You are on page 1of 6

TRAFOTECH 2018 –Tenth International Conference on Transformers

POWER TRANSFORMER TANK RUPTURE-CAUSE, MODE AND MITIGATION

Anil Babu Boppana, Pramod Reddy


ABB India Limited, Vadodara

1. INTRODUCTION 2. CAUSE OF TANK RUPTURE


Transformer tank may rupture when a severe low Power transformers are insulated and cooled by
impedance fault occurs inside the transformer mineral oil. When a fault develops in secondary
tank. Generally it will be a flash over from primary winding or part of primary winding, it is a high
winding line end/bushing bottom to tank, impedance fault as winding reactance limits the
generating high fault current as the grid fault level fault current. But when it is a direct line fault either
collapses inside the tank. Energy flow in the arc from the winding line end or bushing bottom tail to
vaporizes the oil and the gas volume generated ground, the only impedance stopping the fault
will be manifold. This causes a pressure rise in the current is the low system impedance. The entire
transformer tank. The location, duration, and system fault current is released inside tank till the
magnitude of the arc fault will greatly influence the breaker clears the fault. The energy released
amount of the pressure rise in the transformer depends on the peak of current value, duration of
tank. The dynamic pressure wave can rupture the fault and the arc voltage. This energy from
tank side before it reaches the pressure relief electrical arc decomposes oil and the rapidly
device to vent out the excess pressure. Tank expanding gas bubble (70-100 cc of gas /kJ of
rupture will result in considerable oil spillage to energy at 20000 K) at high pressure and
environment. It can result in oil fire when the hot temperature, generates a dynamic pressure rise
combustible gases from oil catch fire as it comes in inside the tank, of the order of 25-5000 bar/sec
contact with oxygen in atmosphere. Such fires can and local static pressures of the order of 14 bar.
completely gut the transformer and sometimes This creates a mechanical stress on tank plates
may cause collateral damages. In future, and when it exceeds the yield strength of material,
engineers may have to take proactive design steps tank ruptures.
to make rupture resistant tanks and adopt steps to
mitigate tank rupture. National standards have
come out, such as IEEE C57.156-2016 “Guide for
tank rupture mitigation of liquid immersed power
transformers and reactors” to meet this
requirement. Method for estimating the pressure
rise from different types of electric arcs is
formulated and general design measures to
mitigate tank rupture under such situations are
proposed in this standard.
This paper reviews the tank rupture phenomena by
cause and mode. Mitigation and prevention
methods are presented to alleviate tank rupture by
modifying tank designs, adopting protection Fig-1: Ruptured Tank
practices to reduce arc energy flow and using
alternate solutions to eliminate chances for tank
rupture. The pressure rise generates pressure waves that
propagate inside the oil and interact with the tank

1-5
TRAFOTECH 2018 –Tenth International Conference on Transformers

structure. This wave and structure interaction build up inside the tank, subject to tank expansion
eventually leads to the tank rupture or even coefficient. Based on a conservative assumption of
explosion. These ruptures can result in outflow of a an isothermal expansion of the gas bubble, the
large amount of oil and may also cause a fire when tank pressure build up can be estimated from the
the hot combustible gases come in contact with following formula.
oxygen from outside air. Oil spills will cause
Ps (calculated tank pressure k Pa above atmosphere) = F
environmental pollution apart from fire. It is
{100 [√1/4 +√ (kE /100 C)] -50} [2]
reported that tank rupture is seen when the arc
energy is more than 8.5MJ and possibility of oil fire Where F =Dynamic amplification factor (Ratio of
is more when energy levels exceed 20 MJ [1]. It is localized dynamic pressure to static pressure
also seen that chances of tank rupture is more with developed from arc) =1.5-2.5 (for C/V between 20-
Generator Transformers, for the same level of arc 180)
energy release probably due to continued energy C= tank expansion coefficient (m3/ k Pa) i.e.
feed from generator and HV side. flexibility of tank
3. MODE OF TANK RUPTURE V= Oil volume in main tank (m3)
Chance for tank rupture depends on the pressure
build up inside the tank. This in turn, depends on k = Arc energy to gas conversion factor = 5.8 x10 -4
the volume of gas generated by the arc, arc m3 /kJ at 2000 0 K.
location and the tank expansion characteristics.
Gas volume is related to energy release from arc Assumption: A gas generation rate of 85 cc/kJ and
(which in turn is the product of arc current (I), arc 24 % of arc energy is transferred in to enthalpy for
voltage (V) and duration time (T)). gas bubble expansion and mechanical energy to
deform tank.
Arc Energy (J) Earc = 0.9 V I t [1]
E = Fault energy level (kJ)
Arc Voltage (volt) = 55L √P where L= length of arc
in cm, P = Absolute pressure in the gas bubble 4. TANK RUPTURE MITIGATION AND
surrounding the arc (atm) PREVENTION METHODS
5. 4.1 Mitigation methods
HV Voltage class Arc Energy (kJ) ● Flexible tank – absorbs part of arc energy
of by the deformation process of tank.
Transformer(kV) ● Bracing critical areas of tank.eg. Tank
cover joint, tank corner welds.
72.5 2000 ● Use of Fast depressurisation valve or
rupture disc.
145 4000 ● Use of an automatic shutter valve in
conservator to tank pipe to stop oil flow in
245 8000 the event of a tank rupture
● Large expansion tank with large connecting
420 20000 trunk to tank for absorbing the pressure
rise.
765 20000
6. 4.1.1 Flexible Tank
Table-1: Relationship between arc energy and By making the tank flexible, certain portion of
voltage class [1] pressure from arc energy is absorbed by the side
With reference to above table, it is clear that higher panel deforming action, thereby reducing the
the voltage class, it will results in greater arc pressure levels below the tank rupturing levels.
energy which in turn generates higher pressure Design is done for maximum tank side deflection

2-5
TRAFOTECH 2018 –Tenth International Conference on Transformers

without causing plate or weld rupture. The example


below show a 20 MJ arc energy event. The risk of Fig-3: High voltage Transformer
tank rupture is mitigated by much lower tank
stresses in a flexible tank (250kPa) compared to a
rigid tank (630kPa) [4].

Some typical considerations for flexible tank:


● Tank wall of round corners with weld joint
shifted from corners.
● Reinforcing tank corners and wall to bottom
base joints with inside plates / gussets
● Reinforcing the weld joints at the ends of
stiffeners by adding plates that spread the end
reaction loads and connecting the stiffeners to
adjacent walls
● Tank with flat bottom and flat cover.
● Welded Cover
Fig-2a: Flexible Tank [4] Fig-2b: Rigid Tank [4] ● Tank wall weld joints of full penetration with
ultrasonic testing.
Flexible tank solution is always better than a ● Cover anchoring to active part for maximum
pressure venting approach (traditional large- upward deflection.
volume expansion chambers) for reducing the ● Steel of lower yield stress and higher
static pressures developed. Studies show that elongation to get more flexibility.
even a large venting area of 1.0-1.5 m2 would ● Integral bushing turrets with extra
reduce the peak pressure by only 10 to 30 percent reinforcement at sides.
during an internal arcing fault. Such level of ● PRD with exit pipe to guide the oil directly to
reduction is insufficient to mitigate tank rupture risk the pit.
under normal circumstances. ● Reinforcing the ends of stiffeners by adding
plates that spread the end reaction loads.
● Strengthening throats (bushing turrets) and
7. 4.1.1a Flexible Tank design wall penetrations using reinforcing angles or
considerations and gusset plates
bracing
8. 4.1.1b Checking tank for rupture strength
Tank wall thickness shall be as thin as possible
without exceeding the yield strength of plate In future, customers may ask to prove the rupture
between stiffeners. Optimum balance is to be resistance of tanks. This is usually checked by non
achieved between stiffener rigidity and flexibility –linear static finite element analysis. A simplified
of un-supported side plate between stiffeners. solid (3D) model of the tank with actual thickness
and geometry of different parts, is used for getting
detailed stress analysis. Static simulation generally
gives more conservative results.
To find out the flexibility of tank, tank pressure is
increased and the volumetric flexibility is estimated
using static FEM. There are reported studies with
3D CAD model in ANSYS space creating a mid-
surface model [3] (in between shell model and
solid model with less nodes for faster calculation )
and using static pressure simulation Calculate arc
pressure for each step and use this as applied
pressure. Strain shall be less than ultimate

3-5
TRAFOTECH 2018 –Tenth International Conference on Transformers

permissible strain for tank material. Weakest parts 11. 4.2 Prevention methods
are kept at the top of the tank. To determine local
● Alternate insulating medium to oil- SF6 gas
pressure concentration, dynamic simulation will be
or esters
required (eg. ANSYS -LS DYNA) [6].
● Use of Generator circuit breakers with large
The rupture resistant transformer design will Generator Transformers
mitigate the risk of tank rupture thereby avoiding ● Reducing chances of a low impedance fault
insulating fluid spills and consequent fires. For through better insulation clearances at
faults, higher than the specification limits, vulnerable areas (bottom tail of bushings,
manufacturer should demonstrate by calculation line end of windings) inside tank and
the first rupture point is at tank cover [1]. insulation monitoring
● Fast acting protective relays and fast
9. 4.1.2 Conservator shutter
clearing breakers reduce the duration of
valve
arc, thereby preventing tank rupture.
The conservator shutter valve is installed on the oil
12. 4.2.1 Ester Fluids
pipe connecting the conservator to the tank .The
shutter valve allows oil flow in both directions. It Ester fluids (natural or synthetic) when used as
will close and initiate an alarm if the flow rate back alternate insulating fluid, may not reduce the
to tank exceeds a certain limit. This will prevent oil chances of tank rupture from internal arcs but will
feed from conservator to the oil spill through reduce the risk of fire initiation and propagation to
ruptured tank joint a great extent[7]. Esters fluids have higher flash
point, fire point and auto ignition temperatures
compared to mineral oils (approx. 2000C higher
each). It is the inflammable gases from the
insulating fluids that act as fuel for starting fire. The
gases generated due to high temperature of arc in
different insulating fluids will have varying content
of flammable or explosive elements .There are
lower and upper concentration of these
inflammable gases in air within which range the
mixture would be considered flammable. With
esters, a higher percent volume of gases is
Fig-4: Conservator shutter valve required before a fire can be ignited and
maintained .eg: with natural esters approx. 10
times more than with mineral oil (0.6% vs 9%) [7].
10. 4.1.3 Modern Rupture Disc
Heat release rate (amount of thermal energy
Fast acting depressurization systems have been released per unit time) of ester is less than that of
developed as an improvement over conventional mineral oil (eg: natural ester 1/8 of mineral oil)
PRD. It is claimed that such pressure relief devices giving better self-extinguishing properties [7].
can reduce the chances of tank rupture.
Depressurization set is activated within
milliseconds by the first dynamic pressure peak of 13. 4.2.2 Gas insulated
the shock wave, thereby releasing tank pressure Transformers
quickly and tripping the actuating relays fast there
Use of SF6 gas as dielectric insulation, instead of
by reducing the arc duration. The diameter of the
mineral oil, will eliminate the risk of transformer
Depressurization Set is sized individually based on
tank rupture during severe faults. SF6 gas is
the transformer power rating and the transformer
compressible and will result in only low pressure
function (Generation, Distribution or Transmission)
rises inside the transformer tank during internal
[6]
arcing faults. SF6 gas is nonflammable and even if
tank rupture were to occur, the release of SF6 gas
will not pose an explosion or fire risk. The main
4-5
TRAFOTECH 2018 –Tenth International Conference on Transformers

limitation for its application is due to its very high 15. CONCLUSION
cost and requirement of pressurized tanks [1]
16. Transformer tank rupture
14. 4.2.3 Generator Circuit due to internal arcing fault is
Breakers a complex problem.
Pressure rise in the
Generator circuit breakers (GCB) between
transformer is affected by
generator and transformer can prevent energy flow
both the expanding gas
from generator to a transformer internal fault
bubble generated by the
quickly. [8] This will reduce the energy flow through
arcing fault as well as the
arc and hence the internal pressure build up in
interaction of the
tank.
propagating pressure wave
4.2.4 Protection System with the transformer tank
Protective relays should sense the internal low and its internal components.
impedance faults quickly and activate the breakers Still we can minimize the
fast to reduce the arc duration time and there by severity of pressure rise by
the quantum of energy release. From the speed adopting flexible tank
and sensitivity angle, it is claimed that Restricted concepts which allows tank
Earth Fault Relay (REF) is superior to differential to absorb certain generated
relay and can clear the fault within half a cycle pressure and other
protecting up to 95 % of winding. High speed preventive measures.
protection relays with fast acting breaker (<2 Rupture resistant tank can
cycles) can limit arc energy released in to tank be considered to mitigate the
esp. at locations with high fault levels. [9] problems of oil spills and fire
hazards.

17. REFERENCES
[1] IEEE Std C 57.156-2016 –“Guide for Tank
Rupture Mitigation of Liquid Immersed Power
Transformers and Reactors”
[2] Working Group A2.33. “Guide for Transformer
Fire Safety Practices.” CIGRE 2013.
[3] M. Foata, J.B. Dastous, Power Transformer
Tank Rupture Prevention, 2010 Cigré Colloquim,
Paris.
[4] S. Brodeur, Y. Salmi, A. Collier, “A Flexible
Friend”, ABB Review, January 2016
[5] T. Kawamura et al., "Prevention of Tank
Rupture due to Internal Fault of Oil Filled
Transformers," Paper 12-02, CIGRÉ 1988
Session, Paris.
[6]Task force of IEEE Power Transformer
subcommittee, "Power Transformer Tank Rupture
and Mitigation”,IEEE PASVol24,No.4 October,2009
[7]George Frimpong, S.Page etc.; “Transformers
Transformed”, ABB Review No2, 2012

5-5
TRAFOTECH 2018 –Tenth International Conference on Transformers

[8] Prevention of Trank Rupture by Generator


CircuitBreakers”-B.Culver,K.Frohlich, L.Widenhorn,
ETEP Vol 6, No.1 January/February 1996
[9] Tom Rosenberg, Ilija Jankovic “Transformer
Tank Rupture – A Protection Engineer’s
Challenge”, 70th Annual Conference for Protective
Relay Engineers,2017

6-5

You might also like