2. Presentation
2.1 Front panel
6K/6KS/10K/10KS UPS
EBM
2.2 Rear panels
6K/6KS/10K/10KS
EBM
3
1. Intelligent slot
2. USB
3. Dry IN/OUT
4. RS232
5. EPO
6. RJ11 (connect to PDU, only for RT model)
7. Parallel card (optional)
8. Output breaker
9. Output socket
10. Input/Output terminal (4pole IPL, IPN, OPL, OPN. PE is screw)
11. Input breaker (optional)
12. EBM connector
13. Fuse board cover (replace EBM fuse)
14. EBM plug
15. EBM connector
4
5. Operation
5.1 Control panel
The UPS has a graphical LCD. It provides useful information about the UPS itself,
load status, events, measurements and settings.
BAT.
On The UPS is on Battery mode.
(Orange)
Fault
On The UPS has an active alarm or fault.
(Red)
14
The Buzzer definition as below:
15
Display Function
Load Information
Battery Information
Buzzer
The icon will be displayed after panel key operation
or serial command mute
Else
16
It indicates UPS Brand Logo and UPS system
information .
Silence Press 2s ~ 4s
Test/Silence Press ON/OFF and Test/Silence button at
Setting the same time for 4s or more, enter into
setting function
No Output Mode
Bypass Output Mode
○ ○ ○
ECO Mode
● ● ○
●:Icon display
● ○ ●
○:Icon no display
Note:
ECO mode / CVCF mode and the number of parallel machines: The alarm ID is
not displayed when the UPS works normally without alarm information. The
17
Pressing button continuously for more than 1 second, the buzzer will beep
for300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Battery mode. If the utility power comes
back, the UPS will transfer to Line mode without output interruption of the
UPS.
UPS shutdown with utility
To shut down the UPS with utility:
Pressing button continuously for more than 3 seconds and the buzzer will
beep 300ms. After that, the UPS will turn into Bypass mode at once.
When completing the above action, UPS output voltage is still present. In order
to cut off the UPS output, simply cut off the utility power supply. A few seconds
later, the ups will shut down and no output voltage is available from the UPS
output terminal.
UPS shutdown without utility
To shut down the UPS without utility:
To power off the UPS by pressing button continuously for more than 3
second, and the buzzer will beep for 300ms. The UPS will cut off the output at
once.
A few seconds later, the ups will shut down and no voltage is available from the
UPS output.
5.6 LCD operation
The UPS can make some settings via the LCD, including:
1> ECO Setting
The ECO mode ("EO") can be set to on / off. When set to enabled, the UPS can
operate in ECO mode to power the load. When set to disable, the UPS operates In
normal mains mode for the load power supply, the default is not enabled.
19
normal mains mode for the load power supply, the default is not enabled.
Note: Only one of ECO and CVCF can be set to enable. CVCF is automatically set to
disabled when ECO is set to Enabled. ECO is automatically set to Disabled when CVCF
is set to Enable.
Setting Step
Step 1:When the two keys are pressed at the same time for more than 4s (press
the test key first, and then press the on / off key), the UPS enters into the
setting mode and the contents to be set (EO / CF / CH) are displayed to display
the corresponding Option.
Step 2: Set mode, press the power button to select the content to be set for
more than 0.5s (EO, CF or CH).
Step3: Press the test key 0.5s above, the corresponding setting options start
flashing.
Step4: Press the on/off button 0.5s above, select the corresponding setting
20
in less than 3 hours.
However, recommends that the batteries charge for 48 hours after long-term
storage.
If the date has passed and the batteries were never recharged, do not use them.
Contact your service representative.
24
they are preventive alarms intended to alert the user.
Events are silent status information that are recorded into the Event log.
Example = "Battery charging".
Alarms are recorded into the Event log and displayed on the LCD status
screen with the logo blinking. Some alarms may be announced by a beep
every 1 second. Example = "Battery low".
Faults are announced by a continuous beep and red LED, recorded into the
Event log. Example = "Out. short circuit".
Use the following troubleshooting chart to determine the UPS alarm condition.
26
Power overload Power requirements exceed Remove some of the
Fault (Red) LED is Flash the UPS capacity equipment from the UPS.
2beep every 1 second The UPS continues to
Code: 41 operate, but may switch to
Bypass mode or shut down
if the load increases.
The alarm resets when the
condition becomes
inactive.
UPS over temperature The UPS internal heat sink Clear vents and remove
temperature is too high or a any heat sources. Allow
Fault (Red) LED is On. fan has failed. the UPS to cool. Ensure the
Beep continuous. At the warning level, the UPS airflow around the UPS is
Code: 81 generates the alarm but not restricted. Restart the
remains in the current UPS.
operating state. If the condition continues
If the temperature rises to persist, contact your
another 2°C, the UPS transfers service representative.
to Bypass mode or Standby
mode.
ON Maintenance Bypass UPS was manually commanded Check the maintain bypass
Bypass (Orange) LED is on. to switch to bypass and will switch status
Code: 72 remain in bypass until
commanded out of bypass
27
Back feed UPS has a unexpected bypass Transfer to maintenance
Fault (Red) LED is On. current on battery mode bypass and call service.
Beep continuous.
Code: 93
Inv Overload Fault UPS has transferred to bypass The UPS transfers to
Fault (Red) LED is On or fault mode because of Battery mode if supporting
Beep continuous. overload in inverter mode the load.
Code: 42 Remove some of the
equipment from the UPS
Byp Overload Fault UPS has cut off the output and Remove some of the
Fault (Red) LED is On. transferred to fault mode equipment from the UPS
Beep continuous. because of overload in bypass
Code: 43 mode or HE mode.
Output Short Circuit Indicates that the UPS has Remove all the loads. Turn
Fault (Red) LED is On. detected abnormally low off the UPS.
Beep continuous. impedance placed on its Check if UPS output and
Code: 31 output and considers it a short loads is short circuit.
circuit Ensure short circuit is
removed before turning on
again.
Fan Failure Indicates that the fan could not Check fans of UPS
Fault (Red) LED is flash work normally
1 beep every 1 second
Code: 85
BUS Over Voltage Indicates that the UPS get BUS The UPS transfers to
Fault (Red) LED is On. over voltage fault because of Bypass mode if supporting
Beep continuous. BUS. the load
Code: 21
BUS Under Voltage Indicates that the UPS get BUS The UPS transfers to
Fault (Red) LED is On. under voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 22
BUS Unbalance Indicates that the positive BUS The UPS transfers to
Fault (Red) LED is On. voltage and negative BUS Bypass mode if supporting
Beep continuous. voltage are too lopsided to the load
Code: 23 fault
BUS Short Indicates that the BUS voltage Contact your service
Fault (Red) LED is On. decrease very fast representative
Beep continuous.
Code: 24
28
BUS Softstart Fail Indicates that the BUS could Contact your service
Fault (Red) LED is On. not soft start successfully representative
Beep continuous.
Code: 25
Inv Over Voltage Indicates that the UPS get The UPS transfers to
Fault (Red) LED is On. invert over voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 32
Inv Under Voltage Indicates that the UPS get The UPS transfers to
Fault (Red) LED is On. inverter under voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 33
Inv Softstart Fail Indicates that the inverter Contact your service
Fault (Red) LED is On. could not soft start successfully representative
Beep continuous.
Code: 34
Charger Fail Indicates that the UPS has The UPS turns off the
Fault (Red) LED is flash confirmed the charger has charger until the next
1 beep every 1 second failed power recycle. Contact
Code: 15 your service representative
Battery Over Voltage Indicates that the battery The UPS will turn off the
Fault (Red) LED is On. voltage is too high charger until the battery
Beep continuous. voltage is normal
Code: 14
Negative power Fault In parallel system,power of Redundancy mode,the
Fault (Red) LED is On. UPS is negative fault UPS turn to fault
Beep continuous. mode without output
Code: E1 Increase mode,UPS1&
UPS2 turn to fault mode
Parallel cable loss In parallel system,parallel Disconnect parallel cable
Fault (Red) LED is On. cable disconnect one turn to fault mode
Beep continuous.
Code: E2
Parallel system battery status UPS1 connect battery,UPS2 Check battery connect
Fault (Red) LED is flash without battery status
1 beep every 1 second
Code: E6
29
Line input different Parallel system,UPS1 line ok, Check the line input
Fault (Red) LED is flash UPS2 line loss
1 beep every 1 second
Code: E7
Power strategy different Parallel system,UPS mode Check UPS OP mode, Keep
Fault (Red) LED is flash OP mode be the same
1 beep every 1 second different
(normal ,converter,HE)
Code: E9
Rate power different Parallel system rate power Rate power different,not
Fault (Red) LED is flash different allow turn on UPS. Keep
1 beep every 1 second rate power be the same
Code: EA
HE in parallel Parallel system,UPS mode set HE not allow in parallel
Fault (Red) LED is flash as HE system,change UPS mode
1 beep every 1 second
Code: EB
9. Specifications
9.1 Model specifications
Table 1. Power Module model list
Model Power Ratings
6K UPS (standard model) 6000VA / 6000W
10K UPS (standard model) 10000VA / 10000W
6KS UPS (long backup model) 6000VA / 6000W
10KS UPS (long backup model) 10000VA / 10000W
Table 2. Extended Battery Module model list
Model Configuration Battery voltage For power ratings
EBM Rack 192Vdc 6000-10000VA
30
5. Trouble shooting
NOTE:If the UPS does not operate correctly, please press the "switch
machine" button for a long time to clear the trouble, prevent the battery from long-term
discharge damage, forbid to turn on the machine again, so as to avoid greater damage
to the machine.
1#Fault indicator and UPS shut down due to Ensure that the UPS is not
6#light on,buzzer internal overheating overloaded, the vents are not
beeps continuously plugged, the room temperature
is not too high, wait 10 minutes
for UPS to cool, and then
restart. If failure, please contact
your supplier
1#Fault indicator and UPS shut down due to please contact your supplier
5#light on,buzzer internal faults
beeps continuously
1#Fault indicator and UPS shut down due to please contact your supplier
4#light on,buzzer internal faults
beeps continuously
1#、4#、5# Fault UPS shut down due to please contact your supplier
indicator light on, internal faults
buzzer beeps
continuously
- 31 -
1#Fault indicator and UPS overcharge UPS charger fault,please
3#light on,buzzer protection action contact your supplier
beeps continuously
Overload to battery,
1sec flashing,battery
light is normal
1#Fault indicator and UPS overload in battery Check the load levels and
2#light on,buzzer mode or Load remove non critical devices,
beeps continuously equipment failure recalculate load power, and
reduce the amount of load
connected to the UPS, and
check if the load device is faulty
1#Fault indicator and UPS fan unconnected or please contact your supplier
2#、6#light on, fan damaged
buzzer beeps per sec
1#Fault indicator and UPS output short- Turn off the UPS, remove all
2#、5#light on, circuited the load, confirm the load is not
buzzer beeps fault (manually except for the
continuously fault, long press the switch
button for 3 seconds) or
internal short circuit, restart, if
fail, please contact your
- 32 -
Warning & Fault Possible cause Method
10#battery light The battery voltage is too Check the UPS battery section
flashing low or the battery is not and connect the battery.
connected Contact your supplier if the
battery is damaged
1#Fault light on, UPS charging fault please contact your supplier
10#battery light
flashing,buzzer
beeps continuously
Utility normally, UPS UPS input circuit breaker Manually reset the circuit
without utility is disconnected breaker
connection
Battery discharge Battery is under charged Maintain the UPS and continue
time is short to connect the utility for more
than 10 hours, recharging the
battery
UPS overload Check load levels and remove
non critical devices
The UPS cannot start Press the turn on button Press the boot button for more
after the power time is too short than 1 sec to turn on UPS
button is pressed
UPS not connected to Connect the UPS battery. If the
battery or battery on low battery voltage is low, turn off
voltage and loaded with the power before starting the
power on UPS
An internal fault occurred Please contact your supplier
inside the UPS