0% found this document useful (0 votes)
82 views29 pages

RG and RE Combination Heating and Cooling Outdoor Units

McQuay RG and RE Combination Heating and Cooling Outdoor Units

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
82 views29 pages

RG and RE Combination Heating and Cooling Outdoor Units

McQuay RG and RE Combination Heating and Cooling Outdoor Units

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd

Installation and Maintenance Manual IM-806

Group: Light Commercial

Part Number: IM-806

Date: August 2005

Supersedes: March 2005

RG and RE Combination Heating and Cooling


Outdoor Units
7-1/2 and 10 tons

© 2004 McQuay International

IM-806 Page 1
Table of Contents
MODEL NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . 3 PRELIMINARY IN BUILDING . . . . . . . . . . . . . . . . . . . . . . .18
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CHECK OF ROOF CURB INSTALLATION . . . . . . . . . . . . 18
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CHECK FOR MINIMUM CLEARANCES . . . . . . . . . . . . . . .18
Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CHECK AND REPORT DAMAGE . . . . . . . . . . . . . . . . . . . .18
Codes and Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CHECK FOR OBSTRUCTIONS, FAN CLEARANCE AND
Important Message to the Installer . . . . . . . . . . . . . . . . . . . . 4 WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Important Message to the Owner . . . . . . . . . . . . . . . . . . . . . 4 PRE-STARTUP PRECAUTIONS . . . . . . . . . . . . . . . . . . . .19
Recognize Safety Symbols, Words, and Labels . . . . . . . . . . 4 CHECK FIELD DUCT CONNECTIONS . . . . . . . . . . . . . . .19
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 CONTROL SYSTEM CHECK, TEST & START
GENERAL WARNINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
DIMENSIONAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 CONTROL VOLTAGE CHECK . . . . . . . . . . . . . . . . . . . . . .19
COMPONENT LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . 7 THERMOSTAT PRELIMINARY CHECK . . . . . . . . . . . . . . 19
CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 ECONOMIZER DAMPERS & FILTERS CHECK, TEST &
GAS HEAT UNITS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
ROOF CURB ASSEMBLY & INSTALLATION . . . . . . . . . . 7 FILTER SECTION CHECK . . . . . . . . . . . . . . . . . . . . . . . . .19
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 EVAPORATOR BLOWER FAN CHECK, TEST & START
ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Cantilever Curb: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 ECONOMIZER & DAMPER SECTION CHECK . . . . . . . . .20
Full Perimeter Curb: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 BEARING CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 SET EVAPORATOR FAN RPM . . . . . . . . . . . . . . . . . . . . .20
VERTICAL DISCHARGE DUCT CONNECTIONS . . . . . . . 10 DRIVE BELT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
DUCT INSTALLATION BEFORE UNIT PLACEMENT . . . . 10 TENSION AND ALIGNMENT ADJUSTMENT . . . . . . . . . . .21
DUCT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 EVAPORATOR FAN ROTATION CHECK . . . . . . . . . . . . . 21
DUCT INSTALLATION AFTER UNIT PLACEMENT . . . . . 12 ELECTRICAL INPUT CHECK . . . . . . . . . . . . . . . . . . . . . . .21
HANDLING AND RIGGING . . . . . . . . . . . . . . . . . . . . . . . . 12 RESTORING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . .21
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 REFRIGERATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . 22
RIGGING REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 CHECK, TEST & START PROCEDURE PRELIMINARY
UNIT INSTALLATION ON ROOF CURB . . . . . . . . . . . . . . 13 CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 REFRIGERATION SEQUENCE CHECK . . . . . . . . . . . . . .22
CURB INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 REFRIGERATION PERFORMANCE CHECK . . . . . . . . . .23
PROTRUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 GAS HEAT CHECK, TEST & START PROCEDURE . . . .23
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 GAS SUPPLY PRESSURES & REGULATOR
HORIZONTAL DISCHARGE DUCT CONNECTIONS . . . . 13 ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
ACCESSORY OUTSIDE AIR OPTIONS - FIELD SEQUENCE OF OPERATION - GAS HEATING . . . . . . . .24
INSTALLED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 LS Automatic Reset High Limit Control . . . . . . . . . . . . . . . .24
ELECTRICAL INSTALLATION . . . . . . . . . . . . . . . . . . . . . 14 ALS Automatic Reset High Limit Control . . . . . . . . . . . . . . 24
INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 RS Manual Reset Flame Rollout Control . . . . . . . . . . . . . .24
ELECTRICAL ENTRANCE LOCATIONS . . . . . . . . . . . . . . 14 INPUT RATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
MAIN POWER WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 AIR BALANCING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
LOW VOLTAGE CONTROL WiRING . . . . . . . . . . . . . . . . . 15 DRIVE ADJUSTMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . 25
GAS SUPPLY PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 MOUNTING & ADJUSTING MOTOR SHEAVES VL, VM &
LOCATION AND INSTALLATION . . . . . . . . . . . . . . . . . . . 16 2VP VARIABLE PITCH KEY TYPE SHEAVES
CONDENSATE DRAIN CONNECTION . . . . . . . . . . . . . . . 17 MOUNTING: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
EXTERIOR WIND SHIELD INSTALLATION . . . . . . . . . . . 17 ADJUSTING VL & VM SHEAVES: . . . . . . . . . . . . . . . . . . .25
CHECK, TEST AND START PROCEDURES . . . . . . . . . . 18 AFTER ADJUSTING: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
BEFORE STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TOOLS REQUIRED TO PERFORM CHECK, FILTERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
TEST & START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 LUBRICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
TEMPORARY HEATING OR COOLING . . . . . . . . . . . . . . 18 VENTOR MOTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
CONTRACTOR RESPONSIBILITY . . . . . . . . . . . . . . . . . . 18 INSPECTION & CLEANING . . . . . . . . . . . . . . . . . . . . . . . .26

© 2004 McQuay International, Minneapolis MN. All rights reserved throughout the world.
McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible
for determining whether this product is appropriate for his or her application.
Manufactured by Goodman Manufacturing Co., L. P., Houston, TX 77008

Page 2 IM-806
MODEL NOMENCLATURE

RG 090 A C F P Y

Model Future Use


RG = Rooftop Gas
RE = Rooftop Electric Voltage/Phase
P = 208-230/3/60
Nominal Capacity (tons) Q = 460/3/60
090
120
Heating Input
Vintage (BTUH)
EER F = 195,000
C = 10 G = 225,000
Y = Not Applicable

Table 1: Unit Nameplate Model Number Identifier


Unit Nameplate McQuay Model Number
PCC090-3A RE090ACYPY
PCC090-4A RE090ACYQY
PCC120-3A RE120ACYPY
PCC120-4A RE120ACYQY
PGC090195-3A RG090ACFPY
PGC090195-4A RG090ACFQY
PGC120225-3A RG120ACGPY
PGC120225-4A RG120ACGQY

IM-806 Page 3
INTRODUCTION
Important Message to the Owner
General Description
Read these instructions carefully and keep them near the prod-
These installation instructions cover the outdoor installation of uct for future reference. Although these instructions are
single package gas-electric heating and cooling units. See the
product catalog applicable to your model for information addressed primarily to the installer, useful maintenance infor-
regarding specifications applicable to your model and accesso- mation is included. Have the installer acquaint you with the
ries. operation of the product and periodic maintenance require-
ments.
Receiving Inspection
McQuay products are carefully inspected prior to shipment Recognize Safety Symbols, Words, and Labels
and the carrier has assumed responsibility for loss or damage The following symbols and labels are used throughout this
upon acceptance of the shipment. manual to indicate immediate or potential hazards. It is the
Upon receiving your shipment, check all items carefully owner's and installer's responsibility to read and comply with
against the Bill of Lading. Inspect the unit and/or accessories all safety information and instructions accompanying these
for shipping damage as soon as they are received. Immedi- symbols. Failure to heed safety information increases the risk
ately file claims for loss or damage, either shipping or con- of property damage and/or product damage, serious personal
cealed, with the shipping company. injury or death. Improper installation, operation and mainte-
Check the unit nameplate to verify the model number and elec- nance can void the warranty.
trical characteristics are correct. In the event an incorrect unit
is shipped, it must be returned to the supplier and must NOT
be installed. The manufacturer disclaims all responsibility for DANGER
the installation of incorrectly shipped units. Immediate hazards which WILL result in property
Codes and Regulations damage, product damage, severe personal injury and/
This product is designed and manufactured to permit installa- or death.
tion in accordance with National Codes. System design
should, where applicable, follow information presented in
accepted industry guides such as the ASHRAE Handbooks. It WARNING
is the installer' s responsibility to install the product in accor- Hazards or unsafe practice CAN result in property
dance with National Codes and/or prevailing local codes and damage, product damage, sever personal injury and/or
regulations. The manufacturer disclaims all responsibility for death.
equipment installed in violation of any code or regulations.
Important Message to the Installer
This equipment is to be installed by an experienced installation CAUTION
company and fully trained personnel. Carefully read all Hazards or unsafe practices which CAN result in
instructions and take into account any special considerations property damage, product damage, and/or personal
prior to installing the unit. Give this manual to the owner and injury.
explain its provisions.
Replacement Parts
Replacement parts can be obtained by contacting McQuay at
1-800-37-PARTS. When contacting McQuay for service or
replacement parts, refer to the model number and serial num-
ber of the unit as stamped on the nameplate attached to the
unit.

Page 4 IM-806
GENERAL WARNINGS
DANGER WARNING
CARBON MONOXIDE (CO) POISONING HAZARD This product contains or produces substances which
CO can cause brain damage and death. It is odorless may cause serious illness or death, and which are
and colorless. Do not install this unit in any enclosure known to the State of California to cause cancer, birth
or location where fumes many enter an enclosure. defects or other reproductive harm.

WARNING
DANGER
To avoid property damage, personal injury or death,
To avoid property damage, personal injury or death, do follow the planned maintenance instructions provided in
not store or use gasoline or other flammable vapors or the "Maintenance" section of this document.
liquids in the vicinity of this unit or in any area sharing
ventilation.
CAUTION
WARNING Freezing can burst pipes. Routinely inspect and
monitor unit and premise. If vacant, drain all water
IF YOU SMELL GAS pipes and close water source. Drain hydronic coils and
• Immediatly evacuate the area. use alternative heat source.
• Do not try to light any appliances.
• Do not touch any electrical switches.
• Do not use any phones in your building.
• Immediately call your gas supplier from a phone CAUTION
located in a neighboring building. Do not use this unit as a "construction heater" during
• Follow the gas supplier's instructions. finishing phases of construction on a new structure.
• If you cannot reach your gas supplier, call the fire Extremely low return air temperatures and corrosive or
department. dirty atmosphere can damage unit.

Failure to follow these instructions can result in fire,


explosion, severe personal injury or death.
CAUTION
Sheet metal parts, screws, clips and similar items have
WARNING sharp edges. Use caution and wear protective clothing
If overheating occurs or the gas supply fails to shut off, when installing or servicing this equipment.
turn off the manual gas shutoff valve outside the
furnace before turning off the electricity supply to avoid
property damage, severe personal injury or death. CAUTION
Keep these instructions in a safe and accessible space
for future reference or in case of an emergency.
WARNING
To avoid property damage, personal injury or death, do
not use this unit if any part has been under water.
Immediately call a qualified service technician to
inspect the furnace and replace any affected part.

IM-806 Page 5
DIMENSIONAL DATA
Figure 1. Vertical and Horizontal Discharge
All dimensions in inches; no scale

74 9/16

Vertical Discharge
(Factory Configuration)
74 9/16

17 9/32
40
17 9/32

5 7/8

18
4
18

28 11/16

Horizontal Discharge
(With Field Installed
Accessory)

3/4
*

17 9/32 7/8

40
MODEL A B C C
HEIGHT SUPPLY RETURN
17 9/32
AIR AIR
Table 2: Horizontal discharge (with field 1 9/32
090 B
installed accessory) 36 12 1/2 17 9/16
102 A B C
Model
Height
120, 150 Supply Air Return Air
52 20 1/4 25 13/16
090 180 36 12 1/2 17 9/16
3 25/32
120 *Field Installed
52 Accessory.
20 1/4 25 13/16

Page 6 IM-806
COMPONENT LOCATION
Figure 2. Typical Component Location

CLEARANCES GAS HEAT UNITS


1. As indicated in Figure 3 and on the unit's nameplate, a min-
Keep adequate clearance around the unit for service, mainte-
imum clearance of 36" to any combustible material is
nance and proper unit operation. Keep a total clearance of 75"
required on the furnance access side of the unit. All com-
on the main control panel side of the unit to facilitate possible
bustible materials must be kept out of this area.
fan shaft, coil, electric heat and gas furnace removal (Figure
3). Keep a clearance of 48"on all other sides of the unit to 2. This 36" clearance must also be maintained to provide
facilitate possible compressor removal, to allow service access proper combustion air and flue gas flow. The combustion
and to provide proper ventilation and condenser airflow. The air intake and furance flue discharge must not be blocked
unit must not be installed beneath any obstruction. The unit for any reason, including blockage by snow.
must be installed away from all building exhausts, windows,
3. Adequate clearances from the furnace flue discharge to any
vents and other entrances to any enclosure. Exhaust air must
adjacent public walkways, adjacent buildings, building
not enter an enclosure or any unit fresh air intake. openings or openable windows must be maintained in
accordance with the latest edition of the National Fuel Gas
DANGER Code (ANSI Z223.1)
CARBON MONOXIDE (CO) POISONING HAZARD
4. A minimum horizontal clearance of 48" from the furnace
CO can cause brain damage and death. It is odorless
and colorless. Do not install this unit in any enclosure flue discharge to any electric meters, gas meters, regulators
or location where fumes many enter an enclosure. and relief equipment is required.

Figure 3. Minimum Clearance — Gas Heat Units Note: Model RG090 through 120 rooftop units are
designed for outdoor installation only. They may be
installed over wood flooring or over Class A, B or C
roof covering materials.

48"
48"

36"
Min.

48"
75"

IM-806 Page 7
ROOF CURB ASSEMBLY 4. Assemble the duct connection frame accessory as shown in
Figure 6. Fasten the pieces together using the sheet metal
& INSTALLATION screws provided (3/8" hex head).
GENERAL Note: The duct connection frame can be oriented two ways
1. Roof curbs are shipped unassembled. Field assembly, when set into the curb. The frame position must cor-
squaring, leveling and mounting on the roof structure are the respond to the intended unit orientation on the curb.
responsibility of the installing contractor. All curb installatons The gasket provided with the duct connection acces-
must comply with local codes and should be done in accor-
sory should be applied after duct installation. Refer
dance with the established guidelines of the National Roofing
to the "Vertical Discharge Duct Connections" sec-
Contractors Association.
tion of these instructions.
2. All required hardware necessary for the assembly of the Figure 4. Cantilever Curb Joint
sheet metal curb is included in the curb accessory.
3. Full perimeter type curb accessories are available. Cantile-
ver type curbs are not available from the factory. Dimen-
sions shown can be used for fabrication in the field. The
full perimeter curb (PGC-5) includes a duct connection
frame to be assembled with the curb. A separate duct con-
nection frame can be constructed for use with the cantilever
curb. The unit can be set on the cantilever curb so that
either the condenser end or the two sides overhang the
curb.
4. Curbs must be supported on at least two parallel sides by
roof members. Roof members must not penetrate supply Figure 5. Typical Curb Installation
and return duct opening areas.
5. Curb insulation, cant strip, flashings and general roofing
materials are to be furnished by the contractor. Wood nail-
ing strip and curb gasketing are furnished with the curb
accessory.
6. The unit and curb accessories are designed to allow vertical
duct installation before unit placement. Do not install duct
after unit placement.
ASSEMBLY

CAUTION Table 3: Curb Dimensions


Curb Type A B C
All curbs look similar. To avoid incorrect curb Cantalever 45" 63 1/2" 77 13/16"
positioning, check job plans carefully and verify Full Perimeter 63 6/16" 63 9/16" 89 7/8"
markings on the curb assembly. Instructions may vary
with curb styles and supersede the information shown. Figure 6. Cantilever Curb Duct Connection Accessory
3 9/32"
Cantilever Curb: 3 5/8" 18 23/32" 18 23/32"
1. Position the perimeter pieces, items 1 and 2, as shown in
Figure 4. Check the lengths of all pieces against the bill of
material to verify proper placement and assembly.
40 23/32"
2. Assemble side channels, item 1, to the front and back chan-
nels, item 2, using bolts, washers, lock washers, and nuts
(items 3, 4, 5 and 6). Hand tighten ONLY at this time.
Note: Flanges on item 1 must go outside of item 2 and
under the wood nailer strip. Curb styles may vary, so
check the curb instructions.
3. Referring to Table 3 and Figure 5, the assembled roof
mounting curb should now be checked for squareness. The
curb assembly must be adjusted until both diagonal mea-
surements, dimension "C", are equal within a tolerance of
1/8". All hand tightened fasteners should now be fully
secured.

Page 8 IM-806
Full Perimeter Curb: Note: Do not apply gasket material to the curb perimeter
1. Position perimeter pieces, item A, as shown in Figures 7 and the duct connection frame until the ducts are
and 8. All perimeter pieces are identical. placed in the frame. Refer to the "Vertical Discharge
2. The duct connection frame, items B and C, should be Duct Connections" section of these instructions.
assembled with the curb as shown in Figures 7 and 8. Figure 7. Full Perimeter Curb
Note: The top of the duct connection frame must be flush
with the top of the curb as shown in Figure 7.
3. Fasten the pieces together using the sheet metal screws
provided (item D). Use three screws at each corner of the
curb frame (item A), when positioned, and two screws at
each joint of the duct connection members (items B and C).
4. The assembled roof mounting curb should now be checked
for squareness. Referring to Table 3 and Figure 5, the curb
assembly must be adjusted until both diagonal measure-
ments (dimension "C") are equal within a tolerance of 1/8".
5. Gasket material sufficient to seal the curb perimeter and the
duct connection frame is included and attached to a duct
connection member
.
Figure 8. Full Perimeter Curb Detail
3-9/32

18-23/32 18-23/32

1
2
3
68-1/16
40-23/32 63-9/16
4

1-1/2
1 2 3

9-5/8 5-1/2

3-1/2
3-1/4
GASKETING BETWEEN
26-5/32 UNIT BOTTOM UNIT & CURB
SUPPLY AIR
2-1/4 RETURN AIR
63-9/16 2-1/4

68-1/16 3-1/4
DUCT
3-9/32
SUPPORT DUCT
(B) SUPPORT
WOOD NAILER (C)
1-1/2
SUPPLIED 14
WITH CURB FIELD SUPPLIED
DUCT

CURB NOT SHOWN: INSULATION, CANT STRIP,


PERIMETER FLASHING AND ROOFING MATERIALS
(A) BY OTHERS
4

IM-806 Page 9
INSTALLATION placement is possible, but not recommended. Ducts must never
be fastened to the bottom of the unit, as the base pan may be
1. Place the assembled curb in the proper location over the penetrated. Use flexible duct connectors in the ducts near the
roof opening. Check for squareness and adjust if required. unit. Support all ducts by securing them to the building struc-
2. Curb installation must be level. One method to achieve a ture. Weatherproof all external ductwork, joints and roof open-
level installation is to stretch two diagonal lines equipped ings with flashing and mastic in accordance with applicable
with line levels across the curb. There must not be more codes. Ducts in an unconditioned space must be insulated and
than 1/8" spacing between the two lines at the point of covered with a vapor barrier.
intersection. If the lines touch at the intersection, recheck DUCT INSTALLATION BEFORE UNIT PLACEMENT
by placing the bottom line on top. Shim curb as required to
Ductwork may be installed prior to unit placement by using a
bring it to within the specified tolerance.
duct connection frame. Two duct connection frame systems fit
3. Attach the squared and leveled curb to the roof structure into the three possible curb configurations as shown in Figures
following industry accepted practice. 8, 9 and 10. The frame to be used with full perimeter curbs is
included with the curbs. It must be assembled and attached to
4. Install insulation, cant strip, roofing materials, flashing, and the curb as shown in Figures 7 and 8. The frame to be used
counterflashing in accordance with the established guide-
with either configuration of the cantilever curb should be fabri-
lines of the National Roofing Contractors Association. The
cated by installing contractor. It must be assembled as shown
finished roof, including counterfiashing around the curb,
in Figure 6 and then set into the curb as shown in Figures 9 and
must be installed prior to setting the unit on the curb.
10. Fastening the frame to the curb is not necessary.
VERTICAL DISCHARGE DUCT CONNECTIONS
The unit curb accessories have been designed to allow duct
installation before unit placement. Duct installation after unit

Figure 9. Cantilever Curb and Duct Connection Frame Kit (Condenser Section Overhang)
3 9/32

18 23/32 18 23/32

68 1/4 63 1/2 40 23/32

5 1/2

2 1/2
2 1/2
5 5/32

17 5/32

2 3/8 45 2 3/8

3 5/32 49 3/4 21 21/32

Page 10 IM-806
Figure 10. Cantilever Curb and Duct Connection Frame Kit (Side Overhang)
3 9/32

18 23/32 18 23/32

12 13/32

40 23/32 49 3/4
45

2 29/32

6 3/8
12 13/32

3 1/2
9 19/32
2 3/8 63 1/2 2 3/8

68 1/4

DUCT INSTALLATION Figure 12. Duct Placement (Cantilever Curb)


After the duct connection system has been assembled and
installed, the ductwork may be set in place. To make the con-
nection, prepare the duct with a 1-1/2" flange as shown in Fig-
ures 11 and 12. Then, place the section into position on the
connection frame. Riveting or bolting is not necessary and is
not recommended. Both duct connection systems include gas-
keting, which must be applied to the connection frame and
duct flanges after duct installation. Gasket must be installed
over the duct flanges so that an airtight seal is made between
the unit and the ductwork after the unit is placed on the curb.
Figure 11. Duct Placement (Full Perimeter Curb)

Full Perimeter Curb


All gasketing must be field installed on the full perimeter curbs
as shown in Figure 8. After duct sections have been installed,
apply gasketing supplied with the curb accessory over the duct
flanges, exposed connection frame and curb penmeter.
Cantilever Curb
All gasketing must be field installed on the perimeter of the
curb. After the duct connection frame and duct sections have
been set on the curb, field-supplied gasketing should be
applied over the duct flanges and exposed frame as shown in
Figures 9 and 10.

IM-806 Page 11
DUCT INSTALLATION AFTER UNIT PLACEMENT NOTES:
Duct installation after the unit has been placed is not recom- 1. Weights are for basic cooling only unit; no options.
mended. If ductwork must be installed after the unit is placed
2. Add 50% of weight listed to corners A and D.
on the curb, one of the duct connection frame systems should
still be used. Apply gasketing to the curb and duct connection 3. Add 50% of weight listed to corners B and C.
frames before unit placement as shown in Figures 8, 9, and 10.
4. Add 25% of weight listed to each corner.
The duct sections should be fastened to the vertical flanges of
the connection frame and curb and sealed as required. Ducts 5. Center of gravity weights are for cooling only units with no
must never be fastened to the bottom of the unit, as they may options
cause the base pan to be penetrated.
Provisions for forks have been included in the unit base frame
HANDLING AND RIGGING on three sides. If unit is moved by forklift, no other fork loca-
tions are approved.
GENERAL
To assist in determining rigging requirements, unit weights are Do not stand or walk on the unit. Do not drill holes anywhere
shown as follows: in the panels or in the base frame of the unit. Unit access pan-
els provide structural support. Do not remove any access pan-
Figure 13. Corner and Center of Gravity Locations els until unit has been installed on roof curb or field supplied
structure. Do not roll unit across finished roof without prior
approval of owner or achitect. Do not skid or slide on any sur-
face as this may damage unit base. The unit must be stored on
a flat, level surface. Provisions must be made to protect the
condenser coil from damage.

CAUTION
If units are to be lifted two at a time, the fork holes on
the condenser end of the unit must not be used.
Minimum fork length is 42" to prevent damage to the
unit. However, 48" is recommended.

RIGGING DETAILS
1. Unit must be lifted by the four lifting holes located at the
base frame corners.
2. Attach lifting cables to the unit with shackles as shown in
Figure 14.
Table 4: Unit and Component Weights (lbs.) and Center of 3. The distance between the crane hook and the top of the unit
Gravity (inches) must not be less than 60".
RG/RE
Data
090 120 4. Two spreader bars must span over the unit to prevent dam-
Corner Weight - A1 304 367 age to the cabinet by the lift cables. Spreader bars must be
Corner Weight - B1 245 318 of sufficient length so that cables do not come into contact
Corner Weight - C1 196 267 with the unit during transport. Remove wood struts
1 235 318
mounted beneath unit base frame before setting the unit on
Corner Weight - D
5
roof curb. These struts are intended to protect the unit base
Center of Gravity - X (in.) 33.5 34.2
frame from forklift damage. Remove struts by extracting
Center of Gravity - Y (in.) 5 34.5 34.5
the sheet metal retainers and pulling the struts through the
Unit Shipping Weight 1 1000 1290
base of the unit. Refer to the rigging label on the unit.
Unit Operating Weight 1 980 1270
2 30 40
Coil Guards CAUTION
Motorized O.A. Actuator 3 5 5
Do not fork lift unit after wood struts have been
Economizer 3 28 39 removed; severe damage will occur to the bottom of the
Gas Heat - Model 195 4 110 120 unit.
Gas Heat - Model 222 4 120 130
Electric Heater 4 85 100
Full Perimeter Curb 4 120 120
Cantilever Curb 112 112
Cantilever Curb Duct Support 27 27

Page 12 IM-806
RIGGING REMOVAL duct. Refer to the "Roof Curb Assembly & Installation" sec-
Remove spreader bars, lifting cables and other rigging equip- tion of this manual.
ment.
CAUTION
Figure 14. Rigging
To avoid equipment damage, do not allow crane hooks
or spreader bars to rest on on the roof of the unit.

HORIZONTAL DISCHARGE DUCT


CONNECTIONS
A 3/4" flange is provded for making duct connections on units
with the optional field installed horizontal discharge kit. Refer
to Figure 15. Units not equipped with an economizer may be
converted from vertical to horizontal discharge in the field by
using accessory number PGHDK0905A (RE090 and RG090)
or PGHDK1205 (RE120 and RG120). The kits include parts
for conversion to horizontal duct installation. The kit provides
3/4" duct flanges with the dimensions shown in Figure 15 and
Table 5.
Use flexible duct connectors between the unit and ducts. Insu-
late and weatherproof all external ductwork and joints as
required and in accordance with local codes.
Figure 15. Horizontal Discharge Connections Dimensions
UNIT INSTALLATION ON ROOF
CURB 3/4

LOCATION A

Units may look identical, but they can have significant internal
differences. Check the specific unit location carefully, referring
to plans if necessary, prior to setting the unit.
CURB INSTALLATION 17-9/32 7/8

The roof curb must be firmly and permanently attached to the 40


C
roof structure. Check for adequate fastening method prior to
setting the unit on the curb. Verify that the top of the duct con- 17-9/32
19/32

nection frame is flush with the top of the roof curb. Refer to B

the "Roof Curb Assembly & Installation" section of this man-


3-25/32
ual. Check the top of the curb, duct connection frame and duct
flanges to verify that the gasket has been applied properly. Table 5: Horizontal Discharge Connections Dimensions
Apply gasket firmly to the top of the curb perimeter, duct A B C
RG/RE
Height Supply Air Return Air
flanges and any exposed duct connection frame. If the gasket 090 36 12 1/2 17 9/16
is loose, re-apply using strong weather-resistant adhesive. 120 52 20 1/4 25 13/16
PROTRUSION ACCESSORY OUTSIDE AIR OPTIONS - FIELD
Inspect the curb to verify that none of the utility services (elec- INSTALLED
tric) routed through the curb protrude above the curb. If fresh air is required for the installation, three alternatives are
available.
WARNING Manual Fresh Air Damper-A manual fresh air damper
To avoid damage or electrical shock, do not attempt to (PGMD-5) is available for 0% to 25% outside air. Two may be
set unit on the curb if protrusions exist. used in the locations shown in Figure 2 for a maximum
UNIT INSTALLATION of 50% outside fresh air.
Carefully lower the unit onto the roof curb. While rigging the Motorized Fresh Air Damper- A motorized fresh air damper
unit, the center of gravity may cause condenser end to be (PGMDM-5) is available and is mounted in the same locations
slightly lower than supply/return air end. Bring the condenser shown in Figure 2.
end of unit into alignment with the curb. With condenser end
Economizer- (PGED090-5A & PGED120-5A) A full
of the unit resting on the curb member and using the curb as a
modulation enthalpy controlled economizer is available for
fulcrum, lower the opposite end of the unit until the entire unit
field installation. It is mounted between fresh air damper
is seated on the curb. When a rectangular cantilever curb is
blockoff locations. See accessory instructions for
used, take care to center the unit. Check for proper alignment
installation.
and orientation of the supply and return openings with the

IM-806 Page 13
ELECTRICAL INSTALLATION Figure 17. External Electrical Enterance Locations
(Non-Electric Heat Units)

WARNING
Do not tamper with factory wiring. The internal power
and control wiring of these units is factory installed and
each unit is thoroughly tested prior to shipment. Contact
the factory or your local representative if assistance is
required.
INSTRUCTIONS
1. The main power supply wiring to the unit and low voltage
wiring to accessory controls must be done in accordance
with these instructions, the latest edition of the National 9 3/32"
Electncal Code (ANSI/NFPA 70), and all local codes and 2 29/32"
ordinances. All field wiring shall conform with the temper-
ature limitations for Type T wire (63°F/35°C rise). 6 23/32"
2. Main power and low voltage wiring may enter the unit
through the side or, with some models and curb configura- Figure 18. Through The Curb Electrical Enterance Locations
tions, through the roof curb and base frame. Refer to Fig-
ures 16 and 17 for external electrical entrance locations.
Refer to Table 6 and Figures 8, 9, 10 and 18 for the
through-the-curb electrical entrance locations. Install con-
duit connectors at the desired entrance locations. External
connectors must be weatherproof. All holes in the unit base
must be sealed, including around conduit nuts, to prevent
water leakage into building. All required conduit and fit-
tings must be supplied by others.
3. Bring an independant 115V power source to the vicinity of
the rooftop unit for portable lights and tools used by service
personnel.
Figure 16. External Electrical Enterance Locations (Electric
1 2
Heat Units)
INTERNAL DISCONNECT
ACCESSORY MOUNTING LOCATION 7 8 5 6 3 4

MAIN Table 6: Through The Curb Electrical Enterance Locations


POWER Curb Configuration
Condenser
Full Perimeter Side Overhang
Model Type Overhang
Low Low Low
Power Power Power
LOW VOLTAGE Voltage Voltage Voltage
Cooling Only 4 3 8 7 2 1
Gas Heat 4 3 8 7 2 1
6 1/4 Electric Heat 6 3 5, 6 7 N/A 1
16 27/32

12

6 21/32

Page 14 IM-806
ELECTRICAL ENTRANCE LOCATIONS 4. Some disconnect switches are not fused. The power leads
1. Protect wiring from sharp edges. Follow National Electrical must be protected at the point of distribution in accordance
Code and all local codes and ordinances. Do not route with the unit nameplate.
wires through removable access panels. 5. The unit must be electrically grounded in accordance with
2. Locations 7 and 8 require wiring to exit unit through the local codes or, in the absence of local codes, with the latest
base rail and then re-enter the unit at the external electrical edition of the National Electrical Code (ANSIINFPA 70).
entrance locations shown in Figures 9, 16, and 17. A ground lug is provided for this purpose. Size the ground-
ing conductor in accordance with Table 250-95 of the
3. Locations 1 and 2 require wiring to be routed through the National Electrical Code. Do not use the ground lug for
back of the main control box. Refer to Figure 9. connecting a neutral conductor.

CAUTION 6. Connect power wiring to the main power terminal block.


This terminal block is located within the main control box
Conduit and fittings must be weather tight to avoid water on units without electric heat (PB1) and within the electri-
entry into the building.
cal heat control box on units with electric heat (PB3).
4. Knockouts are provided at locations 3, 4, 5 and 6. 7. Supply voltage to rooftop unit must not vary by more than
5. If an external field-supplied disconnect is used, the power 10% of the value indicated on the unit nameplate. Phase
wiring will route as follows: voltage unbalance must not exceed 2%. Contact the local
a. Power entry location other than location 8: Exit unit via power company for correction of improper voltage or
side location shown in Figures 16 and 17. Enter via a phase unbalance.
disconnect box. Connect to the disconnect and leave the
disconnect box. Enter the unit again at the side location WARNING
shown in Figures 16 and 17. Failure of unit due to operation on improper line voltage
b. Power entry at location 8: Exit the unit via base rail as or with excessive phase unbalance constitutes product
shown in Figure 9. Enter the disconnect box, connect to abuse that may cause severe damage to the unit's
electrical components and will void the unit warranty.
the disconnect and then leave the disconnect box. Enter
the unit again at the side location shown in Figure 17. LOW VOLTAGE CONTROL WiRING
It may be easier to penetrate the roof outside the curb versus 1. A 24V thermostat must be field installed. It may be pur-
using Locations 7 and 8. chased with the unit or field supplied. All cooling and heat-
ing systems available in Models RG/RE090 and 120 are 2-
MAIN POWER WIRING stage. Thermostats may be programmable or electrome-
1. The main power supply for the RG/RE090 and 120 roof-
chanical as required.
tops units shall be three phase, three wire. The unit is fac-
tory wired for the voltage shown on the unit's nameplate. 2. Locate the thermostat or remote sensor in the conditioned
space where it will sense average temperature. Do not
Note: If supply voltage is 208V, the lead on the primary of
locate the device where it may be directly exposed to sup-
transformer TRANS 1 must be moved from the
ply air, sunlight or other sources of heat. Follow the instal-
230V to the 208V tap.
lation instructions packaged with the thermostat.
2. Main power wiring should be sized for the minimum wire 3. Use #18 AWG wire for 24V control wiring runs not
ampacity shown on the unit's nameplate. Size wires in exceeding 75 feet. Use #16 AWG wire for 24V control wir-
accordance with the ampacity tables in Artical 310 of the
ing runs not exceeding 125 feet. Use #14 AWG wire for
National Electrical Code. If long wires are required, it may
24V control wiring runs not exceeding 200 feet. Low volt-
be necessary to increase the wire size to prevent excessive
age wiring may be National Electrical Code (NEC) Class 2
voltage drop. Wires should be sized for a maximum of 3%
where permitted by local codes.
voltage drop.
4. Route thermostat wires from the sub-base terminals to the
WARNING unit. Control wiring should enter through the unit base
frame as shown in Figure 18, or through the fixed side
To avoid risk of fire and equipment damage, use copper panel as shown in Figures 16 and 17. Connect the thermo-
conductors only
stat and any accessory wiring to the low voltage terminal
3. A weather tight disconnect switch, properly sized for the block TB1 in the main control box as shown in Figure 19.
unit total load, must be field installed. A non-fused internal
disconnect can be used which fits into the unit at the loca- Note: Field supplied conduit may need to be installed
tions shown in Figures 16 and 17. Knockouts for mounting depending on unit/curb configuration.
the disconnect are provided in the exterior panels. An exter- Note: Use 18-gauge solid conductor wire when connecting
nal, field-supplied disconnect may be mounted on the same thermostat wires to the terminals on the sub-base.
fixed exterior panel shown in Figures 16 and 17. DO NOT use wire that is larger than 18 gauge. A
Note: Do not cover the nameplate with field supplied dis- transition to 18-gauge wire may be required before
connect switch. entering the thermostat sub-base.

IM-806 Page 15
Figure 19. RG/RE 090 Through 120 3. These units are designed for either natural or LP gas and
(Cooling Only, Gas Heat /Electric Heat) are specifically constructed at the factory for only one of
THERMOSTAT ROOFTOP these fuels. The fuels are NOT interchangeable. However,
UNIT
TB1 the furnace can be converted in the field from natural gas to
R R LP gas with the appropriate factory kit (LPW-06). Only a
qualified contractor, experienced with natural and propane
G G gas systems, should attempt conversion. Kit instructions
must be followed closely to provide proper and reliable
Y1 Y1 unit operation.
4. With all units on a common line operating under full fire,
Y2 Y2 the natural gas main supply pressure should be adjusted to
SEE NOTE approximately 7.0" W.C., measured at the unit gas valve. If
W1 W1
the gas pressure at the unit is greater than 10.5" W.C., the
W2 SEE NOTE
W2 contractor must furnish and install an external-type positive
shutoff service pressure regulator. The unit will not func-
tion satisfactorily if supply gas pressure is less than 5.5"
Note: Connections between unit terminals 'W1" and "W2" W.C. or greater than 10.5" W.C.
and the corresponding thermostat terminals "W1" Note: A minimum horizontal distance of 48" between the
and "W2" are not required on cooling only units. regulator and the furnace flue discharge is required.
GAS SUPPLY PIPING 5. With all units on a common line operating under full fire,
the LP gas main supply pressure should be at least 11.0",
WARNING W.C. and must be no greater than 13.0" W.C., measured at
Improper installation, adjustment, alteration, service or the unit gas valve. The unit will not function satisfactorily
maintenance can cause personal injury or property if the supply gas pressure is less than 11.0" W.C. or greater
damage. Refer to the user's information manual than 13.0" W.C.
provided with this furnace. For assistance or additional
information, consult a qualified installer, service agency 6. Seal all pipe connections with a pipe thread compound that
or the gas supplier. is resistant to the fuel used with the furnace. Use a soapy
water solution to check all joints for leaks. A 1/8" NPT
LOCATION AND INSTALLATION plugged tap is located on the entering side of the gas valve
1. The gas supply piping location and installation on the roof- for test gauge connection to measure the supply (main) gas
top unit must be in accordance with local codes or, in the pressure. Another 1/8" tap is provided on the side of the
absence of locals codes, with the ordinances of the latest manifold for checking the manifold pressure.
edition of the National Fuel Gas Code (ANSI Z223.1). A
manual gas shutoff valve must be field-installed external to CAUTION
the rooftop unit. In addition, a drip leg must be installed
near the inlet connection. A ground joint union connection The furnace and its individual shutoff valve must be
disconnected from the gas supply system during any
is required between the external shutoff valve and the unit pressure testing of the system at test pressures in
connection to the gas valve to permit removal of the burner excess of 1/2 psig (13.8" W.C.)
assembly for servicing. Locate the union near the gas valve
as shown in Figure 20. Route gas piping to the unit so that
it does not interfere with removal of access panels. Piping
must be supported and aligned to prevent strains or mis- CAUTION
alignment of the manifold assembly. Refer to Figure 20.
The furnace must be isolated from the gas supply
2. All units are furnished with standard female NPT pipe con- piping system by closing its individual manual shutoff
nections. Connection pipe sizes for RG090 and 120 units is valve during any pressure testing equal to or less than
1/2 psig (13.8" W.C.).
3/4" NPT on 195 and 225 MBH furnaces. The size of the
gas supply piping to the unit must be based on length of 7. There must be no obstruction to prevent the flow of com-
run, number of units on the system, gas characteristics, bustion and ventilating air. A vent stack is not required and
BTU requirement and available supply pressure. All piping must never be used. The power ventor will supply an ade-
must be done in accordance with local codes or, in the quate amount of combustion air as long as the air passage-
absence of local codes, with the latest edition of the ways are kept free of any obstructions and the
National Fuel Gas Code (ANSI Z223.1). recommended external unit clearances are maintained.
Note: The gas connection size at the unit does NOT estab- (The wind shield must be in place during furnace opera-
lish the size of the supply line. tion. See Exterior Wind Shield Installation).

Page 16 IM-806
Figure 20. Gas Supply Piping

CONDENSATE DRAIN CONNECTION 4. Drain pans will have some moisture in them, so periodic
cleaning is necessary to avoid algae and fungus build-up,
1. All units are equipped with a flexible tube condensate trap which can plug the drain and cause the drain pan to over-
which may be connected to either side of the drain pan as flow.
shown in Figure 21.
Figure 21. Internal Condensate Drain Routing
EXTERIOR WIND SHIELD
INSTALLATION
Details of exterior wind shield installation are as follows:
Figure 22. Exterior Wind Shield

Top Panel

D
C
E B
CAUTION
To avoid condensate build-up and equipment damage,
the end of the tube must be routed through the Outer Shield
insulation and the top of the base rail so that the
condensate has free access to the roof or external Inner Shield
drainage system. Knockouts are provided in the base
rails. The unused hole on the opposite side of the drain
Gas Access Panel
pan must be blocked with the plug provided.
Compressor Access Panel
2. Drainage of condensate directly onto the roof may be
Table 7: Exterior Wind Shield Dimensions
acceptable; refer to local code. Provide a small drip pad of Model A B C D E
either stone, mortar, wood or metal to avoid damage to the 090, 120 1 1/2" 11" 3 1/2" 8 1/4" 2 1/8"
roof.
3. If condensate is to be piped into the building drainage sys-
tem, the drain line must penetrate the roof external to the
unit. Refer to local codes for additional requirements. The
flexible tube condensate trap may be connected to an exter-
nal drain line with a hose clamp.

IM-806 Page 17
CHECK, TEST AND START • All electric power, gas, hot water or steam line connec-
PROCEDURES tions, and the condensate drain installation have been com-
pleted for each unit on the job. These main supply lines
must be functional and capable of operating all units simul-
WARNING
taneously.
Electric shock can cause severe injury or death. Bond
the frame to the building electrical ground with the PRELIMINARY IN BUILDING
grounding terminal provided. Disconnect electric power Prior to the beginning of Check, Test & Start procedures on the
before servicing equipment. Service must be performed roof, complete the following steps.
by qualified personnel only.

BEFORE STARTUP WARNING


With the disconnect on and the thermostat not satisfied,
WARNING the machine will run. To avoid equipment damage, fire
or personal injury, do not start the machine until all the
Disconnect power to the unit and padlock in the "off"
necessary prechecks and tests have been performed.
position before servicing the fans. Moving fans can
cause severe personal injury or death. 1. THERMOSTAT. Set the thermostat in the conditioned
This procedure has been prepared as a guide for the proper space at a point at least 10°F below the zone temperature.
Check, Test & Start of the rooftop unit. The Check, Test & On cooling only models, set the thermostat system switch
Start procedure provides a step-by-step sequence which, if fol- on COOL and the fan switch on AUTO. On heating/cool-
lowed, will provide the proper startup of the equipment in the ing models, set the thermostat system switch on AUTO and
minimum amount of time. Air balancing of duct system is not the fan switch on AUTO.
considered part of the Check, Test & Start of the roof top unit. 2. NIGHT SETBACK THERMOSTAT (OPTIONAL). Set
However, it is an important phase of any air conditioning sys- thermostat at a point at least 10°F below the zone tempera-
tem startup and should be performed upon completion of the ture.
Check, Test & Start procedure. The Check, Test & Start proce-
dure at outside ambient temperatures below 55°F should be CHECK OF ROOF CURB INSTALLATION
limited to a readiness check of the refrigeration system. The Check the proper installation of the unit on the roof curb. Note
required final check and calibration should be completed when any deficiencies in a separate report and forward it to the con-
the outside ambient rises above 55°F tractor. The unit and curb assembly should be installed level.
The flashing of the roof mounting curb to the roof should be
TOOLS REQUIRED TO PERFORM CHECK, TEST &
START checked, especially at the corners, for good workmanship.
1. Refrigeration gauge and manifold. CHECK FOR MINIMUM CLEARANCES
2. Voltmeter. A minimum of 36" clearance must be provided on the main
3. Clamp-on ammeter. control box side of the unit. A minimum of 48" clearance is
recommended on all other sides. A clearance of 75" is desir-
4. Ohmmeter. able on the control box side for removal of the fan shaft or
5. Test lead. Minimum #16 AWG with insulated alligator heating section. The outside air intake must be remote from all
clips. building exhausts. The condenser air intake (if used) must be
6. Manometer for verifying gas pressure from 0" to 20" W.C. remote from all exhausts to provide full condenser capacity.
7. Air temperature measuring device.
DANGER
8. General refrigeration mechanic tools.
CARBON MONOXIDE (CO) POISONING HAZARD
TEMPORARY HEATING OR COOLING CO can cause brain damage and death. It is odorless
If it is planned that the unit will be used for temporary heating and colorless. Do not install this unit in any enclosure
or cooling, the Check, Test & Start must first be performed in or location where fumes many enter an enclosure.
accordance with this bulletin. Failure to comply with this
requirement will void the warranty. Install new filters after the CHECK AND REPORT DAMAGE
machines are used for temporary heating or cooling, and the Itemize damaged or missing parts, if any, in a separate report
coils, fans, and motors must be checked for unacceptable lev- stating what action has been initiated by the Contractor to cor-
els of construction dust and dirt. rect them. The absence of this information will mean that the
unit was complete and in good condition on the date of the
CONTRACTOR RESPONSIBILITY Check, Test & Start.
The installing contractor must verify that:
• All supply and return air ductwork is in place and corre-
sponds with installation instructions.
• All thermostats are mounted and wired in accordance with
installation instructions.

Page 18 IM-806
CHECK FOR OBSTRUCTIONS, FAN CLEARANCE CHECK FIELD DUCT CONNECTIONS
AND WIRING Verify that all duct connections are tight and that there is no air
During the performance of the Check, Test & Start procedure, bypass between the supply and return.
you will work in the various sections of the unit. It is important
that you remove extraneous construction and shipping materi- CONTROL SYSTEM CHECK, TEST &
als that may be found during this procedure. Rotate all fans START PROCEDURE
manually to check for proper clearances, and to verify that
CONTROL VOLTAGE CHECK
they rotate freely. Check bolts and screws that may have jarred
loose during shipment to the jobsite. Re-tighten all electrical With the disconnect switch in the open "OFF" position, dis-
connections. connect blue wire from the low voltage transformer TRANS1.
Close the disconnect switch to energize the TRANS1 control
PRE-START-UP PRECAUTIONS transformer. Check the primary and secondary (24V) of con-
It is important that the unit has been properly grounded during trol transformer TRANS1.
installation. Before start-up, check the ground lug connection
THERMOSTAT PRELIMINARY CHECK
in the main control box for tightness, and closing the circuit
breaker or disconnect switch. Verify that the supply voltage on With disconnect switch open and blue wire disconnected from
the line side of disconnect agrees with the voltage on the unit the TRANS1 transformer, attach one lead of ohmmeter to ter-
nameplate, and that it is within the utilization voltage range as minal R on the TB1 terminal block. Touch, in order, the other
indicated in Table 8. ohmmeter lead to terminals Y1, Y2 and G at the TB1 terminal
block. There must be continuity from terminal R to terminals
Table 8: Utilization Voltage Range Y1, Y2 and G. R to Y1 indicates first stage cool. R to Y2 indi-
Utilization Voltage
System Voltage Nameplate cates second stage cool. R to G indicates fan (auto). Replace
Min. Max.
the blue wire on TRANS1 transformer.
208-230/60/3 208/230 187 253
480/60/3 460 414 506 ECONOMIZER DAMPERS & FILTERS
System Voltage - That nominal voltage value assigned to a
CHECK, TEST & START
circuit or system for the purpose of designating its voltage FILTER SECTION CHECK
class. Remove the filter section access panels and check that the fil-
ters are property installed. Note the airflow arrows on the filter
Nameplate Voltage - That voltage assigned to a piece of
frames.
equipment for the purpose of designating its voltage class and
for the purpose of defining the minimum and maximum volt- Figure 23. Filter Access
age at which the equipment will operate.
Utilization Voltage - The voltage of the line terminals of the
equipment at which the equipment must give fully satisfactory
performance. Once it is established that the supply voltage will
be maintained within the utilization range under all system
conditions, check and calculate to see if an unbalanced condi-
tion exists between phases. Calculate the percent voltage
unbalance as follows:
MAXIMUM VOLTAGE DEVIATIONS
PERCENT VOLTAGE FROM AVERAGE VOLTAGE 2
UNBALANCE 3 = 100 X
AVERAGE VOLTAGE 1
HOW TO USE THE FORMULA:
EXAMPLE: With voltage of 220, 216, and 213
1) Average Voltage..... 220 + 216 + 213 = 649 / 3 / 216
2) Maximum Voltage Deviations from Average Voltage 220 -
216 = 4
4 400
3) Percent Voltage Unbalance = 100 x = = = 1.8%
216 216
Percent voltage unbalance MUST NOT exceed 2%.

IM-806 Page 19
EVAPORATOR BLOWER FAN the disconnect switch open, disconnect the thermostat wires
from terminals Y1, Y2, W1 and W2 to avoid heating and
CHECK, TEST & START mechanical cooling from coming on. Place a jumper wire
PROCEDURE across terminals R and G at the TB1 terminal block. Close the
ECONOMIZER & DAMPER SECTION CHECK disconnect switch. The evaporator fan motor will operate so
Follow instructions in the accessory for check, test & start pro- that the RPM can be checked.
cedures.
CAUTION
BEARING CHECK
Prior to energizing any fans, verify that all setscrews are tight To avoid overheating and equipment damage, airflow
must be adjusted so that the temperature rise does not
so that the bearings are property secured to the shafts.
exceed 40°F on electric heat units with 70°F entering
SET EVAPORATOR FAN RPM air.
Actual RPM's must be set and verified with a tachometer or For gas heat units, the airflow must be adjusted so that the air
strobe light. Refer to Tables 9 and 10 for basic unit fan RPM. temperature rise falls within the ranges given in Table 11.
Refer also to the "Air Balancing" section of this manual. With
Table 9: Supply Fan Performance Data(5)
External Static Pressure (Inches W.C.)
RG/RE CFM 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2600 669 0.44 816 0.59 916 0.75 1004 0.92 1084 1.09 1157 1.28 1226 1.47 1291 1.67
2000 734 0.53 847 0.69 944 0.85 1030 1.03 1109 1.21 1181 1.4 1249 1.6 1312 1.91
090 3000 770 0.62 877 0.79 973 0.97 1053 1.15 1135 1.34 1206 1.54 1273 1.75 1336 1.96
3200 807 0.73 909 0.91 1002 1.1 1086 1.29 1162 1.49 1232 1.7 1298 1.91 1360 2.12
3400 845 0.85 942 1.04 1032 1.24 1114 1.44 1159 1.65 1259 1.87 1324 2.09 1384 2.31
3400 679 0.73 781 0.98 873 1.26 957 1.58 1034 1.91 1105 2.26 1171 2.26 1233 2.99
3600 706 0.83 805 1.1 894 1.39 975 1.71 1051 2.05 1121 2.41 1188 2.78 1249 3.17
3800 733 0.95 829 1.23 916 1.53 995 1.85 1069 2.2 1139 2.57 1204 2.95 1266 3.36
120
4000 761 1.07 855 1.37 938 1.68 1016 2.01 1088 2.36 1156 2.74 1221 3.14 1282 3.55
4200 790 1.21 880 1.52 961 1.84 1037 2.18 1108 2.54 1175 2.93 1239 3.33 1299 3.75
4400 818 1.36 906 1.68 985 2.01 1059 2.36 1128 2.73 1194 3.13 1257 3.54 1316 3.97

DO NOT SELECT IN SHADED AREAS (FOR INTERPOLATION ONLY)


1. Selections in BOLD ITALICS require a field drive change. See Table 8 for drive ranges.
2. Selections below heavy line require oversize motor.
3. Maximum fan RPM = 1500
4. Table Includes all internal pressure drops induding cabinet losses. See the product catalog for additional pressure drops that must
be considered as part of external static pressure drop.
5. Refer to catalog for fan curves.
Table 10: Supply Fan RPM Range
Motor Sheave
Adjustable Factory Setting 2 Turns Open
Model Fan Sheave Fixed
Motor Sheave - Turn Open 0 1 2 3 4 5
090 Fan RPM 1.5 HP Motor 1209 1146 1082 1018 955 891
120 Fan RPM 3.0 HP Motor 1242 1186 1129 1073 1016 960

NOTE: Allow ± 5°/o Variation in blower RPM due to pulley manufacturing tolerances

Table 11: Condenser Fan Motors


FLA
Model Quanity Horsepower
208-230/60/3 460/60/3
090 2 1/2 2.6 1.3
120 2 1/2 2.6 1.3
NOTE: All values are per compressor

Page 20 IM-806
Table 12: Evaporator Fan Motors
Model 195 225 NOTES:
Number of Tubes 6 7 1. Capacities are approved for altitudes to 2000 feet. At higher elevations, heating
Ventor Motor HP 1/16 1/12 capacity must be reduced 4% (xO.96) for each 1000 feet above sea level,
BTUH Input 193,000 225,000 2. AIr temperature rise is for total heating capacity. Temperature rises at other
conditions may be calculated by using the formula:
BTUH Output 154,000 180,000
2600 55.0 - Output Capacity (BTIJH)
Temperature Rise =
2800 51.1 - 1.08 x CFM (Airflow)
3000 47.7 55.6 3. For altitudes over 2000 feet. air temperature rise must be calculated using the
3200 44.7 52.1 formula:
3400 42.1 49.1
Output Capacity (BTUH)
CFM 3600 39.7 46.3 Temperature Rise =
3800 - 43.9 14.4x CFM (Airflow) X Density of Air ([Link])
4000 - 41.7
4 Two-stage control is standard.
4200 - 39.7
5. Output capacity based on nominal 1000 Btu/FI' natural gas or 2500 BtuIFt3
4400 - 37.9 propane.
4600 - 36.3 6. See nameplate data for maximum air temp. flse for specific unit.

DRIVE BELT Table 13: Recommended Pounds of Force Per Belt


Drive Ratio
Small
TENSION AND ALIGNMENT ADJUSTMENT Belt
Sheave Dia. 1 1.5 2 4.0 & Over
Section
(in.)
Check the drive for adequate run-in belt tension. Correct belt Min. - Max Min. - Max Min. - Max Min. - Max
tension is very important. A loose belt will have a substantially 3 2.0 - 3.0 2.3 - 3.5 2.4 - 3.6 2.6 - 3.9
shorter life, and a belt that is too tight may cause premature A 4 2.6 - 3.9 2.8 - 4.2 3.0 - 4.5 3.3 - 5.0
motor and bearing failure. Correct belt tension on these units 5 3.0 - 4.5 3.3 - 5.0 3.4 - 5.1 3.7 - 5.6

can be checked by measuring the force required to deflect the EVAPORATOR FAN ROTATION CHECK
belt 1/8" at the midpoint of the span length (Figure 24). Belt Verify that the fan rotates clockwise when viewed from the
tension force can be measured using a belt tension checker, drive side of unit, and in accordance with rotation arrow
available through most belt manufacturers. The correct deflec- shown on blower housing. If it does not, reverse the two
tion force is 5 lbs. for a new belt and 3.5 lbs. for a belt that has incoming power cables at PB1 terminal block and repeat the
been run in. New belt tension includes initial belt stretch. bearing check.
When new V-belts are installed on a drive the initial tension
will drop rapidly during the first few hours. Check tension fre- Do not attempt to change the load side wiring. Internal wiring
quently during the first 24 hours of operation. Subsequent is set so that all motors and compressors will rotate in the cor-
retensioning should fall between the minimum and maximum rect direction once the evaporator fan motor rotation check has
force. To determine the deflection distance from the normal been made.
position, use a straightedge or stretch a cord from sheave to ELECTRICAL INPUT CHECK
sheave to use as a reference line. On multiple belt drives, an
Make a preliminary check of evaporator fan ampere draw and
adjacent undeflected belt can be used as a reference.
verify that the motor nameplate amps are not exceeded. A final
Figure 24. Drive Belt Tension Adjustment check of the amp draw should be made when air balancing of
the duct system is complete.
SPAN LENG
TH (t) Table 14: Evaporator Fan Motors
DEFLECTIO
N FLA
FORCE Horsepower
208-230/60/3 460/60/3
1.5 4.2/4.6 2.1
D 3 8.4/8.6 4.2
h
d RESTORING CONNECTIONS
With disconnect switch open, remove the jumper wire from
terminals R and G at the TB1 terminal block, and reconnect
C the thermostat wires to terminals V1, Y2, W1 and W2.
t = Span Length, inches
C = Center Distance, inches
D = Large Sheave Diameter, inches
d = Small Sheave Diameter, inches
h = Deflection Height, inches

IM-806 Page 21
REFRIGERATION SYSTEM tion of correct supply fan rotation at initial startup will also
indicate correct compressor rotation. Reconnect power and
CHECK, TEST & START PROCEDURE PRELIMI- check for proper operation.
NARY CHECK
Verify that the hold-down bolts on the compressors are secure 4. Contactor C1 closes its contacts L1, L2 and L3 to
and have not vibrated loose during shipment. Check to see that LT1, T2 and T3 to provide power to the compressor
vibration grommets have been installed. Visually check all pip- motor COMP.1. In addition, contactor C1 closes its
ing and clamps. The entire refrigeration system has been fac- contact L3 to T4 , energizing all of the condenser fan
tory charged and tested, making it unnecessary to field charge. motors.
Factory charges are shown in Table 15 and on the unit name- 5. Check that the compressors are operating correctly. The
plate. scroll compressors in these units must operate in the proper
Table 15: Refrigerant Charge Per Circuit rotation. Check the compressor discharge line pressure or
RG/RE Charge (oz.) temperature.
090 115
120 150
CAUTION
Install service manifold hoses. Gauges should read a saturation To avoid personal injury, do not touch the discharge line
pressure corresponding to the ambient temperature. The charge because it may be hot.
should be checked to obtain 12° to 15° of sub-cooling per sys-
After each compressor is started, the discharge pressure and
tem (i.e. compressor circuits).
discharge line temperature should increase. If this does not
REFRIGERATION SEQUENCE CHECK occur, and if the compressor is producing an exceptional
With the disconnect switch open, remove the field connected amount of noise, the compressor motor may be operating in
thermostat wire from terminal R on the TB1 terminal block. the wrong direction. If a problem is encountered, it will be nec-
Place a jumper across terminals R and G, and across R and V1 essary to check all of the compressors and the supply fan
on the TB1 terminal block. Close the disconnect switch. The motor. If a single motor is operating backward, check the
following operational sequence should be observed. power wiring for that motor and correct any leads that have
been interchanged at the contactor or at the motor. If all of the
1. Current through the primary winding of transformer motors are operating backward, disconnect the unit power sup-
TRANS1 energizes the 24-volt control circuit. ply and lock it in the "OFF" position. Switch the two leads of
2. The first stage of cooling is energized when the room tem- the power supply at the unit power terminal block PB1. Recon-
perature is above the thermostat set-point. The thermostat nect power and check for compressor and supply fan motor
makes R to G and R to V1. operation.
a. Supply contactor BC is energized. 6. To simulate a second stage call for mechanical cooling
from the wall thermostat, place a jumper across terminals R
b. UNITS WITHOUT ECONOMIZER OPTION: The and Y2 of terminal block TB1. The second stage of cooling
first stage compressor circuit is energized through low- is energized when the room temperature is above the ther-
pressure switch LP1, high pressure switch HP1, and mostat set-point for both first and second stages of cooling.
optional Freezestat. Compressors all rotate in the proper The thermostat makes R to Y2.
direction. Verification of the correct supply fan rotation
at initial startup will also indicate correct compressor a. UNITS WITHOUT ECONOMIZER OPTION: The
rotation. Reconnect the power and check for proper second stage compressor circuit is energized through the
operation. low pressure switch LP2, high pressure switch HP2, time
delay llC (pin 11 & 12) and optional freezestat.
c. UNITS WITH ECONOMIZER OPTION: The first
stage of cooling is interlocked through terminal 1 and 2 b. UNIT WITH ECONOMIZER OPTION: The second
on the economizer module. Control power must be stage compressor circuit is interlocked through terminals
available to the damper motor DM through terminal 3 and 4 of the economizer module (refer to 2c under
ECON on terminal block IIC (refer to economizer Refrigeration Sequence Check). If the outdoor air
instructions). If the outdoor enthalpy is not suitable for enthalpy is not suitable for cooling, the economizer ter-
cooling, the economizer module terminals will be minals will be closed, permitting compressor circuit 2 to
closed, permitting the compressor circuit to be ener- be energized.
gized. 7. Contactor C2 closes its contacts L1, L2 and L3 to T1, T2
3. Contactor BC closes its contacts L1, L2 and L3 to T1, T2 and T3 to provide power to the compressor motor
and T3 to provide power to the supply fan motor (refer to COMP. 2. In addition, contactor C2 closes its contact L3
"Evaporator Blower Fan Check, Test & Start Procedure"). to T4 duplicating the power circuit to all of the con-
Check the supply fan rotation. If the supply fan is rotating denser fan motors, allowing condenser air for compres-
in the wrong direction, disconnect and lock-off power sor circuit 2 to operate (if compressor circuit 1 is
block PB1. Do not attempt to change load side wiring. tripped).
Internal wiring is set at the factory so that the supply fan
and compressors all rotate in the proper direction. Verifica-

Page 22 IM-806
8. With all unit protective devices closed, the system will con- GAS SUPPLY PRESSURES & REGULATOR
tinue cooling operation until the thermostat is satisfied. ADJUSTMENTS
The first step in checking out the gas-fired furnace is to test the
9. Disconnecting the jumper wire between R and Y2 on TB1
gas supply piping to the unit for tightness, and to purge the
terminal block will simulate a satisfied second stage of the
system of air using methods outlined in the latest edition of the
thermostat. The second stage compressor will cycle off and
National Fuel Gas Code (ANSI Z223.1). Verify that the dis-
11C (pin 12) will initiate its time delay cycle.
connect switch is in the "OFF" position. Use a soapy water
[Link] the jumper wire between R and Yl and solution to check for gas leaks. Since the unit must be subject
between R and G on TB1 terminal block will simulate a to considerable jarring durring shipment, it is extremely impor-
satisfied first stage of the thermostat. The first stage com- tant that all gas connections and joints be tested for tightness.
pressor and the supply fan will cycle off. Check gas piping downstream from the unit inlet for leaks dur-
ing the subsequent sequence check.
11. After a time delay of approximately 3 minutes, the second
stage compressor control circuits will be ready to respond Adjust the supply gas pressure to 7.0" W.C. for natural gas and
to a subsequent call for cooling from the wall thermostat. 11.0" W.C. for propane gas, with the gas burners operating. If
there is more than one unit on a common gas line, the pres-
[Link] the disconnect switch. Reconnect the field thermostat
sures should be checked with all units under full fire. A supply
wire at terminal R on terminal block TB1.
pressure tap is provided on the upstream side of the gas valve.
REFRIGERATION PERFORMANCE CHECK A manifold pressure tap is provided on the manifold as shown
Under normal summertime (full load) operating conditions, in Figure 20. The normal manifold pressure for full input is
superheat should be between 8°F and 12°F. Sub-cooling, mea- 3.5" W.C. for natural gas and 9.5" W.C. for propane gas. Mini-
sured at the condenser outlet, should be 15°F (nominal). A mum gas supply pressure is 5.5" W.C. for natural gas and 11.0"
25°F to 35°F temperature difference should exist between the W.C. for propane gas. In order to obtain rating, the gas supply
entering condenser air and the temperature corresponding to pressure must be 11.0" W.C. for propane gas. The pressure reg-
the compressor saturated discharge pressure. The adjustable ulator on propane gas models is adjusted for 9.5" W.C. mani-
expansion valves can be used to obtain the proper subcooling fold pressure and is intended only to prevent over-firing. Do
setting. This is factory set and should not need to be used not attempt adjustment of the built-in pressure regulator unless
unless operation is unsatisfactory. Check to see that the com- the supply pressure is at least 7.0" W.C. on natural gas or 13.0"
pressor RLA corresponds to the values shown in Table 16. W.C. on propane gas. Check the location of the ignition elec-
RLA draw can be much lower than values in Table 16 at low trode and the flame sensor for correct gap setting. Refer to Fig-
load conditions and low ambient condensing temperatures. ure 25 and Tables 17 and 18. Because gas appliances located
Values in Table 16 can be slightly exceeded at high load condi- more than 2000 feet above sea level must be derated 4% per
tions and high ambient condensing temperatures. 1000 feet of total elevation, and because variance in the gas
heating value and specific gravity require a change in manifold
Table 16: Compressor RLA and LRA pressure to obtain rating, it is mandatory that the input be
208-230/60/3 460/60/3
RG/RE Qty. HP adjusted at the installation site. All installations must be made
RLA LRA RLA LRA
as outlined in the latest edition of the National Fuel Gas Code
090 2 2.9 12.5 88 5.9 44
120 2 3.9 17.4 123 6.8 49.5
ANSI Z223.1. Follow the section entitled "Procedures To Be
Followed To Place An Appliance in Operation". Refer also to
GAS HEAT CHECK, TEST & START the "User's Information Manual" supplied with the unit for
PROCEDURE additional information on the gas furnace.
Figure 25. Ignition Electrode and Flame Sensor
WARNING
If overheating occurs or the gas supply fails to shut off,
turn off the manual gas valve off before shutting off the
electrical supply to avoid fire, explosion, personal injury
or death. 11/16 ±1/32 5/8±1/32

WARNING
To avoid fire, explosion, personal injury or death, do not
fire the gas furnace with the flue box cover removed.

CAUTION
Except during brief periods, when gas pressures are 1/8±1/32
being measured by qualified service personnel, the
furnace access panel must always be secured in place
when the furnace is in operation. An inspection port in
the access panel is provided to monitor the flame.

IM-806 Page 23
Table 17: Heat Exchanger Specifications [Link] the event that the temperature at the thermostat continues
Maximum Input BTUH Number of Burners
Maximum BTUH Per to fall, the thermostat will also close the contact between
Burner
terminals R and W2. This will energize the second stage of
193,000 6 32,200
225,000 7 32,000
the gas valve (W2-C). After a delay of about 30 seconds,
the gas manifold pressure will increase to approximately
Table 18: Burner Orifice Specification 3.5" W.C. for natural gas and 9.5" W.C. for propane.
Drill Size Number (Dia.)
[Link] the space temperature rises, the thermostat will first
Gas Furnace Natural Gas LP Gas
No. of Tubes open R-W2 and finally R-W1. Opening R-W1 will cause
Carryover Carryover
Main Orifices
Orifices
Main Orifices
Orifices the gas valve to close and the furnace to shut down.
6, & 8 36 (.111") 58 (.042") 52 (.070") 73 (.024") [Link] furnace has three high temperature limit controls,
which can shut down the burner. They do not shut down the
SEQUENCE OF OPERATION - GAS HEATING
ventor motor.
1. This unit has one Manual Reset Limit Control. Check the
limit to make sure it has not tripped. The limit may arrive at LS Automatic Reset High Limit Control
Located in the blower compartment next to the rear blower, its
the job site tripped as a result of shipping shock.
sensing element projects through the blower section bulkhead
2. If the ventor motor comes on, but the unit does not attempt and senses the temperature at the rear of the furnace. It will
ignition, check if the ALS Automatic Reset High Limit cycle the furnace off if the temperature exceeds 100°F plus
Control requires resetting. maximum rise.
3. With electricity and gas turned on, the system switch in the ALS Automatic Reset High Limit Control
"HEAT" or "AUTO" position and the fan switch in the Located next to LS in the blower compartment, it senses air
"AUTO" position, the thermostat will dose the circuit temperature within the blower compartment and protects the
between unit terminals R and W1 (R-W1) when the tem- filters from excessive temperature. It will shut down the fur-
perature falls below the thermostat setting. nace if it senses excessive temperatures.
4. D1 on 11C energizes relay IDMR. RS Manual Reset Flame Rollout Control
5. Relay IDMR energizes the ventor motor IDM. Located in the burner compartment on the top shelf behind the
6. Operation of the ventor motor closes the centrifugal switch ventor motor, it senses high temperature that could occur if the
ES located in the ventor motor. Unless excessive tempera- heat exchanger tubes were plugged and the flame was rolling
tures or shipping shock have opened high limit control out instead of entering the tubes. It has a manual push-button
ALS, power is fed to the integrated ignition control, which reset that cannot be actuated until the limit control has cooled.
then initiates a 15-second pre-purge time delay. During this INPUT RATING
period, the ventor motor will clear the combustion chamber It is the responsibility of the contractor to adjust the gas input
of any residual gas. to the unit. The input rate can be calculated by using the for-
mula:
7. After the pre-purge period, the ignition control energizes
the first stage operator (Wl-C) on the gas valve and simul- 3600 X HV
taneously initiates a "3-try" spark ignition sequence. INPUT Btu/Hr =
T
8. When the burners are ignited, a minimum 4 micro-amp DC WHERE:
current will flow through the flame between the sensor HV = Heating value of fuel = Btu/ft3 of gas
electrode and the grounded burner.
T = Time in seconds per ft3 of gas flow as read from gas meter
9. When the controller proves that the flame has been estab-
lished, it will keep the gas valve energized and discontinue Adjust input rate by varying the adjustment of the gas pressure
the ignition spark. First stage manifold pressure will be regulator on the gas valve (see Figure 26). All adjustments
approximately 1.6" W.C. for natural gas and 4.5" W.C. for must be made with the furnace operating at high fire and at
propane. normal operating temperature. Clockwise rotation of the pres-
sure regulator screw increases pressure and gas flow rate. Turn
[Link] the control is unable to ignite the burners after its initial the screw counterclockwise to decrease the pressure and gas
attempt, it will initiate another purge and spark sequence. A flow rate. After adjustment, the furnace temperature rise must
third purge and spark sequence will be initiated if the sec- be within the range specified on the unit nameplate.
ond attempt is unsuccessful. If the third attempt is unsuc-
Note: Thermal efficiency of the furnace is a product effi-
cessful, the controller will close the gas valve and lock
ciency rating determined under continuous operat-
itself out. It may be reset by momentarily interrupting
power. This may be accomplished by briefly lowering the ing conditions independent of any installed system.
room thermostat set-point below room temperature, or by
shutting off the main power to the unit. CAUTION
Do not exceed input rating or manifold pressure values
11. Integrated ignition control will close its normally open con- on the unit nameplate. If the input rating on the
tacts after a delay of approximately 30 seconds. This action nameplate cannot be attained without exceeding the
energizes contactor BC and starts the supply fan motor. listed manifold pressure, contact your local service
Operation of the supply fan circulates air across the heat representative.
exchanger and delivers heated air to the conditioned space.

Page 24 IM-806
Figure 26. Pressure Adjustments AFTER ADJUSTING:
1. Put on belts and adjust belt tension. DO NOT FORCE
BELTS OVER GROOVES.
2. Future adjustments should be made by loosening the belt
tension and increasing or decreasing the pitch diameter of
the sheave by half or full turns as required. Readjust belt
tension before starting drive.
3. Be sure that all keys are in place and that all set screws are
tight before starting drive. Check set screws and belt ten-
sion after 24 hours service.
Figure 27. Motor Sheave Adjustment
A

VL & VM

Do not operate the sheave with the flange projecting beyond


the hub end.
AIR BALANCING MAINTENANCE
The drive on the supply fan is typically set in the middle of the
RPM range. The drive motor sheave pitch diameter is field- WARNING
adjustable for the required airflow (refer to "Drive Adjust- Improper installation can cause equipment damage,
ments"). severe personal injury or death. Installation and
When the final adjustments are complete, check the current maintenance must be performed only by qualified
draw of the motor and compare it to the full load current rating personnel who are familiar with local codes and
regulations and experienced with this type of
of the motor. The amperage must not exceed the service factor equipment.
stamped on the motor nameplate. The total airflow must not be
less than that required for operation of the electric heaters or
the furnace. CAUTION
Check the operating balance with the economizer at full out- Avoid sharp edges and coil surfaces because they are
side air and at minimum outside air. Upon completion of the potential injury hazards.
air balance, it is a common industry practice that the variable Planned maintenance is the best way to avoid unnecessary
pitched motor sheave be replaced with a properly-sized fixed expense and inconvenience. Have this system inspected at reg-
sheave. A matching fixed sheave will provide longer belt and ular intervals by qualified service personnel, at least twice a
bearing life. Initially, it is best to have a variable pitched motor year. Routine maintenance should cover the following items:
sheave for the purpose of air balancing, but once the balance 1. Tighten all belts, set screws, and wire connections.
has been achieved, fixed sheaves maintain alignment and min-
imize vibration more effectively. 2. Clean evaporator and condenser coils mechanically or with
cold water, if necessary. Any fouling is normally matted on
DRIVE ADJUSTMENTS the entering air face of the coil and can be removed by
MOUNTING & ADJUSTING MOTOR SHEAVES VL, brushing.
VM & 2VP VARIABLE PITCH KEY TYPE SHEAVES
MOUNTING: 3. Lubricate motor bearings (see Lubrication).
1. Mount all sheaves on the motor or driving shaft with the set 4. Align or replace belts as needed.
screw "A" toward the motor.
5. Replace filters as needed (see Filters).
2. Verify that both driving and driven sheaves are in align-
ment and that shafts are parallel. 6. Check for blockage of the condensate drain.
3. Fit internal key "C" between the sheave and shaft, and lock 7. Check power and control voltages.
set screw "A" securely in place. 8. Check running amperage.
ADJUSTING VL & VM SHEAVES: 9. Check operating temperatures and pressures.
1. Loosen set screw "B" (5/32" Allen key). [Link] and adjust temperature and pressure controls.
2. Adjust sheave pitch diameter for the desired speed by open- 11. Check and adjust damper linkages.
ing the moving part by half or full turns from closed posi-
[Link] operation of all unit protective controls.
tion. DO NOT OPEN MORE THAN FIVE FULL
TURNS. [Link] gas furnaces (see "Inspection and Cleaning).
3. Securely tighten set screw "B" over flat. [Link] condenser fans and tighten set screws.

IM-806 Page 25
FILTERS INSPECTION & CLEANING
Different applications can require that filters be replaced at dif- All flue product carrying areas of the furnace, its vent system,
ferent intervals. Filters must be replaced at least every three (3) and main burners should be examined by a qualified service
months during operating seasons. agency before the start of each heating season. This examina-
tion is necessary for continued proper operation. Particular
Filters supplied with the units are the disposable type and are
attention should be given to deterioration from corrosion or
as follows:
other sources. This examination is accomplished in the follow-
Table 19: Filters ing manner.
Part No.
Unit Size Quantity Filter Size
(One Filter) 1. Disconnect power to the unit and remove the furnace sec-
090 3 25 x 25 x2 B13696-12 tion access panel.
120
3 16 x 25 x2 B13696-10 2. Refer to Figure 29. Remove burner assembly:
3 20 x 25 x2 B13696-11
a. Disconnect the three wires from the gas valve after not-
LUBRICATION ing which wires are connected to each terminal.
The fan shaft bearings, the 1 to 3 HP supply fan motors, and b. Disconnect wires from the flame rod and ignition elec-
the condenser fan motors are permanently lubricated. For trode.
lubrication of the compressors, use Suniso 3GS, Texaco c. Disconnect the gas piping at the union.
WF32, or Calumet ROl5 oils. All three oils are compatible if
d. The entire burner assembly can now be removed from
mixed, and are suitable for both high and low temperature sys-
the unit. Note how the front of the burner assembly
tems. nests around wide location tabs, one at the top and one
at the bottom.
CAUTION
3. Remove the flue box cover. The cover consists of two
Excessive grease will overheat the bearings. Use only a pieces which can be removed as a single unit. Remove
high grade lithium base grease with a 200°F operating the flue baffle.
temperature.
4. Remove the turbulator from within each heat exchanger
Note: Specific greasing instructions may be found on a tag tube. The end corner of the turbulator mates with the
attached to the motor. If special lubrication instruc- groove at the tube end seam. To release the turbulator, grip
tions are shown on the motor nameplate, they will the end of the turbulator with a pliers, force the corner
supersede all other instructions. away from the groove, and pull the turbulator out of the
tube.
VENTOR MOTOR
5. Inspect the burner assembly, the heat exchanger tubes, the
To lubricate the ventor motor, remove the furnace access
turbulators, the flue box, the ventor fan and the ventor fan
panel. Lubricate the motor in two locations as shown in Figure
outlet openings for accumulations of soot and deterioration.
28. Use SAE 20W lubricant and add five (5) drops to each
Soot can be removed with a flexible wire brush. The inside
location. The motor should be lubricated at the beginning of
of the tubes can be cleaned with a boiler tube type wire
each heating season. Do not over lubricate. brush. If the bends of the tubes must be cleaned, remove
the plate surrounding the burner end of the tubes. A brush
CAUTION or steel wool can then be pulled through the tube with a
Do not drip oil on the gas valve. The oil may damage cable. Be cautious not to damage the corrosion resistant
the non-metallic parts and render the valve inoperative. coating on the various metal parts. Remove all residue.
Remove any oil residues from the burner compartment.
6. If deterioration is evident, contact a qualified service
Figure 28. Ventor Motor agency. Minor deterioration of the turbulator ends is not
cause for concern.
7. Upon completion of inspection and cleaning, replace all
parts in the reverse order in which they were removed.

CAUTION
Use all screws that were removed; they are necessary
for proper operation of the unit.

8. Inspect and periodically clean the vent outlet (bird screen)


on the access panel.
Note: Periodic observation of the flame through the
inspection port and a log of C02 measurements are
recommended. This will aid in determining whether
the furnace is operating efficiently, or if the furnace
requires cleaning.

Page 26 IM-806
Figure 29. Gas Fired Furnance

IM-806 Page 27
Page 28 IM-806
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to [Link].

[Link] • 800-432-1342

You might also like