Check the ladder program.
calculation is infinite.
DB=24.8 Dead band: Operation parameter DB DB= -24.8 Computation does not end within the Change the control period or reduce
Load factor over 100% control period (load factor is 100% or the number of steps for the ladder
Manipulated output change Manipulated output change more). program.
when a dead band is positive (+) when a dead band is negative (-) Normal indication LADDER lamp blinks Setup parameter (LA.ER)
Load factor over 200% Computation does not end within the control Change the control period or reduce the
Normal
(Forced end) period (load factor is 200% or more). number of steps for the ladder program.
indication
Download the ladder program again. If
Ladder program error Ladder program is corrupted. the error indication is still not erased,
9. Troubleshooting there is a fault. Contact us for repair.
0.000 00000 Check that the target devices are
(Decimal point on the left of — Setup parameter (OP.ER) Peer-to-peer communication error Peer-to-peer communication error connected correctly.
■ Troubleshooting Flow the Symbol display blinks) Recovery at normal receipt.
■ Remedies if Power Failure Occurs AT.E Normal indication — Setup parameter (PV1.E) Auto-tuning time-out
Auto-tuning does not end even when 24 Check the process. Hold down any key to
If the Operation Display does not appear after turning on the controller’s power, check the procedures in the following flowchart. during Operations hours have elapsed after the start of tuning. erase the error indication
If a problem appears to be complicated, contact our sales representatives. Valve position automatic
Fully-closed valve position is equal to or larger
Check wiring and valve. Hold down any
• Instantaneous power failure within 20 ms. VAT.E Normal indication — Setup parameter (AD2.E) than the fully-open valve position after automatic
Is the controller adjustment error key to erase the error indication.
A power failure is not detected. Normal valve position adjustment is performed.
defective? Framing parity error
operation continues.
Yes Buffer overflow
• Power failure for less than about 5 seconds, 0.000 00000 Inter-character time-out Check the communication parameters.
Normal Communication error
No Key No No No or for about 5 seconds or more. (Decimal point on the left of — Setup parameter (OP.ER) Checksum error (PC link communication with Recovery at normal receipt.
Completely operation Display I/O signal Communication indication
the Symbol display blinks)
(RS-485 communication)
checksum) Hold down any key to stop blinking.
inactive? failure? failure? failure?
Affects the "settings" and "operation sta-
failure? CRC check error (Modbus/RTU)
* tus." LRC check error (Modbus/ASCII)
Yes Yes Yes Yes Yes
For details, see User's Manual (IM
Inconsistence of loop between coordinated Check the communication parameters.
05P01D31-01EN). Recovery at normal receipt. Change from remote
Check wiring of the Check the key lock Turn off power, and Check the I/O specifications Check the specifications 0.000 00000 master and slaves
power terminals. setting. of the controller. Normal Communication error to local mode to stop blinking.
then turn it on again. of the controller. (Decimal point on the left of — Setup parameter (OP.ER)
indication (coordinated operation) When the mode is changed from remote to
the Symbol display blinks) Communication from coordinated master is local, SP tracking does not work even if it is
NOTE interrupted for 2 seconds. set to ON.
Check the Check the No With
supply voltage. specifications and polarity communi- Write down the settings of parameters for a 0.000 00000
of connected devices . cation? Normal
(Decimal point on the left of — Setup parameter (OP.ER) User profile error User profile is corrupted. Download the user profile again.
Yes repair request. indication
the Symbol display blinks)
Normal Rightmost decimal point on
No Normal indication Setup parameter (PA.ER) Faulty FRAM Writing (storing) data to FRAM is impossible. Faulty. Contact us for repair.
No communication Check the communication- indication Symbol display blinks.
Normal? capability related parameters. Faulty MCU / DCU
No Is the Undefined Undefined — — MCU / DCU is corrupted. Faulty. Contact us for repair.
Yes (ROM / RAM error, corrupted)
key locked?
Yes Note: When an error occurs in input shown in Analog input display (Operation display), Setpoint display shows the same symbol as the PV display.
Correct the error(s). Check the
communication wiring.

No * The LCD (a liquid crystal display) is used for


Correct? a display portion of this product.
The LCD has a characteristic that the display action Check the specifications
Yes of communication
Cancel the setting. becomes late at the low temperature. devices.
Additionally, the luminance and contrast degradation
are caused due to aged deterioration.
Contact us for repair. Problem solved. However, the control function is not affected. IM 05P01D31-11EN page 8/12
■ PID Setting Parameter
Operation UT35A, UT32A ■ SP and Alarm Setpoint Setting Parameter ■ Alarm Function Setting Parameter
Menu symbol: (PID)
Guide Digital Indicating Controller (Panel Mounting Type) Menu symbol: (SP) Menu symbol: (ALRM)
Parameter Initial User Display
Operation Guide tiona
l Parameter
Name of Parameter Setting Range
Initial User Display Parameter
Name of Parameter Setting Range
Initial User Display symbol
Name of Parameter Setting Range
value setting level
Func ment symbol value setting level symbol value setting level
Parameters Enha
nce
0.0 to 100.0% of PV input range (EU) Set a 5-digit value in the following
Proportional band
0.0 to 999.9%
When 0.0% is set, it operates as
Target setpoint SPL Heating-side proportion-
(SP) (Setting range: SPL to SPH) order. 0.1%. 5.0%
[Latch action (0/1/2/3/4)] + [Energized (P) al band (in Heating/cool-
Heating-side ON/OFF control applies
«Standard Code Model» 0.0 % (0) or De-energized (1)] + [Without (0)
AL1,
ing control)
when 0.0% in Heating/cooling control
Sub-target setpoint (in Set the offset from SP. of PV or With (1) Stand-by action] + [Alarm
Yokogawa Electric Corporation Two-position two-level -100.0 to 100.0% of PV input range input type: 2 digits (see below)] AL3: Integral time
Latch OFF: Disable
(SUB) control) span (EUS) range For latch action, see User's Manual Heating-side integral time 240 s
action (I) 1 to 6000 s
span (IM 05P01D31-01EN). (in Heating/cooling control)
This operation guide describes the functions of parameters briefly. The parameter (0)
symbols listed are in the order shown on the display in each group of menu symbols. In Set a PID group number to use. Table Alarm type: 2 digits Derivative time
EASY PV high OFF: Disable
addition, each parameter table has a “User Setting” column, where you can record your PID number selection 1 to 4 (Depends on the setup param- 1 to 4 below 00: Disable Heating-side derivative time 60 s
limit (01) (D) 1 to 6000 s
(PIDN) eter PIDG. setting.) 01: PV high limit (in Heating/cooling control)
setpoints when setting them in the controller. The scrolling guide is displayed on PV Without
02: PV low limit Stand- Control output high limit
display in the Parameter Setting Display. This guide can be turned on/off with the Fn key. Set a display value of setpoint of PV -4.9 to 105.0%, (OL<OH)
03: SP high limit by Heating-side control
For details of the each function, refer to the electronic manual. Manuals can be alarm, SP alarm, deviation alarm, In Heating/cooling control: 0.1 to 100.0%
downloaded or viewed at the following URL. to output alarm, or velocity alarm. Alarm-1 to 4 type
04: SP low limit
05: Deviation high limit
action (OH) output high limit (in
105.0% (OL<OH)
Alarm-1 to -4 setpoint -19999 to 30000 (Set a value within the 0 (0) Heating/cooling control)
Example: Alarm-1 06: Deviation low limit Ener-
http://www.yokogawa.com/ns/ut/im/ (A1 to A4)
input range.)
07: Deviation high and low limits gized
Control output low limit -5.0 to 104.9%, (OL<OH), SD: Tight
Decimal point position depends on the
input type to Alarm 08: Deviation within high and low limits (0)
Heating-side control
output low limit (in Heat-
shut
In Heating/cooling control: 0.0 to
0.0%
09: Target SP high limit (OL)
Operation Parameters For the parameter SP (target setpoint), 4 groups are displayed for the factory default. (AL1 to AL4)
Latch action
Energized/
type
10: Target SP low limit
11: Target SP deviation high limit
AL2,
AL4:
ing/cooling control) 104.9% (OL<OH)
Enabled when integral time is OFF.
The number of groups can be changed by the setup parameter SPGR. (number of SP De-energize
12: Target SP deviation low limit Latch The manual reset value equals the
Hold down the PARAMETER key or PARA key for 3 seconds to move from the Opera- Stand-by Manual reset 50.0%
groups). For the alarm setpoint parameter, alarm-1 to -4 are displayed for the factory 13: Target SP deviation high and low limits action (MR) output value when PV = SP.
action 14: Target SP deviation within high
tion Display to the Operation Parameter Setting Display. Press the DISPLAY key or default. The number of alarms can be changed using the setup parameter ALNO. (0) -5.0 to 105.0%
and low limits Ener-
DISP key once to return to the Operation Display. (number of alarms). To change the number of SP groups or alarms, see User's Manual 15: OUT high limit gized EASY
In
ON/OFF
Operation Dsipaly DISPLAY key (IM 05P01D31-01EN). 16: OUT low limit (0) control
17: Cooling-side OUT high limit Without Table
Hold down PARAMETER key or PARA key or DISP key Use the following table to record SP and alarm setpoints. or
18: Cooling-side OUT low limit Stand- below
for 3 sec. Two-
Parameter n=1 n=2 n=3 n=4 19: Analog input PV high limit by
Menu Menu Menu END position
20: Analog input PV low limit action
key SP two-level EASY
key 27: Feedback input high limit (0)
SUB Hysteresis (in ON/OFF control:
SET/ENTER key PARAMETER key 28: Feedback input low limit PV low control, Position In ON/OFF control or Two-position 0.5 % of
or PARA key PIDN 29: PV velocity limit (02) proportional control, or two-level control: 0.0 to 100.0% of PV input
Menu Display and 30: Fault diagnosis
Parameter Parameter Parameter A1 Two-position two-level PV input range span (EUS) range
Parameter Setting 31: FAIL
(HYS) control) span
key key key Display are changed A2 Heating-side ON/OFF In Heating/cooling control or Position
in a circular pattern. A3 control hysteresis (in proportional control: 0.0 to 100.0% In Heat-
Parameter Parameter Parameter
END END END A4
to PV velocity alarm time
Heating/cooling control) ing/
0.01 to 99.59 (minute.second) 1.00 cooling
setpoint 1 to 4 control
n: group number
The parameter groups can be switched using , keys. (VT1 to VT4) or
Set a display value of setpoint of Position
■ SP-related Setting Parameter
Move to the Setup Parameter Setting Display:
hysteresis. proportional
Hold down the PARAMETER key or PARA key and the Left arrow key simultaneously
-19999 to 30000 (Set a value within control:
for 3 sec. Menu symbol: (SPS) to the input range.) 0.5 %
Alarm-1 to -4 hysteresis Decimal point position depends on 10 0.5 %
Parameter Initial User Display
Operation for Setting symbol
Name of Parameter Setting Range
value setting level (HY1 to HY4)
the input type. Sub-hysteresis (in of PV
When the decimal point position for Two-position two-level input
· To select the parameter setting displayed as the initial value, press the Down arrow SP = Remote input x RT + Remote the input type is set to "1", the initial (SU.HY) control) range
key to move to the next parameter. Remote input ratio input bias 1.000 value of the hysteresis is "1.0".
(RT) span
0.001 to 9.999
· To change and set the parameter setting, press the SET/ENTER key to start the set-
0.0 %
to Alarm-1 to -4 On-delay
An alarm output is ON when the delay
timer expires after the alarm setpoint 0.5 %
point blinking. The blinking state allows you to make changes (setting mode). Use the STD 0.00
of PV timer is reached. of PV
-100.0 to 100.0% of PV input range Upper-side hysteresis 0.0 to 100.0% of PV input range
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to Remote input bias input 0.00 to 99.59 (minute.second) input
span (EUS) (DYN1 to DYN4) STD (HY.UP) (in ON/OFF control) span (EUS)
(RBS) range range
register the setting. 0: Always active span
span
Note that there are some parameters which are not displayed depending on the model Alarm mode 1: Not active in STOP mode 0
Used to prevent SP from changing (AMD) 2: Not active in STOP or MAN mode 0.5 %
and suffix codes, control type (CNT), etc. The parameters for professional setting mode SP ramp-up rate suddenly. OFF of PV
Lower-side hysteresis
(LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01D31-01EN). (UPR) Set a ramp-up rate or ramp-down rate For the alarm function setting parameter, 4 alarms are displayed for the factory default. (in ON/OFF control)
input
per hour or minute. Set a time unit (HY.LO) range
The number of alarms can be changed by the setup parameter ALNO. (number of
■ Operation Mode
using the parameter TMU. span
SP ramp-down rate OFF, 0.0 + 1 digit to 100.0% of PV OFF EASY
alarms). To change the number of alarms, see User's Manual (IM 05P01D31-01EN).
(DNR) input range span (EUS)
Menu symbol: (MODE) Parameter n=1 n=2 n=3 n=4 Direct/reverse action
HOUR: Ramp-up rate or ramp-down RVS
ALn (DR) switch
Parameter Initial User Display rate per hour
Name of Parameter Setting Range SP ramp-rate time unit HOUR RVS: Reverse action
symbol value setting level MIN: Ramp-up rate or ramp-down VTn STD
(TMU) Sub-direct/reverse DIR: Direct action
STOP: Stop mode rate per minute HYn action switch (in Two-
RUN: Run mode Tracking is performed when the mode DIR
DYNn (SU.DR) position two-level
Preset output (PO) is generated in changes from Remote to Local. (The control)
STOP/RUN switch RUN
(S.R) STOP mode. SP tracking selection local setpoint keeps track of the ON n: alarm number
Default: Not displayed. STOP/RUN (SPT) 0.0 to 999.9%
remote setpoint.)
switch is assigned to contact input. Cooling-side propor- (Cooling-side ON/OFF control
OFF, ON 5.0%
LCL: Local mode Causes the setpoint to keep track of ■ PV-related Setting Parameter (Pc) tional band applies when 0.0% in Heating/cool-
ing control)
REM: Remote mode the PV so the setpoint automatically
REMOTE/LOCAL switch LCL STD Menu symbol: (PVS)
(R.L) (Displayed only in cases where the reverts to its original value at a preset Cooling-side integral OFF: Disable
communication is specified.) 240 s
rate of change. The UPR, DNR, and Parameter Initial User Display (Ic) time 1 to 6000 s
PV tracking selection TMU are used in combination. Oper- OFF Name of Parameter Setting Range
OFF: Disable symbol value setting level
1 to 4: Perform auto-tuning. Tuning EASY (PVT) ating conditions: 1) MAN → AUTO, 2) Cooling-side derivative OFF: Disable
0.0 % 60 s
result is stored in the specified num- STOP → AUTO, 3) Power-on, 4) SP (Dc) time 1 to 6000 s
AUTO-tuning switch OFF number change, 5) SP change of PV
(AT) bered PID. -100.0 to 100.0% of PV input range
OFF, ON PV input bias input Cooling-side control
R: Tuning result is stored in the PID (BS) span (EUS) 0.1 to 105.0%, (OLc<OHc) 100.0%
range output high limit
for reference deviation. EASY (OHc)
span
1 to 4 (Depends on the setup param- Cooling-side control
SP number selection 1 0.0 to 104.9%, (OLc<OHc) 0.0%
(SPNO.) eter SPGR. setting.) PV input filter OFF, 1 to 120 s OFF (OLc) output low limit
(FL)
The PID group number being selected Cooling-side ON/OFF EASY
is displayed. 0.0 to 100.0% 0.5%
PID number 1 (HYSc) control hysteresis
(PID) 1 to 4, R: PID group for reference
deviation Output dead band (in In Heating/cooling control: -100.0 to
Heating/cooling control 50.0%
3.0%
(DB) or Position proportional In Position proportional control: 1.0
■ SELECT Parameter control) to 10.0%
Preset output In STOP mode, fixed control output
Menu symbol: (CS) Heating-side preset can be generated. In Position propor-
0.0%
Parameter Initial User Display (PO) output (in Heating/cool- tional control, Valve opening can be
Name of Parameter Setting Range ing control) set; -5.0 to 105.0%
symbol value setting level
Setting range of a registered param- Sub-preset output (in In STOP mode, fixed sub-control
Registered
SELECT parameter 10 eter. Table Two-position two-level output can be generated. 0%
parameter — EASY (SU.PO) control) 0%, 100%
to 19 For details, see User's Manual (IM below
symbol 05P01D31-01EN). In STOP mode, cooling-side fixed
Cooling-side preset
control output can be generated. 0.0%
Parameter n=10 n=11 n=12 n=13 n=14 n=15 n=16 n=17 n=18 n=19 (POc) output
-5.0 to 105.0%
CSn
For the PID setting parameter, 4 groups are displayed for the factory default.
For the registration of SELECT parameters, see User's Manual (IM 05P01D31-01EN). The number of groups can be changed by the setup parameter PIDG. (number of PID
groups). To change the number of PID groups, see User's Manual (IM 05P01D31-01EN).
IM 05P01D31-11EN page 9/12
If you are using two or more groups of PID parameters, use the following table to record their setting values.
Setup Parameters ■ PV Input Setting Parameter
Parameter n=2 n=3 n=4 R ■ Zone Control Parameter
P Hold down the PARAMETER key or PARA key and Left arrow key simultaneously for 3 Menu symbol: (PV)
Menu symbol: (ZONE)
I seconds to move from the Operation Display or Operation Parameter Setting Display to Parameter Initial User Display
Parameter Initial User Display Name of Parameter Setting Range
Name of Parameter Setting Range symbol value setting level
D symbol value setting level the Setup Parameter Setting Display.
OH Press the DISPLAY key or DISP key once to return to the Operation Display. OFF: Disable
Set reference points at which switch-
K1: -270.0 to 1370.0 0C / -450.0 to 2500.0 0F
OL to ing is carried out between groups of
PID constants according to the given
100.0%
of PV Table
Operation Dsipaly K2: -270.0 to 1000.0 0C / -450.0 to 2300.0 0F
MR Reference point 1 to 3 DISPLAY key K3: -200.0 to 500.0 0C / -200.0 to 1000.0 0F
temperature zone. input below Hold down PARAMETER key or PARA key and
J: -200.0 to 1200.0 0C / -300.0 to 2300.0 0F
HYS (RP1 to RP3) 0.0 to 100.0% of PV input range (EU) range Left arrow key simultaneously for 3 sec. or DISP key
T1: -270.0 to 400.0 0C / -450.0 to 750.0 0F
(RP1 ≤ RP2 ≤ RP3)
SU.HY T2: 0.0 to 400.0 0C / -200.0 to 750.0 0F
0.5 % Menu Menu Menu END B: 0.0 to 1800.0 0C / 32 to 3300 0F
HY.UP Hysteresis can be set for switching at
of PV key S: 0.0 to 1700.0 0C / 32 to 3100 0F
Zone PID switching a reference point. key
HY.LO input R: 0.0 to 1700.0 0C / 32 to 3100 0F
(RHY) hysteresis 0.0 to 10.0% of PV input range span STD PARAMETER key
range SET/ENTER key N: -200.0 to 1300.0 0C / -300.0 to 2400.0 0F
DR (EUS)
span or PARA key E: -270.0 to 1000.0 0C / -450.0 to 1800.0 0F
SU.DR Set a deviation from SP. The PID for
Menu Display and L: -200.0 to 900.0 0C / -300.0 to 1600.0 0F
Parameter Parameter Parameter Parameter Setting
Pc reference deviation is used if there U1: -200.0 to 400.0 0C / -300.0 to 750.0 0F
is a larger deviation than the preset Display are changed U2: 0.0 to 400.0 0C / -200.0 to 1000.0 0F
Ic key key key
Reference deviation reference deviation. OFF in a circular pattern. W: 0.0 to 2300.0 0C / 32 to 4200 0F
PV input type OFF
Dc (RDV) OFF: Disable Parameter Parameter Parameter (IN) PL2: 0.0 to 1390.0 0C / 32.0 to 2500.0 0F
0.0 + 1 digit to 100.0% of PV input END END END P2040: 0.0 to 1900.0 0C / 32 to 3400 0F
OHc WRE: 0.0 to 2000.0 0C / 32 to 3600 0F
range span (EUS)
OLc JPT1: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
For Zone control, set the setup parameter ZON (zone PID selection) to Zone PID se- Move to the Operation Parameter Setting Display: JPT2: -150.0 to 150.0 0C / -200.0 to 300.0 0F
HYSc Hold down the PARAMETER key or PARA key for 3 sec. PT1: -200.0 to 850.0 0C / -300.0 to 1560.0 0F
lection.
DB PT2: -200.0 to 500.0 0C / -300.0 to 1000.0 0F
Use the following table to record the reference point setting value.
PT3: -150.00 to 150.00 0C / -200.0 to 300.0 0F
PO
Parameter n=1 n=2 n=3 0.4-2V: 0.400 to 2.000 V
SU.PO Operation for Setting 1-5V: 1.000 to 5.000 V
RPn 4-20: 4.00 to 20.00 mA
POc · To select the parameter setting displayed as the initial value, press the Down arrow 0-2V: 0.000 to 2.000 V
n: group number key to move to the next parameter. 0-10V: 0.00 to 10.00 V
■ P Parameter (for Ladder Program) · To change and set the parameter setting, press the SET/ENTER key to start the set- 0-20 : 0.00 to 20.00 mA
EASY
-1020: -10.00 to 20.00 mV
■ Tuning Parameter Menu symbol: (PPAR) point blinking. The blinking state allows you to make changes (setting mode). Use the 0-100: 0.0 to 100.0 mV
Up/Down/Left/Right arrow keys to change the setpoint. Press the SET/ENTER key to -: No unit, C: Degree Celsius
Menu symbol: (TUNE) Parameter Initial User Display
symbol
Name of Parameter Setting Range
value setting level register the setting. PV input unit -: No unit, - -: No unit, - - -: No unit, C
Parameter Initial User Display (UNIT) F: Degree Fahrenheit
Name of Parameter Setting Range Note that there are some parameters which are not displayed depending on the Model
symbol value setting level to -19999 to 30000 (Set a decimal point
Table and Suffix codes, control type (CNT), etc. The parameters for professional setting mode Maximum value of PV
Depends on the input type. Depends
OFF: Disable P01 to P10 parameter position using LL50A Parameter Set- 0 STD - For temperature input - on the
below (LEVL: PRO) are not described in this manual. See User’s Manual (IM 05P01D31- (RH) input range
1: Overshoot suppressing function ting Software.) Set the temperature range that is input type
(normal mode) (P01 to P10)
01EN). actually controlled. (RL<RH)
2: Hunting suppressing function - For voltage / current input -
Parameter n=01 n=02 n=03 n=04 n=05 n=06 n=07 n=08 n=09 n=10
(stable mode) Set the range of a voltage / current
Enables to answer the wider Pn ■ Control Function Setting Parameter signal that is applied.
characteristic changes compared The scale across which the voltage/ Depends
Menu symbol: (CTL) Minimum value of PV
with response mode. current signal is actually controlled on the
(RL) input range
3: Hunting suppressing function Parameter Initial User Display should be set using the maximum input type
Name of Parameter Setting Range
(response mode) symbol value setting level value of input scale (SH) and mini-
Enables quick follow-up and short mum value of input scale (SL).
PID: PID control PID
converging time of PV for the (Input is always 0% when RL = RH.)
Super function OFF EASY ONOF: ON/OFF control (1 point of or
(SC) changed SP.
hysteresis) H/C 0: No decimal place
4: Overshoot suppressing function 1: One decimal place Depends
ONOF2: ON/OFF control (2 points of (for PV input scale decimal
(strong suppressing mode) Control type EASY 2: Two decimal places on the
(CNT) hysteresis) Heat- point position
Note: Setpoints 2 and 3 must be (SDP) 3: Three decimal places input type
2P2L: Two-position two-level control ing/
used in PID control or PI control. 4: Four decimal places
H/C: Heating/cooling control Cooling
Disabled in the following controls:
type) Depends
1) ON/OFF control, 2) PD control, Maximum value of PV
3) P control, 4) Heating/cooling on the
Set a number of SP groups to use. (SH) input scale
control. Number of SP groups 4 -19999 to 30000, (SL<SH), input type
(SPGR.) 1 to 4
Do not use the function for the | SH - SL | ≤ 30000 Depends
control processes with response If set to “SP group number selection,” Minimum value of PV
on the
such as flow or pressure control. allows PID constants to be selected (SL) input scale
input type
for each SP group.
0: Normal If set to “Zone PID selection,” OFF: Disable Depends
Auto-tuning type 0 PV input burnout action UP: Upscale on the
(AT.TY) 1: Stability automatically selects PID constants (BSL) DOWN: Downscale input type
according to the range set in the
Anti-reset windup
Zone PID selection Reference point. 0 STD 0.0 % of
(excess integration AUTO, 50.0 to 200.0% AUTO (ZON)
(AR) 0: SP group number selection 1 -100.0 to 100.0% of each input range PV input
prevention) PV analog input bias STD
1: Zone PID selection (selection by PV) (A.BS) span (EUS) range
OFF: Disable 2: Zone PID selection (selection by span
Output velocity limiter OFF target SP)
(OPR) 0.1 to 100.0%/s
3: SP group number selection 2
PV analog input filter OFF, 1 to 120 s OFF
Select the output used in MAN mode 4: Zone PID selection (selection by SP) (A.FL)
when switched from AUTO to MAN
mode. Set a number of PID groups to use. W: W-5% Re/W-26% Re(Hoskins Mfg.Co.). ASTM E988, WRE: W97Re3-W75Re25
Number of PID groups 4
OFF: Hold the control output in AUTO (PIDG.) 1 to 4
mode (bumpless)
1: Use manual preset output 1 (output
STD ■ Input Range, SP Limiter Setting Parameter
bump)
Manual preset output Menu symbol: (MPV)
2: Use manual preset output 2 (output OFF
(MPON) number selection
bump) Parameter Initial User Display
3: Use manual preset output 3 (output Name of Parameter Setting Range
symbol value setting level
bump)
4: Use manual preset output 4 (output -: No unit
bump) C: Degree Celsius Same
5: Use manual preset output 5 (output -: No unit as PV
Control PV input unit
bump) (P.UNI) - -: No unit input
- - -: No unit unit
to Manual preset output 1
-5.0 to 105.0%
Table
F: Degree Fahrenheit
However, output is limited to the 0.0%
to 5 below 0: No decimal place
output high limit and low limit.
(MPO1 to MPO5) 1: One decimal place Depends
Control PV input decimal
2: Two decimal places on the
Use the following table to record the manual preset output setting value. (P.DP) point position
3: Three decimal places input type
Parameter n=1 n=2 n=3 n=4 n=5 4: Four decimal places

MPOn Depends
Maximum value of
on the
(P.RH) control PV input range
-19999 to 30000, (P.RL<P.RH), input type STD
| P.RH - P.RL | ≤ 30000
Depends
Minimum value of control
on the
(P.RL) PV input range
input type

100.0 %
of PV
SP high limit
(SPH) input
range
0.0 to 100.0% of PV input range (EU),
(SPL<SPH)
0.0 %
of PV
SP low limit
(SPL) input
range

IM 05P01D31-11EN page 10/12


■ Output Setting Parameter ■ Heater Break Alarm Setting Parameter ■ Ethernet Communication Setting Parameter (E3-terminal Area) ■ CC-Link Communication Setting Parameter (UT35A: E3-terminal Area,
Menu symbol: (OUT) Menu symbol: (HBA) Menu symbol: (ETHR)
UT32A: E1-terminal Area)
Parameter Initial User Display Parameter Initial User Display Parameter Initial User Display Menu symbol: (CC-L)
Name of Parameter Setting Range Name of Parameter Setting Range Name of Parameter Setting Range
symbol value setting level symbol value setting level symbol value setting level
Parameter Initial User Display
Name of Parameter Setting Range
Control output or Heating-side control Heater break alarm-1 High-speed response symbol value setting level
output (Lower two digits) 1 OFF, 1 to 8 1
(HB1.S) function selection 0: Heater current measurement (HSR) mode 156K: 156k bps
00: OFF 1: Heater break alarm (Heating-side) 625K: 625k bps
01: OUT terminals (voltage pulse) Heater break alarm-2 2: Cooling-side heater break alarm 9600: 9600 bps
1 Baud rate 2.5K: 2.5k bps 10M
02: OUT terminals (current) function selection (BPS) Baud rate 19200: 19.2k bps 38400 (BR)
(HB2.S) 5M: 5M bps
03: OUT terminals (relay) 38400: 38.4k bps
10M: 10M bps
Output type selection 06: OUT2 terminals (relay) Standard Heater break alarm-1 NONE: None
07: RET/OUT2 terminals (voltage type: OFF
(HB1) current setpoint Parity EVEN: Even EVEN
pulse) 00.03 (PRI) Address 1 to 64 1
OFF, 0.1 to 300.0 Arms EASY ODD: Odd (ADR)
08: RET/OUT2 terminals (current) EASY
Heater break alarm-2
OFF
(OT) Upper two Cooling-side control output (Upper Heating/
(HB2) current setpoint to 0 to 255
Initial value: Table
9600: 9600 bps
digits two digits) cooling IP address 1 to 4 See left Baud rate 19200: 19.2k bps 38400
Lower two 00: OFF type: CT1 (IP1).(IP2).(IP3).(IP4) = below (BPS) 38400: 38.4k bps
digits 01: OUT terminals (voltage pulse) 06.03 coil winding number ratio
800 (IP1 to IP4) (192).(168).(1).(1)
(CT1.T)
02: OUT terminals (current) 1 to 3300 0 to 3 and 6
03: OUT terminals (relay) CT2 to 0 to 255
Initial value: Table Profile number (0, 1 and 6: Ver.1.10) (2 and 3: 0
06: OUT2 terminals (relay) 800 Subnet mask 1 to 4 See left (FILE) Ver.2.00)
(CT2.T) coil winding number ratio (SM1).(SM2).(SM3).(SM4) = below
07: RET/OUT2 terminals (voltage (SM1 to SM4) (255).(255).(255).(0)
pulse) Heater break alarm-1
08: RET/OUT2 terminals (current) (HDN1) On-delay timer
0.00
to 0 to 255
Initial value: Table
■ Key Action Setting Parameter
Control output cycle time 0.00 to 99.59 (m.s) STD Default gateway 1 to 4 See left EASY
Heater break alarm-2 (DG1).(DG2).(DG3).(DG4) = below Menu symbol: (KEY)
Heating-side control 0.00 (0).(0).(0).(0)
30.0 s On-delay timer (DG1 to DG4)
(CT) output cycle time (in (HDN2)
Parameter Initial User Display
Heating/cooling control) EASY Name of Parameter Setting Range
0.5 to 1000.0 s In cases where the current transformers manufactured by U.R.D. Co., Ltd are used, set Port number 502, 1024 to 65535 502 symbol value setting level
(PRT)
the following value for the coil winding number ratio. OFF: Disable
Cooling-side control
30.0 s A/M: AUTO/MAN switch
(CTc) output cycle time CTL-6-S-H: 800 IP access restriction OFF: Disable, ON: Enable OFF User function key-1 R/L1: REM/LCL switch
(IPAR) OFF
CTL-12L-30: 3000 (F1) action setting S/R: STOP/RUN switch
Automatic valve position OFF: Stop automatic adjustment
OFF to 0 to 255
AUTO: Switch to AUTO
MAN: Switch to MAN
■ RS-485 Communication Setting Parameter (UT35A: E3-terminal
adjustment ON: Start automatic adjustment
(V.AT)
, Permitted IP address 1-1 Initial value: REM1: Switch to REM
Setting V.RS to ON resets the valve
Valve position setting
adjustment settings and causes the OFF Area, UT32A: E1-terminal Area) to to 1-4
Permitted IP address 2-1
(1.IP1).(1.IP2).(1.IP3).(1.IP4) =
(255).(255).(255).(255)
See left
Table
below User function key-2
LCL1: Switch to LCL
STOP: Switch to STOP EASY
reset OFF
(V.RS) indication “V.RS” to blink. to 2-4 (2.IP1).(2.IP2).(2.IP3).(2.IP4) = (F2) action setting RUN: Switch to RUN
Menu symbol: (R485)
(1.IP1 to 1.IP4, (255).(255).(255).(255) AT: Auto-tuning
Pressing the SET/ENTER key with
Parameter Initial User Display 2.IP1 to 2.IP4) LTUP: LCD brightness UP
valve position set to the fully-closed Name of Parameter Setting Range
symbol value setting level LTDN: LCD brightness DOWN
Fully-closed valve posi- position by Down arrow key causes Setting this parameter to “ON”
- BRI: Adjust LCD brightness
(V.L) tion setting the adjusted value to be stored. When PCL: PC link communication enables the Ethernet communication User function key-n
Ethernet setting switch OFF LCD: LCD backlight ON/OFF switch PID
V.L adjustment is complete, V.L stops PCLSM: PC link communication (with parameter settings. action setting
(ESW) (Fn) LAT: Latch release
blinking. checksum) OFF, ON PID: PID tuning switch
Pressing the SET/ENTER key with LADR: Ladder communication
Use the following table to record Ethernet communication setting value.
valve position set to the fully-opened CO-M: Coordinated master station
Fully-opened valve posi- position by Up arrow key causes the CO-S: Coordinated slave station Parameter n=1 n=2 n=3 n=4
(V.H) tion setting adjusted value to be stored. When V.H
- Protocol selection MBASC: Modbus (ASCII) MBRTU
IPn
■ Display Function Setting Parameter
adjustment is complete, V.H stops (PSL) MBRTU: Modbus (RTU)
CO-S1: Coordinated slave station SMn Menu symbol: (DISP)
blinking
(Loop-1 mode) Parameter Initial User Display
DGn Name of Parameter Setting Range
Valve traveling time 5 to 300 s 60 s CO-S2: Coordinated slave station symbol value setting level
(TR.T) (Loop-2 mode) 1.IPn
P-P: Peer-to-peer communication 0: Fixed in white
0: Valve position feedback type 2.IPn 1: Fixed in red
1: Valve position feedback type STD 600: 600 bps 2: Link to alarm 1 (Alarm OFF: white,
(moves to the estimating type if a 1200: 1200 bps Alarm ON: red)
(V.MOD)
Valve adjusting mode
feedback input error or break oc-
0
Baud rate
2400: 2400 bps
4800: 4800 bps 19200
EASY ■ PROFIBUS-DP Communication Setting Parameter (E3-terminal Area) 3: Link to alarm 1 (Alarm OFF: red,
Alarm ON: white)
curs.)
2: Valve position estimating type (BPS) 9600: 9600 bps 4: Link to alarm 1 or 2 (Alarm OFF:
Menu symbol: (PROF)
19200: 19.2k bps white, Alarm ON: red)
38400: 38.4k bps Parameter Initial User Display Active color PV display 5: Link to alarm 1 or 2 (Alarm OFF:
OFF: Disable Name of Parameter Setting Range red, Alarm ON: white) 0
PV1: PV symbol value setting level switch
NONE: None (PCMD) 6: PV limit (Within range: white, Out
SP1: SP Parity EVEN: Even EVEN 9.6K: 9.6k bps of range: red)
OUT1: OUT (Valve opening: 0 to 100 (PRI) ODD: Odd 19.2K: 19.2k bps 7: PV limit (Within range: red, Out of
% in Position proportional control) EASY
93.75K: 93.75k bps range: white)
Retransmission output LPS: 15 V DC loop power supply Stop bit 1: 1 bit, 2: 2 bits 1 187.5K: 187.5k bps 8: SP deviation (Within deviation:
PV1 EASY white, Out of deviation: red)
(RTS) type of RET TSP1: Target SP (STP) 0.5M: 0.5M bps
HOUT1: Heating-side OUT Baud rate 1.5M: 1.5M bps AUTO 9: SP deviation (Within deviation: red,
COUT1: Cooling-side OUT (BR) 3M: 3M bps Out of deviation: white)
Data length 7: 7 bits, 8: 8 bits 8 10: Link to DI (ON: red, OFF: white)
MV1: Position proportional output (DLN) 6M: 6M bps
(internal computed value) 12M: 12M bps PV color change high Set a display value when in PV limit
PV: PV terminals analog input AUTO or SP deviation. 0
Address 1 to 99 1 (PCH) limit
(ADR) 45.45K: 45.45k bps EASY -19999 to 30000 (Set a value within
the input range.)
When RTS = PV1, SP1, TSP1, PV 100 % PV color change low limit Decimal point position depends on 0
Maximum value of Address 0 to 125 3
RTL + 1 digit to 30000 of PV (ADR) (PCL) the input type.
retransmission output -19999 to RTH - 1 digit
(RTH) input
scale of RET Decimal point position: 9600: 9600 bps 0: Disable
range
When RTS=PV1, SP1, or TSP1, Baud rate 19200: 19.2k bps 38400 1: OUT, Heating-side OUT, Internal value
decimal point position is same as (BPS) 38400: 38.4k bps in Position proportional control
0% 2: Cooling-side OUT
Minimum value of that of PV input.
of PV 3: PV 5
retransmission output When RTS=PV, decimal point position Profile number 0 to 3 0
(RTL) input Bar-graph display regis- 4: SP (Heating
scale of RET is same as that of PV input scale. (FILE)
range (BAR1) tration 5: Deviation /cooling
6 to 16: Disable type: 1)
Retransmission output 17: Feedback input (valve opening)
(O1RS)
type of OUT current Same as RTS OFF ■ DeviceNet Communication Setting Parameter (E3-terminal Area) 18: PV terminals analog input
output 24: TSP
Menu symbol: (DNET) 25: TSP deviation

Parameter Initial User Display 1.0 %


Name of Parameter Setting Range of PV STD
symbol value setting level Bar-graph deviation 0.0 to 100.0% of PV input range span
Maximum value of input
125K: 125k bps (BDV) display band (EUS)
retransmission output range
- 250K: 250k bps
(O1RH) scale of OUT current When O1RS = PV1, SP1, TSP1, PV, Baud rate 125K span
output STD (BR) 500K: 500k bps
O1RL + 1 digit to 30000
-19999 to O1RH - 1 digit Guide display ON/OFF OFF: Nondisplay, ON: Display ON
Decimal point position: (GUID)
When O1RS=PV1, SP1, or TSP1, Address 0 to 63 63 OFF: Disable
decimal point position is same as (ADR)
1: Economy mode ON (All indications
that of PV input. EASY except PV display OFF)
When O1RS =PV, decimal point posi- 9600: 9600 bps Economy mode OFF
(ECO) 2: Economy mode ON (All indications
tion is same as that of PV input Baud rate 19200: 19.2k bps 38400
Minimum value of OFF)
scale. (BPS) 38400: 38.4k bps
retransmission output 3: Brightness 10 % (whole indication)
-
(O1RL) scale of OUT current
output Brightness (Dark) 1 to 5 (Bright) 3 EASY
Profile number 0 to 3 0 (BRI)
(FILE)
Least significant digital OFF: With least significant digit
OFF STD
(MLSD) mask of PV display ON: Without least significant digit
OUT current output
4-20: 4 to 20 mA 4-20 Method for least signifi-
(OU.A) range
0-20: 0 to 20 mA cant digital mask of PV 0: Rounding, 1: Rounding-off 0 STD
20-4: 20 to 4 mA (MKTP) display
RET current output
20-0: 20 to 0 mA 4-20
(RET.A) range

IM 05P01D31-11EN page 11/12


■ SELECT Display Setting Parameter ■ AL1-AL3 Function Registration Parameter ■ Error and Version Confirmation Parameter (for display only)
Menu symbol: (CSEL) Menu symbol: (ALM) Menu symbol: (VER)
Parameter Initial User Display Parameter Initial User Display Parameter Display
Name of Parameter Setting Range Name of Parameter Setting Range Name of Parameter Status record
symbol value setting level symbol value setting level symbol level
Register the operation parameter Set an I relay number. For the items
(except the Operation Mode) that is other than below, see Communication Parameter error status
to SELECT Display-1 to -5
frequently modified to display it in the
Table (AL1.S)
AL1 function selection
User's Manual.
4353 (PA.ER)
Operation Display. OFF STD Ex.) Set the number 4353 for AL1.S
registration below
OFF, 2301 to 5000, 6701 to 6710 to use the alarm 1. Option error status
(CS1 to CS5) (OP.ER)
For the setting range, see Communi- Set “OFF” to disable the function.
cation User's Manual. AL2 function selection 4354
(AL2.S) No function: OFF A/D converter error status 1
Use the following table to record SELECT Display setting value. Alarm 1: 4353 (AD1.E)
Parameter n=1 n=2 n=3 n=4 n=5 Alarm 2: 4354
AL3 function selection Alarm 3: 4355 4355 STD A/D converter error status 2
CSn Alarm 4: 4357 (AD2.E)
(AL3.S)

AUTO (OFF) / MAN (ON) status: 4193 PV input error status


■ Key Lock Setting Parameter OUT relay function REM (ON) / LCL (OFF) status: 4194
STOP (ON) / RUN (OFF) status: 4195 OFF
(PV1.E)

(OR.S) selection
Menu symbol: (KLOC) FAIL (Normally ON) output: 4256 Ladder error status
(LA.ER)
Parameter Initial User Display
Name of Parameter Setting Range OUT2 relay function
symbol value setting level OFF MCU version
(OR2.S) selection (MCU)
Communication write
OFF: Enable, ON: Disable OFF
(COM.W) enable/disable DCU version
(DCU) • Authorised Representative in the EEA
Front panel parameter
(DATA) data (▼,▲) key lock
OFF STD ■ DO Setting Parameter (E1/E4-terminal Area) ECU-1 version (E1-terminal area)
Yokogawa Europe BV. (Address: Euroweg 2 , 3825 HD Amersfoort, The
OFF: Unlock, ON: Lock (ECU1) Netherlands) is the Authorised Representative of Yokogawa Electric Corporation
Menu symbol: (DO) EASY
Front panel A/M key lock OFF for this Product in the EEA.
(A/M) Parameter Initial User Display
symbol
Name of Parameter Setting Range
value setting level
ECU-3 version (E3-terminal area) • Printed Manuals
(ECU3)
Model Description
DO11/DO41 function
■ DI Function Registration Parameter (DO1.S) selection
OFF
(ECU4)
ECU-4 version (E4-terminal area) UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide IM 05P01D31-11EN
«Standard Code Model»
Menu symbol: (DI.SL) DO12/DO42 function UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide IM 05P01D31-15EN
OFF Parameter version
(DO2.S) selection (PARA) «Detailed Code Model»
Parameter Initial User Display
Name of Parameter Setting Range UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) IM 05P01D81-11EN
symbol value setting level
Same as AL1.S Table Operation Guide «Standard Code Model»
DO43 function selection OFF STD Product version
(DO3.S) Set “OFF” to disable the function below (H.VER)
AUTO/MAN switch 5025 UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) IM 05P08D31-11EN
(A/M) Operation Guide «Standard Code Model»
DO44 function selection OFF Serial number 1 UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) IM 05P08D81-11EN
(DO4.S) (SER1)
REMOTE/LOCAL switch OFF Operation Guide «Standard Code Model»
(R/L)
DO45 function selection OFF UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote IM 05P01D31-81EN
Serial number 2
STOP/RUN switch (DO5.S) (SER2) Input Type) Operation Guide «Standard Code Model»
5026
(S/R) UT32A Digital Indicating Controller Operation Guide «Entry model» IM 05P01F31-11EN
Use the following table to record DO setting value.
MAC address 1 (E3-terminal area) Precautions on the Use of the UTAdvanced Series IM 05P01A01-11EN
Switch to AUTO OFF Parameter E1-terminal Area E4-terminal Area (MAC1)
(AUTO) • Electronic Manuals
Set an I relay number of contact DO1.S
MAC address 2 (E3-terminal area)
Switch to MAN
input.
OFF DO2.S (MAC2) You can download the latest manuals from the following website:
Set “OFF” to disable the function.
(MAN)
DO3.S URL: http://www.yokogawa.com/ns/ut/im/
MAC address 3 (E3-terminal area)
Standard terminals DO4.S (MAC3) Model Description
Switch to REMOTE OFF STD
(REM) DI1: 5025, DI2: 5026 UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide IM 05P01D31-11EN
DO5.S
«Standard Code Model»

(LCL)
Switch to LOCAL
E1-terminal area
DI11: 5041, DI12: 5042, DI13: 5043,
OFF ■ Parameter Display Level Parameter UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) Operation Guide IM 05P01D31-15EN
DI14: 5044, DI15: 5045 ■ System Setting Parameter Menu symbol: (LVL)
«Detailed Code Model»
Auto-tuning START/STOP UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) IM 05P01D81-11EN
OFF Menu symbol: (SYS) Operation Guide «Standard Code Model»
(AT) switch Parameter Initial User Display
Name of Parameter Setting Range
Parameter Initial User Display symbol value setting level UT35A/UT32A Digital Indicating Controller User’s Manual IM 05P01D31-01EN
Name of Parameter Setting Range
Latch release OFF symbol value setting level EASY: Easy setting mode UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) IM 05P08D31-11EN
(LAT) Set how the controller should recover Parameter display level STD: Standard setting mode STD EASY Operation Guide «Standard Code Model»
(LEVL) PRO: Professional setting mode
LCD backlight ON/OFF from a power failure of 5 seconds or UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) IM 05P08D81-11EN
OFF more. Operation Guide «Standard Code Model»
(LCD) switch * For Professional setting mode, see User’s Manual.
Restart mode CONT: Continue action set before CONT UT32A-D, UT32A-D/MDL Digital Indicating Controller Controller User’s Manual IM 05P08D31-01EN
(R.MD) power failure.
PV red/white switch OFF MAN: Start from MAN. UT35A/RSP, UT32A/RSP Digital Indicating Controller (Non-isolated Remote IM 05P01D31-81EN
(PVRW) AUTO: Start from AUTO. Input, Panel Mounting Type) Operation Guide «Standard Code Model»
UT32A Digital Indicating Controller Operation Guide «Entry Model» IM 05P01F31-11EN
Set time between power on and the
UT32A Digital Indicating Controller User’s Manual «Entry Model» IM 05P01F31-01EN
■ DI Function Numbering Parameter (R.TM)
Restart timer
instant where controller starts compu-
tation.
0 STD
UTAdvanced Series Communication Interface (RS-485, Ethernet) User’s Manual IM 05P07A01-01EN
Menu symbol: (DI.NU) 0 to 10 s UTAdvanced Series Communication Interface (Open Network) User’s Manual IM 05P07A01-02EN
Set preset output value when the LL50A Parameter Setting Software Installation Manual IM 05P05A01-01EN
Parameter Initial User Display input burnout or ADC error occurs.
Name of Parameter Setting Range LL50A Parameter Setting Software User’s Manual IM 05P05A01-02EN
symbol value setting level Manual output is prioritized when the
Input error preset output input burnout occurs in MAN. 0 Precautions on the Use of the UTAdvanced Series IM 05P01A01-11EN
Bit-0 of SP number OFF (EPO) 0: Preset output
(SP.B0) 1: 0% output • General Specification
2: 100% output Model Description
Bit-1 of SP number OFF EASY
(SP.B1) UT35A, UT32A Digital Indicating Controller (Panel Mounting Type) GS 05P01D31-01EN
Power frequency AUTO, 60: 60 Hz, 50: 50 Hz AUTO
(FREQ) UT35A/MDL, UT32A/MDL Digital Indicating Controller (DIN Rail Mounting Type) GS 05P01D81-01EN
Bit-2 of SP number OFF UT32A-D Digital Indicating Controller (Dual-loop, Panel Mounting Type) GS 05P08D31-01EN
(SP.B2) OFF: Disable
Quick setting mode ON UT32A-D/MDL Digital Indicating Controller (Dual-loop, DIN Rail Mounting Type) GS 05P08D81-01EN
Set an I relay number of contact input. (QSM) ON: Enable
Bit-0 of PID number Set “OFF” to disable the function. OFF LL50A Parameter Setting Software GS 05P05A01-01EN
(PN.B0) Depe-
Standard terminals nds * The last two characters of the manual number and general specification number indicate the
ENG: English EASY
Bit-1 of PID number DI1: 5025, DI2: 5026 OFF on the
FRA: French language in which the manual is written.
(PN.B1) Guide display language model
(LANG) GER: German
E1-terminal area and
SPA: Spanish
Bit-2 of PID number DI11: 5041, DI12: 5042, DI13: 5043, OFF suffix
(PN.B2) codes
DI14: 5044, DI15: 5045
STD Trademarks
Bit-0 of manual preset Password setting 0 (No password) to 65535 0
● Our product names or brand names mentioned in this manual are
OFF
(MP.B0) output number (PASS) the trademarks or registered trademarks of Yokogawa Electric Corporation.
Bit-1 of manual preset
● Adobe, Acrobat, and Postscript are either registered trademarks or trademarks
OFF of Adobe Systems Incorporated.
(MP.B1) output number
● Ethernet is a registered trademark of XEROX Corporation in the United States.
Bit-2 of manual preset ● Modbus is a registered trademark of Schneider Electric.
OFF
(MP.B2) output number
● PROFIBUS-DP is a registered trademark of PROFIBUS User Organization.
Bit changing method of SP 0: Status switch 1 ● DeviceNet is a registered trademark of Open DeviceNet Vendor Association.
0 STD
(SP.BC) number 1: Status switch 2 ● CC-Link is a registered trademark of CC-Link Partner Association.
● We do not use the TM or ® mark to indicate these trademarks or
registered trademarks in this manual.
● All other product names mentioned in this manual are trademarks
or registered trademarks of their respective companies.

IM 05P01D31-11EN page 12/12