Fault Cause What to Do

MOTOR TEMP Motor temperature is too high (or appears to be Check motor ratings and load.
(4310) too high) due to excessive load, insufficient Check start-up data.
motor power, inadequate cooling or incorrect
02.18FW 1 bit 06 Check Fault Function parameters.
start-up data.
(programmable
Fault Function
30.04…30.09)

MOTOR 1 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4312) fault limit set by parameter 35.03. Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.

MOTOR 2 TEMP Measured motor temperature has exceeded Check value of fault limit.
(4313) fault limit set by parameter 35.06. Let motor cool down. Ensure proper motor
cooling: Check cooling fan, clean cooling
surfaces, etc.

NO MOT DATA Motor data is not given or motor data does not Check motor data parameters
(FF52) match with inverter data. 99.05…99.09.
02.19 FW 2 bit 01

OVERCURR xx Overcurrent fault in inverter unit of several Check motor load.


(2310) parallel connected inverter modules. xx (1...12) Check acceleration time.
refers to inverter module number.
02.18 FW 1 bit 01 Check motor and motor cable (including
phasing).
Check encoder cable (including phasing).
Check motor nominal values from group 99
START-UP DATA to confirm that motor model
is correct.
Check that there are no power factor correction
or surge absorbers in motor cable.

OVERCURRENT Output current exceeds trip limit. Check motor load.


(2310) Check acceleration time.
02.18 FW 1 bit 01 Check motor and motor cable (including
phasing).
Check that there are no power factor correction
capacitors or surge absorbers in motor cable.
Check encoder cable (including phasing).

OVERFREQ Motor is turning faster than highest allowed Check minimum/maximum speed settings.
(7123) speed due to incorrectly set minimum/ Check adequacy of motor braking torque.
maximum speed, insufficient braking torque or
02.18 FW 1 bit 09 Check applicability of torque control.
changes in load when using torque reference.
Check need for brake chopper and resistor(s).
Trip level is 40 Hz over operating range
absolute maximum speed limit (Direct Torque
Control mode active) or frequency limit (Scalar
Control active). Operating range limits are set
by parameters 20.01 and 20.02 (DTC mode
active) or 20.07 and 20.08 (Scalar Control
active).

Fault tracing