I. CS Imaging 8: Overview
II. CS Imaging 8: Requirements - installation and licensing
III. CS Imaging 8: Features
IV. CS Imaging 8: Troubleshooting and error codes
The CS Imaging 8 technical training offers the contents: A presentation of
the software with the important points as well as a comparison with the
previous versions. A description of the system requirements for computers.
Then the installation steps, as part of an update and as part of a new
installation. A review of the new features, including the Dash Board and
Patient Brower At the end of the module, the licensing is explained in detail
‐ then you will be able to pass the validation test of the training.
Page ‐ 2
3
I. CS Imaging 8: Overview
CS Imaging 8.0.0 is the new Imaging Software of Carestream Dental
CS Imaging 8.0.0 is composed of 2 parts:
• Patient Browser:
• Patient Browser is similar to CSI 7
• New 2D Viewer:
Different tools available in
left side
CS Imaging 8.0.0 is Carestream Dental's new imaging software provided with
Carestream Dental product range as an evolution of Imaging Software .
In this version, main changes is the 2D viewer . The patient browser is
similar to CS Imaging 7 . Those 2 elements are explained in detail in the
following pages.
Page ‐ 3
4
I. CS Imaging 8: Overview
Comparison between:
KDIS/DIS/CSI 7 CS Imaging 8
Acquisition Monitor
‐On the left side of the slide are the steps and structure of the previous KDIS
/ DIS software: We move from the Patient Card to the 2D viewer imaging
where the acquisition can be done for all Carestream Dental products The
patient browser allows acquisition for the extra‐oral range only.
‐On the right side, we present the use of CS Imaging 8.0.0: Note that the
acquisition E / O (Extra‐Oral) and I / O (intra‐oral) can be performed directly
from the Patient Browser. From the Patient Browser we can open the 2D
viewer imaging, where the acquisition can be performed for all products.
‐CSDM Lite and Monitor are programs in the background that keep the
Patient Browser running.
‐The new database from CSI 8 cannot be shared with previous Imaging
software version (KDIS / DIS and CSI 7) due to CSDM Lite improvement –
(new features which cannot be read by previous version of CSDM Lite )
Page ‐ 4
5
I. CS Imaging 8: Overview
No hybrid installation
Windows File
Storage
Page ‐ 5
6
I. CS Imaging 8: Overview
Patient Browser
Page ‐ 6
7
I. CS Imaging 8: Overview
Patient Browser
Patient browser new Features
• Global search
• Searching a patient by the family name, first name, patient ID or date of
birth, Social security number
• Patient list
• Sort by family name, first name, patient ID or Social security
number
The patient browser allows you to do a global search, by last name, patient
ID, date of birth, social security number.
The patient list can be sorted on these same criteria.
Page ‐ 7
8
I. CS Imaging 8: Overview
Patient Browser
Patient browser new Features
• Image gallery
• Display by thumbnails or by list
• Sort by Date or by Type
• Filter by tooth or by modality type
The image gallery of the Patient Browser allows you to display by thumbnail
or list, sort by date or type of images, filter by tooth or type of modality.
In this image, some teeth in the dental arch are highlighted : this means
that all thumbnails displayed in the gallery contain these teeth
Page ‐ 8
9
I. CS Imaging 8: Overview
Patient Browser
Patient browser:
• Image management
• Import / Export
Import files / DICOMDIR
Export images to Email, to Folder or to DICOMDIR
Print of 2D images
• Other management
Copy
Delete
Localize
Right clicking on an image provides access to the different image
management options such as Copy / display / localize / Delete …
The Location menu allows you to locate the image file in the database
folder.
Import / Export images is possible ‐ from or into the images folder or a
Dicom directory.
They can be emailed ‐ and printed for 2D images.
New feature : Image information pop up provides Dicom Tags.
Page ‐ 9
10
I. CS Imaging 8: Overview
Patient Browser
Patient browser Features
• Launch extra-oral acquisition, 3D scanner ( camera) and Intra oral directly from the
patient browser
Now, 3D Scanner icon and I/O icons are also available.
Page ‐ 10
11
I. CS Imaging 8: Overview
Patient Browser
Patient browser Features
• Patient card Create Edit
• More information available New existing
Gender Patient Patient
Pregnancy status
Page ‐ 11
12
I. CS Imaging 8: Overview
CSDM Lite
CS Imaging manages your image database and patient list via CSDM lite. An application called Monitor
allows to check the status of CSDM lite. You can also use Monitor to:
The CSDM Lite runs in the background.
The Monitor is displayed from the Carestream Dental icon in the taskbar.
(no fica on area of the icons)
Page ‐ 12
13
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Home
• Shows the CSDM Lite Status
Reminder: To open Monitor, click on the Carestream Dental logo on the
taskbar. The role of Monitor is to display the status of CSDM Lite. In normal
situation, it is not necessary to open Monitor. This is necessary only for
troubleshooting or during setup / installation.
Page ‐ 13
14
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Start
• Starts CSDM Lite
Monitor starts automatically when Windows OS starts
The interface illustrates the different Monitor’ options ‐ In this example : “Start”
Page ‐ 14
15
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Stop
• Stops CSDM Lite
In this example : Stop
This option allow us to stop the CSDM Lite
Page ‐ 15
16
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Restart
• Stops and starts CSDM Lite
In the example: Restart
This option allows to restart the CSDM Lite
Page ‐ 16
17
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Version
• Displays the CSDM Lite version
In the example : Display version
It shows the CSDM Lite version
Page ‐ 17
18
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Get configuration
• Displays the path of the CSDM Lite database
In the example : Get Configuration
“Get configuration” provides information about the database path
Page ‐ 18
19
I. CS Imaging 8: Overview
Monitor and CSDM Lite
Monitor
• Set configuration
• Changes the path of the CSDM Lite database
For the item “ Set configuration “ : Detailed explanations will be presented
in the Installation section of this course.
“Set configuration” allows the user to specify the database path
The Database folder (patient images) must be moved if the CSDM Lite path
is modified
Page ‐ 19
20
I. CS Imaging 8: Overview
Patient database architecture – Patient File Mode
When CS Imaging 8 is installed on a PC where DIS was previously installed, the previous Patient database is not modified for
existing patients (patient created before the installation of CSI 8) . For more details, refer to TechNews TN#252 on Infotec
C:\Users\Public\Documents\Carestream\DB
Architecture of the patient base. The patient database is identical to DIS
except for a folder named ".csi_data" which has been added to the root of
the database folder and for each patient folder. This directory contains
thumbnails of the gallery
Page ‐ 20
21
I. CS Imaging 8: Overview
Patient database architecture – Patient File Mode
When CS Imaging 8 is installed on a PC where DIS was NOT previously installed and for newly created
patient with CSI 8, the Patient database architecture is not similar to a DIS Patient database architecture. It is
a CSDM Lite Patient database architecture.
C:\Users\Public\Documents\Carestream\DB
Patient database architecture:
The patient base presents a new architecture.
When CS Imaging 8 is installed on a computer where DIS or / and CS Imaging
V7 have never been installed:
The architecture of the patient database is different from the DIS patient
database.
We obtain the architecture of a patient database CSDM Lite.
Each patient is represented by a folder named GUID ‐ which means Global
Unique Identifier.
Page ‐ 21
22
I. CS Imaging 8: Overview
Patient database architecture – DPMS Case
When a DPMS launches CSI 8: the DPMS manages the patient directories, not CSI 8
•No modification required if CSI8 is launched from DPMS
•No behavior change if CSI8 is launched from DPMS
CSI 8
Windows File
Storage
Page ‐ 22
23
I. CS Imaging 8: Overview
Patient database architecture – DPMS Case
CSI 8
Windows File
Storage
CSI 8
CSDM lite shared database
Warning: By default in DPMS mode, the CSDM Lite database is in C drive.
The CSDM Lite patient list is not synchronized between all PC ‘s( When
opening CSI in stand‐alone, the patient list is not the same on all PC)
Guidelines for installation
•If the user does not open CSI8 in stand‐alone and DPMS is always
working => No configuration required
Otherwise, it is recommanded to set the CSDM lite database path in all
CSI 8 PC to an image server location so that the local CSDM Lite
database becomes a shared one.
Page ‐ 23
24
I. CS Imaging 8: Overview
II. CS Imaging 8: Requirements - installation and licensing
III. CS Imaging 8: Features
IV. CS Imaging 8: Troubleshooting and error codes
Page ‐ 24
25
CS Imaging 8.0.0
CS Link / VDDS
Trace Module
…
Note: Version Trophy Imaging is the equivalent product for Japan region
Note: Version Trophy Imaging is the equivalent product for Japan region
Page ‐ 25
26
ITEM Requirement
CPU Computer With 2.4 Ghz Intel Duo Core or equivalent
RAM • 4 GB (Recommended)
• 2 GB (Minimum)
Graphics card 512 MB
Hard disk 1.2 GB for Software installation
40 GB Free space (Recommended)
Display 1024 x 768 minimum screen resolution - 32 bit color mode
It is essential to have the configuration and environment required to install
and run CS Imaging 8.
This table shows the minimum requirements.
These information are also available in the User Guide. (available on infotec)
The minimum requirement is the same as for the previous imaging software
versions
Page ‐ 26
27
ITEM Requirement
Network requirements If you have a deployment where the image database is located on a different
computer from the CS Imaging installation:
• no 3D volumes are present, then use 10 BaseT network bandwidth (10 MB/s) for a
2D environment.
• 3D volumes are present, then use 100 BaseT network bandwidth (100 MB/s) for
2D/3D environments.
Compatibility details
CSI8 is compatible for
• IO drivers Suite v1.5.0 minimum
• EO drivers Suite v1.0.0 minimum
• IO/EO drivers together Suite v1.8.0 minimum
Page ‐ 27
28
ITEM Recommandations
General Although a image server might look no different from a high-end desktop PC, the
Image server image server shall be designed for very different tasks.
requirements A desktop computer is designed for one person who needs a user-friendly operating
(applicable to all file system to run desktop applications.
share) The image server makes it easy for your CS Imaging users to share data and
collaborate, since it operates as a central repository for all of your images.
Warning : Having a undersized image server will slow down your CSI application.
Example server for a PC •CPU >= 2,3 GHz quad core Processor
designed for 10 •RAM >=8 GB
connected PC •Network interface 1GB
•Hard Disk > 1TB
Example NAS designed •CPU >= 2,5 Ghz dual core
to handle 10 connected •RAM >= 2 GB of memory,
PC •Network interface 1GB
•Hard Disk > 1TB
Example of image server requirements
Page ‐ 28
29
For the installation of the CS Imaging 8 software, simply follow the steps of
the installer (Wizard) clicking Next ‐ after accepting the conditions on the
license.
Page ‐ 29
30
It is necessary to differentiate 2 cases:
as part of a new installation or as part of a system upgrade.
For a new installation, the installation path is: C: \ program files (x86) \
Carestream
For an upgrade, the directory already used will be selected automatically so
no need to uninstall previous version to upgrade to CSI 8
Page ‐ 30
31
The demo database will only be available for a new installation.
The Demo box is grayed out if a patient database already exist
From this step, you can select needed software (CS 3D Imaging, CS Restore
and CS Model)
CS Restore and CS Model require License
Page ‐ 31
32
Select CS Link if a Third DPMS is used instead of the Carestream Patient browser
VDDS is a bridge between Third DPMS and CS imaging software (Used in Germany only)
During the installation procedure, it is necessary to deal with the case where
a DPMS is used by the customer.
For France, the DPMS is Trophy Gestion. DPMS stands for: Dental Practice
Management software => This is the manufacturer’s patient management
software. In this case, click "Yes" to the question about configuring a DPMS
and then choose CS Link.
You will need to refer to the CS Link configuration manual.
Note: VDDS is a gateway between CS Imaging and a third‐party DPMS =>
VDDS is used only in Germany.
If no third DPMS is used then click “No”
Page ‐ 32
33
II. CS Imaging 8: Requirements-Installation-Licensing
Patient Database Demo
Demo patient name Detail
RVG DEMO RVG 5100/6100/6500 demo images (x58)
9000 panoramic (x4) and cephalometric (x4) demo images, including ceph auto trace
9000 DEMO
images
9000 3D ENDO CS 9300 3D volume demo - Endodontic case (1 3D volume and 1 RVG)
9000 3D ORTHO 9000 3D stitched volume demo - Ortho case (1 panoramic & 1 stitched 3D volume)
CS1200 DEMO CS 1200 intraoral camera demo images (x42)
CS1500 DEMO CS 1500 intraoral camera demo images (x41)
CS1600 DEMO CS 1600 intraoral camera demo images (x129)
CS7600 DEMO CS 7600 imaging plate demo images (x26)
CS8100 DEMO CS 8100 panoramic demo images (x12)
CS8100 2D+ COMPOUNDED
CS 8100 2D+ Compounded Odontoma case (x8 panoramic & x3 intraoral)
ODONTOMA
CS8100 2D+ GERMINATION
CS 8100 2D+ Germination case (x8 panoramic)
CASE
CS8100 2D+ IMPACTED CANINE CS 8100 2D+ Impacted canine case (x8 panoramic)
CS8100 2D+ IMPACTED TOOTH CS 8100 2D+ Impacted tooth #13 case (x8 panoramic)
CS8100 2D+ IMPACTED TOOTH
CS 8100 2D+ Impacted tooth #23 case (x8 panoramic)
#23
CS9300 5X5 - IMPACTED
CS 9300 3D Impacted 3D molar case (1 intraoral & 1 5x5 3D volume)
MOLLAR
CS9300 DEMO CS 9300 panoramic (x5) and cephalometric (x4) images
CS9300 3D 10X10 - IMPLANT CS 9300 3D volume Implant planning case - odontome on #27 (1 10x10 3D volume &
PLANNING 1 3D screenshot)
CS 9500 3D demo volumes
CS9500 DEMO 1 3D volume - 15x9 : Impacted tooth #43
1 3D volume - 18x20 TMJ Ankylosis
LOGICON CARIES DETECTION Logicon caries detection - RVG demo images (x4 RVG & x9 intraoral camera)
The table above lists all the patients in the demo database.
This database can be installed only in the case of a new installation.
Page ‐ 33
34
On customer’s request, one license is provided with the Carestream product to be activated
on one computer.
Principle and procedure of Licensing..
A license per CSI 8 installation and has to be activated.
Computers sharing the same database need license activation. different
package available (1, 5 or 20 activations)
Page ‐ 34
35
I. CS Imaging 8: Overview
II. CS Imaging 8: Requirements - installation and licensing
III. CS Imaging 8: Features
IV. CS Imaging 8: Troubleshooting and error codes
The CS Imaging 8 technical training offers the contents: A presentation of
the software with the important points as well as a comparison with the
previous versions. A description of the system requirements for computers.
Then the installation steps, as part of an update and as part of a new
installation. A review of the new features, including the Dash Board and
Patient Brower At the end of the module, the licensing is explained in detail
‐ then you will be able to pass the validation test of the training.
Page ‐ 35
36
New features provided by CS Imaging 8
The image gallery dashboard allows:
A wide visualization and proposes an intuitive search thanks to a
representation of the dental arch.
The auto‐arrange function: In one click, all the images displayed are
reorganized
The Dark Room mode: large screen without interface graphic.
All tools are available including the acquisition and navigation from one
image to another.
Simultaneous enhancement of selected images: in 1 click, an image
enhancement correction is applied to all selected images.
Page ‐ 36
37
in only a couple of easy clicks, this simplifies error in one right-click, get to your image folder location for that patient
management
New features provided by CS Imaging 8
• Move images from one patient to another: avoid possible errors with a
few simple clicks
• Locating images: right‐click to display this patient's images folder
• Magnifying glass: zooms in on an area of the image
• 3D rendering: combination of a visualization of a 2D pano image with a
3D volume as well as curved slices
Page ‐ 37
38
III. CS Imaging 8: Features
Acquisition icons (including IO) – there are as many icons as
Patient Browser there are installed devices
Image
management
(import, export,
email, print,
Patient list DICOMDIR…
+ summary any selected
details images)
(patient name,
DOB, Social
Security#, ID#)
Image gallery tools : display the image gallery in thumbnails view / Filter down the image gallery by Image gallery display : all-in-one instant
list view / large preview view (including 3D’s that can be rotated) / tooth numbers (one or more), by thumbnail views (including 3D’s),
Cover Flow view image type, or a combination of any automatically imported snapshots/cross-
+ organize by date or image type of these sections, pseudo cephs, directly edit image
comments including 3D’s (in list view)
CS Imaging 8 - Technical Training - 07-2018
Thank you for reading all the descriptions. Click Continue when playback is
complete.
Page ‐ 38
39
The Dashboard is the first point of entry when launching from a DPMS (any).
It regroups all « Patient Browser » tools less the Patient Management capabilities.
From this initial page, the user has an instant zero-click view of all the available images for the patient, and benefits from
the full image gallery capabilities of the Patient Browser, including image acquisitions.
The Dashboard ‐ from a DPMS The dash board is the gateway when you
launch the application from a DPMS
It groups all the tools of the patient browser.
From this initial page, the user has a snapshot of all available images for that
patient.
It can also benefit from all the possibilities of the image gallery, including
the Acquisition menu
Page ‐ 39
40
III. CS Imaging 8: Features
Acquisition icons Display 3D cross- Screen options
Image viewing workspace sections (and
navigate through
(activate Auto-Arrange
mode, manage templates
Title bar with Patient name
Display CAD/CAM’s (zoom/rotate) the slices) or Analysis, show/hide
options
System icons
Toolbar selector
(switch Go back to
between image / Dashboard or go to
drawings / share) Darkroom
Overview of the image review space.
Thank you for reading the different descriptions.
Click Continue at the end of the playback.
Page ‐ 40
41
Go back to the
Toolbar selector image viewing
workspace
Toolbar
Measurements
(here with the
Window (applies to
Measurements
any image type
group icon
containing
extended list of
measurement
tools)
results + can be
used to compare
measurement
results between
multiple selected
Group icons are images)
notified by the
white triangle :
clicking on the
white triangle or
making a long click
will extend a list of
more tools Control Panel
Image gallery
Right-click menus are available at any time Image title bar (includes info/save) Darkroom image viewing workspace enables to
whatever the workspace, whether over an and navigate from one image to the next display any image (2D/3D/CAD-CAM), one at a
image, a thumbnail, or the image viewing (or directly through the arrow keyboards) time, and use any tool (including image
workspace acquisitions) as per in the image viewing
workspace.
CS Imaging 8 - Technical Training - 07-2018
Overview of the image review space.
Thank you for reading the different descriptions.
Click Continue at the end of the playback.
Page ‐ 41
42
Overview of the image review space.
Thank you for reading the different descriptions.
Click Continue at the end of the playback.
Page ‐ 42
43
I. CS Imaging 8: Overview
II. CS Imaging 8: Requirements - installation and licensing
III. CS Imaging 8: Features
IV. CS Imaging 8: Troubleshooting and error codes
The CS Imaging 8 technical training offers the contents: A presentation of
the software with the important points as well as a comparison with the
previous versions. A description of the system requirements for computers.
Then the installation steps, as part of an update and as part of a new
installation. A review of the new features, including the Dash Board and
Patient Brower At the end of the module, the licensing is explained in detail
‐ then you will be able to pass the validation test of the training.
Page ‐ 43
44
CSDM Lite is automatically started when Windows starts:
2 processes are listed in the task manager
‐CSDMLite.exe
‐CSDMLwdog.exe (WatchDog)
‐If they are not listed in the Windows task manager, make sure that the
antivirus doesn’t block them
‐Depending on the antivirus, you have to put exceptions to allow them to
start
Page ‐ 44
45
Monitor interface starts automatically when Windows OS starts:
The process is listed in the Windows task manager : Monitor.exe
Page ‐ 45
46
Here is an example of CSDM issue:
Err_S_CSDM_‐2 appears when launching CSI 8
See root cause and solution in next slide.
Page ‐ 46
47
Please read the steps of the troubleshooting in the slide.
Page ‐ 47
48
Here is an example of CSDM issue:
Err_S_CSDM_100 No access to images
See root cause and solution in next slide.
Page ‐ 48
49
Please read the steps of the troubleshooting in the slide.
Page ‐ 49
50
Open Monitor from Windows task bar.
Click on “Set configuration”
See details in next slide
Page ‐ 50
51
Select the root of the desired database path, and validate.
Launch CS Imaging 8 to verify that patients and images are available
Note : CSDM Lite will restart automatically when configuration is set.
Page ‐ 51
52
On this example the cause of this error is: The tracing template
specified in the image doesn't exist, please copy it to the template
folder, then try to import again.
2 kind of error messages can occur: Err_S_CSI and Err_S_CSDM
Error codes will be available and described on infotec website
(https://infotec.carestreamdental.com/).
Note: infotec access is restricted to trained and certified technicians
Page ‐ 52
End of the CS Imaging 8 course
Your are ready to validate this technical training
Please take the online Quizz .
A minimum score of 85% of correct answers is expected to validate the training completion.