MOTOR TEMP Motor temperature is too high (or appears to be Check motor ratings and load.
(4310) too high) due to excessive load, insufficient Check start-up data.
motor power, inadequate cooling or incorrect
02.18FW 1 bit 06 Check Fault Function parameters.
start-up data.
(programmable
Fault Function
30.04…30.09)
MOTOR 1 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4312) fault limit set by parameter 35.03. Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
MOTOR 2 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4313) fault limit set by parameter 35.06. Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.
NO MOT DATA Motor data is not given or motor data does not Check motor data parameters
(FF52) match with inverter data. 99.05…99.09.
02.19 FW 2 bit 01
OVERFREQ Motor is turning faster than highest allowed Check minimum/maximum speed settings.
(7123) speed due to incorrectly set minimum/ Check adequacy of motor braking torque.
maximum speed, insufficient braking torque or
02.18 FW 1 bit 09 Check applicability of torque control.
changes in load when using torque reference.
Check need for brake chopper and resistor(s).
Trip level is 40 Hz over operating range
absolute maximum speed limit (Direct Torque
Control mode active) or frequency limit (Scalar
Control active). Operating range limits are set
by parameters 20.01 and 20.02 (DTC mode
active) or 20.07 and 20.08 (Scalar Control
active).
Fault tracing