900 Series
Split Case Fire Pump Systems
MODEL 481
MODEL 483
FM UL
®
Built Per
N.F.P.A. 20
Pentair Water
Approved Listed
Horizontal Split Case Pump Features
page 4
Fire Pump Feature Selector
STANDARD OPTIONAL
Bronze fitted pump construction Ductile iron casings (available in selected 481
Bronze shaft sleeves & 485 sizes)
Bronze case wearing rings Right or left hand rotation
Dynamically balanced impellers Impeller wearing rings
Stainless steel impeller key Double row ball bearings on inboard side
Carbon steel shaft External by-pass line from casing to stuffing
Corrosion-resistant lantern rings* boxes
Bronze stuffing box bushings Formed steel drip-lip base (horizontal electric
Bronze glands driven units only)
Interwoven graphite-impregnated T.F.E. 15’ Suction lift test to verify performance at
packing rings 150% of rated flow
Cast integral bearing arms N.P.S.H. test
Regreasible ball bearings
Double row thrust bearing (outboard side)
Upper casing lifting lugs
Water slingers and grease seals
Hydrostatic and Certified Performance test**
Coupling guard on 481 & 485 models
Suction and discharge gauges with shut-off * Furnished when suction pressure is below
cocks 40 PSI
Automatic air release valve ** Test is performed with POSITIVE
Casing relief valve (electric driven units only) SUCTION PRESSURE
page 5
Jockey Pump Introduction
AP-900/Rev. E 6.98
NOTE: Aurora Pump reserves the right to make revisions to its products and their specifications, and to this bulletin and related information without notice.
ITY
SYSTEM
WEB: www.aurorapump.com
EMAIL: aurora_info@pentairpump.com
Pentair Water
SALES OFFICES IN ALL MAJOR CITIES AND COUNTRIES
Refer to “Pumps” in yellow pages of your phone directory for
your local Distributor
CURVA DE PERFORMANCE Y
DIMENSIONES
1000 G.P.M. 913 SERIES Section 913 Page 447
Date September 2009
DIESEL ENGINE DRIVE
Supersedes All Previous Editions
75 78%
(METERS of H 2O)
100 76%
100 PSI
74%
100
P.S.I.
1000
80
50 to
60
1500 120
40
P.S.I.
25
20
BHP
BHP FOR 120 PSI CURVE 150
100
BHP FOR 100 PSI CURVE 50
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000
L/S 20 40 60 80 100 120
M 3/HR 100 200 300 400
PC-168521
75 70%
(METERS of H 2O)
100
95 PSI
95
P.S.I.
50
80
1000 to
60 150
1500 P.S.I.
40
25
BHP
BHP FOR 150 PSI CURVE
20 160
120
80
BHP FOR 95 PSI CURVE
40
0
U.S. GPM 200 400 600 800 1000 1200 1400 1600 1800 2000
L/S 20 40 60 80 100 120
M 3/HR 100 200 300 400
PC-168522
AURORA MODELS 491 & 492 Section 913 Page 215
SINGLE STAGE FIRE PUMPS Date March 2009
CLARKE JU6H-UF30/32/34, -UF50/52/54/58/60/62/68/84, Supersedes Section 913 Page 215
-UFDO/D2, -UFG8, -UFMO/M2/M8 Dated April 2005
DIESEL DRIVE
C
WIDTH
(SEE NOTE 6)
CP
1/2 NPT
ZZ NPT
W 45.75 (1162) FAR SIDE
GUARD
YY X
SEE NOTE 4 SUCTION DISCHARGE
S Z
HD
6 (152)
K K K
STANDARD * OPTIONAL OPTIONAL
125# SUCTION AND 125# SUCTION FLANGE, 250# SUCTION AND ENGINE MODEL C WIDTH
DISCHARGE FLANGES 250# DISCHARGE FLANGE DISCHARGE FLANGES JU6H-UF30 61.06 29.64
PUMP SIZE -UF32, -UF34 (1551) (753)
SUCTION
-UF50, -UF52
DISCH MODEL CASE S W X Z CP YY ZZ HB HD HF1 HY
BORE -UF54, -UF58
-UFDO, -UFD2
4 491 14C 6 6.88 17.63 13 8.38 31.69 15.25 3/4 98 20 44 22.38
-UFG8, -UFM0
(175) (448) (330) (213) (805) (387) (2489) (508) (1118) (568) -UFM2, -UFM8
4 492 18 5 9.5 18.38 14 9.5 33.25 14 3/4 98 22 44 21.63 JU6H-UF60 62.80 31.74
(241) (467) (356) (241) (845) (356) (2489) (559) (1118) (549) -UF62, -UF68 (1595) (806)
5 491 14A 8 8.25 17.63 13.5 9.75 31.69 17.25 1 98 23 44 22.38 -UF84
(210) (448) (343) (248) (805) (438) (2489) (584) (1118) (568)
5 491 18A 8 8.13 18.88 15 10.63 33.38 18.75 1 98 23 44 21.13
(207) (480) (381) (270) (848) (476) (2489) (584) (1118) (537)
5 492 18 6 10 21 14 10 37.13 14 1 98 23 44 19
(254) (533) (356) (254) (943) (356) (2489) (584) (1118) (483)
6 491 12A 6 6.88 16.63 20.5 7.13 29.69 14 1 98 23 44 13.38
(175) (422) (521) (181) (754) (356) (2489) (584) (1118) (340)
6 491 14C 10 9.38 20.13 13.25 10 35.88 18 1 98 25 44 19.88
NOTES
(238) (511) (337) (254) (911) (457) (2489) (635) (1118) (505) 1. All dimensions are in inches (mm).
6 491 18C 10 9.38 20.13 16 11.75 35.88 20 1 98 25 44 19.88 2. Dimensions may vary ± 3/8" (9).
(238) (511) (406) (298) (911) (508) (2489) (635) (1118) (505) 3. Not for construction purposes unless certified.
6 492 15 8 8.75 22.5 15.5 8.75 40.25 15 1 98 23 44 17.5 4. The drive shaft is not designed to operate at 0° angle.
(222) (572) (394) (222) (1022) (381) (2489) (584) (1118) (445) The engine crankshaft is to be parallel offset .35 ± .18
8 491 14A 12 10.75 20.5 16 10.75 36.63 22 1 98 28 44 19.5 above the pump shaft. The engine crankshaft may be
(273) (521) (406) (273) (930) (559) (2489) (711) (1118) (495) parallel offset from the pump shaft .35 right or left.
8 491 18A 12 10.75 23.75 16 12.5 41.5 22 1 98 28 44 16.25 Refer to the engine manual for alignment instructions.
(273) (603) (406) (318) (1054) (559) (2489) (711) (1118) (413) 5. Pump suction and discharge flanges are ANSI Standard
8 492 15 10 9.25 22.5 17 9.25 40.25 17 1 98 25 44 17.5 flat face.
(235) (572) (432) (235) (1022) (432) (2489) (635) (1118) (445) 6. Refer to individual engine dimension print for reference
point used to determine “C” dimension.
7. Left hand (CCW) rotation not available.
ENGINE EQUIPMENT
EQUIPMENT STANDARD OPTIONAL
Air Cleaner Direct Mounted, Washable, Indoor Service with Drip Shield Disposable, Drip Proof, Indoor Service Outdoor Type, Single or
Two Stage
Alternator 12V-DC, 42 Amps with Poly-Vee Belt and Guard 24V-DC, 40 Amps with Poly-Vee Belt and Guard
Exhaust Protection Metal Guards on Manifolds and Turbocharger
Coupling Bare Flywheel Listed Driveshaft and Guard, UFD0/D2/30/32/34 – CDS20-S1;
UFG8/ABL8/ABL0/ABL2/M8/M0/M2/58/50/52/54/AB76/68/60/62/AA
Q8/AARG/AAPG/84/S0 – CDS30-S1
E h
Exhaust Flex
Fl Connection
C i S i l
Stainless S
Steell Fl
Flex, 1150#
0# ANSI Fl
Flangedd Connection,
C i 5”” S i l
Stainless S
Steell Fl
Flex, 1150#
0# ANSI Fl
Flangedd Connection,
C i 6”
Flywheel Housing SAE #3
Flywheel Power Take Off 11.5” SAE Industrial Flywheel Connection
Fuel Connections Fire Resistant, Flexible, USA Coast Guard Approved, Supply and Stainless Steel, Braided, cUL Listed, Supply and Return Lines
Return Lines
Fuel Filter Primary Filter with Priming Pump
Fuel Injection System Stanadyne Direct Injection
Engine Heater 115V-AC, 1360 Watt 230V-AC, 1360 Watt
G
Governor, S
Speed
d C t t Speed,
Constant S d Mechanical
M h i l
Heat Exchanger Tube and Shell Type, 60 PSI (4 BAR), NPT(F) Connections –
Sea/Salt Water Compatible
Instrument Panel English and Metric, Tachometer, Hourmeter, Water Temperature,
Oil Pressure and Two (2) Voltmeters
Junction Box Integral with Instrument Panel; For DC Wiring Interconnection to
Engine Controller
Lube Oil Cooler Engine Water Cooled, Plate Type
Lube Oil Filter Full Flow with By-Pass Valve
Lube Oil Pump Gear Driven, Gear Type
Manual Start Control On Instrument Panel with Control Position Warning Light
Overspeed Control Electronic with Reset and Test on Instrument Panel
Raw Water Solenoid Operation Automatic from Fire Pump Controller and from Engine Instrument
Panel
Run – Stop Control On Instrument Panel with Control Position Warning Light
Run Solenoid 12V-DC Energized to Run 12V-DC Energized to Stop; 24V-DC Energized to Run; 24V-DC
Energized to Stop
St t
Starters T (2) 12V-DC
Two 12V DC T (2) 24V-DC
Two 24V DC
Throttle Control Adjustable Speed Control, Tamper Proof
Water Pump Centrifugal Type, Poly-Vee Belt Drive with Guard
Abbreviations :DC – Direct Current, AC – Alternating Current, SAE – Society of Automotive Engineers, NPT(F) – National Pipe Tapered Thread (Female)
C13556 revK Specifications and information contained in this brochure subject to change without notice. .
08MAY12 Page 2 of 11
Page 3 of 11
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O Data)
USA Produced
Basic Engine Description
Engine Manufacturer John Deere Co.
Ignition Type Compression (Diesel)
Number of Cylinders 6
Bore and Stroke - in (mm) 4.19 (106) X 5 (127)
Displacement - in³ (L) 415 (6.8)
Compression Ratio 17.0:1
Valves per cylinder
Intake 1
Exhaust 1
Combustion System Direct Injection
Engine Type In-Line, 4 Stroke Cycle
Fuel Management Control Mechanical, Rotary Pump
Firing Order (CW Rotation) 1-5-3-6-2-4
Aspiration Turbocharged
Charge Air Cooling Type None
Rotation, viewed from front of engine, Clockwise (CW) Standard
Engine Crankcase Vent System Open
Installation Drawing D536
Weight - lb (kg) 1657 (752)
NOTE: This engine is intended for indoor installation or in a weatherproof enclosure. 1Engine H 2O temperature is
dependent on raw water temperature and flow. 2Positive and Negative Cables Combined Length.
Page 1 of 2
Page 4 of 11
JU6H-UF52
INSTALLATION & OPERATION DATA (I&O Data)
USA Produced
Exhaust System 2350 2600
Exhaust Flow - ft.³/min (m³/min) 1359 (38.5) 1496 (42.4)
Exhaust Temperature - °F (°C) 977 (525) 953 (512)
Maximum Allowable Back Pressure - in H 20 (kPa) 30 (7.5) 30 (7.5)
Minimum Exhaust Pipe Dia. - in (mm) [3] 5 (127) 5 (127)
Lubrication System
Oil Pressure - normal - lb/in² (kPa) 40 (276) - 60 (414)
Low Oil Pressure Alarm Switch - lb/in² (kPa) 20 (138)
In Pan Oil Temperature - °F (°C) 220 (104) - 245 (118)
Total Oil Capacity with Filter - qt (L) 21.1 (20)
Page 2 of 2
C133697 Rev B
MD 12FEB12
Page 5 of 11
CLARKE
Fire Protection Products
JU4H & JU6H ENGINE MODELS
ENGINE MATERIALS AND CONSTRUCTION
Air Cleaner Valves
Type…………..………….. .. Indoor Usage Only Type…….. …………………Poppet
Oiled Fabric Pleats Arrangement………… ……Overhead Valve
Material……..…..…….…… Surgical Cotton Number/Cylinder………… 1 intake
Aluminum Mesh 1 exhaust
Operating Mechanism……Mechanical Rocker Arm
Air Cleaner - Optional Type of Lifter…………….. Large Head
Type…………………………Canister Valve Seat Insert…………Replaceable
Material………………………Pleated Paper
Housing………………..……Enclosed Fuel Pump
Type…………………………Diaphragm
Camshaft Drive……………………… Cam Lobe
Material………….…………. Cast Iron
Chill Hardened Heat Exchanger (USA)
Location…………...….……. In Block Type………………………… Tube & Shell
Drive……………….……….. Gear, Spur Materials
Type of Cam…………..…... Ground Tube& Headers……………Copper
Shell…………………………Copper
Charge Air Cooler (JU6H-60,62,68,74,84, ADK0, Electrode…………………… Zinc
AD58, ADNG, ADN0, ADQ0, ADR0, AAQ8, AARG,
ADP8, ADP0, ADT0, AD88, ADR8, AD98, ADS0,
ADW8, ADX8, AD98 only)
Type………………….Raw Water Cooled
Heat Exchanger (UK)
Materials (in contact with raw water) Type………………………… Tube & Bundle
Tubes…… ………………… 90/10 CU/NI Materials
Headers ………………… 36500 Muntz Tube& Headers……………Copper
Covers ………………… 83600 Red Brass Shell………………. Aluminum
Plumbing ………………… 316 Stainless Steel/ Brass
90/10 Silicone
Coolant Pump Injection Pump
Type……….…………………Centrifugal Type………………………. Rotary
Drive……………………………Poly Vee Belt Drive……………………… Gear
Crankshaft Piston
Material………………………Forged Steel Type and Material…………Aluminum Alloy with Reinforced
Type of Balance……………Dynamic Top Ring Groove
Cooling…………………… Oil Jet Spray
Cylinder Block
Type…………………………One Piece with Piston Pin
Non-Siamese Cylinders Type…………………………
Full Floating - Offset
Material………………………Annealed Gray Iron
6 Cylinders
Four Cycle
Lean Burn
Turbocharged
Notes:
1) 6068TF220 Base Engine Model manufactured by John Deere Corporation.
For John Deere Emissions Conformance to EPA 40 CFR Part 60 see Page 2 of 2.
2) The Emission Warranty for this engine is provided directly to the owner
by John Deere Corporation. A copy of the John Deere Emission Warranty can
be found in the Clarke Operation and Maintenance Manual.
3) Engines are rated at standard conditions of 29.61in. (7521 mm) Hg barometer
and 77°F (25° C) inlet air temperature. (SAE J1349)
4) PM is a measure of total particulate matter, including PM 10 .
CLARKE
FIRE PROTECTION PRODUCTS
3133 EAST KEMPER ROAD
C131852 REV.C CINCINNATI, OH 45241
01NOV 07 KRW PAGE 1 OF 2
Page 9 of 11
John Deere Power Systems
3801 W. Ridgeway Ave., PO Box 5100
Waterloo, Iowa USA 50704-5100
31 October 2007
Subject: Fire Pump Ratings – Conformance to EPA 40 CFR Part 60 (NSPS requirements)
All John Deere stationary fire pump engines conform to the requirements of 40 CFR Part 60. All such
engines include an emission label, stating the engine conforms to the requirements of 40 CFR Part 60. An
example of the emission label is show below:
This label applies to all of the following engine models, sold to Clarke Fire Protection, for use in stationary
fire pump applications:
All engines conforming to 40 CFR Part 60 (identified by emission label, as shown above) are covered under
the emissions warranty of 40 CFR Part 89.
Sincerely,
Kyle J. Tingle
Regional Sales Manager, JDPS
Page 2 of 2
Page 10 of 11
CLARKE
www.clarkefire.com Fire Protection Products
JU6H-UF52
FIRE PUMP DRIVER
NOISE DATA
2350 210 106.6 67.0 68.4 81.9 87.9 93.0 99.0 102.2 100.9 92.4 85.9
2600 210 108.6 68.3 69.4 84.8 92.3 93.7 100.5 103.7 103.5 94.6 88.5
2350 210
To Be Provided Later
2600 210
* Values above are provided at 3.3ft (1m) from engine block and do not include the raw exhaust noise.
** Values above are provided at 3.3ft (1m), 90 o horizontal, from a vertical exhaust outlet and does not include noise created mechanically
by the engine
The above data reflects values for a typical engine of this model, speed and power in a free-field environment.
Installation specifics such as background noise level and amplification of noise levels from reflecting off of surrounding objects, will affect
the overall noise levels observed. As a result of this, Clarke makes no guarantees to the above levels in an actual installation.
C131782 revA
23MAR06
Page 11 of 11
SISTEMA DE CONTROL Y
AUTOMATIZACIÓN DE LA BOMBA
PRINCIPAL SEGÚN NFPA20 UL/FM
DIESEL
MARCA ),5(752/
Fire Pump Controllers for
Business Critical Continuity ™
Battery Chargers
The controllers are supplied with two fully au-
tomatic, 200 amp hour, 4 step battery chargers.
The chargers feature Switching Technology and Operator Interface
10Adc Pulse-Width Modulated Output Current. The fire pump controllers feature an opera-
The 4 step charging cycle is as follows: tor interface with user keypad. The interface
Step 1 - Qualification Stage monitors and displays motor operating condi-
During this stage, the battery charger tions, including all alarms, events, and pressure
checks the batteries to insure they can conditions. All alarms, events, and pressure
accept a fast charge. It also checks conditions are displayed with a time and date
for missing or defective batteries. If stamp. The display is a 128x64 Backlit LED ca-
a missing or defective battery is de- pable of customized graphics and Cyrillic type
tected, a fault will be given. character display. The display and interface are
Step 2 - Fast Charge Stage NEMA rated for Type 2, 3R, 4, 4X, and 12 pro-
Charges the batteries until they reach tection and is fully accessible without opening
peak voltage. the controller door. The user interface utilizes
Step 3 - Bulk Charge Stage multiple levels of password protection for sys-
Charges the batteries at a constant tem security. A minimum of 3 password levels
potential of peak voltage until current are provided.
reaches 500mA.
Step 4 - Float Charge Stage
Trickle charges the batteries to main-
tain peak potential.
Standard features include:
Approvals • AC Line and Battery Circuit Breakers
Firetrol fire pump controllers are listed by Un- • Manual-Off-Auto Selector Switch
• Manual Test Push-Button
derwriters’ Laboratories, Inc., in accordance • Two (2) Manual Crank Push-Buttons
with UL218, Standard for Fire Pump Controllers, • Two (2) 10 Amp Battery Chargers with 4 stage charging
cycle, selectable AC voltage (110/220), selectable DC
CSA, Standard for Industrial Control Equipment, voltage (12/24) and selectable battery type (Lead Acid,
Ni-Cad 9/18 Cell, Ni-Cad 10/20 Cell
and approved by Factory Mutual. They are • Minimum Run Timer/Off Delay Timer
built to meet or exceed the requirements of • Programmable Daylight Saving Time Option
• Weekly Test Timer
the approving authorities as well as NEMA and • Engine Run Time Meter
the latest editions of NFPA 20, Installation of • Digital Pressure Display
• Solid State Pressure Transducer
Centrifugal Fire Pumps, and NFPA 70, National • Door mounted display/interface panel featuring a 128 x
64 pixel backlit LED Graphical Display, Membrane Type
Electrical Code. User Control Push-buttons and easy to read LED Indica-
tors for:
• AC POWER AVAILABLE
• ALARM
• MAIN SWITCH IN AUTO
• MAIN SWITCH IN MANUAL
• SYSTEM PRESSURE LOW
• ENGINE RUNNING
• ENGINE FAIL TO START
• ENGINE TEMPERATURE HIGH
• ENGINE OIL PRESSURE LOW
• ENGINE OVERSPEED
• ENGINE ALTERNATE ECM
• ENGINE FUEL INJECTOR MALFUNCTION
Digital Status/Alarm Messages • FUEL LEVEL LOW
The digital display indicates text messages for • AUTOMATIC SHUTDOWN DISABLED
• CHARGER MALFUNCTION
the stats and alarm conditions of: • BATTERY #1 TROUBLE
• BATTERY #2 TROUBLE
• Engine Run • Sequential Start Time • USB Host Controller and Port
• Minimum Run Time • Crank/Rest Time Cycle • Data Log
• Event Log (3000 Events)
/ Off Delay Time • Remote Start • Simultaneous Display of Battery Voltages, Charging
Rates, AC Volts, System Pressure and Alarm Messages
• Engine Fail to Start • System Battery Low • Disk Error message
• Low Suction Pressure• Manual Engine Crank • Disk Near Full message
• Pressure Error message
• Drive Not Installed • Fail To Start message
• Disk Error • Low Suction Pressure message
• Crank Cycle Status Indication (Displays Cranking Bat-
• Disk Near Full tery, Number of Starting Attempts and Crank/Rest Time
Remaining
• Pressure Error • 300 psi (20.7 bar) wet parts (solid state pressure trans-
ducer, solenoid valve, plumbing) for fresh water applica-
tions
The Sequential Start Timer and Minimum Run • NEMA Type 2 enclosure
Timer/Off Delay Times are displayed as numeric • Suitable for use as Service Equipment
• Each standard controller comes with user configurable
values reflecting the value of the remaining options for:
• AC Power Loss Start • Interlock Alarm
time. •Low Pressure Audible • Low Suction Pressure
• Main Switch Mis-Set • Manual Test
• Pump Run Alarm • Remote Start
• User Defined Input • Weekly Test Setup
• Low Pump Room Temp • Low Reservoir
• Relief Valve Open • High Fuel Level
• High Reservoir
LED Visual Indicators Event Recording
LED indicators, visible with the door closed, Memory - The controller records all opera-
indicate: tional and alarm events to system memory. All
• AC Power Available • Alarm • Main Sw. in events are time and date stamped and include
Auto • Main Sw. in Manual • System Pressure an index number. The system memory has the
Low • Engine Running • Engine Fail to Start capability of storing 3000 events and allows
• Engine Temperature High • Engine Oil Pres- the user access to the event log via the user in-
sure Low • Engine Overspeed• Engine Alter- terface. The user can scroll through the stored
nate ECM • Engine Fuel Injector Malfunction • messages in groups of 1 or 10.
Fuel Level Low • Automatic Shutdown Disabled
• Charger Malfunction • Battery #1 Trouble USB Host Controller
• Battery #2 Trouble The controller is equipped with a built-in USB
Host Controller. A USB port capable of accept-
Data Logging ing a USB Flash Memory Disk is provided. The
The user interface monitors the system controller saves all operational and alarm events
and logs the following data: to the flash memory on a daily basis. Each saved
• Number Calls/Starts • Engine Total Run event is time and date stamped. The total
amount of historical data saved depends on
Time • Last Run Time • Controller Power On
the size of the flash disk utilized. The operator
Time • Last Start • Minimum System Pres-
can save settings and values to the flash disk on
sure • Maximum System Pressure • Last High
demand via the user interface.
Temperature • Last Low Oil Pressure • Last
Engine Overspeed • Last Low Fuel Level •
Last Charger Fail • Last Battery Trouble • Bat-
tery #1 Volts • Battery #2 Volts • Batter #1 USB Host Port
Amps • Battery #2 Amps and Flash Disk
CB1100-50
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
'iretrol Brand Products
Cary
North Carolina 21 6SA
Phone 1 0 200
'aY 1 0 20
www.firetrol.com
FTA1100 Fire Pump Controllers for
Business-Critical Continuity
Diesel Engine Fire Pump Controllers
Product Description
PD1100-50
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
'iretrol Brand Products
Cary
North Carolina 21 6SA
Phone 1 0 200
'aY 1 0 20
www.firetrol.com
SISTEMA DE PRESURIZACIÓN
SEGÚN NFPA20 UL/FM
BOMBA JOCKEY
Flow
Models GPM
Series HP Range
PVM/PVMI/PVMX 2 1/2 – 5 1 – 20
PVM/PVMI/PVMX 4 1/2 – 7.5 3 – 40
PVM/PVMI/PVMX 8 3/4 – 15 5 – 65
PVM/PVMI/PVMX 16 5 – 25 8 – 115
PVM 32 3 – 40 15 – 215
PSI
250 18 Stage, 5 HP
350 800
17 Stage, 5 HP
16 Stage, 5 HP
700
300 15 Stage, 5 HP
200
14 Stage, 5 HP
600
13 Stage, 3 HP
250
12 Stage, 3 HP
500 11 Stage, 3 HP
150
200 10 Stage, 3 HP
PSI
9 Stage, 3 HP
400
150
100
300
100
200
50
50
100
0 0 0
0 2 4 6 8 10 12 14 16 18
0.0 0.4 0.8 1.2 1.6 2.0 2.4 2.8 3.2 3.6 4.0
3
TABLE OF CONTENTS CONFIRM THAT YOU
Safety Instructions..............................................................2 HAVE THE RIGHT PUMP
Applications and Operating Ranges................................2-4
Installation.........................................................................5
Electrical ........................................................................6-7
PVM_2-30/2
Aurora Vertical
Operation.......................................................................7-8 Multistage Pump
Maintenance ................................................................9-12 Material Code (SS only)
Troubleshooting Guide....................................................13 I = all wetted surfaces 304SS;
Repair Parts ................................................................14-17 X = all wetted surfaces 316SS
Nominal flow rate in m3/hr
Carefully read and follow all safety instructions (multiply by 4.4 to get GPM)
in this manual or on pump. Number of stages ( 10)
Number of impellers - only used if pump
This is the safety-alert. When you see this symbol on has fewer impellers than chambers (stages)
your pump or in this manual, look for one of the
following signal words and be alert to the potential for
personal injury. MODEL # PART # MFG. DATE
warns about hazards that can cause serious FIGURE 1 - Model Plate Information
personal injury, death or major property damage if ignored.
2
420
Foundation
390
360 Foundation should be concrete or a similarly rigid
330
foundation to provide a secure, stable mounting base for
the pump.
300
270 Secure pump to foundation using all bolt holes. Refer to
Figures 2 and 3 for bolt plate dimensions. Be sure that all
Pressure in PSI
240
210 four pads on the base are properly supported.
180 Shim pump base to make sure that pump is level.
150
120
Piping
90 Explosion and burn hazard. Do not run
60 pump with discharge valve closed; the water in the pump
30 may boil, with risk of explosion and steam burns to
0 0 to100 120 140 160 180 200 220 240 260 280
anyone near. If there is any danger of the pump running
212 250
against a closed discharge valve, install a pressure relief or
bypass valve in the discharge pipe to allow for minimum
Temperature in Degrees F 3355 1298
liquid flow through the pump. Minimum liquid flow
through the pump is needed for cooling and lubrication of
FIGURE 4 - Maximum Permissible Operating Pressure the pump (See Table IV). Run the bypass/relief valve and
discharge pipe to a floor drain or a tank for collection.
TABLE III – Permissible Operating Pressures Suction pipe should be adequately sized (See Table V) and
PVM2-30/2 to PVM2-180 run as straight and as short as possible to keep friction
PVM4-20/1 to PVM4-160 losses to a minimum. Pipes, valves, and fittings must have a
PVM8-20/1 to PVM8-160 pressure rating equal to or greater than the maximum
PVM16-30/2 to PVM16-120 system pressure.
TABLE IV – Minimum Pumping Rates
Liquid Temperature
Maximum Inlet Type +5° F to +250° F
Model Number Pressure (PSI)
PVM2 1 GPM
30/2 - 60 145 PVM4 2 GPM
PVM2
70 - 180 220
PVM8 4 GPM
20/1 - 20 90
PVM16 8 GPM
PVM4 30 - 80/7 145
80 - 160 220
20/1 - 40 90 TABLE V – Minimum Suction Pipe Sizes
PVM8
50 - 160 145 Type Pipe Size
30/2 - 30 90 PVM2 1-1/4” Nominal Diameter, Schedule 40 Pipe
PVM16
40 - 120 145 PVM4 1-1/4” Nominal Diameter, Schedule 40 Pipe
PVM8 2” Nominal Diameter, Schedule 40 Pipe
INSTALLATION PVM16 2” Nominal Diameter, Schedule 40 Pipe
Hazardous voltage. Voltage can shock, burn, Pressure check the discharge piping as required by codes or
or cause death. Ground pump motor correctly before local regulations.
connecting to power supply, per article 250-80 of the
“Inlet” and “Outlet” are marked on the pump base to show
National Electrical Code (NEC) in the U.S., or the Canadian
the direction of the liquid flow through the pump.
Electrical Code (CEC), as applicable.
Install anti-vibration mountings on either side of the pump
Location if a minimum noise level is desired.
Locate pump in a dry, well-ventilated area, not subject to
freezing or extreme variations in temperature.
Mount pump a minimum of 6” from any obstruction or hot
surface. Install the pump with the motor shaft vertical.
Make sure that an adequate supply of cool air reaches the
motor cooling fan. Maximum ambient air temperature is
104° F (40° C).
For open systems requiring suction lift, locate the pump as
close to the water source as possible.
5
SISTEMA DE CONTROL Y
AUTOMATIZACIÓN DE LA BOMBA
JOCKEY SEGÚN NFPA20 UL/FM
MARCA TORNATECH
PROYECTO
O: ______________________________________
CLIENTE: _
________________________________________
INGENIERO
O: _______
_______________ ________________
MARCA DE LA BOMB
BA: ___________________________
MODE
M ELO: JP3
AR
RRANQ
QUE A
A TENSSION PLENA
A
CONT
C ROLA
ADOR D
DE BO
OMBA AS JOC
CKEY
DOCU
UMEN
NTOS Y
Y DIBUJOS DE PR
RESEN
NTACION
CON
NTENIDO:
‐ PANFLEETO DE CARACTERISTTICAS
‐ DIBUJO
OS DE DIMEENSION
‐ ESQUEMMAS ELECTTRICOS
‐ CONEXIIONES DE C
CAMPO
NOTTA: Los dibujjos y descrip
pciones inclu
uidos en este paquete dde presentacción, son para controlad dores
estándares y pueden variar si el controlador es fabbricado siguiiendo especcificaciones eespeciales o
o con
opciones adicionnales.
N.Y.C. JP
MODELO
APPROVED
Controlador de Bombas de
Mantenimiento Jockey
Arranque Directo a Tensión Plena,
Basado en Micro-Procesadores OPCIONAL
(Patente Pendiente)
CARACTERISTICAS PRINCIPALES:
• Puesta en marcha y en operación muy fáciles y rápidas
• Gabinete NEMA 2
• Basado en lógica de micro-procesadores
• Indicación de presiones del sistema
• Transductor de presión
• Protección del motor sin fusibles
• Temperaturas límites de
operación: 41˚F a 122˚F (5˚C a 50˚C)
Los Controladores de Bombas de
Mantenimiento de Presión Jockey, modelo JP,
están diseñados específicamente para
mantener la presión de agua deseada en el
sistema contra incendio en el que están
instalados. La instalación de una bomba de
ajuste, previene los arranques innecesarios
de la bomba contra incendio debido a fugas
de agua por goteo
2
6
3
5
Tornatech Inc. USA Sales Office Tornatech Pte Ltd. Tornatech S.P.R.L. Tornatech Fz-Llc.
Derechos reservados. Impreso en Canada
7075, Place Robert-Joncas, 9578, Atchison Court, Paya Ubi Industrial Park, Avenue Sabin 3, P.O. Box 502221,
Suite # 132, Cincinnati, Ohio, 51 Ubi 1 Avenue, 1300 Wavre, Dubai, UAE
Sujeto a cambios sin previo aviso.
Montreal, Canada 45069 U.S.A. Unit # 01-18, Belgium Tel.: + 971 50 8574639
H4M 2Z2 Tel.: + 1 513 307 6766 Singapore 408933 Tel.: + 32 (0) 10 84 40 01
JP-BRO-001/S Rev.8
Tel.: + 1 514 334 0523 Fax: + 1 513 759 0509 Tel.: + 65 6844 3285 Fax: + 32 (0) 10 24 75 05
+ 1 800 363 8448 + 65 6844 3917
Fax: + 1 514 334 5448 Fax: + 65 6844 8549
tornatech.com info@tornatech.com
tornatech.com
ACCESORIOS
AURORA FIRE PUMPS Section 916 Page 205
OPTION 79 - MAIN RELIEF VALVE Date June 2007
Supersedes Section 916 Page 205
OPTION 80 - WASTE CONE Dated June 2002
"A" MAIN RELIEF VALVE INLET SIZE "A" MAIN RELIEF VALVE INLET SIZE
C F
B E
Y Y
WASTE CONE WASTE CONE
NOTES:
1. All dimensions are in inches (mm) and may vary ± 1/4
(6). 4. Relief valve discharge is intended to be piped to waste.
2. Valves are available with inlet flange ratings of 125# or Refer to factory if discharge is to be piped to a line
250#. All waste cones have 125# flange ratings. where back pressure is present.
3. Dimensions for conventional relief valves are not affected 5. Maximum operating pressure for valves rated for 125# is
by flange rating. 175 PSI.
6. Maximum operating pressure for valves rated for 250# is
Pentair Water
Section 916 Page 262 AURORA FIRE PUMPS
Date August 2011 EXHAUST FLEX CONNECTORS
Supersedes Section 916 Page 262
Dated June 2007
MUFFLER FLEX
CONNECTION CONNECTOR
ENGINE MODEL SIZE STYLE
CATERPILLAR ANSI FLANGE
3406C 6" FLANGED B BY AURORA
3412C, 18 8" FLANGED B FLEX CONNECTOR
CLARKE FIRE PROTECTION BY DIESEL ENGINE
JU4H-UF10, -UF12, -UF14, -UF20, -UF22, -UF24, MANUFACTURER
3" NPT A
-UFAB26, -UFAEA0, -UFAEE8, -UFAEF2
JU4H-UF30, -UF32, -UF34, -UF40, -UF50, -UF52,
-UF54, -UFH0, -UFH2, -UFH8, -UFADJG, -UFADJ2, STYLE A
-UFADJ8, -UFADP0, -UFADR0, -UFADW8, -UFADY8, 4" FLANGED B
-UFAD4G, -UFAD5G
JU4R-UF09, -UF11, -UF13, -UF19, -UF21, -UF23,
-UFAEA9, -UFAEE7, -UFAEF1 3" NPT A
JU4R-UF40, -UF49, -UF51, -UF53 4" FLANGED B
JU6H-UF30, -UF32, -UF34, -UF50, -UF52, -UF54, FLANGE TO FIT
-UF58, -UF60, -UF62, -UF68, -UF84, -UFAAPG, DIESEL ENGINE
-UFAAQ8, -UFAARG, -UFAAS0, -UFAB76, -UFABL0, 5" FLANGED B EXHAUST OUTLET
-UFABL8, -UFD0, -UFD2, -UFG8, -UFM0, -UFM2,
-UFM8
JU6H-UFAD58, -UFAD88, -UFADM0, -UFADM8, 5" FLANGED B STYLE B*
-UFADN0, -UFADNG, -UFADP8
JU6H-UFAD98, -UFADP0, -UFADQ0, -UFADR0,
-UFADR8, -UFADS0, -UFADS8, -UFADT0, -UFADW8, 6" FLANGED B *FLANGED FLEX CONNECTOR PROVIDED BY DIESEL
-UFADX8 ENGINE MANUFACTURER. NO ADDITIONAL FLEX
JW6H-UF30, -UF40, -UF48 5" FLANGED B
CONNECTOR
F OR ADAPTOR FITTING IS REQUIRED OR
JW6H-UF50, -UF58, -UF60, -UFAAM8, -UFAA80,
-UFADD0, -UFADF0, -UFADJ0, -UFAD70, -UFAD80, 6" FLANGED B PROVIDED BY AURORA.
-UFH8
JX6H SERIES 8" FLANGED B
DP6H SERIES 6" FLANGED B
DQ6H SERIES 6" FLANGED B
DT2H SERIES 6" FLANGED B
CUMMINS
CFP 33, 7E 3" NPT A
CFP 83, 5E, 59, 9E 4" FLANGED B
CFP 11E 5" FLANGED B
CFP 15E, 23E, 30E 6" FLANGED B
DEUTZ
DFP4 2011 3" NPT A
DFP4 2012 4" FLANGED B
DFP6 SERIES 6" FLANGED B
A DIA.
Pentair Water
Section 916 Page 256 AURORA FIRE PUMPS
Date April 2009 SINGLE WALL FUEL TANKS WITH FITTINGS
Supersedes Section 916 Page 256
Dated May 2004
19
11
2
17
C D E F 6"
12 "A" DIA.
22
14
L
13
2" NPT CPLGS. FOR
CUST. FURN. LEGS H
4 G
B FUEL SUPPLY
FUEL RETURN 14
NOMINAL USABLE
TANK SIZE VOLUME A B C D E F G H L Z
IN GALLONS IN GALLONS
119 105 24 (609) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 14 (355) 3 (76) 4
187 165 30 (761) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 16 (406) 3 (76) 4
300 270 38 (964) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 37 (939) 23 (584) 3-3/4 (95) 4
359 320 36 (914) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 23 (584) 3-3/4 (95) 4
572 515 48 (1218) 73 (1853) 6 (152) 6 (152) 6 (152) 31 (787) 44 (1117) 30 (761) 4-3/4 (121) 4
849 766 64 (1626) 61 (1548) 6 (152) 6 (152) 6 (152) 19 (482) 44 (1117) 30 (761) 4-3/4 (121) 4
1100 993 64 (1626) 79 (2007) 6 (152) 6 (152) 6 (152) 37 (940) 44 (1117) 30 (761) 4-3/4 (121) 6
625 750
1200
1300
1300 1400
1400
625 750
500 1500
500 USGPM 1500
450
450
375
FM
375
6"-1250 APPROVED
S/N: 0000
S/N: 0000
HIGH PRESSURE
HIGH PRESSURE
FM
FM
APPROVED
NOMINAL
PIPE DIA
5"-789
AURORA PUMP PIPE DIA
Pentair Water
AURORA MODEL 481 & 485 PUMPS Section 916 Page 251
DIESEL BATTERIES, RACKS, & CABLES Date June 2002
Supersedes Section 916 Page 251
Dated July 2001
POS NOTES:
20.75
(527)
BATTERY
16.25
(419)
BATTERY
5.5 (140) RACK
20.5 23.5
(521) (597)
60" or 80"
NOTES: POSITIVE CABLE (1524 or 2032)
1. All cables are SAE J55BA type SGT with
tensile attachment of 700-800 lbs.
2. Positive & negative cables 60" (1524) long are 17/32 DIA. HOLE (TYPICAL)
2/0 gauge; positive & negative cables 80" 60" or 80"
(2032) long are 3/0 gauge.
3. Terminal clamps have steel reinforced (1524 or 2032)
inserts.
NEGATIVE CABLE
4. Not all cable types are required for every
engine. Refer to Section 916 page 252 for
cable applicability. 12"
INTERCONNECTING (305)
CABLE
Pentair Water
AURORA MODEL 481 & 485 Section 916 Page 301
DIESEL ENGINE DRIVEN FIRE PUMP Date July 2001
Supersedes Section 916 Page 301
COOLING WATER PIPING DATA Dated January 1997
BY-PASS VALVES
NORMALLY CLOSED GAUGE
TO
ENGINE
REGULATOR VALVES
STRAINERS SOLENOID
VALVE
FROM
PUMP
Model 481 & 485 pumps are shipped from the plant 7. Since cooling loop components are subject to
with the loop piped between the pump and engine. The bumps and movement during shipping. all compo-
pipe and loop sizes are determined by the engine nents must be checked for pipe strain and leakage prior
model. to initial startup.
1. A flushing type strainer is used to protect the regula- The cooling water outlet piping from the engine heat
tor valve, solenoid valve and the tubes of the heat exchanger must be at least the size listed in Table A.
exchanger from foreign material. The piping must be short, have no valves and dis-
charge into an open waste cone. If deviations from the
2. The regulator valve is used to control the volume requirement of discharge to an open waste cone are
and pressure of the cooling water. permitted by the authority having jurisdiction, the
proposed plumbing must be reviewed to assure that
3. The solenoid valve opens automatically when the the back pressure created wiII not reduce the cooling
engine is started and closes automatically on engine shut- water flow to below that required for the engine.
Section 916 Page 302 AURORA MODEL 481 & 495
Date May 2004 DIESEL ENGINE DRIVEN FIRE PUMP
Supersedes Section 916 Page 302
Dated July 2001 COOLING WATER PIPING DATA
If the outlet piping from two or more engines is connected adjusting is necessary, see the following procedure:
to a common manifold, the manifold piping should be
sized such that the velocity resulting from the combined With the pump operating at the rated duty, the adjustment
flow is the same as that in the outlet piping between the is made after the engine block temperature has risen to the
manifold and heat exchanger. level required to open the engine thermostat. The thermo-
stat opens at approximately 170°F. The temperature will
Adequate pipe supports must be provided for the loop and stabilize and then decrease slightly. At this point, the regu-
outlet piping to minimize vibration and prevent excessive lator is adjusted between 15 and 20 PSI by turning the reg-
strain at the heat exchanger, pump and engine connec- ulator screw clockwise to increase the pressure and coun-
tions. terclockwise to reduce the pressure. The regulator screw is
then locked into place with the locknut provided.
Engine coolant should be added in accordance with the
engine manufacturer’s recommendations. MAINTENANCE
The regulator valve is adjusted during operational tests at the 2. If cooling water temperature changes, the regulator
plant and set between 15 and 20 PSI back pressure. If additional valve may require adjustment.