Fluokit M24+
Air insulated switchgear
Instructions
Assembly of the internal arc
kit 12.5 to 25 kA
Fluokit M24+ Contents
AMTNoT112-02 revision: 07 i
Fluokit M24+ 1 Schneider Electric at your
service
© - Schneider Electric - 2012. Schneider Our products are fully quality controlled and Schneider Electric declines any responsibility
Electric, the Schneider Electric logo and their tested at the factory in accordance with the for the following points:
figurative forms are Schneider Electric standards and regulations currently in force. - the non respect of the recommendations in
registered trademarks. The other brand The correct functioning and lifespan of the this manual which make reference to the
names mentioned within this document, product depend on respecting the installation, international regulations in force.
whether they be copyright or not, belong to commissioning and exploitation instructions - the non respect of the instructions by the
their respective holders. found in this manual. Not respecting these suppliers of cables and connection
Schneider Electric request the carefully instructions is likely to invalidate any accessories during installation and fitting
reading of the following instructions in order guarantee. operations,
to familiarize yourself with the product in this - possible aggressive climatic conditions
Local safety requirements which are in (humidity, pollution, etc.) acting in the
document before trying to install, operation, accordance with these instructions,
put into service or conduct the maintenance immediate environment of the materials that
especially those regarding the safety of are neither suitably adapted nor protected for
on it. product operators and other site workers, these effects.
must be observed.
Code for a product recommended 21 Tightening torque value Mark corresponding to a key
06 and marketed by Schneider Electric Nm Example: 21 Nm ATTENTION
10
1.5 Contacts
Group Schneider Electric service centers are
there for:
J Engineering and technical assistance
J Commissioning Schneider Electric Energy France
J Training
35 rue Joseph Monier - CS 30323
J Preventive and corrective maintenance
J Spare parts F-92506 Rueil-Malmaison Cedex
J Adaptation work
www.schneider-electric.com
AMTNoT112-02 revision: 07 1
Fluokit M24+ 2 With regards to this User Manual
2.3 Tools required for the operations described in this user manual
- Open-ended spanners sizes 10 and 13 mm
2.4 Tightening torque values [Nm] for standard assemblies (nut + bolt)
2 AMTNoT112-02 revision: 07
Fluokit M24+ 3 Equipment for AF and AFL
switchboards
Top view
2
1
100 mm
J To each far end Functional Unit for the J Mount and fix the rear deflector, at J Assembly detail: the deflector (2) is fixed
blanking off side panel (1) by all its 2 points (2) to each Functional Unit on by 2 bolts H M6x20 + washers.
points. the switchboard.
2
J If the switchboard is near a wall, begin by 4
that side.
J Position the first Functional Unit.
3
J Apply and respect the installation
instructions given in Manual AMTNoT090. 3
J The switchboard being connected,
assemble the rear deflectors between one
another (3).
J Fix the reinforcement bracket(4) on to the
left-hand Functional Unit, using the 3 fixing
points on the roof and by fitting it flush
against the wall.
J Finish off the assembly by fixing the
reinforcement bracket (4) to the left-hand
side wall.
AMTNoT112-02 revision: 07 3
Fluokit M24+
3.2 Switchboard 12.5 kA (AF or AFL - 1 s) and 16 kA (AF or AFL - 1 s) (IEC 62271-200)
1 Top view
2
100 mm
J To each far end Functional Unit, fix the J Mount and fix the rear deflector, at J Assembly detail: the deflector (2) is fixed
blanking off side panel (1), thickness 2 points, (2) to each Functional Unit of by 2 bolts H M6x20 + washers.
40 mm, by all its points. the switchboard.
Right or left: panels are 1 Top view Right or left: panels are
2 4
identical identical
Functional
3 Unit
3
3 1
J At the rear, fix the sheet metal (3) to the J Details of the assembly. J Fix the upper rear side panel (4) on to
side blanking off panel (1). the sheet metal (3).
4 AMTNoT112-02 revision: 07
Fluokit M24+
1
2 3
J To each far end Functional Unit, fix the J Mount and fix, at 2 points, the rear J Assemble the side panels (3) and the
blanking off side panel (1), thickness deflector (2) to each Functional Unit of reinforcement panels (4) at 3 central
40 mm, by all its points. the switchboard. fixing points (fasteners supplied).
1 2 Top view
Functional
3 Unit
3 1
J Metal panels (3) and (4) assembled. J At the rear, clip the metal panel (3) into J Details of the assembly.
the slot of the Functional Unit and fix it on
to the side blanking off panel (1).
5 7
4
7 6
6
J Unscrew the 2 front bolts on the roofs (if J Fit and fix the side deflectors (5) on to J Apply and respect the installation
there is no roof box). the lateral blanking off panels (1). instructions given in User Manual
J Fit and fix the vertical deflectors (4) at J Also fix these deflectors to the front (4). AMTNoT090.
the front. J The switchboard being connected,
assemble the rear deflectors (6) and the
front ones (7) between one another.
N.B.: Front deflectors are assembled if
there is no LV top cabinet.
AMTNoT112-02 revision: 07 5
Fluokit M24+ 4 Equipment for AFLR
switchboards
5
J At the rear of each Functional Unit, fix J Order of fitting: Begin by placing and J Fit and fix 4 reinforcements (6) on to
the spacer (5) to the lower right-hand fixing the metal panel D, then by each large panel (D, I and G).
side. following the panels I, to finish with the J Fix these reinforcements by all their
metal panel G. fixing points.
J N.B.: Fix the panels between each other,
by all their fixing points, as well as on the
spacers (5).
8
J At the rear of each Functional Unit, fix J Order of fitting: Begin by placing and J Fit and fix 4 reinforcements (9) on to
the spacer (8) to the lower right-hand fixing the metal panel D, then by each large panel (D, I and G).
side. following the panels I, to finish with the J Fix these reinforcements by all their
metal panel G. fixing points.
J N.B. : fix the panels between each other,
by all their fixing points, as well as on the
spacers (8).
6 AMTNoT112-02 revision: 07
Fluokit M24+
1 1
1 Rear view 1
2 2
1 1
1 Rear view 1
Rear view
AMTNoT112-02 revision: 07 7
Fluokit M24+
J Order of fitting: Begin by placing and fixing the metal J Fit and fix 4 reinforcements (4) on to each large panel
panel D, then by following the panels I, to finish with the (D, I and G).
metal panel G. J Fix these reinforcements by all their fixing points.
J N.B.: Fix the panels between each other and on to the
spacers, by all of the fixing points.
G
I
D
Rear view of the switchboard Rear view of the switchboard
8 AMTNoT112-02 revision: 07
Fluokit M24+ 5 Notes
If you have any comments on the use of this document or on the use of the equipment and services that are described in it, please
send us your remarks, suggestions and wishes to:
Schneider Electric Service Technique BP 84019 F-71040 Mâcon Cedex 9 - FRANCE
Fax: 33 (0)3 85 29 36 36
AMTNoT112-02 revision: 07 9
E 2011 Schneider Electric - All rights reserved
Schneider Electric Energy France Due to possible changes in standards and equipment, the characteristics and images
35, rue Joseph Monier shown in this document can only be confirmed by contacting our departments.
CS 30323
F - 92506 Rueil-Malmaison Cedex