You are on page 1of 3

DATA SHEET FOR 10000 CFM AIR WASHER UNIT

EQUIPMENT DESCRIPTION AERONOM EQUIPMENTS AND PROJECT


HOUSING
MOC of Outer panel Sheet 0.6 MM G.I. Pre coated Sheet
MOC of Inner panel Sheet 0.6 MM G.I. Sheet
PUF Thickness 25 MM
Density 40 Kg / M³
BLOWER
Blower Material Sheet Steel and Angle Iron
Air Flow 10000 CFM
Type of Blower DIDW Backward Curved
Static Pressure 55 mmwg
Blower Make Nicotra / Kruger Make
BLOWER MOTOR
Motor Type Totally Enclosed Fan Cooled (TEFC)
Volts-Phase –Hz 415 volts ±10% - 3 phase- 50 Hz
Rated H.P. / RPM 7.5 H.P. / 4 Pole
Motor Make Crompton / ABB
DRIVE
Bearing Self-Aligned
Type Belt Driven
Pulley and Belts 2 – B Section
Pulley Type Tapper Lock
COOLING SECTION
Water distribution Through GI Splashier
Cellulose Paper Make Any Reputed Make
Cellulose paper req. 20 Sq. Ft
Pad depth 200 mm
Efficiency 80 - 90%
PVC ELIMINATOR
PVC Eliminator Req. 20 Sq. Ft
WATER PUMP
Pump Make CRI/CG/Any Reputed Make
FILTER SECTION
PRE – FILTERS
Efficiency 90% down to 40 
Frame G.I Sheet
Media Al. Wire Mesh
Filtration area req. 20 Sq. Ft
Filter frame req. 20 Sq. Ft
DATA SHEET FOR 25000 CFM AIR WASHER UNIT
EQUIPMENT DESCRIPTION AERONOM EQUIPMENTS AND PROJECT
HOUSING
MOC of Outer panel Sheet 0.6 MM G.I. Pre coated Sheet

MOC of Inner panel Sheet 0.6 MM G.I. Sheet

PUF Thickness 25 MM

Density 40 Kg / M³

BLOWER

Blower Material Sheet Steel and Angle Iron

Air Flow 25000 CFM

Type of Blower DIDW Backward Curved

Static Pressure 60 mmwg

Blower Make Nicotra / Kruger Make

BLOWER MOTOR

Motor Type Totally Enclosed Fan Cooled (TEFC)

Volts-Phase –Hz 415 volts ±10% - 3 phase- 50 Hz

Rated H.P. / RPM 15.0 H.P. / 4 Pole

Motor Make Crompton / ABB


DRIVE

Bearing Self-Aligned

Type Belt Driven

Pulley and Belts 3 – B Section

Pulley Type Tapper Lock


COOLING SECTION
Water distribution Through GI Splashier
Cellulose Paper Make Any Reputed Make
Cellulose paper req. 50 Sq. Ft
Pad depth 200 mm
Efficiency 80 - 90%
PVC ELIMINATOR
PVC Eliminator Req. 50 Sq. Ft
WATER PUMP
Pump Make CRI/CG/Any Reputed Make
FILTER SECTION
PRE – FILTERS
Efficiency 90% down to 40 
Frame G.I Sheet
Media Al. Wire Mesh
Filtration area req. 50 Sq. Ft
Filter frame req. 50 Sq. Ft

AIR WASHER UNIT

NICOTRA MAKE BLOWER ABB MAKE ELECTRIC MOTOR TAPPER LOCK PULLEY

FENNER MAKE BELTS CELLULOSE COOLING PAD PVC ELIMINATOR