You are on page 1of 60

Powering your way to safety

Since 1972
Powering your way to safety
Since 1972

01
ABOUT US

COMPANY PROFILE
Fire has been the most quintessential discovery made by mankind. But it is also the most dangerous
discovery, as a little negligence can lead to ruin and destruction - "A Spark Neglected Burns the House," as
Tolstoy had written years ago. In cases of fire emergencies, fire extinguishers play crucial roles in
preventing and mitigating casualties caused by fire. Founded in 1972, Safex Fire Services Ltd. is an
eminent manufacturer, exporter, and supplier of various fire fighting equipments.
With excellent after sales services and highly customized products of best quality, we have earned a
golden reputation among our esteemed clients. Our products are exported to many countries in Europe,
Gulf and Asia. We are a proud member of the National Fire Protection Association (NFPA). The company
has established 7 Branch Offices & more than 75 Distributors at several cities in the country for after sales
service.

PRODUCT GALLERY
Safex Fire Services Ltd. is a trusted manufacturer, exporter and supplier of the following products:
Ÿ Fire Extinguishers - ISI, EN & MMD (IRS) APPROVED.
Ÿ Hydrant Products - ISI APPROVED & Customized Hose Boxes
Ÿ Flexible Dropper for Sprinkler System - UL & FM APPROVED.
Ÿ Sprinklers - UL LISTED.
Ÿ Deluge and Alarm Valves - UL & FM APPROVED
Ÿ Fire Tubing Systems
Ÿ Butterfly Valves - UL & FM APPROVED
Ÿ Forrex Fire Suppression Systems.
Ÿ Pre-engineered Easy Spray Sprinkler System
Ÿ Special products: 150/200/300 Kg DCP Fire Extinguishers, 600 Kg DCP Fire Extinguishers, Twin 5050
Fire extinguishers (Mobile and Foam, Powder Fire Extinguisher), etc.
Ÿ Other products: Photo Luminescent Signages, Rosette Plates, Spray Nozzle, Water Monitor, etc.

UNBEATABLE QUALITY
Our company offers safe, efficient and highest quality Fire Fighting Equipments. The products
manufactured by us adhere to the international standards of quality and are as per the ISO, ISI, UL, MMD,
CE and EN 3.7 standards.
Our labs are outfitted with a range of sophisticated testing instruments for ensuring complete quality.
With over Forty years of experience in the field of engineering fire protection devices, we can provide the
right solutions for our customers at cost effective prices.
ROBUST INFRASTRUCTURE
We are equipped with an advanced manufacturing unit comprising of sophisticated machines and
equipments. Our high capacity plants function on completely automated machinery and a big staff of
experienced engineers and technocrats is fully committed towards fulfilling the production targets with
optimum resource utilization.
We have invested substantially in acquiring state-of-the-art machines from Europe for our unit to bring
global standard quality products to our customers. The sustained usage of best manufacturing practices
as well as the experience & support of our personnel give us the necessary edge of our competitors.
POWERING YOUR WAY TO SAFETY

02
OUR CLIENTELE

Many many more.....


03
Powering your way to safety
INDEX Since 1972

Products Pg. No.


§ Alarm Valves & Deluge Valves 06

§ Sprinklers 08

§ Unbraided Flexible Dropper For Sprinkler Systems 10

§ Braided Flexible Dropper For Sprinkler Systems 12

§ Hydrant Accessories 14

§ Dafo Forrex Fire Suppression Systems 16

§ Automatic Fire Tubing Systems 18

§ Aluminum Fire Extinguishers 20

§ Clean Agent Gas Based Fire Extinguishers ( Aluminum) 22

§ Powder Based Fire Extinguishers 24

§ Higher Capacity Stored Pressure 26

§ Stainless Steel Fire Extinguishers 28

§ Water And Foam Based Fire Extinguishers 30

§ Clean Agent Gas Based Fire Extinguishers 32

§ Co2 Gas Based Fire Extinguishers 34

§ Charge Control 35-36

§ Automatic Modular Fire Extinguishers 38

§ EN 3.7 Approved Fire Extinguishers 40

§ Trolley Mounted Foam Based Fire Extinguishers 42

§ Twin 5050 Foam And Powder Based Fire Extinguishers 44

§ Gate Valve 45-54

§ Butterfly Valve 55-56

§ Photo Luminescent Signages & Accessories 57-58

04
05
ALARM VALVE AND DELUGE VALVE Powering your way to safety
Since 1972

ALARM VALVE
Safex Alarm Valve are designed to confirm to International Standard. It is highly anti-corrosive are made of
cast bronze. The Alarm Valve is divided into paddle type, retard chamber type, alarm switch type and groove
type depending on the condition of use.

Specification Assembly Diagram


Model No. FAVB 100R - UL FAVB 150R - UL
Size 100NB 150NB
Approved Standards UL and FM UL and FM
Max, Flow 175 PSI 175 PSI
Test Pressure 350 PSI 350 PSI
Direction Vertical Vertical
Flange ANSI 150lb FF Type ANSI 150lb FF Type
Weight (Kg) 35 53.7
Packing (Ea) 1 1

Dimension
Model No. Size A B C D E F G H
FAVB 100R UL & FM 394 169 50 250 153 353 190.5 8-ø19
FAVB 100(150)R-UL FAVB 150R UL & FM 459 199 50 280 153 378 241.5 8-ø23

Part List
No. Part Material Qty.
1 Alarm Valve Body FC200 1
APPROVED
2 Pressure Switch AC125/250 1
3 Pressure Gauge (Outlet) 1
4 Pressure Gauge (Inlet) 1

DELUGE VALVE
Safex Deluge Valve are designed to minimize the friction loss inside and inner parts such as clapper are made
of cast bronze to offer excellent corrosion and pressure resistance.
Specification Dimension
Model No. PPD 100 PPD 150 Model No. PPD 100 PPD 150
Size 100NB 150NB A 242 259
Approved Standards UL and FM UL and FM B 260 285
Max, Flow 175 PSI 175 PSI C 367 372
Test Pressure 350 PSI 350 PSI D 270 290
Pressure Loss 0.02MPa 0.02MPa E 150 150
Direction Vertical Vertical
Flange Size ANSI 150lb FF Type ANSI 150lb FF Type
PPD 100(150)-UL Weight (Kg) 59 79
Packing (Ea) 1 1

Part List
No. Part No. Part
1 Pre-Action Valve 1 Pressure Valve (Inlet)
APPROVED
2 OS & Y Valve 2 Pressure Valve (Outlet)
3 Air control Valve 3 Drip Check Valve
4 Pressure Gauge (Setting) 4 Pressure Switch Test Valve
5 Pressure Switch 5 Ball Valve
6 Actuating Unit Water Supply Valve 6 Drain Valve
7 Solenid Valve 7 Emergency Relrase Valve

Assembly Diagram

06
07
SPRINKLERS Powering your way to safety
Since 1972

SF Concealed, Pendent, Upright & Sidewall Standard Response and Quick Response Sprinklers

Safex Standard Response Spray Sprinklers are intended for use in the Sprinkler Systems designed in accordance with the
standard installation rules recognized by the applicable listing or approval agency. They are available in Pendent, Uprigh,
Horizontal Sidewall Styles.
Safex Quick Response Spray Sprinklers are designed with a 3mm glass-bulb to react quicker at the specified temperature.
They are available in Pendent, Upright, Horizontal Sidewall Styles.
During a fire conditions, the thermal-sensitive liquid in the Glass Bulb expands, causing the bulb to shatter, releasing the
button and spring seal assembly. Water flowing through the Sprinkler orifice strikes the Sprinkler deflector, forming a
uniform spray pattern to extinguish or control the fire.
Safex Standard and Quick Responders are designed for use in a wild range of applications including office buildings,
libraries, hotels, restaurants, banks, band shells, theaters, factories, and storehouses.

Horizontal Sidewall Sprinkler Upright Sprinkler Pendent Sprinkler Concealed Pendent Concealed Pendent
Model SF001 / SF002 Model SF003 / SF004 Model SF005 / SF006 Sprinkles Model SF007 Sprinkles Model SF008
5/3mm Bulb Type, K-5.6 5/3mm Bulb Type, K-5.6 5/3mm Bulb Type, K-5.6 5mm Bulb Type, K-5.6 3mm Bulb Type, K-5.6

Response: Standard/Quick Response: Standard/Quick Response: Standard/Quick Response: Standard Response: Quick
Coverage: Coverage: Coverage: Coverage: Coverage:
Water discharge is directed Produce a hemispherical water Produce a hemispherical water Produce a hemispherical water Produce a hemispherical water
primarily outward and distribution pattern below the distribution pattern below the distribution pattern below the distribution pattern below the
downward in a quarter deflector. deflector. deflector. deflector.
spherical pattern, a portion of
the spray is also directed Installation: Installation: Installation: Installation:
towards the backwall. Upright installed in accordance Pendent installed in Pendent installed in Pendent installed in
with the standard installation accordance with the standard accordance with the standard accordance with the standard
Installation: rules recognized by the installation rules recognized by installation rules recognized by installation rules recognized by
Designed for installation along applicable Listingor Approval the applicable Listingor the applicable Listingor the applicable Listingor
a wall or the side of a beam agency Approval agency Approval agency Approval agency
just beneath a smooth (Ref. NFPA 13 requirements). (Ref. NFPA 13 requirements). (e.g. NFPA 13 requirements). (e.g. NFPA 13 requirements).
ceiling.(Ref.NFPA13)
Orifice Size: ½"/15mm Orifice Size: ½"/15mm Orifice Size: ½"/15mm Orifice Size: ½"/15mm
Orifice Size: ½"/15mm
Thread Size: ½" Pipe thread Thread Size: ½" Pipe thread Thread Size: ½" Pipe thread Thread Size: ½" Pipe thread
Thread Size: ½" Pipe thread
Temp. Rating: Temp. Rating: Temp. Rating: Temp. Rating:
Temp. Rating: 135°F/57°C, 155°F/68°C 135°F/57°C, 155°F/68°C 135°F/57°C, 155°F/68°C 135°F/57°C, 155°F/68°C
135°F/57°C, 155°F/68°C 175°F/79°C, 200°F/93°C 175°F/79°C, 200°F/93°C 175°F/79°C, 200°F/93°C 175°F/79°C, 200°F/93°C
175°F/79°C, 200°F/93°C
Maximum Service Pressure: Maximum Service Pressure: Maximum Service Pressure: Maximum Service Pressure:
Maximum Service Pressure: 175 psig / 1.2MPa(12bar) 175 psig / 1.2MPa(12bar) 175 psig / 1.2MPa(12bar) 175 psig / 1.2MPa(12bar)
175 psig / 1.2MPa(12bar)
Listings and Approvals: UL Listings and Approvals: UL Listings and Approvals: UL Listings and Approvals: UL
Listings and Approvals: UL
Finishes: Finishes: Finishes: Finishes:
Finishes: Natural brass, chrome plate Natural brass, chrome plate Cover plates are supplied Cover plates are supplied
Natural brass, chrome plate chrome plated or with any chrome plated or with any
color factory applied paint color factory applied paint

*Rosette Plates for Sprinklers are available in White and Chrome finish.

APPROVED

08
09
FLEXIBLE DROPPER FOR SPRINKLER SYSTEM Powering your way to safety
Since 1972

SAFEX UNBRAIDED TYPE SPRINKLER HOSE


SIMPLIFIED INSTALLATION, EASY RELOCATION. INTERNATIONAL LABORATORY APPROVED.
The mounting of sprinklers in suspended ceiling system Including Commercial, Clean Room and Duct sprinkler
with conventional mounting method is very laborious and mounting system. All models of Safex flexible sprinkler
time consuming. The use of the stainless steel sprinkler hose hoses had been conducted with severe tests and got the
significantly minimises the efforts and laborious costs products approved by famous laboratories. The quality and
required for installation purpose, because the flexibility of security is controlled and kept all the time. Meet the local fire
the hose enable you to change the sprinkler location during protection laws worldwide and the insurance requirements.
renovation or conversions. Beauty, economy, security can be You could have a peace mind all the time using Safex
preserved at the same time. Flexible Sprinkler Hoses.
HIGH PRESSUE RESISTANCE AND GOOD FLEXIBILITY. EASY REPAIR, KEEP RUNNING AND NO DOWNTIME.
One piece style construction, require no welding, painting For Commercial system, the sprinkler could be relocated
or epoxy coating on site. All Sprinkler Hoses are tested with 2 and mounted within the flexible area defined by the
times the design pressure before delivery. The hydrostatic Sprinkler Hose length. It just needs a small constructed area,
pressure resistance is 4 times the design pressure. All models no pipes cutting and threading on site. For Clean Room and
of the sprinkler hoses had been passed fatigue life test with Duct system, the sprinkler can be inspected and replaced in
50000 cycles. Allow for independent motion between a few minutes. The factory or working site can be kept clean
ceiling grids and main pipe system during seismic activity. and running during maintenance. Require no downtime for
The stresses and leaks caused by the earthquake or the routine inspection and replacement. Eliminate the total cost
misalignment can be avoided. for system repairment.
2 1 UNIT:mm

SF 9500 TIG
Ø1”-PT The hoses are tested in a straight position with a sprinkler.

I.D.Ø20.2
Ø25.4

6
Rb = 100mm
min. Bend Radius
R
b

W+ 3
TOTAL LENGTH = L
50
5 Square Pipe - 650mm x 1pc, Pipe Clamp x 2sets, Adapter Holder x 1set
3
TIG

Ø1/2”-NPT
Ceiling Grid
Sprinkler 4

Features of the Sprinkler Hose. Friction Loss Data


1. Pressure & Temperature Capabilities: Hazen-Williams coefficient of friction C=120
Rated working pressure: 12.3 kg/cm², 175 psi Total Length EQL (Φ1"-sch40)
Hydrostatic pressure: 24.6 kg/cm², 350 psi m ft m ft N
Rated working temperature: -40~+200ºC 0.7 2 11.6 2 2
1.0 3 17.4 3 3
2. Quality & Security of products. 1.2 4 22.9 4 3
a. The bellows is made with thick stainless 1.5 5 23.8 5 3
steel, have good corrosion resistance and 1.8 6 31.4 6 3
good shaped feature. N : 90 / No. of 900 bend

b. One piece style structure. Pre-assembled


Construction
and tested for pressure leak in the factory
100% before delivery. Item Fitting Material
1 Round Nipple SUS-304
3. Patent anchoring components Union SS-400
2 Bellows SUS-304
Patent No.: M281654, M364521
3 Adapter SUS-304
a. All-purpose anchoring component is flexible
4 Square Pipe SPCC(Galv.)
to mount to different installation conditions.
5 Adapter Holder SPCC(Galv.)
b. Opened type adapter holder is more flexible
6 Pipe Clamp SPCC(Galv.)
and easy to mount the sprinkler system.

10
11
FLEXIBLE DROPPER FOR SPRINKLER SYSTEM Powering your way to safety
Since 1972

SAFEX BRAIDED TYPE SPRINKLER HOSE


SF 9400

Square Pipe - 650mm x 1pc, Pipe Clamp x 2sets, Adapter Holder x 1set

Friction Loss Data


Features of the Sprinkler Hose. Hazen-Williams coefficient of friction C=120
Total Length EQL (Φ1"-sch40)
1. Pressure & Temperature capabilities : APPROVED
m ft m ft N
Rated working pressure : 12.3 kg/cm2, 175 psi 0.7 2 12.2 40 2
Hydrostatic pressure : 49.3 kg/cm2, 700 psi 1.0 3 18.0 59 3
Rated working temperature : -40 ~ +200 0C 1.2 4 23.5 77 3
1.5 5 24.4 80 3
2. Approval identification : 3043954 1.8 6 33.0 105 3
a. All purpose anchoring component is flexible to N : 90 / No. of 900 bend

mount to different installation conditions. Construction


b. Opened type adapter holder is more flexible and Item Fitting Material
easy to mount the sprinker system. 1 Round Nipple SUS-304
Union SS-400
3. Installation with security 2 Collar SUS-304
a. Construction with screws, Provide builders with 3 Bellows SUS-304
security. 4 Wire Braids SUS-304
5 Adapter SUS-304
b. One piece style structure. Pre-assembled and
6 Square Pipe SPCC(Galv.)
tested for pressure leak in the factory 100%
7 Adapter Holder SPCC(Galv.)
before delivery.
8 Pipe Clamp SPCC(Galv.)
Ÿ Advantages of high flexibility
a. Flexible to adjust the sprinklers to installation Friction Loss Data
conditions. Flow Rate: 115 I/min. C=100
b. Prevent the pipe cracks and ceiling deformations Total Length EQL Φ1"-sch40 m (ft)
during seismic sway. m ft Straight with bends-N
c. Simple installation. Reduce the laborious costs 0.7 2.0 1.6(5.4) 1.9(6.5)-1
effectively. 1.0 3.3 3.8(8.3) 3.8(12.8)-2
1.2 4.0 2.9(9.7) 4.8(15.9)-3
1.5 5.0 3.6(11.8) 7.1(23.1)-4
SF 9200 1.8 6.0 4.2(13.9) 8.0(26.2)-4
2.1 7.0 5.0(16.4) 8.0(26.2)-4
N : 90 / No. of 900 bend

Construction
Item Fitting Material
1 Round Nipple SUS-304
Union SS-400
2 Collar SUS-304
3 Bellows SUS-304
4 Wire Braids SUS-304
5 Adapter SUS-304
6 Square Pipe SPCC(Galv.)
7 Adapter Holder SPCC(Galv.)
8 Pipe Clamp SPCC(Galv.)

APPROVED
12
13
HYDRANT ACCESSORIES Powering your way to safety
Since 1972

HOSE BOX HOSE REEL AS PER INDIAN STANDARDS


Material: MS / SS / FRP 1. Hub
Thickness: 16 Gauge, 18 Gauge 2. Two Sides
Single door: 560W x 560L x 250H 3. Swivel Joint
Double door: 600W x 750L x 250H 4. Pips with fittings
*Customized Sizes are Available 5. Wall Bracket
6. Nozzle with shut
off arrangement
7. Stop Valve
8. Rubber / Thermoplast Hose
9. Variants : 20 mtr, 30 mtr, 36 mtr,
36.5 mtr and 40 mtr

LANDING VALVE / INTERNAL HYDRANT

IS:5290

STAINLESS STEEL GUNMETAL


Performance Type A Single Type B Single Dimension Type A Single Type B Single
Water tightness test 14 kgF/ cm² 14 kgf/ cm² Flange Inlet 75 mm 100 mm
Hydrostatic pressure test 21 kgF/ cm² 21 kgF/ cm² Female Outlet 63 mm 63 mm
Flow test per minute 900 Litter at 7 kgF/ Flange DiA 200 mm 220 mm

DELIVERY HOSE COUPLING NOZZLES / BRANCH PIPE


MOC : STAINLESS STEEL/GUNMETAL MOC : STAINLESS STEEL/GUNMETAL
Size & Dimension: Hydrostatic Pressure Test:
63 mm IS:903 21kgF/cm² IS:903

Hydrostatic Pressure
Test: 21kgF/cm² for a
period of 2 ½ minutes.

FEATURES OF HOSE REEL HOSE REEL AS PER INTERNATIONAL STANDARDS


Ÿ Side Plate powder painted finish red Sr. no. Description Brief Specifications
Ÿ Threaded Inlet connection 1. Side plates High quality mild steel perfectly shaped
& PE Powder coated.
Ÿ Outlet connection for hose can be rotated
for left and right direction 2. Water way Aluminum Alloy & GI coated steel
against corrosion duly EPE powder coated
Ÿ Waterways made from non ferrous metals
which ensure corrosion free* 3. Pipe spec. High quality PVC Pipe of Diameter 3/4”
and length 20, 30, 36, 40 mtr. the
Ÿ Maximum working pressure 15Bar, test
customer requirements.
pressure 20Bar
4. Nozzle Jet, Spray & Shut off Nozzle in PVC / Brass
Ÿ PVC Hose
5. Swivel 1800 double swivel
Ÿ Available in 20 mtr, 30 mtr, 36 mtr, 40 mtr
6. Working pressure 12 Bar (174 psi)
7. Test Pressure 18 Bar (261 psi)

14
15
DAFO FORREX FIRE SUPPRESSION SYSTEMS Powering your way to safety
Since 1972

TECHNICAL DATA CONSTRUCTION


Most bus fires start in engine compart-ments and surrounding areas. A tested and classified fire suppression system in
combination with good fire detection, is the best first response in case of an emergency, Dafo Forrex Fire Suppression
System get activated by heat detector when the temperature reach 180°C.
The Dafo system is developed to use worldwide in both cold and hot climate and designed after the Swedish guideline SBF
128, which requires 3L extinguishing agent for 1m3 protected space. It means, we leave nothing to chances, safety first! The
Dafo system is designed to avoid false releases - one of many special qualities.

INSTALLATION
Fire is indicated by a linear heat detector wire (1) that
sends a signal to the actuator (2) which punctures the
propellant gas cartridge (3) and releases nitrogen to the Alarm Panel
agent container (4) that distributes the Forrex liquid to
the nozzles (5) through the pipe system. At the same time
the alarm system is activated, an alarm horn (6) in the bus
and a light signal in the panel will warn the driver (7). Linear Heat Detector Nozzle Forrex Container Alarm Horn Alarm Lamp

OPERATING INSTRUCTIONS IN CASE OF FIRE


Have a hand portable extinguisher ready for safety when opening the engine compartment hood. The alarm to the fire
system will sound until the detection wire is cut of, by cutting the wire next to the control unit or by removing the fuses. Do
not start the bus until the cause of fire is determained, and service have been done.

SERVICING
Once a year the system must be inspected and serviced by a trained and authorized service company. The service will be
carried out according to the service manual and the service protocol. Every 4th year comprehensive service, every 10th
extended service.

GUARANTEE
You have twelve months warranty from the installation date. Within
this time, defects in material or manufacture of components delivered
from Dafo give right to replacement free of charge.

CERTIFICATE
The system is certified by TÜV, SBF, FM, Russian Law of Fire Safety no.
123F3. Dafo Forrex extinguishing fluid is certified by the MPA, the SP
Environment certificate, Lloyds Register (ICAO Level B) and CCC
(China). Dafo Forrex Fire Suppression System is tested for EMC,
vibration and temperature according to vehicle standards.

SAFETY & REQUIREMENTS


According to increasing requirements, smoke detectors for toilets and The liquid agent
luggage compartments are available for installation at the bus extinguishes fire in
manufactory. We also have a linear heat detector wire in the range, which less than a second
is currently installed in serial production at various bus manufacturers. and effectively
prevents re-ignition.
A low pressure
system demanding
but modest space
PERSONNEL SECURITY and that operates
down to -50° C.
The harmless extinguishing liquid and no pressure resting state
represents no health risk to passengers or mechanics.

Safex Fire Services Ltd. is the Exclusive Distributor for India.


16
17
AUTOMATIC FIRE TUBING SYSTEM Powering your way to safety
Since 1972

SAFEX AUTOMATIC FIRE TUBING SYSTEM


Automatic self seeking fire tubing system puts out fires when they start, where they start. Designed for installation inside
enclosures and inaccessible areas. No complex electronics. Safe against malfunction. Best cost-performance ratio.

FIRE TUBE - THE DIFFERENCE


Ÿ Acts as a multi-sensor and multi extinguishing jet.
Ÿ Made of a high-tech polymer.
Burst spot
Ÿ Combines long-time resistance & flexibility.
Ÿ Temperature sensitivity, when bursting at the hottest
spot, it ruptures as a nozzle shape opening.

THE DIRECT SYSTEM


The extinguishing agent is transported through the tube
exactly to the origin of the fire.

Cylinder Containing: Powering your way to safety


Since 1972

Water, Foam, Powder, CO2, Argonite, Clean Agent Gas, Etc.. Direct Low
Pressure
System

THE INDIRECT SYSTEM


The detection tube just triggers the valve when it detects a fire.
The extinguishing agent discharges through a conventional
outlet port.

Cylinder Containing: Powering your way to safety


Since 1972

Water, Foam, Powder, CO2, Argonite, Clean Agent Gas, Etc.. Indirect
Low
Pressure
System

ADVANTAGES
Ÿ Linear detection line
Ÿ Rapid reaction time
Ÿ 24 hours a day ready for use
Ÿ No external power supply
Ÿ Flexible positioning of the Safex tube You can’t reach the fire?
Ÿ Can be installed into inaccessible areas
Ÿ Minimal environmental damages SAFEX FIRE TUBING can
Ÿ Minimum maintenance
Ÿ No accidental discharges through a disruption of the fire detector
Ÿ Can be used in every environment (marine, industrial atmosphere)
Ÿ Low and high pressure applications
Ÿ Not affected by vibration or knocks Powering your way to safety
Since 1972

Ÿ Quick and simple installation


Ÿ Low price - high performance relationship

*The System is available in High Pressure and Low Pressure

18
19
Powering your way to safety
Since 1972

ALUMINIUM FIRE EXTINGUISHERS


Thanks to a switch over to aluminum bodies, Safex’s new extinguisher is lighter and thus
more portable. So you spend fewer minutes in carrying the extinguisher to the fire and
fighting it successfully.
There's more to it than meets the eye. The new aluminum cylinders are produced by the
extrusion method, rather than the spinning of steel pipes. This leaves no room for leakage or
tampering. The result is an extinguisher that is not only lighter, but also sturdier and corrosion
free.

FOAM BASED FIRE EXTINGUISHERS (ALUMINIUM)


FOAM BASED STORED PRESSURE TYPE FIRE EXTINGUISHERS
FIRE EXTINGUISHER CAPACITIES 6lt. 9lt.
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 40 sec. 60 sec
MINIMUM RANGE OF JET 2 mts 2 mts
FIRE RATING 3A, 89B 4A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM2 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approvals: IS:15683

WATER BASED FIRE EXTINGUISHERS (ALUMINIUM)


WATER BASED STORED PRESSURE TYPE FIRE EXTINGUISHERS
FIRE EXTINGUISHER CAPACITIES 6lt. 9lt.
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 SEC 13 SEC
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 50 SEC 100 SEC
MINIMUM RANGE OF JET 2 MTS 2 MTS
FIRE RATING 2A 3A
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM2 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approvals: IS:15683

20
21
Powering your way to safety
Since 1972

CLEAN AGENT GAS BASED FIRE EXTINGUISHERS (ALUMINIUM)


CLEAN AGENT STORED PRESSURE TYPE FIRE EXTINGUISHERS

FIRE EXTINGUISHER CAPACITIES 2kg. 4kg. 6kg.


MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 13 sec 13 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 95% OF CONTENTS 15 sec 25 sec 27 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts
FIRE RATING 1A, 21B 2A, 34B 2A, 55B
WORKING PRESSURE 15KGF/CM² 15KGF/CM² 15KGF/CM²
HYDRO PRESSURE 36KGF/CM² 36KGF/CM² 36KGF/CM²
BURSTING PRESSURE 55KGF/CM² 55KGF/CM² 55KGF/CM²

Approval: EN3.7 IS:15683


GAS: DUPONT™ FE36™ Clean Agent

POWDER BASED FIRE EXTINGUISHER (ALUMINIUM)


ABC STORED PRESSURE TYPE FIRE EXTINGUISHER.
FIRE EXTINGUISHER CAPACITYIES 1 KG 2 KG 4 KG 6 KG 9 KG
MINMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 13 sec 13 sec 15 sec 15 sec
MAXIMUM PERIOD OF DISCHARGE
ATLEAST 90% OF CONTENS 12 sec 16 sec 20 sec 25 sec 30 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts 2 mts 2 mts
FIRE RATING 1A, 21B 2A, 34B 3A, 55B 4A, 89B 6A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM²
Approval: IS:15683

22
23
POWDER BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

ABC STORED PRESSURE TYPE FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 1kg. 2kg. 4kg. 6kg. 9kg.
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 13 sec 13 sec 15 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 12 sec 16 sec 20 sec 25 sec 30 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts 2 mts 2 mts
FIRE RATING 1A, 21B 2A, 34B 3A, 55B 4A,89B 6A,183B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM²
Approvals: IS:15683

BC / ABC SQUEEZE GRIP CARTRIDGE TYPE FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 4kg. BC 4kg. ABC 6kg. BC 6kg. ABC 9kg. BC 9kg. ABC
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 15 sec 13 sec 15 sec 15 sec 15 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 25 sec 25 sec 25 sec 25 sec 30 sec 30 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts 2 mts 2 mts 2 mts
FIRE RATING 144B 3A, 55B 183B 4A, 89B 233B 6A, 183B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM²
Approval: IS:15683

TROLLEY MOUNTED BC / ABC TYPE FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 25kg.I/C-BC 25kg.I/C-ABC 25kg.O/C-BC 25kg.O/C-ABC 50kg.BC 50kg.ABC 75kg.BC 75kg.ABC
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 30 sec 30 sec 30 sec 30 sec 30 sec 30 sec 30 sec 30 sec
MINIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 40 sec 40 sec 40 sec 40 sec 50 sec 50 sec 60 sec 60 sec
MINIMUM RANGE OF JET 6 mtr. 6 mtr. 6 mtr. 6 mtr. 6 mtr. 6 mtr. 6 mtr. 6 mtr.
FIRE RATING 233B 20A, 223B 233B 20A, 233B 233B 20A, 233B 233B 20A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM² 55 KGF/CM²
Approval: IS:16018

24
25
Powering your way to safety
Since 1972

HIGHER CAPACITY STORED PRESSURE


TROLLY MOUNTED ABC TYPE FIRE EXTINGUISHERS (STORED PRESSURE)

FIRE EXTINGUISHER CAPACITIES 25kg. 50kg. 75kg.


MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 30 sec 30 sec 30 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 40 sec 50 sec 60 sec
MINIMUM RANGE OF JET 6 mtr. 6 mtr. 6 mtr.
FIRE RATING 20A, 233B 20A, 233B 20A, 233B
WORKING PRESSURE 15KGF/CM² 15KGF/CM² 15KGF/CM²
HYDRO PRESSURE 36KGF/CM² 36KGF/CM² 36KGF/CM²
BURSTING PRESSURE 55KGF/CM² 55KGF/CM² 55KGF/CM²
Approval: IS:16018

TROLLY MOUNTED WATER & FOAM FIRE EXTINGUISHERS (STORED PRESSURE)


FIRE EXTINGUISHER CAPACITYIES 60 ltr.(Water Based) 60 ltr. (Foam Based)
MINMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 30 sec 30 sec
MAXIMUM PERIOD OF DISCHARGE
ATLEAST 90% OF CONTENS 180 sec 180 sec
MINIMUM RANGE OF JET 6 mtr. 6 mtr.
FIRE RATING 20A 20A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approval: IS:16018

26
27
STAINLESS STEEL FIRE EXTINGUISHERS Powering your way to safety
Since 1972

CLEAN AGENT GAS BASED FIRE EXTINGUISHERS


CLEAN AGENT STORED PRESSURE TYPE FIRE EXTINGUISHERS

FIRE EXTINGUISHER CAPACITIES 2kg. 4kg. 6kg.


MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 13 sec 13 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 95% OF CONTENTS 15 sec 25 sec 27 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts
FIRE RATING 1A, 21B 2A, 34B 2A, 55B
WORKING PRESSURE 15KGF/CM² 15KGF/CM² 15KGF/CM²
HYDRO PRESSURE 36KGF/CM² 36KGF/CM² 36KGF/CM²
BURSTING PRESSURE 55KGF/CM² 55KGF/CM² 55KGF/CM²

Approval: EN3.7 IS:15683


GAS: DUPONT™ FE36™ Clean Agent

POWDER BASED FIRE EXTINGUISHER


ABC STORED PRESSURE TYPE FIRE EXTINGUISHER.
FIRE EXTINGUISHER CAPACITYIES 4 KG 6 KG 9 KG
MINMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 sec 15 sec 15 sec
MAXIMUM PERIOD OF DISCHARGE
ATLEAST 90% OF CONTENS 20 sec 25 sec 30 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts
FIRE RATING 3A, 55B 4A, 89B 6A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM² 55 KGF/CM²
Approval: IS:15683

WATER AND FOAM BASED FIRE EXTINGUISHERS


WATER / FOAM BASED STORED PRESSURE TYPE FIRE EXTINGUISHERS
FIRE EXTINGUISHER CAPACITIES 9ltr. (Water) 9ltr. (Foam)
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 sec 25 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 100 sec 60 sec
MINIMUM RANGE OF JET 2 mts 2 mts
FIRE RATING 3A 4A,233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM2 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approvals: IS:15683

28
29
WATER AND FOAM BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

WATER / FOAM BASED STORED PRESSURE TYPE FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 9ltr. (Water) 9ltr. (Foam)
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 100 sec 60 sec
MINIMUM RANGE OF JET 2 mts 2 mts
FIRE RATING 3A 4A,233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM2 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approvals: IS:15683

WATER / FOAM SQUEEZE GRIP CARTRIDGE TYPE FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 9ltr. (Water) 9ltr. (Foam)
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 13 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 100 sec 60 sec
MINIMUM RANGE OF JET 2 MTS 2 MTS
FIRE RATING 3A 4A,233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approval: IS:15683

TROLLEY MOUNTED WATER & FOAM TYPE FIRE EXTINGUISHERS


WATER BASED FOAM BASED
FIRE EXTINGUISHER CAPACITIES 45ltr. 45ltr.
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 30 SEC 30 SEC
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 90% OF CONTENTS 180 SEC 180 SEC
MINIMUM RANGE OF JET 6 MTS 6 MTS
FIRE RATING 20A 20A, 233B
WORKING PRESSURE 15 KGF/CM² 15 KGF/CM²
HYDRO PRESSURE 36 KGF/CM² 36 KGF/CM²
BURSTING PRESSURE 55 KGF/CM² 55 KGF/CM²
Approvals: IS:16018

30
31
CLEAN AGENT GAS BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

CLEAN AGENT STORED PRESSURE TYPE FIRE EXTINGUISHERS

FIRE EXTINGUISHER CAPACITIES 2kg. 4kg. 6kg.


MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 13 sec 13 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 95% OF CONTENTS 15 sec 25 sec 27 sec
MINIMUM RANGE OF JET 2 mtr 2 mtr 2 mtr
FIRE RATING 1A, 21B 2A, 34B 2A, 55B
WORKING PRESSURE 15KGF/CM² 15KGF/CM² 15KGF/CM²
HYDRO PRESSURE 36KGF/CM² 36KGF/CM² 36KGF/CM²
BURSTING PRESSURE 55KGF/CM² 55KGF/CM² 55KGF/CM²
Approval: IS:15683
GAS: DUPONT™ FE36™ Clean Agent

32
33
CO2 GAS BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

WHEEL TYPE / SQUEEZE GRIP TYPE CO2 FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 2kg.Wheel 3kg.Wheel 4.5kg.Wheel 2kg.Squeeze 3kg.Squeeze 4.5kg.Squeeze
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 8 sec 8 sec 8 sec 8 sec 8 sec 9 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 95% OF CONTENTS 18 sec 20 sec 25 sec 18 sec 20 sec 25 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts 2 mts 2 mts 2 mts
FIRE RATING 21B 34B 34B 21B 34B 55B
WORKING PRESSURE 60KGF/CM² 60KGF/CM² 60KGF/CM² 60KGF/CM² 60KGF/CM² 60KGF/CM²
HYDRO PRESSURE 250KGF/CM² 250KGF/CM² 250KGF/CM² 250KGF/CM² 250KGF/CM² 250KGF/CM²
Approval: IS:15683

TROLLEY MOUNTED TYPE CO2 FIRE EXTINGUISHERS


FIRE EXTINGUISHER CAPACITIES 6.5kg. 9kg. 22.5kg.
MINIMUM PERIOD FOR WHICH
THROW OF JET MAINTAINED 15 sec 15 sec 15 sec
MAXIMUM PERIOD TO DISCHARGE
ATLEAST 95% OF CONTENTS 30 sec 40 sec 60 sec
MINIMUM RANGE OF JET 2 mts 2 mts 2 mts
FIRE RATING 55B 55B 89B
WORKING PRESSURE 60KGF/CM² 60KGF/CM² 60KGF/CM²
HYDRO PRESSURE 250KGF/CM² 250KGF/CM² 250KGF/CM²
Approval: IS:16018

34
PATENTED

Support

THE NEW REVOLUTIONARY


MECHANICAL CHARGE CONTROL
SYSTEM FOR CO2 FIRE EXTINGUISHERS
2,3 & 4.5 Kg.

THIS SYSTEM DETECTS AUTOMATICALLY


THE EXTINGUSHER'S WEIGHT
FULL AND EMPTY
GREEN/FULL
RED/EMPTY

SCARICO

EMPTY

SCARICO
CARICO/FULL
EMPTY

FIRE
CARICO/FULL
FIGHTING
DIVISION

35
Powering your way to safety
Since 1972

Support

FULL / EMPTY INDICATOR


FASTENING FOR THE EXTINGUSHER
CALIBRATION SCREW

STANDARDISED HOLES FOR WALL MOUNTING

REMOVABLE BAR
TO AVOID CONTACT
OF THE EXTINGUISHER WITH THE WALL
EXTINGUISHER ADJUSTABLE SUPPORT GUIDES

36
37
AUTOMATIC MODULAR FIRE EXTINGUISHERS Powering your way to safety
Since 1972

AUTO SAFE AUTOMATIC FIRE EXTINGUISHER


Safex presents Modular type ABC Clean Agent Gas along with a range of gaseous Fire
Automatic Extinguishers.
SAFEX Automatic ABC Dry Chemical Powder or Clean Agent Gas & other gaseous Fire
Extinguishers is a technological break through that provides automatic fire protection for
electrical and electronic flammable liquid and variety of other risks.
Auto Safe is an Automatic Extinguisher, which does not require any external source of
power to operate. It can be utilized for local applications or total flooding of hazards.
The Modular type Extinguisher is based on Sprinkler technology. Unlike the Sprinkler, the
Nozzle is Gas-tight. The release temperature can be adjusted to suit prevailing
conditions.
This Extinguishers are most ideal for protection of computer area, ATM Center, server
room, fuel and flammable liquid storage, oil fill-in stations, transformers, automobile
garages, marine engines, paint and varnish booths, welding benches, domestic gas
Storage's particularly for hotels etc, and where water damage cannot be tolerated.

TECHNICAL DATA CONSTRUCTION


Automatic Powder & Clean Agent Gas Fire Extinguisher mainly consist of MIG welded M.S. body 2 mm CRC Sheet upper part
of which is fitted with adapter or Flange for fixing on ceiling wall. And below part fixed automatic release Nozzle based on
Sprinkler technology unlike the Sprinkler Nozzle is gas tight the release temperature is adjusted with sprinkler imported
bulb set at 57° C, or 68° C or special temperatures according to specific requirements and imported pressure gauge fitted for
instant verification of reliability of every unit.
Nozzle is specially designed to give more that 99% discharge. Together with orifice characteristic to cover adequately fire
risks with scattering cone of 40° to 45° angle.
This extinguisher is presently available in 4 sizes:
2, 5, 10 and 15 Kgs with either wall or ceiling mounted, Extinguishers of higher capacities and with special mounting’s
bracket can also be offered.

PERFORMANCE DATA
Cap. Propellent Working Testing Area Volume Hanging Operation App.Net Extinguishing Agent
Avail. Pressure Pressure Protection Protected Vertically Time in Weight
(kgs / cm²) (kgs / cm²) Above Risk Seconds Gross
2 kgs Nitrogen 7 to 15 35 1 to 1.5m² 1m3 1.5m 8-10 3.6 Powder/Clean Agent Gas
3
5 kgs Nitrogen 7 to 15 35 3.5 to 4m² 3m 1.5 to 2m 10-15 8.5 Powder/Clean Agent Gas
10 kgs Nitrogen 7 to 15 35 7 to 8m² 4m3 1.75 to 2.25m 15-20 15 Powder/Clean Agent Gas
15 kgs Nitrogen 13 to 15 35 8 to 10m² 4m3 2 to 3m 18-23 20 Powder/Clean Agent Gas
Note: Utilization temperature: 57°C to 107°C

THE ADVANTAGES
§ Keeps guard and Extinguishes fire quickly and efficiently, especially in those places where
fire could cause extensive damage if not detected and extinguished in time.
§ Hazard free clean agent keeps article safe and intact in case of fire.
§ Provides concentrated fire protection for vital equipments.
§ Highly Cost effective compared to automatic Fixed Fire Protection Systems.
§ It is a Portable unit, easy to install and re-locate.
§ Imported pressure gauge fitted for instant verification of functionality and reliability of every unit.
§ Automatic and reliable security round the clock.
§ Provides security in case of emergencies and power failure without power backup.

38
39
EN 3.7 APPROVED FIRE EXTINGUISHERS Powering your way to safety
in Technical Collaboration with S.R.L. Italy Since 1972

P 6 ELLEN

Features:
KG. 6 Power Fire Extinguisher
with wall hook built in 3 pieces
Ogive - Body and Bottom
Maximum Dimension MM
292 x H. 539
Diameter on the body - MM. 160
Total Mass KG. 10.700
FIRE CLASS
34A 233B C

P 6 SUPER P9
Features: Features:
KG. 6 Power Fire Extinguisher KG. 6 Power Fire Extinguisher
with wall hook built in 3 pieces with wall hook built in 3 pieces
Ogive - Body - Bottom and Band Ogive - Body - Bottom and Band
Maximum Dimension MM Maximum Dimension MM
292 x H. 539 295 x H. 576
Diameter on the body - MM. 160 Diameter on the body - MM. 190
Total Mass KG. 10.700 Total Mass KG. 15.200
FIRE CLASS FIRE CLASS
21A 113B C 21A 113B C

P 12 S S6

Features: Features:
KG. 12 Power Fire Extinguisher KG. 6 Saclon 2 Eco Fire Extinguisher
with wall hook built in 3 pieces with wall hook built in 3 pieces
Ogive - Body - Bottom and Band Ogive - Body - Bottom and Band
Maximum Dimension MM Maximum Dimension MM
345 x H. 648 292 x H. 539
Diameter on the body - MM. 190 Diameter on the body - MM. 160
Total Mass KG. 18.650 Total Mass KG. 10.700
FIRE CLASS FIRE CLASS
34A 144B C 13A 89B C

40
41
TROLLEY MOUNTED FOAM BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

Safex is one of the most dedicated company in manufacturing reliable, high quality fire fighting
equipment and accessories for various safety requirements now bring you.

SALIENT FEATURES
The one man Trolley Mounted Mobile Foam Unit. Foam is used because water (in most
cases) proves ineffective in uenching hydrocarbon liquid based fires in petroleum, chemical
and other similar industries.
Ÿ Unit comes complete with hose, inductor and branch pipe foam compound optional
Ÿ One man operation
Ÿ Extremely mobile
Ÿ Virtually instantaneous operation
Ÿ Suitable for any type of foam
Ÿ Available in various alternative arrangements

PORTABLE FOAM INDUCTOR ALUMINIUM BRANCH PIPE WITH AIR INDUCTION

FIRE HOSE PIPE


Material of construction
Type A Type A
Sr. Description Material
The hose has the outer lining of The outer/inner lining of PVC
1. Body Aluminium Alloy to IS 617 predominantly cotton; a natural Nitrite compound catches fire in
fibre; which does not support mere candle flame! The actual
2. Barrel Aluminium Alloy to IS 617
combustion. Remains five fighting operation can be
3. Female Coupling Aluminium Alloy to IS 617 unaffected by flame. highly risky.
4. Male Coupling Aluminium Alloy to IS 617
The cotton jacket withstand The lining compound melts at
5. Form Coupling CU.ALY.GR.LTB-2 to IS 318 high temperatures. Hot relatively low temperatures.
radiators and hot surfaces has Contract with hot radiators and
6. Pick-up Tube Non-collapsible P.V.C. no effect on it. surfaces cab be dangerous.
Hose with SS 304 Dip pipe
7. Finish Inductor painted yellow to In India, high quality cotton is T h e s o c a l l e d ‘i m p o r t e d
shade no. 358 of IS 5 widely available, which is not technology ’ is merely an
Coupling buffed flammable. Punches the expensive alternative to cover
imported technology hollow! the polyester filament with PVC
Nitrite blend to protect the
Technical Details: In the event of combustion Type polyester jacket in side, which
Working pressure - 7kg/sq cm to 10kg/sq cm A hose produces no dangerous melts at low temperatures.
Max allowable back pressure: 65% of inlet pressure gases or fumes.
Hydraulic test pressure: 25kg/sq cm for 5 mins On combustion, the PVC Nitrite
Type A hoses are lighter in compound produces
Item code Pressure Nominal Foam Weight with handling. dangerous nitrous gases and
Flow Induction pick-up tute fumes. Obviously a health
kg/sq cm PSI LPM GPM Smaller coil diameter. hazard.

PFI-225 7 100 225 59 3% or 6% 4 kg TheType B hose are heavier the


PFI-450 II 7 100 450 118 3% or 6% 4 kg Type A.

Note: All dimension are in mm unless otherwise specified


Higher coil diameter.

42
43
TWIN 5050 Foam and Powder BASED FIRE EXTINGUISHERS Powering your way to safety
Since 1972

GENERAL INFORMATION
TWIN5050 is Mobile Foam and Powder Fire Extinguisher with Nitrogen propellant Cylinder. This Fire Extinguisher is
manufactured by the company SAFEX FIRE SERVICES LTD. that is in operation since 1972 and is ISO 9001 certified. The
qualitative standards fixed are achieved through a careful selection and rating of the suppliers and through continuous and
strict quality controls of all the components in compliance with the ISO 2859-1 standard.
All the components used in Manufacturing the Fire Extinguishers are purchased from major Indian Manufactures.

EXTINGUISHER UNIT

The Foam Cylinder is made of Mild steel, while the one containing
the Powder is made of Mild steel, both tested at 35kgf/cm2. A
large-diameter threaded ring nut is welded at the top of the
cylinders for easy charging and internal inspection during
periodic testing. To the ring nut is screwed a forged brass cap with
built-in safety valve of the type with calibrated spring made of
stainless steel so as to guarantee calibration in time and even in
the worst atmospheric conditions. In the rear part of the trolley is
fixed the pressurization, control and discharge unit consisting of
a Nitrogen Cylinder EKC tested at 250 bars 6.8 Ltr. charged at 200
bars and having a rapid opening valve for quick pressurization of
the powder and foam cylinders.
The discharge of Nitrogen for the pressurization is controlled by
an intermediate pressure reducer calibrated at 12 bars so as to
obtain a uniform discharge at constant pressure. Two on-off
valves placed between the reducer and the cylinders can allow
independent pressurization of the two Cylinders. The cylinders
are pressurized for around 15 seconds, after which the spray guns
can be used for discharging the powder and the foam. The
discharge is controlled by means of two spray nozzles made of
light alloy/plastic with ergonomically designed handgrip for an
easy and rapid grip. The spray nozzles are fed by two plastic hoses.
Each of 19mm diameter and 5m long. And offer maximum agility
and ease of handling to the operator. The unit is charged with ABC
50 % Powder, compatible with the AFFF 6% Film-Forming Foam.

USE
This Mobile Fire Extinguisher is used in large fires of any class A, B, or C type, of vertically stored goods and of Inflammable
Liquids that can spread on the surface. Normally it is used by first discharging the foam to knock down the high flames and
then if necessary using the powder, compatible with the foam, to immediately put out already reduced flames.

Technical Data
Trade Name SAFEX TWIN5050 Range 10-12m
Extinguishing classes A B4 / A B1 C Cylinder Bottom: drawing-body: Rolling and Welding
Charge 50 Ltr. foam AFFF 6% / 50kgs ABC powder Steel Mild steel IS:1079 thickness 3mm
Working pressure 15kgf / cm² Max Test pressure 35 kgf/ cm²
Safety Valve 20 kgf / cm² +/-0,2 Anti corrosive treatment 1. Phosphating
Cap 75 mm 2. Inside & outside epoxy powder coating
Utilization temperature +5 +60°C Propellant Nitrogen 6.8 ltr. - 200 bar
Discharge time 30 sec. powder / 30 sec. foam Dimensions(H x I x W) 1020 x 1060 x 850
Hose 19 mm x5 mm Total Weight 250 kgs

44
Powering your way to safety
Since 1972

NRS Type Gate Valve


105QS / 108QS
105QS / 108QS Non-rising Stem Groove Joint Ends Resilient Wedge Gate Valves
1 Bolted Bonnet·Non-Rising Stem·Resilient Wedge·Flanged XGroove·GrooveXGroove
2 250 PSI/300 PSI/17.2 Bar Non-Shock Cold Working Pressure
3 CONFORMS TO AWWA C 509.
4 Coating-Electrostatically applied fuaion-bonded epoxy 0.2-0.5mm.inside and outside.Meets or exceeds AWWA C550.Maximum operating
temperature 1600C/710C. Freezing Weather Precaution-Subsequent to testing a piping system,valves should be in an open position to allow
complete drainage.

Assembly Diagram

105QS Groove X Grove


Non-rising Stem Groove

Fr e e z i n g We a t h e r Pr e c a u t i o n -
Subsequent to testing a piping system,
valves should be in an open position to
allow complete drainage.

108QS Groove X Flanged


APPROVED
Non-rising Stem Groove

45
Powering your way to safety
Since 1972

Dimension
Bolt
Size
Circle
L C D E F G d D1 T Turns
Flange
To
Holes
Open

In mm ln mm ln mm ln mm ln mm ln mm ln mm ln mm ln mm ln mm ln mm

3 80 8.0 203 0.08 2 3.50 89 0.35 9 0.98 25 10.00 254 3.0 73 7.5 191 0.75 19 6.00 152.5 4-Φ19 10.5

4 100 9.0 229 0.08 2 4.49 114 0.35 9 0.98 25 10.00 254 4.0 100 9.0 229 0.94 24 7.50 190.5 8-Φ19 13.75

6 150 10.5 267 0.08 2 6.61 168 0.35 9 0.98 25 12.40 315 6.0 150 11.0 279 1.00 25.4 9.50 241 8-Φ23 16

8 200 11.5 292 0.09 2.3 8.62 219 0.47 12 1.22 31 14.76 375 8.0 200 13.5 343 1.13 28.6 11.73 298.5 8-Φ23 17.5

10 250 13.0 330 0.10 2.55 10.74 272.9 0.52 13.2 1.25 31.7 16.38 416 10 250 15.95 406 1.19 30.2 14.25 362 12-Φ23 21.5

12 300 14.0 356 0.13 3.35 12.78 324.5 0.52 13.2 1.25 31.7 17.52 445 12 300 19.02 483 1.25 31.8 17.01 432 12-Φ23 26

No. Part List Specification


1 Valve Body Cast Iron ASTM A 536
2 Resilient Wedge Ductile Iron ASTM A 536/EPDM ASTM D 2000
3 Wedge Nut Bronze ASTM B 584 UNS C83600
4 Stem Stainless Steel ASTM A 276 UNS C41000
5 Bonnet Gasket EPDM ASTM D 2000
6 Bonnet Screw Alloy Steel ASTM A 574M Zinc Plated
7 Bonnet Cast Iron ASTM A 126-B
8 Stem Primary O-Ring EPDM ASTM D 2000
9 Stem Thrust Washer Stainless Steel ASTM A 276 UNS C41000
10 Gland Seal O-Ring EPDM ASTM D 2000
11 Stem Ring Wiper EPDM ASTM D 2000
12 Operating Nut Washer Carbon Steel Zinc Plated
13 Operating Nut Screw Alloy Steel ASTM A 574M Zinc Plated
14 Square Operating Nut Cast Iron ASTM A 126-B
14A Handwheel(Optional) Ductile Iron ASTM A 536
15 Stem Secondary O-Ring EPDM ASTM D 2000
16 Stem Seal Bushing Brass ASTM B 16 UNS C36000

46
Powering your way to safety
Since 1972

NRS Type Gate Valve


S909

S909 Non-rising Stem Flanged Joint Ends Resilient Wedge Gate Valaves
1 Bolted Bonnet·Non-Rising Stem ·Resilient Wedge·Flanged Ends
2 250 PSI/300 PSI/17.2 Bar Non-Shock Cold Working Pressure
3 CONFORMS TO AWWA C509

Assembly Diagram

S909 Flanged X Flanged


Non-rising Stem Flanged

Shown with optional handwheel


Fr e z z i n g We a t h e r P r e c a u t i o n -
Subsequent to testing a should be an
APPROVED
open position to plate drainage.

47
Powering your way to safety
Since 1972

Dimension
Bolt Weight
Size
Circle
A B C D H Turns
Flange To
Holes Open

Lbs. kg

ln mm ln mm ln mm ln mm ln mm ln mm In mm

2 50 7.0 178 10.0 255 0.63 16.0 6.0 152 7.9 200 4.75 121 4 6.5 30 14

2½ 65 7.5 190 11.3 287 0.69 17.5 7.0 178 7.9 200 5.50 140 4 8.8 35 16

3 80 8.0 203 12.6 321 0.75 19.0 7.5 191 10.2 260 6.00 152 4 10.6 45 20

4 100 9.0 229 13.5 344 0.94 24.0 9.0 229 10.2 260 7.50 191 8 13.0 71 32

6 150 10.5 267 17.4 441 1.00 25.4 11.0 279 14.8 375 9.50 241 8 15.6 122 55

8 200 11.5 292 20.8 529 1.13 28.6 13.5 343 14.8 375 11.75 298 8 17.3 196 89

10 250 13.0 330 24.2 614 1.19 30.2 16.0 406 15.7 400 14.25 362 12 21.4 294 134

12 300 14.0 256 27.6 700 1.25 31.8 19.0 483 19.7 500 17.00 432 12 25.3 426 194

No. Part List Specification


1 Valve Body Ductile Iron ASTM A 536
2 Resilient Wedge ASTM D 2000Ductile Iron ASTM A 536/EPDM ASTM D 2000
3 Wedge Nut Bronze ASTM B 584 UNS C83600
4 Stem Bronze ASTM B 150 UNS C61400
5 Bonnet Gasket EPDM ASTM D 2000
6 Bonnet Screw Alloy Steel ASTM A 574M Zinc Plated
7 Bonnet Ductile Iron ASTM A 536
8 Stem Primary O-Ring EPDM ASTM D 2000
9 Stem Thrust Washer(lower) Bronze ASTM B 584 UNS C83600
10 Stem Thrust Washer(upper) Stainless Steel ASTM A276 UNS S41000
11 Gland Seal O-Ring EPDM ASTM D 2000
12 Stem Seal Bushing Bronze ASTM B 584 UNS C83600
13 Stem Secondary O-Ring(2) EPDM ASTM D 2000
14 Gland Flange Ductile Iron ASTM A 536
15 Gland Flange Screw Alloy Steel ASTM A 574M Zinc Plated
16 Stem Ring Wiper EPDM ASTM D 2000
17 Square Operating Nut Cast Iron ASTM A 126-B
17A Handwheel(Optional) Ductile Iron ASTM A 536
18 Flat Washer Carbon Steel Zinc Plated
19 Screw Alloy Steel ASTM A 574M Zinc Plated

48
Powering your way to safety
Since 1972

OS & Y Type Gate Valve


135QS / 138QS

250 PSI AWWA C509 Iron Body Rising Stem Groove Joint Ends Resilient Wedge Gate Valves
1 Bolted Bonnet · Non-Rising Stem · Resilient Wedge · FlangedxGroove · GroovexGroove
2 250 PSI/17.2 Bar Non-Shock Cold Working Pressure 250 PSI / 17.2 Bar
3 250 PSI/17.2 Bar Non-Shock Cold Working Pressure (160° F/71° C max. operating temperature)
4 CONFORMS TO AWWA C509

FREEZING WEATHER PRECAUTION: Subsequent to testing a piping system, gate valve should be in an open position to allow complete
drainage.
* Electrostatically applied fusion-bonded epoxy coated inside and outside per AWWA C-550

Assembly Diagram

135 QS Groove x Groove

FREEZING WEATHER PRECAUTION:


subsequent to testing a piping system,
gate valve should be in an open
position to allow complete drainage.

138 QS Flanged x Groove


APPROVED

49
Powering your way to safety
Since 1972

Dimension
Bolt
Size
Circle Turns
Flange To
A H Open H Closed C D E F G D D1 T Holes Open

In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm In mm

3 80 8.0 203 20.1 510 15.9 405 0.08 2 3.50 89 0.35 9 0.98 25 10.00 254 3.0 73 7.5 191 0.75 19 6.00 152.5 4-Φ19 10.5

4 100 9.00 229 22.4 568 16.6 422 0.08 2 4.49 114 0.35 9 0.98 25 10.00 254 4.0 100 9.0 229 0.94 24 7.05 190.5 8-Φ19 13.75

6 150 10.5 267 30.3 769 22.9 581 0.08 2 6.61 168 0.35 9 0.98 25 12.40 315 6.0 150 11.0 279 1.00 25.4 9.50 241 8-Φ23 16

8 200 11.5 292 37.8 960 28.5 724 0.09 2.3 8.62 219 0.47 12 1.22 31 14.76 375 8.0 200 13.5 343 1.13 28.6 11.73 298.5 8-Φ23 17.5

10 250 13 330 45.1 1145 35.1 891 0.1 2.55 10.74 272.9 0.52 13.2 1.25 31.7 16.38 416 10 250 15.98 406 1.19 30.2 14.25 362 12-Φ26 21.5

12 300 14 356 52.4 1330 40.2 1020 0.13 3.35 12.78 324.5 0.52 13.2 1.25 31.7 17.52 445 12 300 19.2 483 1.25 31.8 17.01 432 12-Φ26 26

No. Part List Specification


1 Valve Body Ductile Iron ASTM A 536
2. Resilient Wedge STM D 2000 Ductile Iron ASTM A 536/EPDM ASTM D 2000
3. Wedge Nut Bronze ASTM B 584 UNS C83600
4. Dowel Pin Stainless Steel ASTM A 276 UNS S42000
5. Stem Back Seat O-Ring EPDM ASTM D 2000
6. Bonnet Gasket EPDM ASTM D 2000
7. Bonnet Ductile Iron ASTM A 536
8. Stem Packing EPDM ASTM D 2000
9. Threaded Rod Carbon Steel Zinc Plated
10. Gland Bushing Bronze ASTM B 584
11. Gland Cast Iron ASTM A 126-B
12. Gland Nut Stainless Steel 18-8
13. Yoke Screw Alloy Steel ASTM A 574M Zinc Plated
14. Yoke Cast Iron ASTM A 126-B
15. Yoke Bushing Bronze ASTM B 584
16. Flat Point Set Screw Alloy Steel ASTM F 912M Black Oxide
17. Yoke Bushing Retainer Cast Iron ASTM A 126-B
18. Handwheel Ductile Iron ASTM A 536
19. Handwheel Nut Carbon Steel Zinc Plated
20. Flat Head Screw Carbon Steel Zinc Plated
21. Stem Bronze ASTM B 150 UNS C61400
22. Bonnet Screw Alloy Steel ASTM A 574M Zinc Plate

50
Powering your way to safety
Since 1972

NRS Type Gate Valve


SJ 909

SJ909 Mechanical Joint Ends Resilient Wedge Gate Valves


1 Bolted Bonnet·Non-Rising Stem·Resilient Wedge·MJ Ends 250 PSI/17.2 Bar
2 250 PSI/300 PSI/17.2 Bar Non-Shock Cold Working Pressure
3 CONFORMS TO AWWA C509
5 Coating-Electrostatically applied fusion-bonded epoxy 0.2-0.5mm.inside and outside. Meets or exceeds AWWA C550.Maximum
operating temperature 160℉/71℃.
6 Freezing Weather Precaution Subsequent to testing a piping system,valves should be in an open position to allow complete drainage.

Assembly Diagram

SJ909 Flanged X Flanged

Shown with optional hand wheel


Fr e e z i n g w e a t h e r Pr e c a u t i o n -
Subsequent to testing a should be in an
open position to plate drainage.

APPROVED

51
Powering your way to safety
Since 1972

Dimension Weight

Bolt
Size
Circle Turns
Flange To
A B C D E F H Holes Open

Lbs Kg

In mm In mm In mm In mm In mm In mm In mm In mm In mm

3 80 8.0 203 12.7 322 0.94 24 7.7 196 4.9 126 3.1 80 12.2 260 6.19 157 4 10.8 43 20

4 100 10.0 254 13.5 344 1.00 26 9.1 232 6.0 153 3.9 100 10.2 260 7.50 191 4 13.0 70 36

6 150 11.5 292 17.4 441 1.06 27 11.1 283 8.1 206 5.9 150 14.8 375 9.50 241 6 15.7 112 51

8 200 11.5 292 20.8 529 1.12 28 13.4 340 10.3 261 7.9 300 14.8 375 11.75 298 6 17.3 170 77

10 250 13.0 330 24.2 614 1.18 30 15.7 400 12.3 313 9.8 250 15.7 400 14.00 356 8 21.4 267 121

12 300 14.0 356 27.6 700 1.25 32 18.0 456 14.4 367 11.8 300 19.7 500 16.25 413 8 25.3 388 176

Part List Specification


1 Valve Body Ductile Iron ASTM A 536
2 Resilient Wedge ASTM D 2000Ductile Iron ASTM A 536/EPDM ASTM D 2000
3 Wedge Nut Bronze ASTM B 584 UNS C83600
4 Stem Bronze ASTM B 150 UNS C61400
5 Bonnet Gasket EPDM ASTM D 2000
6 Bonnet Screw Alloy Steel ASTM A 574M Zinc Plated
7 Bonnet Ductile Iron ASTM A 536
8 Stem Primary O-Ring EPDM ASTM D 2000
9 Stem Thrust Washer(lower) Bronze ASTM B 584 UNS C83600
10 Stem Thrust Washer(upper) Stainless Steel ASTM A276 UNS S41000
11 Gland Seal O-Ring EPDM ASTM D 2000
12 Stem Seal Bushing Bronze ASTM B 584 UNS C83600
13 Stem Secondary O-Ring(2) EPDM ASTM D 2000
14 Gland Flange Ductile Iron ASTM A 536
15 Gland Flange Screw Alloy Steel ASTM A 574M Zinc Plated
16 Stem Ring Wiper EPDM ASTM D 2000
17 Square Operating Nut Cast Iron ASTM A 126-B
17A Handwheel(Optional) Ductile Iron ASTM A 536
18 Flat Washer Carbon Steel Zinc Plated
19 Screw Alloy Steel ASTM A 574M Zinc Plated

52
Powering your way to safety
Since 1972

OS & Y Type Gate Valve


S907

S907(OS&Y) GATE VALVE,


Flanged, UL / FM,
Rated pressure 250PSI,
Flange Conforms to ANSI B16.1 Class125,

Freezing Weather Precaution – S907 Flanged X Flanged


Subsequent to testing a piping system,
valves should be in an open position to
allow complete drainage.

APPROVED

53
Powering your way to safety
Since 1972

F907 Dimension Weight


Bolt
Size Turns
Circle Flange To
A B C D F Holes Open
Lbs Kg
In mm In mm In mm In mm In mm In mm In mm

2 50 7.0 178 10.0 255 0.63 16.0 6.0 152 7.9 200 4.75 121 4 6.5 44 20

21/2 65 7.5 190 11.3 287 0.69 17.5 7.0 178 7.9 200 5.50 140 4 8.8 46 21

3 80 8.0 203 12.6 321 0.75 19.0 7.5 191 10.2 260 6.00 152 4 10.6 50 23

4 100 9.0 229 13.5 344 0.94 24.0 9.0 229 10.2 260 7.50 191 8 13.0 75 34

6 150 10.5 267 17.4 441 1.00 25.4 11.0 279 14.8 375 9.50 241 8 15.6 134 61

8 200 11.5 292 20.8 529 1.13 28.6 13.5 343 14.8 375 11.75 298 8 17.3 225 102

10 250 13.0 330 24.2 614 1.19 30.2 16.0 406 15.7 400 14.25 362 12 21.4 328 149

12 300 14.0 356 27.6 700 1.25 31.8 19.0 483 19.7 500 17.00 432 12 25.3 487 221

14 350 15.0 381 34.3 870 1.38 35.0 21.0 533 19.7 500 18.74 476 12 30.0 676 307

16 400 16.0 406 34.3 870 1.46 37.0 23.5 597 19.7 500 21.24 539.5 16 34.0 881 400

No. Name Materials Remarks


1 Body Ductile Iron ASTM A536 65-45-12
2 Wedge Ductile Iron+Rubber ASTM A536 65-45-12+ASTM D2000 EPDM
3 Stem Trim Bronze ASTM B584 C83600
4 Retainer Stainless Stool ASTM A276 SS304
5 O-Ring Rubber ASTM D2000 EPDM
6 Stem Al Bronze or SS STM B 150 C61400/A276 SS304
7 Seai Gasket Rubber ASTM D2000 EPDM
8 Inside Hexgonal Bolt Carbon Steel ASTM A574
9 Bonnet Ductile Iron ASTM A536 65-45-12
10 Stuffing Rubber ASTM D2000 EPDM
11 Threaded Rod Carbon Steel ASTM A307
12 Stuffing Bushing Bronze ASTM B584 C83600
13 Stuffing Gland Ductile Iron ASTM A536 65-45-12
14 Nut Carbon Steel ASTM A574
15 Yoke Ductile Iron ASTM A536 65-45-12
16 Handwheel Nut Carbon Steel ASTM A194-2H
17 Handwheel Ductile Iron ASTM A536 65-45-12
18 Stem Nut Bronze ASTM B584 C83600
19 Nut Bolt Carbon Steel ASTM F912M
20 Gland Ductile Iron ASTM A536 65-45-12
21 Inside Hexgonal boit Carbon Steel ASTM A574

54
Powering your way to safety
Since 1972

55
Powering your way to safety
Since 1972

56
Powering your way to safety
PHOTO LUMINESCENT SIGNAGES
Since 1972

57
ACCESSORIES Powering your way to safety
Since 1972

FIRE HOSE FB-5X / FB-10X FIRE WATER MONITOR

TRIPLE PURPOSE NOZZLE CO2 GAS CARTRIDGES FIREMAN’s AXE

ROSSETE PLATE 2 WAY / 3 WAY / 4 WAY FIRE BRIGADE INLAY

SPRAY NOZZLE FIRE EXTINGUISHER FLOOR STAND FIRE EXTINGUISHER TROLLEY

58
Email: info@safexfire.com