Professional Documents
Culture Documents
Modbus RTU
WebCode 9440B
9440/15 series CPU & power modules (CPM) for Zone 2 are used for the intrinsically safe supply of
power to up to 16 IS1+ I/O modules and to field circuits. RS485 with V0/V1 HART PROFIBUS DP
is used for communicating with the automation system. The CPMs support system redundancy and
optical rings. A DTM and process bus or service bus are used for asset management integration.
Technical Data
Explosion Protection
Application range (zones) 2
21
22
Ex interface zone 2
21
22
IECEx gas certificate IECEx PTB 14.0039
IECEx gas explosion protection Ex ec [ia, ib Gb] IIC T4 Gc
ATEX gas certificate PTB 99 ATEX 2222
ATEX gas explosion protection E II 3 (2) G Ex ec [ia, ib Gb] IIC T4 Gc
Certificate FMus FM17US0332X
Certificate cFM FM16CA0134X
Marking cFMus NI, Class I, Div. 2, Groups A,B,C,D;
Class I, Zone 2, Group IIC
ANI Class I,II,III, Div. 2, Groups A,B,C,D,E,F,G;
Class I, Zone 2, Group IIC
T4 at Ta = 65 °C
See Doc. 9440 6 031 002 1
EAC certificate TS RU S-DE.GB04.B.00448
EAC certificate valid until 2020-07-01
EAC gas explosion protection 7 2 Ex nA [ia Ga, ib Gb] IIC T4 Gc X
Certificates ATEX (PTB), Brazil (ULB), Canada (FM), IECEx (PTB), Korea (KTL), USA (FM)
Ship approval EU RO MR
Notes CCC certificate available from 2021 onward
Installation Zone 2 / Division 2
Further information see respective certificate and operating instructions
Electrical Data
Protocols Profibus DP V0
Profibus DP V1
Profibus DP V1 HART
Redundancy full redundancy
Connection Fieldbus RS485 1
Connection ServiceBus RS485 1
Interface RS485 1
Transmission speed RS-485 9,6 kbps ... 1,5 Mbps
Address setting RS485 0 – 127
Transmission distance/rate for copper 1
RS485 2
3
4
Transmission distance/rate FO RS485 1
Transmission distance/rate Service- 1
BusRS485
Transmission distance/rate note For greater lengths fibre optic technology is available.
Data transmission RS485 3
4
Internal signal delay max. (8 I/O mod- 7 ms for Digital modules, 10 ms for Analog modules
ules)
Auxiliary Power
Nominal voltage 24 V DC
Auxiliary power voltage range 8
Polarity reversal protection yes
Undervoltage monitoring Yes
Current consumption (without I/O mod- 0.3 A at 24 V DC
ules)
Current consumption (with 8 I/O mod- approx. 2.5 A at 24 V DC
ules)
Current consumption approx. 4.9 A at 24 V DC
(with 16 I/O modules)
Power dissipation (without I/O modules) 7.2 W
Power dissipation 1 W
(per I/O module)
Galvanic Isolation
Auxiliary power/system components 1500 V AC
Fieldbus/ServiceBus interface/system 1
components
Bus interface/Bus interface 1
Device Specific Data
Software 1
2
LED operating conditions LED "RUN", green
LED group error LED "ERR", red
LCD display 1
LCD Display 1
Mounting / Installation
Mounting position horizontal
vertical
148 [5,83]
167 [6,57]
96,50 [3,80]
39 [1,54]
45 [1,77]