You are on page 1of 4

FPC-7034

Installation Guide
EN Four Loop Expander
FPC-7034 | Installation Guide | 1.0 Notice

Refer to Figure 1 below and Figure 2 on page 3 for


1.0 Notice installation details.
These instructions cover the installation of the Bosch Figure 1: Installing the FPC-7034 on the
Security Systems, Inc. FPC-7034 Four Loop Expander FPD-7024 Control Board
in a fire system supervised by a Bosch FPD-7024 Fire
Alarm Control Panel (FACP). R2
HR2
HT2

Install, test and maintain the FPC-7034 according to AUX-


AUX+
T2

R1
RH1

these instructions, NFPA 72, Local Codes and the N A+


A B+
C
B-
TH1
T1

1 NC3

Authority Having Jurisdiction. Failure to follow these A-

N A+
COM3
NO3
A B+

instructions may result in failure of the detector to C


2
B-
A-
NC2
COM2
NO2 1
operate properly. Bosch is not responsible for BAT-
24V
BAT+ Power Trouble
NC 1
COM1
NO 1
Alarm Silenced
improperly installed, tested or maintained devices. Supervisory Gnd Flt
SMK+
SMK-
2
4A+
4B+
4B-

These instructions contain procedures to 4A-

3A+ 3
3B+

follow in order to avoid personal injury and 3B-


3A-

damage to equipment.
2A+
1 2 3 Drill
Acknowledge 2B+

4 5 6 Disable

Silence
2B-
2A-
1A+
4
7 8 9 Test 1B+
1B-
1A-
*
B ack
0
Prog
#
Enter
History Reset

2.0 Device Description R B G Y OPTION BUS

The FPC-7034 allows an FPD-7024 FACP to support 1 - 8-Pin Connector


four additional loops. The expander plugs into the 2 Connect Green/Yellow wire from FPC-7034
control and provides four Class B, Style B or Class A, here
Style D loops that are identical in characteristics to the 3 Location of FPC-7034
loops on the control panel. 4 Holes for stand-offs

3.0 Installing the FPC-7034


Before installing the FPC-7034, remove
system power (AC and battery).

The FPC-7034 mounts on the FPD-7024 control board,


just to the right of the keypad. Use the four nylon
stand-offs supplied with the expander.
Use the following steps when connecting the FPC-7034
to an FPD-7024 control panel.
1. Install the four stand-offs into the four mounting
holes on the control.
2. Align the connector on the bottom of the
FPC-7034 with the eight pins extending from the
control board. Carefully press the FPC-7034 into
place.
3. Press each corner of the FPC-7034 until it is
locked onto each nylon stand-off.
4. Connect the green/yellow wire of the FPC-7034
to the ground terminal ( ) on the control board.
5. When power is restored, the FPC-7034 is
detected automatically and used by the system.

2 Bosch Security Systems, Inc. | 9/08 | F01U005542-01


FPC-7034 | Installation Guide | 4.0 Wiring
.

4.0 Wiring 5.0 FPC-7034 Specifications


The four loop inputs are wired the same as loop inputs Table 1: FPD-7034 Power Requirements
on the control board. Four EOL resistors are provided
with the FPC-7034 for installation at the end of each
point wiring run. Per Initiation Circuit
Alarm Current Threshold > 25 mA
Figure 2: FPC-7034 Circuit Board Trouble Current Threshold < 7 mA
BACK SIDE FRONT SIDE Normal Current > 7 mA and < 25 mA
2 Total Detector Standby Loop 3 mA
Current
Alarm Current (Short Circuit) 46 mA
Supply Voltage 18.0 VDC to 25.5 VDC
Per Module:
Standby Current 60 mA
1 Alarm Current 184 mA
For additional specifications and device compatibility,
refer to the FPD-7024 Operation and Installation Guide
(P/N: F01U008458).

1 - Earth ground wire (green with yellow stripe)


2 - 8-pin connector

Bosch Security Systems, Inc. | 9/08 | F01U005542-01 3


Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450-9199 USA
(800) 289-0096

© 2008 Bosch Security Systems