You are on page 1of 2

NOTES

1 a.- The Bidder shall fill in this Data Sheet and send it with his offer (Excel & pdf files).
2 b.- (*) To be defined by Bidder.
3 c.- TBC: To be confirmed.
4 d.- N/A: Not applicable.
5 e.- Seismic Zone indicated in IT-002GP0668B-000-99-001 "Site Conditions".
6 f.- If flanges are not possible be ASME B16.5, then Vendor shall supply a companion flange.
7
8
9

A.- OPERATING AND DESIGN CONDITIONS


10 ITEM UNITS DATA BY BUYER DATA BY VENDOR NOTES
11 Service WATER
12 Flowrate (Minimum/Nominal/Design) m³/h 10.6 / 11.8 / 13.5
13 Total Head (Minimum/Nominal/Design) m.c.a. 27.4 / 27.4 / 27.6
14 Static Head (Design) m 0.4
15 NPSHA (Minimum/Nominal/Design) m.c.a. 5.9 / 5.9 / 5.9
16 Head pressure required kPag 260.9
17 Quantity 01 Operación + 01 Stand by
18 Pump Location (Indoor/Outdoor) Outdoor
19 Operating schedule average h/day 2
days/year 365
20 Amb. Temperature °C -9.1 - 16.3
21 Elevation above sea level m 4713.3 e
22 Gear reducer cooling (air or water) (*)
23 Enviroment Wet and dusty
24 Special Requirements Self dreinage
25 Slurry:
26 % Solids by weight % N/A
27 Slurry specific gravity N/A
28 Solids specifc gravity N/A
29 Kinematic viscosity (estimated) m²/s 1.14E-06
30 Vapor pressure (estimated) Pa 0.174
31 pH 7
32 Temperature °C 15
33 Froth Factor N/A
34 Screen analysis:
35 d50 Size μm N/A
36 Principal corrosives f

Documento elaborado por BISA AGUA FRESCA

Larrabure y Unanue 146, Lima 1 – Perú T.(511)6266200 F.(511)4332842 Página 1 de 5


B.- INFORMATION REQUIRED FROM BIDDER
37 ITEM UNITS DATA BY BUYER DATA BY VENDOR NOTES
38 GENERAL
39 Model No. (*)
40 Pump size (*)
41 Impeller diameter selected mm (*)
42 Max. Working pressure kPag (*)
43 Hydrostatic test press kPag (*)
44 Connections (suction / discharge): ASME B16.5
45 Inside diameter mm (*)
46 Flange nominal size inch (*)
47 Flange rating lb 150
48 Flange facing FF
49 CAPACITY AND MODEL DATA
50 Proposal curve No (*)
51 At required flow:
52 Total head (Minimum/Nominal/Design) m, slurry (*)
53 Efficiency (Minimum/Nominal/Design) % (*)
54 Brake kW (Minimum/Nominal/Design) kW (*)
55 Max allowable speed rpm (*)
56 Effect of slurry on pump performance:
57 Head derate factor (HR) (*)
58 Efficiency derate factor (ER) (*)
59 Motor power required kW (*)
60 Motor speed rpm (*)
61 Pump speed (Minimum/Nominal/Design) rpm (*)
62 Peripheral speed (Minimum/Nominal/Design) m/s 24 max tip speed
63 NPSHR m, slurry (*)
64 Max. Brake kW @ Max conditions kW (*)
65 Max. / Min stable flow continuos m³/h (*)
66 CONSTRUCTION
67 Base plate material (*)
68 Casing (*)
69 Type (*)
70 Material (*)
71 Hardness (*)
72 Thickness mm (*)
73 Lining material (if requided) Elastomer
74 Lining material thickness mm (*)
75 Lining material hardness (*)
76 Lining material repleceable (*)
77 Connections:
78 Gage (*)
79 Drain (*)
80 Vent (*)
81 IMPELLER
82 Type (*)
83 Model (*)
84 Size-diameter mm (*)
85 Max. possible diameter mm (*)
86 Material (*)
87 Lining material (*)
88 Lining thickness mm (*)
89 Lining hardness (*)
90 Impeller rotation (CW/CCW) CW
91 SHOP TEST
92 Hydrostatic test-required/witnessed Yes
93 Performance test-required/witnessed Yes
94 DRIVE
95 Type
96 Fixed Speed (*)