RACK 6K(S)/10K(S)

2. Presentation
2.1 Front panel

6K/6KS/10K/10KS UPS

EBM
2.2 Rear panels

6K/6KS/10K/10KS

EBM

3
1. Intelligent slot
2. USB
3. Dry IN/OUT
4. RS232
5. EPO
6. RJ11 (connect to PDU, only for RT model)
7. Parallel card (optional)
8. Output breaker
9. Output socket
10. Input/Output terminal (4pole IPL, IPN, OPL, OPN. PE is screw)
11. Input breaker (optional)
12. EBM connector
13. Fuse board cover (replace EBM fuse)
14. EBM plug
15. EBM connector

2.3 Circuit diagram

4
5. Operation
5.1 Control panel
The UPS has a graphical LCD. It provides useful information about the UPS itself,
load status, events, measurements and settings.

The following table shows the indicator status and description:

Indicator Status Description

ONLINE The UPS is operating normally on Online or on High


On
(Green) Efficiency mode.

BAT.
On The UPS is on Battery mode.
(Orange)

On The UPS is on Bypass mode.


Bypass
(Orange)
Flash The UPS is on Standby mode.

Fault
On The UPS has an active alarm or fault.
(Red)

14
The Buzzer definition as below:

UPS condition Buzzer status


Fault active Continuous
Over Load
2 Beep every second
Warning active
Other Warning active Beep every second
Battery output Beep every 4 seconds, if battery low, buzzer Beep every second
Bypass output Beep every 2 minutes

5.2 LCD description


The LCD backlight automatically dims after 2 minutes of inactivity (except UPS is
fault). Press any button to wake up the screen.

15
Display Function

Input & Output Information


It indicates input & output voltage/frequency value,
which are displayed alternately. It also indicate load
per cent and battery voltage value .

UPS Operating Mode Display

It indicates UPS operating mode .

Load Information

It indicates the load level. Every grid represents the


level of 25%. If UPS is overloaded , the icon
would flash once time per second .

Battery Information

It indicates the battery capacity. Every grid


represents the capacity of 20%. If the battery
charger is running , the icon would show .

Buzzer
The icon will be displayed after panel key operation
or serial command mute

The icon will be displayed when the buzzer sounds


normally.

Else

alarm ID indicates the UPS is in Fault mode or has


some warnings. It Indicates Fault kind or Warning
kind, several warning kinds at the same time could
be displayed alternately.
The icon would flash when having warnings . The
icon would show continuous when in Fault
mode.

16
It indicates UPS Brand Logo and UPS system
information .

5.3 Display functions

Button Name Description Setting


Switch UPS operating mode Press 0.5s or more (ON / OFF) : Standby
When the UPS is faulty, press the key for
ON/OFF
Remove the fault alarm more than 0.5s to release the UPS fault
alarm
Bat. test ONLINE Mode, Press 4s or more

Silence Press 2s ~ 4s
Test/Silence Press ON/OFF and Test/Silence button at
Setting the same time for 4s or more, enter into
setting function

5.4 Operation Mode


The different UPS Operating Mode would be displayed on the LCD screen corresponding to
their operating modes, and they are illustrated as the following table.

Normal Operation Mode

No Output Mode
Bypass Output Mode
○ ○ ○

ONLINE/Converter Output Mode


○ ○ ●

Battery/Battery Test Mode


● ○ ○

ECO Mode
● ● ○

●:Icon display
● ○ ●

○:Icon no display

Note:
ECO mode / CVCF mode and the number of parallel machines: The alarm ID is
not displayed when the UPS works normally without alarm information. The

17
Pressing button continuously for more than 1 second, the buzzer will beep
for300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Battery mode. If the utility power comes
back, the UPS will transfer to Line mode without output interruption of the
UPS.
UPS shutdown with utility
To shut down the UPS with utility:
Pressing button continuously for more than 3 seconds and the buzzer will
beep 300ms. After that, the UPS will turn into Bypass mode at once.
When completing the above action, UPS output voltage is still present. In order
to cut off the UPS output, simply cut off the utility power supply. A few seconds
later, the ups will shut down and no output voltage is available from the UPS
output terminal.
UPS shutdown without utility
To shut down the UPS without utility:
To power off the UPS by pressing button continuously for more than 3
second, and the buzzer will beep for 300ms. The UPS will cut off the output at
once.
A few seconds later, the ups will shut down and no voltage is available from the
UPS output.
5.6 LCD operation
The UPS can make some settings via the LCD, including:
1> ECO Setting
The ECO mode ("EO") can be set to on / off. When set to enabled, the UPS can
operate in ECO mode to power the load. When set to disable, the UPS operates In
normal mains mode for the load power supply, the default is not enabled.

2> CVCF Setting


The CVCF mode ("CF") can be set to on / off. When set to enabled, the UPS can
operate in CVCF mode as a load function. When set to Disabled, the UPS operates In

19
normal mains mode for the load power supply, the default is not enabled.
Note: Only one of ECO and CVCF can be set to enable. CVCF is automatically set to
disabled when ECO is set to Enabled. ECO is automatically set to Disabled when CVCF
is set to Enable.

3> Charging Current


Charging current (CH) can be setting
Standard model (6K/10K), charging current can be set to 1A/1.4A/2A/2.5A/3A
/3.5A/4.0A. Long backup model (6KS/10KS), the charging current can be set to 1A to
12A (in steps of 1A), the default is 4A, the corresponding LCD display is 01/02/03/04
/05/06/07/08/09/10/11/12.

 Setting Step
Step 1:When the two keys are pressed at the same time for more than 4s (press
the test key first, and then press the on / off key), the UPS enters into the
setting mode and the contents to be set (EO / CF / CH) are displayed to display
the corresponding Option.
Step 2: Set mode, press the power button to select the content to be set for
more than 0.5s (EO, CF or CH).
Step3: Press the test key 0.5s above, the corresponding setting options start
flashing.
Step4: Press the on/off button 0.5s above, select the corresponding setting

20
in less than 3 hours.
However, recommends that the batteries charge for 48 hours after long-term
storage.
If the date has passed and the batteries were never recharged, do not use them.
Contact your service representative.

7.4 Replacing batteries

DO NOT DISCONNECT the batteries while the UPS is in Battery mode.

Consider all warnings, cautions, and notes before replacing batteries.


 Servicing should be performed by qualified service personnel with
knowledgeable of batteries and required precautions. Keep unauthorized
personnel away from batteries.
 Batteries can present a risk of electrical shock or burn from high short
circuit current. Observe the following precautions:
1. Remove watches, rings, or other metal objects,
2. Use tools with insulated handles,
3. Do not lay tools or metal parts on top of batteries,
4. Wear rubber gloves and boots.
 When replacing batteries, replace with the same type and number of
batteries or battery packs. Contact your service representative to order
new batteries.
 Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
 Never dispose of batteries in a fire. Batteries may explode when exposed
to flame.
 Do not open or mutilate the battery or batteries. Released electrolyte is
harmful to the skin and eyes and may be extremely toxic.
 Take care if the battery is inadvertently grounded. If grounded, remove
source from ground. Contact with any part of a grounded battery may
cause electrical shock.
 The likelihood of such shock can be reduced if such grounds are removed
during installation and maintenance (applicable to equipment and remote
battery supplies not having a grounded supply circuit).
 ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or
connectors. It may cause injury.
 Please disconnect battery charging source before battery replacing or
maintenance.

24
they are preventive alarms intended to alert the user.
 Events are silent status information that are recorded into the Event log.
Example = "Battery charging".
 Alarms are recorded into the Event log and displayed on the LCD status
screen with the logo blinking. Some alarms may be announced by a beep
every 1 second. Example = "Battery low".
 Faults are announced by a continuous beep and red LED, recorded into the
Event log. Example = "Out. short circuit".
Use the following troubleshooting chart to determine the UPS alarm condition.

8.1 Typical alarms and faults


To check the Event log:
Conditions Possible cause Action
Battery mode A utility failure has occurred The UPS is powering the
Battery(Orange) LED is On. and the UPS is in Battery mode. equipment with battery
1 beep every 4 seconds. power. Prepare your
Code: 62 equipment for shutdown.
Battery low The UPS is in Battery mode and This warning is
Battery(Orange) LED is On. the battery is running low. approximate, and the
1 beep every 1 second. actual time to shutdown
Code: 12 may vary significantly.
Depending on the UPS
load and number of
Extended Battery Modules
(EBMs), the "Battery Low"
warning may occur before
the batteries reach 20%
capacity.
No battery The batteries are disconnected. Verify that all batteries are
Fault (Red) LED is Flash properly connected.
1beep every 1 second If the condition persists,
Code: 11 contact your service
representative.
Bypass mode An overload or a fault has Equipment is powered but
Bypass (Orange) LED is on. occurred, or a command has not protected by the UPS.
Code: 60 been received and the UPS is in Check for one of the
Bypass mode following alarms: over
temperature, overload or
UPS failure.

26
Power overload Power requirements exceed Remove some of the
Fault (Red) LED is Flash the UPS capacity equipment from the UPS.
2beep every 1 second The UPS continues to
Code: 41 operate, but may switch to
Bypass mode or shut down
if the load increases.
The alarm resets when the
condition becomes
inactive.
UPS over temperature The UPS internal heat sink Clear vents and remove
temperature is too high or a any heat sources. Allow
Fault (Red) LED is On. fan has failed. the UPS to cool. Ensure the
Beep continuous. At the warning level, the UPS airflow around the UPS is
Code: 81 generates the alarm but not restricted. Restart the
remains in the current UPS.
operating state. If the condition continues
If the temperature rises to persist, contact your
another 2°C, the UPS transfers service representative.
to Bypass mode or Standby
mode.
ON Maintenance Bypass UPS was manually commanded Check the maintain bypass
Bypass (Orange) LED is on. to switch to bypass and will switch status
Code: 72 remain in bypass until
commanded out of bypass

In HE Mode The UPS is on bypass while The equipment transferred


Line(green) LED is on. operating on the High to bypass utility power as a
Code: 63 Efficiency setting. normal function of High
Efficiency operation.
Battery mode is available
and your equipment is
protected.
Site Wiring Fault Site Fault detection is Site Fault detection should
Fault (Red) LED is flash supported on all models be enabled by default. It
1beep every 1 second anytime there is a Grounding can still be enabled /
Code: 04 Neutral connection. disabled from the LCD
Alarm triggers when the settings menu.
difference between ground and Reconnect all input wires.
neutral voltage is > 15v.

27
Back feed UPS has a unexpected bypass Transfer to maintenance
Fault (Red) LED is On. current on battery mode bypass and call service.
Beep continuous.
Code: 93

Inv Overload Fault UPS has transferred to bypass The UPS transfers to
Fault (Red) LED is On or fault mode because of Battery mode if supporting
Beep continuous. overload in inverter mode the load.
Code: 42 Remove some of the
equipment from the UPS

Byp Overload Fault UPS has cut off the output and Remove some of the
Fault (Red) LED is On. transferred to fault mode equipment from the UPS
Beep continuous. because of overload in bypass
Code: 43 mode or HE mode.
Output Short Circuit Indicates that the UPS has Remove all the loads. Turn
Fault (Red) LED is On. detected abnormally low off the UPS.
Beep continuous. impedance placed on its Check if UPS output and
Code: 31 output and considers it a short loads is short circuit.
circuit Ensure short circuit is
removed before turning on
again.
Fan Failure Indicates that the fan could not Check fans of UPS
Fault (Red) LED is flash work normally
1 beep every 1 second
Code: 85
BUS Over Voltage Indicates that the UPS get BUS The UPS transfers to
Fault (Red) LED is On. over voltage fault because of Bypass mode if supporting
Beep continuous. BUS. the load
Code: 21
BUS Under Voltage Indicates that the UPS get BUS The UPS transfers to
Fault (Red) LED is On. under voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 22
BUS Unbalance Indicates that the positive BUS The UPS transfers to
Fault (Red) LED is On. voltage and negative BUS Bypass mode if supporting
Beep continuous. voltage are too lopsided to the load
Code: 23 fault
BUS Short Indicates that the BUS voltage Contact your service
Fault (Red) LED is On. decrease very fast representative
Beep continuous.
Code: 24

28
BUS Softstart Fail Indicates that the BUS could Contact your service
Fault (Red) LED is On. not soft start successfully representative
Beep continuous.
Code: 25
Inv Over Voltage Indicates that the UPS get The UPS transfers to
Fault (Red) LED is On. invert over voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 32
Inv Under Voltage Indicates that the UPS get The UPS transfers to
Fault (Red) LED is On. inverter under voltage fault Bypass mode if supporting
Beep continuous. the load
Code: 33
Inv Softstart Fail Indicates that the inverter Contact your service
Fault (Red) LED is On. could not soft start successfully representative
Beep continuous.
Code: 34
Charger Fail Indicates that the UPS has The UPS turns off the
Fault (Red) LED is flash confirmed the charger has charger until the next
1 beep every 1 second failed power recycle. Contact
Code: 15 your service representative

Battery Over Voltage Indicates that the battery The UPS will turn off the
Fault (Red) LED is On. voltage is too high charger until the battery
Beep continuous. voltage is normal
Code: 14
Negative power Fault In parallel system,power of Redundancy mode,the
Fault (Red) LED is On. UPS is negative fault UPS turn to fault
Beep continuous. mode without output
Code: E1 Increase mode,UPS1&
UPS2 turn to fault mode
Parallel cable loss In parallel system,parallel Disconnect parallel cable
Fault (Red) LED is On. cable disconnect one turn to fault mode
Beep continuous.
Code: E2
Parallel system battery status UPS1 connect battery,UPS2 Check battery connect
Fault (Red) LED is flash without battery status
1 beep every 1 second
Code: E6

29
Line input different Parallel system,UPS1 line ok, Check the line input
Fault (Red) LED is flash UPS2 line loss
1 beep every 1 second
Code: E7
Power strategy different Parallel system,UPS mode Check UPS OP mode, Keep
Fault (Red) LED is flash OP mode be the same
1 beep every 1 second different
(normal ,converter,HE)

Code: E9
Rate power different Parallel system rate power Rate power different,not
Fault (Red) LED is flash different allow turn on UPS. Keep
1 beep every 1 second rate power be the same
Code: EA
HE in parallel Parallel system,UPS mode set HE not allow in parallel
Fault (Red) LED is flash as HE system,change UPS mode
1 beep every 1 second
Code: EB

9. Specifications
9.1 Model specifications
Table 1. Power Module model list
Model Power Ratings
6K UPS (standard model) 6000VA / 6000W
10K UPS (standard model) 10000VA / 10000W
6KS UPS (long backup model) 6000VA / 6000W
10KS UPS (long backup model) 10000VA / 10000W
Table 2. Extended Battery Module model list
Model Configuration Battery voltage For power ratings
EBM Rack 192Vdc 6000-10000VA

Table 3. Weights and dimensions


Description Weights (kg) Dimensions (mm) W x H x D
6K UPS 14 438*86.3*573
10K UPS 16 438*86.3*573
6KS UPS 14 438*86.3*573
10KS UPS 16 438*86.3*573
EBM 16 BAT 52 438*129*593
Note:The weight in this table is reference only, please see the labels on the carton for
details
Table 4. Electrical input

30
5. Trouble shooting
NOTE:If the UPS does not operate correctly, please press the "switch
machine" button for a long time to clear the trouble, prevent the battery from long-term
discharge damage, forbid to turn on the machine again, so as to avoid greater damage
to the machine.

UPS fault handle list

Warning & Fault Code Possible cause Method

1#Fault indicator and UPS shut down due to Ensure that the UPS is not
6#light on,buzzer internal overheating overloaded, the vents are not
beeps continuously plugged, the room temperature
is not too high, wait 10 minutes
for UPS to cool, and then
restart. If failure, please contact
your supplier

1#Fault indicator and UPS shut down due to please contact your supplier
5#light on,buzzer internal faults
beeps continuously

1#Fault indicator and UPS shut down due to please contact your supplier
4#light on,buzzer internal faults
beeps continuously

1#、4#、5# Fault UPS shut down due to please contact your supplier
indicator light on, internal faults
buzzer beeps
continuously

1#、2#、3#、4#、5# UPS shut down due to please contact your supplier


internal faults
Fault indicator light
on,buzzer beeps
continuously

- 31 -
1#Fault indicator and UPS overcharge UPS charger fault,please
3#light on,buzzer protection action contact your supplier
beeps continuously

8#utility indicator The utility voltage or UPS is working in the battery


flashing frequency is beyond the mode, saving data and closing
UPS input range the application to ensure that
the utility is in the input voltage
or frequency range that UPS
allows
Utility input reversed, 1 Reconnect the utility line to
beep every 2mins for correct
UPS
“Freerun” or “Converter” please contact your supplier

Overload to battery,
1sec flashing,battery
light is normal

1#Fault indicator and UPS overload in battery Check the load levels and
2#light on,buzzer mode or Load remove non critical devices,
beeps continuously equipment failure recalculate load power, and
reduce the amount of load
connected to the UPS, and
check if the load device is faulty
1#Fault indicator and UPS fan unconnected or please contact your supplier
2#、6#light on, fan damaged
buzzer beeps per sec

1#Fault indicator and UPS output short- Turn off the UPS, remove all
2#、5#light on, circuited the load, confirm the load is not
buzzer beeps fault (manually except for the
continuously fault, long press the switch
button for 3 seconds) or
internal short circuit, restart, if
fail, please contact your
- 32 -
Warning & Fault Possible cause Method
10#battery light The battery voltage is too Check the UPS battery section
flashing low or the battery is not and connect the battery.
connected Contact your supplier if the
battery is damaged
1#Fault light on, UPS charging fault please contact your supplier

10#battery light
flashing,buzzer
beeps continuously
Utility normally, UPS UPS input circuit breaker Manually reset the circuit
without utility is disconnected breaker
connection
Battery discharge Battery is under charged Maintain the UPS and continue
time is short to connect the utility for more
than 10 hours, recharging the
battery
UPS overload Check load levels and remove
non critical devices

Battery aging, capacity Replace the battery, please


degradation contact your supplier to obtain
the battery and its components

The UPS cannot start Press the turn on button Press the boot button for more
after the power time is too short than 1 sec to turn on UPS
button is pressed
UPS not connected to Connect the UPS battery. If the
battery or battery on low battery voltage is low, turn off
voltage and loaded with the power before starting the
power on UPS
An internal fault occurred Please contact your supplier
inside the UPS

- 33 -