Professional Documents
Culture Documents
1
Introduction
Circuit breaker is an electrical isolation equipment
Make or break a circuit either manually or by remote control
under normal conditions
Break a circuit automatically under fault conditions
Make a circuit either manually or by remote control under
fault conditions
Essentially consists of fixed and moving contacts /
electrodes
Remains closed under normal operation
Open after receiving trip command from
• User directly or by remote control
• Protection relays
2
Introduction ..
3
The Arc Phenomenon
After the contacts separation, the current continues to
flow due to arc struck between separated contacts.
Delays the current interruption process
Generates enormous heat which may cause damage to the
system or to the circuit breaker itself.
The main problem in a circuit breaker is to extinguish
the arc within the shortest possible time so that heat
generated by it may not reach a dangerous value.
The arc provides a low resistance path and
consequently the current in the circuit remains
uninterrupted so long as the arc persists.
During the arcing period, the current flowing between
the contacts depends upon the arc resistance.
4
Arc Extinguishment
High Resistance Method
Arc can extinguish with the increase in the arc resistance
Degree of ionisation— the arc resistance increases with
the decrease in the number of ionised particles between the
contacts
Cooling the arc
Removing the ionised particles
Length of the arc— the arc resistance increases with the
length of the arc
Increased separation of contacts
Cross-section of arc— the arc resistance increases with
the decrease in area of X-section of the arc.
Passing the arc through a narrow opening or by having smaller area
of contacts.
5
Arc Extinguishment ..
Current zero method
Applicable to AC systems only.
50Hz system have current zero crossing after every
10ms.
All modern high power AC CBs employ this method
for arc extinction.
Arc resistance is kept low until current crosses zero
where the arc extinguishes naturally.
Medium between the contacts still contains ions and electrons
Therefore, it has small dielectric strength which can easily
broken down by the rising contact voltage to the value known
as re-striking voltage.
If such a breakdown does occur, the arc will persist for
another half cycle . 6
Arc Extinguishment ..
Arc Voltage: The voltage that appears across the
contacts of the circuit breaker during the arcing
period.
Restriking voltage: Transient voltage that appears
across the contacts at or near current zero during
arcing period.
Also known as transient recovery voltage (TRV)
If the dielectric strength of the medium builds up more
rapidly than the restriking voltage, the arc fails to restrike and
the current will be interrupted.
Recovery voltage: It is the normal frequency (50 Hz)
rms voltage that appears across the contacts of the
circuit breaker after final arc extinction.
Approximately equal to the system voltage.
7
CB Operating Times
The operating time of a circuit breaker involves a
number of carefully defined time intervals, such as:
8
CB fluids
The basic function of a circuit
breaker is to insert an insulating
medium.
The fluid medium commonly used
in circuit breakers depends on the
type and rating of the breaker
Air at atmospheric pressure
Compressed air
Mineral oil
Sulfur hexafluoride (SF6)
Ultra-high vacuum
These fluids vary widely in their
relative dielectric strengths
9
Oil CBs
Earlier circuit breaker technology.
Insulating oil (e.g. transformer oil) is
used as an arc quenching medium.
The first oil circuit breakers were of
simple design
Switch put in a tank filled with mineral oil,
without any arc quenching device.
Then metal explosion pot was used.
Breaker was fitted with an insulating arcing
chamber through which the breaker contacts
moved.
The oil filled arcing chamber, fixes the arc
Increased pressure inside the arcing chamber
improved the cooling effects on the arc.
10
Oil CBs ..
Later, the design of the arcing
chamber was further improved
by pumping mechanisms, such
as cross jet explosion pot
A cross flow of oil was created,
giving extra cooling to the arc.
The gas due to arc exerts pressure on
the oil in the back passage.
Moving contact uncovers the arc
splitter ducts, fresh oil is forced
across the arc path.
The arc is driven sideways into the
arc splitters which increase the arc
length, causing arc extinction.
11
Oil CBs ..
A next step in the development of
oil circuit breakers was the low/
minimum oil circuit breaker.
The contacts and arcing chamber placed
into a porcelain insulator instead of in a
bulky metal tank.
Employs solid materials for insulation
purposes
Uses a small quantity of oil which is
just sufficient for arc extinction.
The oil behaves identically in bulk as
well as low oil circuit breaker.
By using suitable arc control devices,
the arc extinction can be further
facilitated.
12
Air Blast CB
Air is used as insulator in outdoor-type
substations and for HV transmission lines.
Air can also be used as extinguishing medium
for current interruption.
At atmospheric pressure, the interrupting
capability is limited to low voltage and
medium voltages only.
Compressed air can interrupt higher currents at
considerable higher-voltage levels due to high cooling
power of air at high pressure.
The arcing products are completely removed by the blast
whereas the oil deteriorates with successive operations.
The air blast circuit breakers are finding wide applications
in high voltage installations, typically around 110kV.
13
Air Blast CB ..
In cross-blast type CB, compressed air blows the arc
into a segmented arc-chute compartment.
Because the arc voltage increases with the arc length, this is
also called high-resistance interruption
In the axial-blast design, the arc is cooled in axial
direction by the airflow.
Because the arc voltage hardly increases this is called low-
resistance interruption
14
SF6 CB
SF6 gas has superior dielectric properties for arc
quenching.
Contacts are opened in a high pressure flow of SF6 gas
from reservoir to interruption chamber and an arc is struck
between them.
Conducting free electrons in the arc are rapidly captured
by the gas to form relatively immobile negative ions.
Loss of conducting electrons in the arc quickly builds up
enough insulation strength.
Developed for voltages up to 115 kV to 230 kV, power
ratings 10 MVA to 20 MVA.
Interruption time is less than 3 cycles.
Additional equipment is required to recondition SF6 after
each breaking operation.
15
Vacuum CB
Metallurgical developments made it possible to
manufacture gas-free electrodes.
Since vacuum offers the highest insulating strength, it
has far superior arc quenching properties than any
other medium.
Fats operation – interruption occurs on first zero-
crossing.
The production of arc is due to the ionisation of metal
ions and depends upon the material of contacts.
Arc extinguished quickly as metallic vapours, ions,
electronic diffuse quickly on metallic surfaces.
The arc extinction in a vacuum breaker occurs with a
short contact separation.
16
Vacuum CB ..
18
Analysis of Circuit Interruption..
Simplified form of fault current
𝑑
𝐸𝑚 sin(𝜔𝑡 + 𝛼) = 𝑅𝑖𝑓 + 𝐿 𝑖𝑓
𝑑𝑡
𝑅
𝐸𝑚 −𝐿 𝑡
𝑖𝑓 𝑡 = 𝑒 sin 𝛼 − 𝜃 + sin 𝜔𝑡 + ∅ − 𝜃
𝑍
𝑍 = 𝑅2 + 𝜔𝐿 2
𝜔𝐿
𝜃 = tan−1 𝑅
α is angle at switching
instant
1 𝐶
𝑣𝐶 = . 𝑣. . 𝐿𝐶 − cos 𝜔𝑛 𝑡 + 𝑘
𝐶 𝐿
𝑣𝐶 = 𝑣 − cos 𝜔𝑛 𝑡 + 𝑘
Initial Condition: vC=0, k=1
𝑣𝐶 = 𝑣 − cos 𝜔𝑛 𝑡 + 1
𝑣𝐶𝑚𝑎𝑥 = 2𝑣
20
Analysis of Circuit Interruption..
Upon the fault clearance by breaker:
Contacts are opened and the arc finally extinguishes at
some current zero.
The generator voltage v is suddenly applied to the
inductance and capacitance in series.
Transients are generated at natural frequency of LC circuit
1
𝑓𝑛 =
2𝜋 𝐿𝐶
The system losses cause the oscillations to decay fairly
rapidly but the initial overshoot increases the possibility of
arc re-striking the arc.
This transient rise in voltage is the restriking voltage
21
RRRV
RRRV is the rate of rise of restriking voltage, which
depends on
Recovery voltage – i.e. normal system voltage
• Magnitude can approximately rise to 2Em
fn – RRRV is high for high natural frequency
For a short-circuit occurring near the power station
bus-bars, C being small, the natural frequency can be
high.
Consequently, RRRV will attain a large value.
Thus the worst condition for a circuit breaker would be
that when the fault takes place near the bus-bars of terminal
power station.
22
Current Chopping
Phenomenon of current interruption
before the natural current zero.
In vacuum interrupters
High speed movement of contacts can be
obtained due to
• Low mass of breaker contacts
• Small separation requirement
Arc is to be interrupted at first zero-crossing within a half
cycle.
Arc usually tends to go out even before current zero due to
rapid dielectric recovery.
As a result, current can instantaneously drops to zero with
high di/dt.
23
Current Chopping
The problem can be more
severe in air blast CB due
to multiple chops
The powerful air-blast can
interrupt arc before actual
zero-crossing.
The prospective restriking voltage can be very high as
compared to the dielectric strength gained by the gap so that
the breaker restrikes.
Chop can again occurs due to deionizing force still in action.
The arc current this time is smaller than the previous case.
This induces a lower prospective voltage to re-ignite the arc.
Consequently, the final interruption of current takes place
after several chopping attempts.
24
Current Chopping
Interruption on non-zero current cause production of
high voltage transients across breaker contacts.
Transfer of inductive energy (Li2/2) to capacitance can
be approximated as
1 2 1 2
𝐿𝑖 = 𝐶𝑒 𝐿
is also known as surge
2 2 𝐶
𝐿 impedance or characteristic
𝑒=𝑖 impedance
𝐶
25
Practice Problem
50 Hz, 11 kV, 3-phase alternator with earthed neutral has a
reactance of 5 ohms per phase and is connected to a bus-bar
through a circuit breaker. The distributed capacitance upto circuit
breaker between phase and neutral in 0·01 μF. Determine
i. Peak re-striking voltage across the contacts of the breaker
2
= 2𝐸𝑚𝑎𝑥 =2× × 11 = 17.96𝑘𝑉
3
ii. Frequency of oscillations
𝑋𝐿 5 1
𝐿= = = 15.9𝑚𝐻 𝑓𝑛 = = 12.61𝑘𝐻𝑧
2𝜋𝑓 100𝜋 2𝜋 𝐿𝐶
iii. The average rate of rise of re-striking voltage upto the first
peak 1 1
𝑇𝑛 = = 12.61𝑘𝐻𝑧 = 79𝜇𝑠 𝑇𝑛 = 39.5𝜇𝑠
𝑓𝑛 2
𝑃𝑒𝑎𝑘 17.96𝑘𝑉
𝑅𝑅𝑅𝑉 = = = 453000 𝑘𝑉
𝑇𝑖𝑚𝑒 𝑡𝑜 𝑝𝑒𝑎𝑘 39.5𝜇𝑠
26
Practice Problem
In a short circuit test on a circuit breaker, the following
readings were obtained on single frequency transient:
i. Time to reach the peak re-striking voltage is 50μs
ii. The peak re-striking voltage, 100 kV
Determine the average RRRV and frequency of
oscillations.
𝑃𝑒𝑎𝑘 100𝑘𝑉
𝑅𝑅𝑅𝑉 = = = 2 × 106 𝑘𝑉
𝑇𝑖𝑚𝑒 𝑡𝑜 𝑝𝑒𝑎𝑘 50𝜇𝑠
27
Resistance Switching
To reduce the severity of the transient oscillations, a
resistance is connected across the contacts of the
circuit breaker.
After contact opening, part of arc current flows
through shunt resistance.
Decrease of arc current and an increase in the rate of de-
ionisation of the arc path.
Also reduce the di/dt of chopping current MOSA
Valve type
arrester
28
CB Ratings
Breaking capacity: The current (or MVA) that a circuit
breaker is capable of breaking at given recovery voltage under
specified conditions.
The prospective short-circuit current should not exceed the rated breaking
capacity.
Making Capacity: Current magnitude during the first cycle of
current wave after the CB closing.
Possibility of CB closing during short circuit always exists.
Therefore, making capacity should be equal to peak breaking capacity.
Approximate DC component = 0.8 × (Peak AC component)
• DC component dies away rapidly
• Typical decrement factor is 0·8 per cycle
Making capacity = 1.8 × (Peak AC component)
Short-time rating: It is the period for which the CB is able to
carry fault current while remaining closed.
Normal current rating: The current which the CB is capable
of carrying continuously under normal operation.
29
Practice Problem
A circuit breaker is rated as 1500 A, 1000 MVA, 33
kV, 3-second, 3-phase oil circuit breaker. Point out
i. Rated normal current 𝐼𝑅𝑎𝑡𝑒𝑑 = 1500𝐴