Professional Documents
Culture Documents
1-5
TRAFOTECH 2018 –Tenth International Conference on Transformers
structure. This wave and structure interaction build up inside the tank, subject to tank expansion
eventually leads to the tank rupture or even coefficient. Based on a conservative assumption of
explosion. These ruptures can result in outflow of a an isothermal expansion of the gas bubble, the
large amount of oil and may also cause a fire when tank pressure build up can be estimated from the
the hot combustible gases come in contact with following formula.
oxygen from outside air. Oil spills will cause
Ps (calculated tank pressure k Pa above atmosphere) = F
environmental pollution apart from fire. It is
{100 [√1/4 +√ (kE /100 C)] -50} [2]
reported that tank rupture is seen when the arc
energy is more than 8.5MJ and possibility of oil fire Where F =Dynamic amplification factor (Ratio of
is more when energy levels exceed 20 MJ [1]. It is localized dynamic pressure to static pressure
also seen that chances of tank rupture is more with developed from arc) =1.5-2.5 (for C/V between 20-
Generator Transformers, for the same level of arc 180)
energy release probably due to continued energy C= tank expansion coefficient (m3/ k Pa) i.e.
feed from generator and HV side. flexibility of tank
3. MODE OF TANK RUPTURE V= Oil volume in main tank (m3)
Chance for tank rupture depends on the pressure
build up inside the tank. This in turn, depends on k = Arc energy to gas conversion factor = 5.8 x10 -4
the volume of gas generated by the arc, arc m3 /kJ at 2000 0 K.
location and the tank expansion characteristics.
Gas volume is related to energy release from arc Assumption: A gas generation rate of 85 cc/kJ and
(which in turn is the product of arc current (I), arc 24 % of arc energy is transferred in to enthalpy for
voltage (V) and duration time (T)). gas bubble expansion and mechanical energy to
deform tank.
Arc Energy (J) Earc = 0.9 V I t [1]
E = Fault energy level (kJ)
Arc Voltage (volt) = 55L √P where L= length of arc
in cm, P = Absolute pressure in the gas bubble 4. TANK RUPTURE MITIGATION AND
surrounding the arc (atm) PREVENTION METHODS
5. 4.1 Mitigation methods
HV Voltage class Arc Energy (kJ) ● Flexible tank – absorbs part of arc energy
of by the deformation process of tank.
Transformer(kV) ● Bracing critical areas of tank.eg. Tank
cover joint, tank corner welds.
72.5 2000 ● Use of Fast depressurisation valve or
rupture disc.
145 4000 ● Use of an automatic shutter valve in
conservator to tank pipe to stop oil flow in
245 8000 the event of a tank rupture
● Large expansion tank with large connecting
420 20000 trunk to tank for absorbing the pressure
rise.
765 20000
6. 4.1.1 Flexible Tank
Table-1: Relationship between arc energy and By making the tank flexible, certain portion of
voltage class [1] pressure from arc energy is absorbed by the side
With reference to above table, it is clear that higher panel deforming action, thereby reducing the
the voltage class, it will results in greater arc pressure levels below the tank rupturing levels.
energy which in turn generates higher pressure Design is done for maximum tank side deflection
2-5
TRAFOTECH 2018 –Tenth International Conference on Transformers
3-5
TRAFOTECH 2018 –Tenth International Conference on Transformers
permissible strain for tank material. Weakest parts 11. 4.2 Prevention methods
are kept at the top of the tank. To determine local
● Alternate insulating medium to oil- SF6 gas
pressure concentration, dynamic simulation will be
or esters
required (eg. ANSYS -LS DYNA) [6].
● Use of Generator circuit breakers with large
The rupture resistant transformer design will Generator Transformers
mitigate the risk of tank rupture thereby avoiding ● Reducing chances of a low impedance fault
insulating fluid spills and consequent fires. For through better insulation clearances at
faults, higher than the specification limits, vulnerable areas (bottom tail of bushings,
manufacturer should demonstrate by calculation line end of windings) inside tank and
the first rupture point is at tank cover [1]. insulation monitoring
● Fast acting protective relays and fast
9. 4.1.2 Conservator shutter
clearing breakers reduce the duration of
valve
arc, thereby preventing tank rupture.
The conservator shutter valve is installed on the oil
12. 4.2.1 Ester Fluids
pipe connecting the conservator to the tank .The
shutter valve allows oil flow in both directions. It Ester fluids (natural or synthetic) when used as
will close and initiate an alarm if the flow rate back alternate insulating fluid, may not reduce the
to tank exceeds a certain limit. This will prevent oil chances of tank rupture from internal arcs but will
feed from conservator to the oil spill through reduce the risk of fire initiation and propagation to
ruptured tank joint a great extent[7]. Esters fluids have higher flash
point, fire point and auto ignition temperatures
compared to mineral oils (approx. 2000C higher
each). It is the inflammable gases from the
insulating fluids that act as fuel for starting fire. The
gases generated due to high temperature of arc in
different insulating fluids will have varying content
of flammable or explosive elements .There are
lower and upper concentration of these
inflammable gases in air within which range the
mixture would be considered flammable. With
esters, a higher percent volume of gases is
Fig-4: Conservator shutter valve required before a fire can be ignited and
maintained .eg: with natural esters approx. 10
times more than with mineral oil (0.6% vs 9%) [7].
10. 4.1.3 Modern Rupture Disc
Heat release rate (amount of thermal energy
Fast acting depressurization systems have been released per unit time) of ester is less than that of
developed as an improvement over conventional mineral oil (eg: natural ester 1/8 of mineral oil)
PRD. It is claimed that such pressure relief devices giving better self-extinguishing properties [7].
can reduce the chances of tank rupture.
Depressurization set is activated within
milliseconds by the first dynamic pressure peak of 13. 4.2.2 Gas insulated
the shock wave, thereby releasing tank pressure Transformers
quickly and tripping the actuating relays fast there
Use of SF6 gas as dielectric insulation, instead of
by reducing the arc duration. The diameter of the
mineral oil, will eliminate the risk of transformer
Depressurization Set is sized individually based on
tank rupture during severe faults. SF6 gas is
the transformer power rating and the transformer
compressible and will result in only low pressure
function (Generation, Distribution or Transmission)
rises inside the transformer tank during internal
[6]
arcing faults. SF6 gas is nonflammable and even if
tank rupture were to occur, the release of SF6 gas
will not pose an explosion or fire risk. The main
4-5
TRAFOTECH 2018 –Tenth International Conference on Transformers
limitation for its application is due to its very high 15. CONCLUSION
cost and requirement of pressurized tanks [1]
16. Transformer tank rupture
14. 4.2.3 Generator Circuit due to internal arcing fault is
Breakers a complex problem.
Pressure rise in the
Generator circuit breakers (GCB) between
transformer is affected by
generator and transformer can prevent energy flow
both the expanding gas
from generator to a transformer internal fault
bubble generated by the
quickly. [8] This will reduce the energy flow through
arcing fault as well as the
arc and hence the internal pressure build up in
interaction of the
tank.
propagating pressure wave
4.2.4 Protection System with the transformer tank
Protective relays should sense the internal low and its internal components.
impedance faults quickly and activate the breakers Still we can minimize the
fast to reduce the arc duration time and there by severity of pressure rise by
the quantum of energy release. From the speed adopting flexible tank
and sensitivity angle, it is claimed that Restricted concepts which allows tank
Earth Fault Relay (REF) is superior to differential to absorb certain generated
relay and can clear the fault within half a cycle pressure and other
protecting up to 95 % of winding. High speed preventive measures.
protection relays with fast acting breaker (<2 Rupture resistant tank can
cycles) can limit arc energy released in to tank be considered to mitigate the
esp. at locations with high fault levels. [9] problems of oil spills and fire
hazards.
17. REFERENCES
[1] IEEE Std C 57.156-2016 –“Guide for Tank
Rupture Mitigation of Liquid Immersed Power
Transformers and Reactors”
[2] Working Group A2.33. “Guide for Transformer
Fire Safety Practices.” CIGRE 2013.
[3] M. Foata, J.B. Dastous, Power Transformer
Tank Rupture Prevention, 2010 Cigré Colloquim,
Paris.
[4] S. Brodeur, Y. Salmi, A. Collier, “A Flexible
Friend”, ABB Review, January 2016
[5] T. Kawamura et al., "Prevention of Tank
Rupture due to Internal Fault of Oil Filled
Transformers," Paper 12-02, CIGRÉ 1988
Session, Paris.
[6]Task force of IEEE Power Transformer
subcommittee, "Power Transformer Tank Rupture
and Mitigation”,IEEE PASVol24,No.4 October,2009
[7]George Frimpong, S.Page etc.; “Transformers
Transformed”, ABB Review No2, 2012
5-5
TRAFOTECH 2018 –Tenth International Conference on Transformers
6-5