OUTDOOR UNIT
AM036FXMDCH
AM048FXMDCH
AM053FXMDCH
AM060MXMDCH
1. Precautions
2. Product Specifications
4. Troubleshooting
5. PCB Diagram
6. Wiring Diagram
7. Reference Sheet
Refer to the service manual in the GSPN(see the rear cover) for the more information.
Section 0
Contents
■. Precautions .............................................................................................................1
1-1 Precautions for the Service...........................................................................................................................................1
1-2 Precautions for the Static Electricity and PL ..........................................................................................................1
1-3 Precautions for the Safety.............................................................................................................................................1
1-4 Precautions for Handling Refrigerant for Air Conditioner...............................................................................2
1-5 Precautions for Welding the Air Conditioner Pipe .............................................................................................2
1-6 Precautions for Additional Supplement of Air Conditioner Refrigerant ...................................................2
1-7 Other Precautions ............................................................................................................................................................2
■. Troubleshooting ................................................................................................. 30
1. Error Display ....................................................................................................................................................................... 30
2. Error Code............................................................................................................................................................................ 31
3. Appropriate Measures for Different Symptom .................................................................................................... 33
3-1. Error due to repeated address setting (E-108) ....................................................................................... 33
3-2. Communication error between indoor and outdoor unit (E-201) ................................................ 34
3-3. Communication error on all PBA within the outdoor unit C-Box,
communication cable error. (E-205) ............................................................................................................ 36
3-4. Error on outdoor temperature sensor of outdoor unit (Short or open). (E-221)...................... 37
3-5. Error on COND OUT temperature sensor of main outdoor unit (Short or open). (E-231) .... 38
3-6. Error on discharge temperature sensor of compressor 1 (Short or open). (E-251) ................. 39
3-7. Discharge temperature sensor of compressor 1 is detached from the sensor holder
on the pipe. (E-262) / Top sensor of compressor 1 is detached (E-266).......................................... 40
3-8. Suction temperature sensor is detached from the sensor holder on the pipe. (E-269)........ 41
3-9. Refrigerant leakage or error on high pressure sensor (Short or open). (E-291)........................ 42
3-10. Refrigerant leakage or error on low pressure sensor (Short or open). (E-296) ....................... 43
3-11. Error on suction temperature sensor (Short or open). (E-308) ..................................................... 44
3-12. Error on temperature sensor of double layer pipe/
liquid pipe(sub heat exchanger) (Short or open). (E-311) ................................................................ 45
3-13. Error on EVI (ESC) IN temperature sensor (Short or open). (E-321) ............................................. 46
3-14. Error on EVI (ESC) OUT temperature sensor(Short or open). (E-322).......................................... 47
3-15. Error due to operation failure of Fan1 (E-446) ....................................................................................... 48
3-16. Lock error on Fan1 of outdoor unit. (E-448) ........................................................................................... 50
3-17. Error due to overheated motor of outdoor unit's Fan1. (E-453) ..................................................... 51
3-18. Error due to overheated IPM of Fan1. (E-455) ........................................................................................ 52
3-19. Output current sensor error of inverter PBA 1. (E-468) /
Error due to input current of inverter 1. (E-485) / ................................................................................ 53
3-20. DC voltage sensor error of inverter PBA 1. (E-469) ............................................................................ 54
3-21. Compressor operation stop due to high pressure protection control. (E-407) ..................... 55
Samsung Electronics 1
Section 0
Contents
3-22. Compressor operation stop due to low pressure protection
control or refrigerant leakage. (E-410) ..................................................................................................... 56
3-23. Compressor operation stop due to discharge temperature protection control. (E-416) .. 58
3-24. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-425) ........................................................................................... 60
3-25. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-428) ........................................................................................... 62
3-26. EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector
insertion of EVI (ESC) EEV. (E-438).............................................................................................................. 64
3-27. Error due to refrigerant leakage. (E-439) /
Operation prohibited due to low pressure. (E-443)............................................................................ 66
3-28. Heating mode restriction due to high air temperature. (E-440) /
Operation prohibited due to low pressure. (E-441)............................................................................ 67
3-29. Refrigerant charging restriction in heating mode
when air temperature is over 15°C. (E-442) ........................................................................................... 68
3-30. CCH is detached. (E-445) .............................................................................................................................. 69
3-31. Error due to operation failure of inverter compressor 1. (E-461) ................................................. 70
3-32. Error due to operation failure of inverter compressor 1. (E-464) ................................................. 71
3-33. Error due to over voltage / low voltage of inverter PBA 1. (E-466).............................................. 72
3-34. Error due to overheat caused by contact failure on IPM of inverter PBA 1. (E-500) ............. 73
3-35. Outdoor unit’s option switch setting error. (E-560) .......................................................................... 74
■. Reference Sheet................................................................................................... 85
1. Refrigerant cycle diagram............................................................................................................................................. 85
1-1. AM036/048/053FXMDCH ............................................................................................................................... 85
1-2. AM060MXMDCH ................................................................................................................................................ 86
2. Nomenclatures .................................................................................................................................................................. 87
2 Samsung Electronics
■ Precautions
OFully repair the connection for the types of harness when repairing the product after breakdown.
– A faulty connection can cause irregular noise and problems.
OWhen disassembling or assembling, make sure that the product is laid down on a work cloth.
– Doing so will prevent scratching to the exterior of the rear side of the product.
OCompletely remove dust or foreign substances on the housing, connection, and inspection parts when performing repairs.
– This can prevent fire hazards for tracking, short, etc.
OPlease tighten the service valve of the outdoor unit and the valve cap of the charging valve as securely as possible by using
a monkey spanner.
OCheck whether the parts are properly and securely assembled after performing repairs.
– These parts should be in the same condition as before the repair.
OCheck if the place of installation is at least 2m away from electronic appliances such as TV, video players, and stereos.
– This can cause irregular noise or degrade the picture quality.
OPlease make sure the customer does not directly repair the product.
– Arbitrary dismantling may result in electric shock or fire.
ODo not pull or touch the power plug or the subsidiary power switch with wet hands.
– This may result in electric shock or fire.
OIf the power line or the power plug is damaged, then it must be changed since this is a hazard.
ODo not bend the wire too much or position it so that it can be damaged by a heavy object on top.
– This may result in electric shock or fire.
OUnplug the power or turn off the subsidiary power switch when changing or repairing electrical parts.
– Doing so will prevent electric shock.
– Although the power is off, Inverter PBA and Fan PBA are dangerous because they are charged with high DC voltage.
– Changing, checking and touching PBA are dangerous because of high DC voltage. So, please turn off the power and wait for
discharging DC voltage. ( To discharging DC voltage naturally, wait for more than 15 minutes.)
OExplain to workers that the battery for the remote control needs to be separated for storage purposes when
the product will not be used for a long time.
– This can cause a problem for the remote control since battery fluid may trickle out.
Samsung Electronics 1
4. Precautions for Handling Refrigerant for Air Conditioner
Environmental Cautions: Air pollution due to gas release
OSafety Cautions
If liquid gas is released, then body parts that come into contact with it may experience frostbite/blister/numbness.
If a large amount of gas is released, then suffocation may occur due to lack of oxygen. If the released gas is heated, then noxious
gas may be produced by combustion.
OIf the refrigerant is kept inside the product or the pipe, then remove the refrigerant prior to welding.
If the welding is carried out while the refrigerant is kept inside, the welding cannot be properly performed. This will also produce
noxious gas that is a health hazard. This leakage will also explode with the refrigerant and oil due to an increase in the refrigerant
pressure, posing a danger to workers.
OPlease remove the oxide produced inside the pipe during the welding with nitrogen gas.
Using another gas may cause harm to the product or others.
ODo not operate the product after removing the product safety pressure switch and sensor.
If the product is blocked inside, then this may cause harm to the product or others due to the excess pressure increase of the
refrigerant gas.
7. Other Precautions
OThere should be no leakage of the pipes after installation. When withdrawing the refrigerant, the compressor should be
stopped before removing the connecting pipe.
If the compressor is operating while the refrigerant pipe is not correctly connected and the service valve is opened, then
air and other substances can enter the pipe. The interior of the refrigerant cycle may then build up excessive high pressure
resulting in explosion and damage.
2 Samsung Electronics
■ Product Specifications
1-1. Feature
QStructure of outdoor unit
Turbo Inter-cooler
䭓Long piping up to 175m with sub-cooling
䭓Up to 50m levela difference is allowed for
installation
Company A
Diameter Ø8 Ø7
Evaporation 14.1%
loss in heat
ᇉ
Samsung Electronics 3
Product Specifications
Feature (cont.)
QApplication of wide fin
High efficient heat exchanger has been applied, therefore it delays the onset of frost formation and increased heat transfer efficiency.
QOptimized cooling/heating and increased system efficiency! Liquid EEV & Turbo Inter-cooler
t-JRVJE&&7GPSJODSFBTFEFGGJDJFODZPGUIFTZTUFN
Through Liquid EEV, controlling of valve opening has become more efficient and it achieved optimized system efficssiency and
minimized noise from the refrigerant in the indoor unit.
t5VSCP*OUFSDPPMFS
High performing shell & tube type heat exchanger has been applied to secure cooling/heating efficiency. It has secured enough
subcooling to acquire reliability on long piping and it also increased cooling/heating efficiency.
온도
Low temperature
liquid refrigerant
Cross section of the Cross section of the
Sub-cooled
Turbo inter-cooler conventional inter-cooler
liquid refrigerant
Turbo Inter-cooler
4 Samsung Electronics
Product Specifications
Feature (cont.)
QReinforced corrosion resistance on the heat exchanger
To prevent corrosion of the products which is installed in saline area, corrosion resistance has been reinforced.
No corrosion after 1,000 hours of test Corrosion is evident after 1,000 hours of test
Company A
* Tested by Samsung
Long piping
175m
(Equivalent length)
Level
High level difference
difference between
50m indoor units
15m
Samsung Electronics 5
Product Specifications
Feature (cont.)
QMemory module
t"DIJFWFTXPSMEDMBTTFGGJDJFODZXJUIIZQFSDPNQSFTTPSUIBUBQQMJFTEPVCMFDPNQSFTTJPOUFDIOPMPHZ
If outdoor unit malfunction occurs, diagnose and repair of the problem will be much quicker with the last 3 minutes worth of a data
saved before the malfunction. (With the extra memory module, 3 months worth of a data can be saved.)
Highest temperature
Operation End
time
7 : 00 13 : 30 19 : 00 7 : 00
6 Samsung Electronics
Product Specifications
Feature (cont.)
QRefrigerant pump-down
If you need to move/replace the outdoor unit or when there are problems on indoor units or on the pipes, outdoor unit will recover
refrigerant remaining on the pipes.
Indoor unit
malfunction
Refrigerant recoveringsss
Samsung Electronics 7
Product Specifications
Feature (cont.)
QMaximum 9 indoor unit connection
You may connect up to 9 indoor units on a single outdoor unit. It will allow more powerful and flexible air conditioning system
and you can select refrigerant pipe length, or number of indoor units depending on the needs for office, commercial and residential
places.
Conventional
* For models with 9kW or larger (Flare type connection)
8 Samsung Electronics
2. Product Specifications
Type
Samsung Electronics 9
■ Disassembly and Reassembly
1. Necessary Tools
Item Remark
+Screw Driver
Monkey Spanner
–Screw Driver
Nipper
L-Wrench
10 Samsung Electronics
2. Disassembly and Reassembly
2-1. AM036/048/053FXMDCH
No Parts Procedure Remark
Samsung Electronics 11
No Parts Procedure Remark
4 Guard Cond 1) Pull the sensor from Guard Cond.
12 Samsung Electronics
No Parts Procedure Remark
Samsung Electronics 13
No Parts Procedure Remark
7 Cabi Front LF
14 Samsung Electronics
No Parts Procedure Remark
Samsung Electronics 15
No Parts Procedure Remark
16 Samsung Electronics
No Parts Procedure Remark
Samsung Electronics 17
No Parts Procedure Remark
18 Samsung Electronics
No Parts Procedure Remark
Samsung Electronics 19
Disassembly and Reassembly
2-2. AM060MXMDCH
No Parts Procedure Remark
20 Samsung Electronics
Disassembly and Reassembly
Samsung Electronics 21
Disassembly and Reassembly
22 Samsung Electronics
Disassembly and Reassembly
Samsung Electronics 23
Disassembly and Reassembly
24 Samsung Electronics
Disassembly and Reassembly
7 Cabi Front LF
Samsung Electronics 25
Disassembly and Reassembly
26 Samsung Electronics
Disassembly and Reassembly
Samsung Electronics 27
Disassembly and Reassembly
28 Samsung Electronics
Disassembly and Reassembly
Samsung Electronics 29
■ Troubleshooting
1. Error Display
ERROR DISPLAY
30 Samsung Electronics
2. Error Code
Samsung Electronics 31
No. Code Explanation
55 E-441 Cooling mode restriction due to low air temperature.
56 E-442 Refrigerant charging restriction in heating mode when air temperature is over 15°C.
57 E-443 Operation prohibited due to low pressure.
58 E-445 CCH is detached.
59 E-446 Error due to operation failure of Fan1.
60 E-447 Motor wire of Fan1 is not connected.
61 E-448 Lock error on Fan1 of outdoor unit.
62 E-452 Error due to ZCP detection circuit problem or power failure.
63 E-453 Error due to overheated motor of outdoor unit's Fan1.
64 E-454 Error due to fan1 PRM.
65 E-455 Error due to overheated IPM of Fan1.
66 E-458 Outdoor fan 1 error3
66 E-461 Error due to operation failure of inverter compressor 1.
67 E-462 Compressor stop due to full current control.
67 E-463 OLP temperature control, compressor stops.
68 E-464 Error due to over-current of inverter compressor 1.
69 E-465 V-limit error of inverter compressor 1.
70 E-466 Error due to over voltage / low voltage of inverter PBA 1.
71 E-467 Error due to unconnected wire of compressor 1.
72 E-468 Output current sensor error of inverter PBA 1.
73 E-469 DC voltage sensor error of inverter PBA 1.
75 E-474 Heat sink temperature sensor error of inverter PBA 1.
76 E-475 Error due to fan2 PRM.
78 E-483 Error due to special overcurrent of Fan1.
79 E-484 PFC overload
79 E-485 Error due to input current of inverter 1.
87 E-500 Error due to overheat caused by contact failure on IPM of inverter PBA 1.
88 E-503 Error due to alert the user to check if the service valve is closed
90 E-554 Gas leak error
Outdoor unit’s option switch setting error(Using E2P option of other models or emergency operation
91 E-560 for compressor malfunction option setting was enabled on all compressors of corresponding outdoor
unit).
92 E-563 Error due to module installation of indoor unit with old version(Micom version needs to be checked).
94 E(P)-702 Error due to closed EEV of indoor unit(1st detection).
95 E(P)-703 Error due to opened EEV of indoor unit(1st detection).
32 Samsung Electronics
3 Appropriate Measures for Different Symptom
3-1. Error due to repeated address setting
(when 2 or more devices has same address within the network). (E-108)
No
Has E108 occurred? End.
Yes
Yes
MCU
E108 occurring machine
Find a unit whose address is duplicated in themanual Check the rotary switch of the address of the
address view on the view mode of the outdoor unit display. installed MCU to check any duplicate address.
(If there is an address that does not appear in the manual
address view even though a unit is actually installed,
the address isduplicated.)
Ex.) When the following is displayed in the view mode at
the site where No. 0 to 4 are installed, possible to judge
that the address of no. 3 indoor unit is duplicated. ఐCheck the manual address
A000 ඨ A001 ඨ A002 ඨ A00 view in the view mode.
(Press and hold K4 switch to enter).
ఐ K3 reset
Replace Inverter PCB. When the system is reset through K3 reset, the previous error (E108) on the
display is sometimes indicated. This indicates the error left previously in the
indoor unit during the course of performing resetting and addressing the
whole system after the outdoor unit is reset. When addressing is completed,
the error indication disappears (up to 5 minutes required).
Replace Inverter PCB.
ఐ Whole system power reset
- To solve the problem through the power reset after the address is reset the
power reset of individual units is meaningless and the power of the whole
system must be reset.
Samsung Electronics 33
3-2. Communication error between indoor and outdoor unit. (E-201)
(Installation number setting error repeated indoor unit address,
indoor unit communication cable error.)
Outdoor unit Display E-201
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation Defrost Timer Fan Filter / MPI
× × ◑ ◑ ×
※ ● : ON ◑: Flash ×: OFF
Judgement Method t$PNNVOJDBUJPOFSSPSCFUXFFOJOEPPSBOEPVUEPPSVOJUT
Cause of problem t3FGFSUIFOFYUQBHF
34 Samsung Electronics
3-2. Communication error between indoor and outdoor unit. (E-201)
Are the
number of actual installed
indoor units and the set value for the No
installation quantity setup switch
the same?
Yes
Is there no sign of
the indoor response on No
the display during
tracking?
Yes No
Remove the communication cable which connects After 2 minutes, nd the indoor unit which displays the
the outdoor unit to the indoor unit, and measure communication error for the indoor units, and check for
the 2 cables of the outdoor unit with a scope. overlaps in the PCB address setup. (If the indoor unit
addresses are overlapped, then a communication
error will occur).
- In this case, a communication error will occur in
every indoor unit (two or more units) with
the address incorrectly set.
Yes
Check the communication cable which connects the Check the communication cable and the connector
outdoor unit to the indoor unit. If there is no peculiarity, of the outdoor unit PCB, and change the PCB.
then connect the indoor units one by one to nd the
indoor unit that is interfering with the communication
for inspection and change the indoor unit PCB.
Samsung Electronics 35
3-3. Communication error on all PBA within the outdoor unit C-Box,
communication cable error. (E-205)
Outdoor unit Display E-205
Duct, Cassette (1 / 2Way), Console, Ceiling
Operation Defrost Timer Fan Filter / MPI
× × ◑ ◑ ×
※ ● : ON ◑: Flash ×: OFF
Judgement Method t$PNNVOJDBUJPOFSSPSCFUXFFOUIF$#PY1$#
t$PNNVOJDBUJPOXJSFJOTJEFUIF$#PYJTVODPOOFDUFE
Cause of problem
t.BJO1$#EFGFDUJWF
Yes
Is inverter PCB CN32 Check the Inverter PCB1 CN32, CN91 and Fan PCB
and Fan PCB CN12 No CN12 Communication wire / Connector .
connector accurately * When performing the connector work, Please
connected? turn off the main power.
Yes
36 Samsung Electronics
3-4. Error on outdoor temperature sensor of outdoor unit (Short or open). (E-221)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t0VUEPPSUFNQFSBUVSFTFOTPS4IPSU0QFOJTEFGFDUJWF
Yes
Samsung Electronics 37
3-5. Error on COND OUT temperature sensor of main outdoor unit. (Short or open) (E-231)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
Temperature(°C) Resistance(KΩ)
Yes 70 2.2
60 3.0
Restart operation after replace the PCB. 50 4.2
40 5.8
30 8.3
20 12.1
10 18.0
0 27.3
-10 43.0
38 Samsung Electronics
3-6. Error on discharge temperature sensor of compressor 1 (Short or open). (E-251)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t$PNQSFTTPS%JTDIBSHFPS5PQ5FNQFSBUVSFTFOTPSEFGFDUJWF 0QFO4IPSU
Yes
Temperature(°C) Resistance(KΩ)
Yes 130 8.9
120 11.2
Restart operation after replace the PCB. 100 18.5
80 32.0
60 59.0
25 200
20 242
10 362
0 553
Samsung Electronics 39
3-7. Discharge temperature sensor of compressor 1 is detached from the sensor holder
on the pipe. (E-262) / Top sensor of compressor 1 is detached (E-266)
※ ● : ON ◑: Flash ×: OFF
1) Relevant compressor frequency of 60Hz or higher.
2) Suction temperature > Low pressure saturation temperature +10ఁ
Judgement Method
3) Relevant discharge or Top temperature < High pressure saturation temperature.
4) In case of keep 30 minutes in state that satisfy all above conditions (1, 2, 3).
t$PNQSFTTPSEJTDIBSHFPS5PQUFNQFSBUVSFTFOTPSCSFBLBXBZBOEEFGFDUJWF
Cause of problem
Starting badness of compressor.
Yes
Is the discharge or
top temperature sensor resistance value No
Defective sensor : Replace sensor.
reasonable? (Refer to E251)
Yes
Complete.
40 Samsung Electronics
3-8. Suction temperature sensor is detached from the sensor holder on the pipe. (E-269)
※ ● : ON ◑: Flash ×: OFF
t+VEHNFOU.FUIPE%JGGFSFODFPGTVDUJPOUFNQFSBUVSFPGDPNQSFTTPSTUBSUJOH
Judgement Method verge and suction temperature that is on present operation : If less than 2 °C for
30 minutes to keep.(Judgment at heating operation only)
Cause of problem t4VDUJPOUFNQFSBUVSFTFOTPSCSFBLBXBZEFGFDUJWF
Is Suction sensor
and sensor Holder accurately No
Re-insert sensor OR and re-attach sensor holder.
attached?
Yes
Is Suction sensor
resistance value reasonable? No
Defective sensor : Replace sensor.
(Refer to E231 )
Yes
Complete.
Samsung Electronics 41
3-9. Refrigerant leakage or error on high pressure sensor. (Short or open) (E-291)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
Is there refrigerant
inside the set? (Please check by connecting No
Refill refrigerant after vacuum.
the manifold gageto the
service valve)
Yes
Yes
42 Samsung Electronics
3-10. Refrigerant leakage or error on low pressure sensor (Short or open). (E-296)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
Is there
refrigerant inside the set ?
No
( Pleasecheck by connecting the manifold Refill refrigerant after vacuum.
gage to the service
valve)
Yes
Yes
Samsung Electronics 43
3-11. Error on suction temperature sensor. (Short or open) (E-308)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Did the
connector for the Liquid Pipe No Restart operation after connecting
Temperature sensor break away the connector to PCB.
from the PCB?
Yes
44 Samsung Electronics
3-12. Error on temperature sensor of double layer pipe.
liquid pipe. (sub heat exchanger) (Short or open) (E-311)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
Samsung Electronics 45
3-13. Error on EVI (ESC) IN temperature sensor. (Short or open) (E-321)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
46 Samsung Electronics
3-14. Error on EVI (ESC) OUT temperature sensor.(Short or open) (E-322)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
Cause of problem t%JTDPOOFDUJPOPSCSFBLEPXOPGSFMFWBOUTFOTPS
Yes
Temperature(°C) Resistance(KΩ)
Yes
70 2.2
60 3.0
Restart operation after replace the PCB. 50 4.2
40 5.8
30 8.3
20 12.1
10 18.0
0 27.3
-10 43.0
Samsung Electronics 47
3-15. Error due to operation failure of Fan1. (E-446)
2. Inspection Method
1) Refer to Figure1 and Table1, respectively the resistance value and diode voltage value measure.
2) According to the criterion in Table 1 to determine whether the failure of IPM.
Measured point
Division Criterion Remark
+ -
40 U
40 V
Measure 40 W Measurement error can
More than 3 MΩ
the resistance values U 34 occur for reasons such
V 34
as the initial measure-
W 34
ment condenser
U 40
discharge.
V 40
Measure the diode W 40 Measured over at least
0.3 ~ 0.7V three times.
voltage values 34 U
34 V
34 W
48 Samsung Electronics
3-15. Error due to operation failure of Fan1. (E-446) (cont.)
Is the resistance
value between dierent No
phases of an Motor (U ׳V,V ׳W,W ׳U) Replace Fan Motor.
less than 10 ?
Yes
Is the resistance
between the body of No
Replace Fan Motor.
Fan Motor and chassis
MΩ?
Yes
Samsung Electronics 49
3-16. Lock error on Fan1 of outdoor unit. (E-448)
No
Did the error occurs? End of Service.
Yes
Yes
Power Off
Yes
Yes
No
Connection wire of
Fan Motor didconrmation ? Yes
(Check the connection Check the connection status, and then restart.
status of the Fan1 and Fan2.)
No
50 Samsung Electronics
3-17. Error due to overheated motor of outdoor unit's Fan1. (E-453)
Yes
Connection wire of
Fan Motor did conrmation ? No
(Verify that the wire folded, or Check the connecting wire and restart it.
the connection is
detached .)
Yes
Yes
Samsung Electronics 51
3-18. Error due to overheated IPM of Fan1. (E-455)
Power Off
Yes
Did check
the foreign objects between the No Remove foreign objects
heat sink pin? *Cold heat sink assembly defect occurs
Yes
Yes
Complete.
52 Samsung Electronics
3-19. Output current sensor error of inverter PBA 1. (E-468)
Error due to input current of inverter 1. (E-485)
Power Off
Is Power connection No
Power Cable re-connection.
accurately connected?
Yes
E -468 / E -485
Samsung Electronics 53
3-20. DC voltage sensor error of inverter PBA 1. (E-469)
Power Off
Is Power connection No
Power Cable re-connection.
accurately connected?
Yes
Is Reactor accurately No
Check the Reactor connection.
connected?
Yes
No
Did the Fuse is short? Replace Fuse.
Yes
Yes
Yes
54 Samsung Electronics
3-21. Compressor operation stop due to high pressure protection control. (E-407)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t7BMVFPGUIFIJHIQSFTTVSFTFOTPSJTEFUFDUFEBULHDN¤PSNPSF
Cooling Operation
t0VUEPPSVOJUGBONPUPSQSPCMFN DPOTUSBJOFE
EFGFDUJWF
t.PUPSESJWFSEFGFDUJWFPSXJSFJTDVU
t0VUEPPSIFBUFYDIBOHFSJTDPOUBNJOBUFE
t4FSWJDFWBMWFMPDLFE'JMMSFGSJHFSBOU
Cause of problem
Heating Operation
t0VUEPPSVOJUGBONPUPSQSPCMFN DPOTUSBJOFE
EFGFDUJWF
t.PUPSESJWFSEFGFDUJWFPSXJSFJTDVU
t4FSWJDFWBMWFMPDLFE&YDFTTJWFSFGSJHFSBOU
Samsung Electronics 55
3-22. Compressor operation stop due to low pressure protection
control or refrigerant leakage. (E-410)
※ ● : ON ◑: Flash ×: OFF
t+VEHNFOU.FUIPE*OTQFDUJPOXIFOUIFWBMVFPGMPXQSFTTVSFTFOTPSJT
Judgement Method
LHDN
PSMFTTGPSBJSDPOEJUJPOJOHBOELHDN¤GPSIFBUJOH
t3FGSJHFSBOUTIPSUBHF
t&MFDUSPOJDFYQBOTJPOWBMWFCMPDLFE
t4FSWJDFWBMWFCMPDLFE
t-PXQSFTTVSFTFOTPSEFGFDUJWF
Cause of problem
t-FBLBHFPGDPNQSFTTPSEJTDIBSHFDIFDLWBMWFPGOPUHPFOEPVUEPPSVOJU
t&SSPSNBZCFGPVOEXIFOVTFEJOUFNQFSBUVSFSBOHFPVUTJEFUIFDPOEJUJPOTPG
use. (Operating outside temperature at -20°C or less for heating and operating
outside temperature at -5°C or less for Cooling)
56 Samsung Electronics
3-22. Compressor operation stop due to low pressure protection control or
refrigerant leakage. (E-410) (cont.)
Yes
Is the S -net
No
estimated value and the Manifold Gauge Replace Low Pressure sensor.
value in range
Yes
No
Is there any
leakage in the Liquid
Pipe Valve or the discharge check Yes
valve of the not-go-end Outdoor Replace Low Pressure sensor.
Unit when only some Outdoor
Units are operating?
No
Samsung Electronics 57
3-23. Compressor operation stop due to discharge temperature protection control. (E-416)
※ ● : ON ◑: Flash ×: OFF
t+VEHNFOU.FUIPE*OTQFDUJPOXIFOUIFWBMVFPGMPXQSFTTVSFTFOTPSJT
Judgement Method
LHDN
PSMFTTGPSBJSDPOEJUJPOJOHBOELHDN¤GPSIFBUJOH
t3FGSJHFSBOUTIPSUBHF
t&MFDUSPOJDFYQBOTJPOWBMWFJTCMPDLFE
t4FSWJDFWBMWFCMPDLFE
Cause of problem t%FGFDUJWFEJTDIBSHFUFNQFSBUVSFTFOTPS
t501UFNQFSBUVSFTFOTPSEFGFDUJWF
t#MPDLFEQJQFBOEEFGFDUJWF
t-FBLBHFPGDPNQSFTTPSEJTDIBSHFDIFDLWBMWFPGOPUHPFOEPVUEPPSVOJU
58 Samsung Electronics
3-23. Compressor operation stop due to discharge temperature protection control. (E-416) (cont.)
Is the resistance
value normal for the
Compressor discharge Temperature sensor/ No Replace Compressor discharge temperature
Top temperature sensor? sensor / Top temperature sensor.
(Refer to E251)
Yes
No
Are all service valves open? Open the Service Valve.
Yes
Yes
Are there
No
any blockage inside the pipe? Pipe inspection.
( lter etc.)
Yes
Samsung Electronics 59
3-24. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-425)
※ ● : ON ◑: Flash ×: OFF
t8IFOUVSOPOUIFQPXFSBOEDIFDLUIFTUBUVTPGUIFQPXFSGSPNUIFJOWFSUFS
If the phase does not connect the power(no phase) : E425 or E466 (E366) is
Judgement Method
displayed (Air conditioner to maintain the normal state.)
t)PXFWFS
/QIBTFNVTUCFQSPQFSMZDPOOFDUFE
t$IFDLUIFJOQVUXJSJOH
Cause of problem
t&.*'VTFTIPSU
60 Samsung Electronics
3-24. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-425) (cont.)
Power Off
Did the Main Power BOX Terminal : Check the phase -to-phase
No
Terminal Block and Power R, S, T, N is connection 380V of the R, S, T and then restart.
connected properly? (N-phase must be properly connected.)
Yes
Yes
No
Yes
Samsung Electronics 61
3-25. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-428)
※ ● : ON ◑: Flash ×: OFF
t$PNQSFTTJPOSBUJP< )JHIQSFTTVSF
-PXQSFTTVSF
>MFTTUIBOBOE
lasts for 10 minutes or more.
Judgement Method
t%JGGFSFOUJBMQSFTTVSF IJHIQSFTTVSFMPXQSFTTVSF
MFTTUIBO.1B(BOE
lasts for 10 minutes or more.
t*OEPPSBOE0VUEPPS&&7CSFBLEPXO
t8BZ7BMWFCSFBLEPXO
Cause of problem
t)JHIBOE-PXQSFTTVSFTFOTPSEFGFDUJWF
t3FGSJHFSBOUTIPSUBHF
62 Samsung Electronics
3-25. Phase reversal or phase failure(3Ø outdoor unit wiring, R-S-T-N),
connection error on 3 phase input. (E-428) (cont.)
Yes
Yes
No
No Compressor inspection
Is current of compressor normally?
Check the refrigerant.
Yes
Complete.
Samsung Electronics 63
3-26. EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector
insertion of EVI (ESC) EEV. (E-438)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t%4)¡$
&7*0VUJO¡$GSFRVFODZ)[NJOVUFTNBJOUBJOJOH
t&7*&&7BOE*OUFSDPPMFSMFBLBHF
FYDFTTJWFSFGSJHFSBOUBNPVOU
0VUEPPS
Check Valve inserted opposite.
Cause of problem
t*OEPPS6OJU&&7MFBLBHF
EJSFDUDPOOFDUJPOCFUXFFO*OEPPS-JRVJE1JQFBOE
the Gas Pipe.
64 Samsung Electronics
3-26. EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect
connector insertion of EVI (ESC) EEV. (E-438) (cont.)
Yes
Yes
Yes
Breakdown
Check the Indoor Unit EEV leakage. Replace Indoor Unit EEV.
Check the
connectionfor Indoor Unit Pipe. Breakdown
(Connect liquid pipe -gas pipe directly) Reinstall pipe.
Samsung Electronics 65
3-27. Error due to refrigerant leakage. (E-439) / Operation prohibited due to low pressure. (E-443)
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
Yes
Is there
refrigerant inside the set?
(Please check by connecting the No
Refill refrigerant after vacuum.
manifold gauge to the service
valve)
Yes
Yes
66 Samsung Electronics
3-28. Heating mode restriction due to high air temperature. (E-440)
Operation prohibited due to low pressure. (E-441)
※ ● : ON ◑: Flash ×: OFF
t)FBUJOHPQFSBUJPO8IFOUIFPVUEPPSUFNQFSBUVSFJTNPSFUIBO¡$
Judgement Method
t$PPMJOHPQFSBUJPO8IFOUIFPVUEPPSUFNQFSBUVSFJTMFTTUIBO¡$
Cause of problem t4ZTUFNQSPUFDUJPOPQFSBUJPOTUBUVT *TOPUCSFBLEPXO
Samsung Electronics 67
3-29. Refrigerant charging restriction in heating mode when air temperature is over 15°C. (E-442)
※ ● : ON ◑: Flash ×: OFF
t8IFOUIFIFBUJOHSFGSJHFSBOUDIBOHF*GUIFPVUEPPSUFNQFSBUVSFJTNPSF
Judgement Method
than 15°C.
Cause of problem t4ZTUFNQSPUFDUJPOPQFSBUJPOTUBUVT *TOPUCSFBLEPXO
68 Samsung Electronics
3-30. CCH is detached. (E-445)
※ ● : ON ◑: Flash ×: OFF
Judgement Method t3FGFSUIFOFYUQBHF
t$$)$POOFDUPS1$#JTOPUDPOOFDUFE$PNQSFTTPS5PQTFOTPSCSFBLBXBZ
Cause of problem
Own problem of CCH.
Yes
Is the compressor No
top temperature sensor fixed in correct Fix the compressor top temperature
position? sensor in correct position.
Yes
Is CCH resistancenormal? No
( 500~700/infinite for disconnection ) Change CCH.
Yes
Yes
Change PCB.
Samsung Electronics 69
3-31. Error due to operation failure of inverter compressor 1. (E-461)
Yes
Yes
Is the resistance
value between dierent phases No
of compressor Replace Compressor.
(U ׳V, V ׳W,W ׳U)
less than 2?
Yes
Is the resistance
between the body of No
Replace Compressor.
Compressor and
chassis M Ω?
Yes
Yes
70 Samsung Electronics
3-32. Error due to operation failure of inverter compressor 1. (E-464)
Power Off
Yes
Is temperature
sensor location and the measurement No Power Off, and then replacement or
value normally? correction of the sensor location.
Yes
Is the resistance
value between dierent
No
phases of compressor Replace Compressor.
(U ׳V, V ׳W,W ׳U)
less than 2?
Yes
Is the resistance
between the body of No
Replace Compressor.
Compressor and
chassis M Ω?
Yes
Yes
Samsung Electronics 71
3-33. Error due to over voltage / low voltage of inverter PBA 1. (E-466)
Power Off
Yes
Yes
72 Samsung Electronics
3-34. Error due to overheat caused by contact failure on IPM of inverter PBA 1. (E-500)
Power Off
Yes
No
Is the bolt of the heat sink fully tightened? Tighten Bolt. (Screw)
Yes
Did check the No Remove foreign objects and apply the thermal
foreign objects between the heat sink
grease and then reassembly.
and IPM?
Yes
No
Did properly apply the thermal grease? Apply the thermal grease and then reassembly.
Yes
Complete.
Samsung Electronics 73
3-35. Outdoor unit’s option switch setting error.
(Using E2P option of other models or emergency operation for compressor malfunction
option setting was enabled on all compressors of corresponding outdoor unit) (E-560)
Is the Compressor Set the compressor breakdown setting value as“not set”.
breakdown setting value is No
ఐ͑When setting breakdown for repair and replace
“not set”? of compressor : Change the setting after replace.
Yes
Yes
74 Samsung Electronics
■ PCB Diagram
1. Outdoor Unit PCB
- Main PCB: AM036/048/053FXMDCH
1 3 8 9 12
2 4 5 6 7 10 11 13 14 15 16 17 18 19 20 21 22 23 24
Samsung Electronics 75
PCB Diagram
CN306-
⑤ CN704-4WAY VALVE 2 ⑥ CN403- TEMP SENSOR ⑦ MICOM DOWNLOAD ⑧ CN802-EEV 1
CN801-
⑬ CN804-EEV 3 ⑭ CN406- ⑮ CN805-EEV 4 ⑯ EXTERNAL CONTROL OUT
#1~4: EEV CONTROL #1~4: EEV CONTROL #1,3: 12V
#5: 12V #5: 12V #2: ERROR CHECK OUT
#4: COM CHK OUT
CN501-
⑰ CN305-COMM INV PBA ⑱ SELECT COOLING ONLY ⑲ CN401-LOW P SENSOR ⑳ CN401-HIGH P SENSOR
CN303-
CN401-MID P SENSOR CN302-COMM SUB PBA CN103-EARTH
COM INDOOR UNIT
#1: INPUT
#2: GND
#4: VCC
76 Samsung Electronics
PCB Diagram
13 7 4 2
22 21 20 19 18 17 16 15 14 12 11 10 9 8 6 5 3 1
Samsung Electronics 77
PCB Diagram
CN403 -
④ CN704 - EVI V/V ⑤ CN705 - EVI BYPASS V/V ⑥ TEMPERATURE SENSOR
CN404 -
⑩ CN404 - EXTERNAL CTRL ⑪ TEMPERATURE SENSOR ⑫ CN12 - 12V OUTPUT
#1: GND #1: Suction temperature sensor #1: DC 12V
#2: EXTERNAL CTRL #2: D_tube temperature sensor #3: GND
#5: EVI out temperature sensor
#7: EVI in temperature sensor
#2,4,6,8: GND
CN401 - CN402 -
⑯ CN501 - MODE SELECTION ⑰ LOW PRESSURE SENSOR ⑱ HIGH PRESSURE SENSOR
#1~3: MODE SELECTION SIGNAL #1: N.C. #1: HIGH PRESSURE SENSOR SIGNAL
#2: LOW PRESSURE SENSOR SIGNAL #2: N.C.
#3: GND #3: GND
#4: DC 5V #4: DC 5V
CN304 -
DRED & UPPER CONTROL
#1 : DRM1
#2 : DRM2
#3 : DRM3
#4 : C
#5 : R1 :
UPPER CTRL COMMUNICAITON SIGNAL
#6 : R2 :
UPPER CTRL COMMUNICAITON SIGNAL
78 Samsung Electronics
PCB Diagram
1 3 6 7 4 5 2 8
79 Samsung Electronics
PCB Diagram
11 10 9 8 7 6 4 3 2 1
5
Samsung Electronics 80
PCB Diagram
2 3 1
Samsung Electronics 81
PCB Diagram
1. Outdoor Unit PCB (cont.)
6 4 3 2 1
5
CN403 -
④ L1 ⑤ N1 ⑥ TEMPERATURE SENSOR
#1 : L OUTPUT #1 : N OUTPUT #1 : L OUTPUT
#1 : N OUTPUT
82 Samsung Electronics
■ Wiring Diagram
1. AM036/048/053FXMDCH
83 Samsung Electronics
Wiring Diagram
2. AM060MXMDCH
Samsung Electronics 84
■ Reference Sheet
1-1. AM036/048/053FXMDCH
Check
V/V
Separator
BLDC Motor o
oG
jG wUV
Oil
Filter
Comp
Accumulator Hot gas
pressor
Double
D bl pipe
i
out tube bypass
Main EEV temperature V/V
AM036FXMDCH
Name AM048FXMDCH AM053FXMDCH
RD050MHXGA(EA)
Samsung Electronics 85
Reference Sheet
1-2. AM060MXMDCH
Service Valve -
Gas pipe (BV_G)
Thermistor -
Ambient (T_A)
Thermistor -
Cond Out (T_CO)
Solenoid Valve -
4Way (V_4W)
Pressure Sensor -
Check Valve - Low (PS_L) Solenoid Valve -
Discharge (CV_D) EVI Bypass Thermistor -
(V_EVI) EVI Out (T_EO)
Heat Exchanger -
Pressure Sensor - Intercooler (HX_IC)
High (PS_H)
Oil Thermistor -
Separator Evi (T_EI)
(OS)
Accumulator
(AC)
Pressure Switch -
High (PW_H)
Thermistor - Electronic Expansion
Discharge Valve - EVI (E_EVI)
Thermistor - pipe (T_D)
Compressor Top (T_CT)
Solenoid Valve -
EVI (V_EVI)
Ball Valve -
Liquid pipe (SV_L)
86 Samsung Electronics
Reference Sheet
2. Nomenclatures
■ OUTDOOR UNIT
AM 053 F X M D C H AA
Samsung Electronics 87
Reference Sheet
1. Check Operation
1-1 Check Operation
1) What is the Check Operation?
DVM MINI main components defective check and check the status of the installation, provide guidelines that can promptly
and accurately resolve the problems that may occur in the field.
If does not end the Automatic Commissioning, normal operation is impossible to enter, it should protect the system from
the abnormal state. ("UP")
- If does not complete the Check operation, Display the "UP"(Unprepared) on the LED after checking communication.
(Compressor to operate general operation is prohibited.)
※ UP Mode will be turned off automatically at finished the Check operation.
(2) When an error occurs during the Check operation, check the error code in the product and then service it.
(3) Shut down the Check operation, resulting report will be issued using the S-NET or S-CHECKER.
- The resulting report of the "Undetermined"item, troubleshoot the accordance with the service manual.
- Troubleshoot all the items of "Undetermined" and then restart the Check operation.
88 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
※ If out of warranty coverage and bounds, installation, operation according to the conditions the some of items displayed as
"Undetermined" and judgment is not.
Ex) system that module installed : If the outdoor unit is not operation by the load on the indoor and outdoor, corresponding
Sub Outdoor Unit does not judge the inspection entries. (However, Indoor / Outdoor Temperature sensor and Pressure
sensor judgment is available.)
Samsung Electronics 89
Check Operation & Amount of Refriherant Automatically Checking
[Discharge
Temperature sensor
resistance value] Resistance(KΩ)
No Indoor Temperature
Temperature(℃)
Is Indoor temperature of the Indoor Unit by wired remote sensor setting(Remote
70 2.2
control setting? control → indoor unit) 60 3.0
50 4.2
40 5.8
30 8.3
No
20 12.1
10 18.0
0 27.3
-10 43.0
Yes
Yes
Complete
[Caution]
- If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Must be carried out Automatic Commissioning after 1
hour from final operation stopped.
90 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
[Discharge
Temperature sensor
resistance value] Resistance(KΩ)
No
Is Temperature sensor properly assembled? Temperature(℃)
70 2.2
60 3.0
50 4.2
Yes 40 5.8
30 8.3
20 12.1
Is Temperature 10 18.0
No
sensor connector properly connect? 0 27.3
-10 43.0
Yes
No
Is Temperature sensor resistance value normal? Replace sensor
Yes
Yes
Complete
[Caution]
- If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Must be carried out Automatic Commissioning after 1
hour from final operation stopped.
Samsung Electronics 91
Check Operation & Amount of Refriherant Automatically Checking
3) Pressure sensor
Ŷ Inspection item : High/Low Pressure sensor of the independent installed Outdoor Unit.
ŶError code: None (The resulting report "Undetermined")
Ŷ Determine the status of the Pressure sensor of the independent installed Outdoor Unit before the compressor start.
Ŷ If the judgment of Outdoor Unit Pressure sensor is "Undetermined" : Checking in accordance with the following order.
No
Is Pressure sensor connector properly connect?
Yes
Is voltage 5V between No
3, 4 pin of PCB Pressure sensor terminal? Replace Hub PCB
Yes
Is deviation of outdoor
No
unit as following?"High pressure Max Replace PCB
/Min deviation : less than 2"
Yes
Complete
[Caution]
- If the Outdoor Unit with a history of operation (Automatic commissioning inclusion) : Maintain the vacuum mode for more than 5 minutes.
92 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
Is Outdoor Unit
No
status normal?
Yes
Yes
Is resistance between No
the phase of compressor normal?
Yes
Is the current
No
measurement results of the compressor and CT Replace Inverter PCB
sensor have the same value?
Yes
No Is refrigerant Yes
Is Compressor current(CT) value normal? in the system properly?
No
Yes
Adjusts the refrigerant
(Addition / Emitted)
IIs operation No
current of Compressor
normal?
Yes
Replace Compressor
Complete
Samsung Electronics 93
Check Operation & Amount of Refriherant Automatically Checking
5) Cycle status
Ŷ Inspection item : Cycle status of Outdoor Unit.
Ŷ Error code: None (The resulting report "Undetermined")
Ŷ Determine the Cycle status of the each Outdoor Unit.
Ŷ If the judgment of Cycle status is "Undetermined" : Checking in accordance with the following order.
Yes
Yes
Complete
94 Samsung Electronics
Check Operation & Amount of Refriherant Automatically Checking
6) 4Way Valve
Ŷ Inspection item : 4Way Valve of Outdoor Unit.
Ŷ Error code: None (The resulting report "Undetermined")
Ŷ Determine the 4Way Valve operation status of the each Outdoor Unit.
Ŷ If the judgment of 4Way Valve is "Undetermined" : Checking in accordance with the following order.
Commissioning results, No
is Valve and Pressure sensor normal? Check the corresponding Pressure sensor.
Yes
No
Is 4Way Valve connector properly connect?
Yes
Yes
No
Is PCB Output signal normal? Replace PCB
Yes
Complete
Samsung Electronics 95
Check Operation & Amount of Refriherant Automatically Checking
7) Main EEV
Ŷ Inspection item : Main EEV of Outdoor Unit.(Automatic Commissioning : Heating only )
Ŷ Error code: None (The resulting report "Undetermined")
Ŷ Determine the Main EEV operation status of the each Outdoor Unit.
Ŷ If the judgment of Main EEV is "Undetermined" : Checking in accordance with the following order.
No
COMMISSIONING RESULTS, IS VALVE AND PRESSURE Check the Valve and Pressure sensor.
SENSOR NORMAL?
Yes
No
IS MAIN EEV CONNECTOR NORMAL? Confirmation and Measures
Yes
Yes
No
S PCB OUTPUT SIGNAL NORMAL? REPLACE HUB PCB
Yes
Complete
Main EEV Coil Voltage between the
(VDC) phase (Ω)
96 Samsung Electronics
2. Automatic refrigerant amount detection function (Checking th amount of refrigerant)
This function detects amount of refrigerant in the system through refrigerant amount detection operation.
Start
Press the Tact switch "K2" 4 times Input S-NET pro signal
End
[Caution]
t*GUIFPQFSBUJPODZDMFJTOPUTUBCMF
SFGSJHFSBOUBNPVOUEFUFDUJPOPQFSBUJPONBZFOE
t"DDVSBDZPGUIFSFTVMUNBZEFDSFBTFJGUIFQSPEVDUXBTOPUPQFSBUFEGPSMPOHQFSJPEPGUJNFCFGPSFUIFSFGSJHFSBOUBNPVOUEFUFDUJPO
operation. Use the refrigerant amount detection operation function after operating the product in cooling mode for at least
30 minutes.
t1SPEVDUNBZUSJHHFSQSPUFDUJPOPQFSBUJPOEFQFOEJOHPOUIFJOTUBMMBUJPOFOWJSPONFOU
In this case, result of refrigerant amount detection may not be accurate.
t*GFTDBQFUIFXBSSBOUZUFNQFSBUVSFT
DBOOPUHFUUIFBDDVSBUFSFTVMUT
- Indoor: 20 ~ 30 °C
- Outdoor: 5 ~ 43 °C
Samsung Electronics 97
GSPN (GLOBAL SERVICE PARTNER NETWORK)
Area Web Site
Asia gspn2.samsungcsportal.com
China china.samsungportal.com