You are on page 1of 1

Temp.

0 25 40 50 60C
Shift index for long- MULTIPLES OF CURRENT RATING
time delay only.

10000
1000

2000

3000

4000

5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 800
700 700
600 Enclosure compensated. For other 600
500 than 40ºC ambient, shift unity index 500

400
for long-time delay (thermal) 400
portion of curve to desired ambient.
300 300

200 200

100 100
90 90
80 80
70 70
60 Maximum Total 60
TIME IN SECONDS

TIME IN SECONDS
50 Clearing Time 50

40 40

30 30

20 20

Minimum Total
10 Clearing Time 10
9 9
8 8
7 7
6 6
5 5

4 4

3 3

2 2

1 1
.9 .9
.8 .8
.7 .7
.6 .6
GES6239

GES6239
.5 .5
.4 .4

.3 .3
70A
.2 .2

80A

.1 .1
.09 .09
.08 90A .08
.07 .07
.06 .06
.05 .05

.04 100A .04

.03
Application .03
Determines
End of Curve
.02 .02

.01 .01
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
100

200

300

400

500
600
700
800
900
1000

2000

3000

4000

5000
6000
7000
8000
9000
10000

MULTIPLES OF CURRENT RATING


1SQC930032D0201, GES6239 September 2019

Molded Case Circuit Breaker GES6239


Current Ratings Type TEY and TEYF, 70-100 Amperes Adjustments
70, 80, 90 and 100 Amperes Enclosure Compensated Long-time delay thermal trip: not
Voltage Ratings Long-time Delay and Instantaneous adjustable.
1-pole – 277 Vac (125 Vdc) Instantaneous magnetic trip: not
2- and 3- pole – 480 Vac (250 Vdc) Time-current Curves adjustable.
Frequency Ratings Curves show enclosure-compensated circuit
60 Hertz breaker in open air, 40ºC ambient, wired with
conductors of corresponding rating, no prior
load. For all other ambients, use rating shift
index at top of sheet.
GE is a registered trademark used under license from General Electric Company