Hilti HVU2 Adhesive
capsule system
HILTI HVU2 ADHESIVE CAPSULE SYSTEM
Product description
Uncracked concrete Cracked Seismic Desing Diamond core Hollow Drill Bit PROFIS Anchor
concrete Categories A-F drilling permitted design software
Listings/Approvals
ICC-ES (International Code Council) ESR-4372 in concrete per ACI 318-14 Ch. 17 / ACI 355.4 / ICC-ES AC308
- 2018 International Building Code / International Residential
Code
This document is a supplement to the Hilti North American Product Technical Guide, Volume 2, Anchor Fastening Technical Guide, Edition 19 (PTG Ed. 19). Please
refer to the publication in its entirety available at www.hilti.com for complete details including data development, product specifications, general suitability, installation,
corrosion and spacing and edge distance guidelines.
2 June 2019
Hilti HVU2 Adhesive Capsule System
Cracked Water-saturated
concrete concrete Diamond core drilling
Figure 2 — Hilti HAS threaded rods installed with Hilti HVU2 adhesive capsule
June 2019 3
Hammer drilling with
carbide tipped drill bit, or
Table 2 — Hilti HVU2 adhesive design strength with lesser of concrete or Hilti TE-CD or TE-YD
bond failure for threaded rod in uncracked concrete 1,2,3,4,5,6,7,8,9 Hollow Drill Bit
4 June 2019
Hilti HVU2 Adhesive Capsule System
June 2019 5
Table 6 — Steel design strength for Hilti HAS threaded rods for use with ACI 318-14 Chapter 17
HAS-R stainless steel
HAS-E-55 / HAS-E-55 HDG HAS-B-105 and HAS-B-105 HDG
ASTM F593 (3/8-in to 1-in)5
ASTM F1554 Gr. 554,6 ASTM A193 B7 and ASTM F 1554 Gr.1054,6
ASTM A193 (1-1/8-in to 2-in)4
6 June 2019
Hilti HVU2 Adhesive Capsule System
Table 7 — Load adjustment factors for 3/8, 1/2, 5/8, and 3/4-in. diameter threaded rods in uncracked
concrete 1,2
Edge distance in shear
3/8, 1/2, 5/8 & Spacing factor in Edge distance factor Spacing factor in ┴ ‖ Concrete thickness
3/4-in. tension in tension shear 3 factor in shear 4
uncracked Toward edge To edge
ƒAN ƒRN ƒAV ƒHV
concrete ƒRV ƒRV
Thread size, in. 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4
Embedment in. 3-1/2 4-1/4 5 6-5/8 3-1/2 4-1/4 5 6-5/8 3-1/2 4-1/4 5 6-5/8 3-1/2 4-1/4 5 6-5/8 3-1/2 4-1/4 5 6-5/8 3-1/2 4-1/4 5 6-5/8
hef (mm) (89) (108) (127) (168) (89) (108) (127) (168) (89) (108) (127) (168) (89) (108) (127) (168) (89) (108) (127) (168) (89) (108) (127) (168)
1-7/8 (48) 0.59 n/a n/a n/a 0.30 n/a n/a n/a 0.53 n/a n/a n/a 0.10 n/a n/a n/a 0.19 n/a n/a n/a n/a n/a n/a n/a
2 (51) 0.60 n/a n/a n/a 0.31 n/a n/a n/a 0.54 n/a n/a n/a 0.11 n/a n/a n/a 0.21 n/a n/a n/a n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
2-1/2 (64) 0.62 0.58 n/a n/a 0.35 0.29 n/a n/a 0.55 0.54 n/a n/a 0.15 0.10 n/a n/a 0.30 0.20 n/a 0.54 n/a n/a n/a n/a
3 (76) 0.64 0.60 n/a n/a 0.38 0.31 n/a n/a 0.56 0.54 n/a n/a 0.19 0.13 n/a n/a 0.38 0.26 n/a 0.54 n/a n/a n/a n/a
3-1/8 (79) 0.65 0.60 0.58 n/a 0.39 0.32 0.31 n/a 0.56 0.54 0.54 n/a 0.21 0.14 0.12 n/a 0.39 0.28 0.24 0.54 n/a n/a n/a n/a
3-1/4 (83) 0.65 0.61 0.59 0.57 0.40 0.33 0.32 0.29 0.56 0.55 0.54 0.53 0.22 0.15 0.13 0.09 0.40 0.29 0.26 0.18 n/a n/a n/a n/a
4 (102) 0.69 0.63 0.61 0.59 0.46 0.37 0.35 0.31 0.57 0.56 0.55 0.54 0.30 0.20 0.18 0.12 0.46 0.37 0.35 0.25 n/a n/a n/a n/a
4-3/4 (121) 0.73 0.66 0.63 0.61 0.53 0.41 0.39 0.34 0.59 0.57 0.56 0.55 0.39 0.26 0.23 0.16 0.53 0.41 0.39 0.32 0.60 n/a n/a n/a
5 (127) 0.74 0.67 0.63 0.61 0.55 0.42 0.40 0.35 0.59 0.57 0.57 0.55 0.42 0.28 0.24 0.17 0.55 0.42 0.40 0.34 0.61 n/a n/a n/a
5-1/2 (140) 0.76 0.68 0.65 0.62 0.61 0.45 0.43 0.36 0.60 0.58 0.57 0.56 0.48 0.32 0.28 0.20 0.61 0.45 0.43 0.36 0.64 0.56 n/a n/a
6 (152) 0.79 0.70 0.66 0.63 0.66 0.48 0.45 0.38 0.61 0.59 0.58 0.56 0.55 0.37 0.32 0.23 0.66 0.48 0.45 0.38 0.67 0.58 n/a n/a
6-3/8 (162) 0.80 0.71 0.67 0.64 0.70 0.51 0.47 0.40 0.62 0.59 0.58 0.57 0.60 0.40 0.35 0.25 0.70 0.51 0.47 0.40 0.69 0.60 0.58 n/a
7 (178) 0.83 0.73 0.69 0.66 0.77 0.56 0.51 0.42 0.63 0.60 0.59 0.57 0.69 0.46 0.41 0.29 0.77 0.56 0.51 0.42 0.72 0.63 0.60 n/a
8 (203) 0.88 0.77 0.71 0.68 0.88 0.64 0.57 0.46 0.65 0.61 0.60 0.58 0.85 0.57 0.50 0.35 0.88 0.64 0.57 0.46 0.77 0.68 0.65 n/a
8-3/8 (213) 0.90 0.78 0.72 0.69 0.92 0.67 0.60 0.48 0.66 0.62 0.61 0.59 0.91 0.61 0.53 0.37 0.92 0.67 0.60 0.48 0.79 0.69 0.66 0.59
10 (254) 0.98 0.84 0.77 0.72 1.00 0.80 0.71 0.54 0.69 0.64 0.63 0.60 1.00 0.79 0.69 0.49 1.00 0.80 0.71 0.54 0.86 0.75 0.72 0.64
12 (305) 1.00 0.90 0.82 0.77 0.96 0.85 0.65 0.72 0.67 0.66 0.62 1.00 0.91 0.64 0.96 0.85 0.65 0.95 0.83 0.79 0.70
14 (356) 0.97 0.88 0.81 1.00 1.00 0.76 0.76 0.70 0.68 0.64 1.00 0.81 1.00 1.00 0.76 1.00 0.89 0.85 0.76
16 (406) 1.00 0.93 0.86 0.87 0.80 0.73 0.71 0.67 0.99 0.87 0.95 0.91 0.81
18 (457) 0.98 0.90 0.98 0.84 0.76 0.73 0.69 1.00 0.98 1.00 0.97 0.86
24 (610) 1.00 1.00 1.00 0.95 0.84 0.81 0.75 1.00 1.00 1.00
30 (762) 1.00 0.93 0.89 0.81
36 (914) 1.00 0.97 0.87
> 48 (1219) 1.00 1.00
Table 8 — Load adjustment factors for 1/2, 5/8, and 3/4-in. diameter threaded rods in cracked concrete1,2
Edge distance in shear
1/2, 5/8 & Spacing factor in Edge distance factor Spacing factor in ┴ ‖ Concrete thickness
3/4-in. tension in tension shear 3 factor in shear 4
cracked Toward edge To edge
ƒAN ƒRN ƒAV ƒHV
concrete ƒRV ƒRV
Thread size, in. 1/2 5/8 3/4 1/2 5/8 3/4 1/2 5/8 3/4 1/2 5/8 3/4 1/2 5/8 3/4 1/2 5/8 3/4
Embedment in. 4-1/4 5 6-5/8 4-1/4 5 6-5/8 4-1/4 5 6-5/8 4-1/4 5 6-5/8 4-1/4 5 6-5/8 4-1/4 5 6-5/8
hef (mm) (108) (127) (168) (108) (127) (168) (108) (127) (168) (108) (127) (168) (108) (127) (168) (108) (127) (168)
2-1/2 (64) 0.58 n/a n/a 0.53 n/a n/a 0.54 n/a n/a 0.11 n/a n/a 0.21 n/a n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
3 (76) 0.60 n/a n/a 0.58 n/a n/a 0.54 n/a n/a 0.14 n/a n/a 0.28 n/a n/a n/a n/a n/a
3-1/8 (79) 0.60 0.58 n/a 0.59 0.53 n/a 0.55 0.54 n/a 0.15 0.12 n/a 0.29 0.24 n/a n/a n/a n/a
3-1/4 (83) 0.61 0.59 0.57 0.60 0.54 0.51 0.55 0.54 0.53 0.16 0.13 0.09 0.31 0.26 0.18 n/a n/a n/a
4 (102) 0.63 0.61 0.59 0.66 0.59 0.55 0.56 0.55 0.54 0.21 0.18 0.12 0.43 0.35 0.25 n/a n/a n/a
4-3/4 (121) 0.66 0.63 0.61 0.73 0.64 0.59 0.57 0.56 0.55 0.28 0.23 0.16 0.55 0.46 0.32 n/a n/a n/a
5 (127) 0.67 0.63 0.61 0.75 0.66 0.60 0.57 0.57 0.55 0.30 0.25 0.17 0.60 0.49 0.35 n/a n/a n/a
5-1/2 (140) 0.68 0.65 0.62 0.80 0.70 0.63 0.58 0.57 0.56 0.34 0.28 0.20 0.69 0.57 0.40 0.57 n/a n/a
6 (152) 0.70 0.66 0.63 0.85 0.73 0.66 0.59 0.58 0.56 0.39 0.32 0.23 0.78 0.65 0.46 0.60 n/a n/a
6-3/8 (162) 0.71 0.67 0.64 0.89 0.76 0.68 0.59 0.58 0.57 0.43 0.36 0.25 0.86 0.71 0.50 0.62 0.58 n/a
7 (178) 0.73 0.69 0.66 0.95 0.81 0.72 0.60 0.59 0.57 0.49 0.41 0.29 0.95 0.81 0.57 0.65 0.61 n/a
8 (203) 0.77 0.71 0.68 1.00 0.89 0.78 0.62 0.60 0.58 0.60 0.50 0.35 1.00 0.89 0.70 0.69 0.65 n/a
8-3/8 (213) 0.78 0.72 0.69 0.92 0.81 0.62 0.61 0.59 0.65 0.53 0.38 0.92 0.75 0.71 0.66 0.59
10 (254) 0.84 0.77 0.72 1.00 0.92 0.65 0.63 0.60 0.84 0.70 0.49 1.00 0.92 0.77 0.72 0.64
12 (305) 0.90 0.82 0.77 1.00 0.68 0.66 0.62 1.00 0.92 0.65 1.00 0.84 0.79 0.71
14 (356) 0.97 0.88 0.81 0.71 0.68 0.65 1.00 0.81 0.91 0.86 0.76
16 (406) 1.00 0.93 0.86 0.74 0.71 0.67 0.99 0.98 0.92 0.81
18 (457) 0.98 0.90 0.77 0.74 0.69 1.00 1.00 0.97 0.86
24 (610) 1.00 1.00 0.86 0.81 0.75 1.00 1.00
30 (762) 0.95 0.89 0.81
36 (914) 1.00 0.97 0.87
> 48 (1219) 1.00 1.00
1 Linear interpolation not permitted.
2 When combining multiple load adjustment factors (e.g. for a four-anchor pattern in a corner with thin concrete member) the design can become very
conservative. To optimize the design, use Hilti PROFIS Anchor Design software or perform anchor calculation using design equations from ACI 318 Chapter 17.
3 Spacing factor reduction in shear, ƒAV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒAV = ƒAN.
4 Concrete thickness reduction factor in shear, ƒHV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒHV = 1.0.
June 2019 7
Table 9 — Load adjustment factors for 7/8, 1, and 1-1/4-in. diameter threaded rods in uncracked concrete1,2
Edge distance in shear
Spacing factor in Edge distance factor Spacing factor in ┴ ‖ Concrete thickness
7/8, 1 & 1-1/4-in. tension in tension shear 4 factor in shear 5
uncracked concrete Toward edge To edge
ƒAN ƒRN ƒAV ƒHV
ƒRV ƒRV
Thread size, in. 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4
in. 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11
Embedment hef
(mm) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279)
4-3/8 (111) 0.58 n/a n/a 0.35 n/a n/a 0.55 n/a n/a 0.14 n/a n/a 0.28 n/a n/a n/a n/a n/a
5 (127) 0.60 0.58 n/a 0.37 0.34 n/a 0.55 0.54 n/a 0.17 0.12 n/a 0.34 0.25 n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
6 (152) 0.61 0.60 n/a 0.41 0.37 n/a 0.56 0.55 n/a 0.23 0.16 n/a 0.41 0.33 n/a n/a n/a n/a
6-1/4 (159) 0.62 0.60 0.58 0.42 0.37 0.34 0.56 0.55 0.54 0.24 0.17 0.11 0.42 0.35 0.22 n/a n/a n/a
7 (178) 0.63 0.62 0.59 0.45 0.40 0.35 0.57 0.56 0.54 0.29 0.21 0.13 0.45 0.40 0.27 n/a n/a n/a
8 (203) 0.65 0.63 0.61 0.50 0.43 0.37 0.58 0.57 0.55 0.35 0.25 0.16 0.50 0.43 0.33 n/a n/a n/a
8-5/8 (219) 0.67 0.64 0.61 0.52 0.45 0.39 0.59 0.57 0.55 0.39 0.28 0.18 0.52 0.45 0.36 0.60 n/a n/a
9 (229) 0.67 0.65 0.62 0.54 0.46 0.40 0.59 0.57 0.56 0.42 0.30 0.19 0.54 0.46 0.39 0.61 n/a n/a
10 (254) 0.69 0.67 0.63 0.59 0.50 0.42 0.60 0.58 0.56 0.49 0.35 0.23 0.59 0.50 0.42 0.64 n/a n/a
10-1/2 (267) 0.70 0.68 0.64 0.62 0.51 0.44 0.61 0.59 0.57 0.52 0.38 0.24 0.62 0.51 0.44 0.66 0.59 n/a
11 (279) 0.71 0.68 0.65 0.64 0.53 0.45 0.61 0.59 0.57 0.56 0.40 0.26 0.64 0.53 0.45 0.67 0.60 n/a
12 (305) 0.73 0.70 0.66 0.70 0.57 0.47 0.62 0.60 0.57 0.64 0.46 0.30 0.70 0.57 0.47 0.70 0.63 n/a
13 (330) 0.75 0.72 0.67 0.76 0.61 0.50 0.63 0.61 0.58 0.72 0.52 0.34 0.76 0.61 0.50 0.73 0.66 n/a
13-3/4 (349) 0.76 0.73 0.68 0.81 0.65 0.52 0.64 0.61 0.59 0.78 0.56 0.37 0.81 0.65 0.52 0.75 0.67 0.58
14 (356) 0.77 0.73 0.68 0.82 0.66 0.53 0.64 0.62 0.59 0.81 0.58 0.38 0.82 0.66 0.53 0.76 0.68 0.59
15 (381) 0.79 0.75 0.70 0.88 0.71 0.55 0.65 0.62 0.59 0.89 0.64 0.42 0.88 0.71 0.55 0.79 0.70 0.61
16 (406) 0.81 0.77 0.71 0.94 0.75 0.58 0.67 0.63 0.60 0.99 0.71 0.46 0.94 0.75 0.58 0.81 0.73 0.63
17 (432) 0.83 0.78 0.72 1.00 0.80 0.62 0.68 0.64 0.61 1.00 0.78 0.50 1.00 0.80 0.62 0.84 0.75 0.65
18 (457) 0.84 0.80 0.74 0.85 0.65 0.69 0.65 0.61 0.85 0.55 0.85 0.65 0.86 0.77 0.67
20 (508) 0.88 0.84 0.76 0.94 0.72 0.71 0.67 0.62 0.99 0.64 0.94 0.72 0.91 0.81 0.70
24 (610) 0.96 0.90 0.82 1.00 0.87 0.75 0.70 0.65 1.00 0.85 1.00 0.87 1.00 0.89 0.77
30 (762) 1.00 1.00 0.90 1.00 0.81 0.75 0.69 1.00 1.00 1.00 0.86
36 (914) 0.97 0.87 0.80 0.72 0.95
> 48 (1219) 1.00 1.00 0.90 0.80 1.00
Table 10 — Load adjustment factors for 7/8, 1, and 1-1/4-in. diameter threaded rods in cracked concrete1,2
Edge distance in shear
Spacing factor in Edge distance factor Spacing factor in ┴ ‖ Concrete thickness
7/8, 1 & 1-1/4-in. tension in tension shear 4 factor in shear 5
cracked concrete Toward edge To edge
ƒAN ƒRN ƒAV ƒHV
ƒRV ƒRV
Thread size, in. 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4 7/8 1 1 1/4
in. 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11 6-5/8 8-1/4 11
Embedment hef
(mm) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279) (168) (210) (279)
4-3/8 (111) 0.58 n/a n/a 0.53 n/a n/a 0.55 n/a n/a 0.14 n/a n/a 0.28 n/a n/a n/a n/a n/a
5 (127) 0.60 0.58 n/a 0.56 0.53 n/a 0.55 0.54 n/a 0.17 0.12 n/a 0.35 0.25 n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
6 (152) 0.61 0.60 n/a 0.61 0.58 n/a 0.56 0.55 n/a 0.23 0.16 n/a 0.46 0.33 n/a n/a n/a n/a
6-1/4 (159) 0.62 0.60 0.58 0.62 0.59 0.53 0.56 0.55 0.54 0.24 0.17 0.11 0.49 0.35 0.23 n/a n/a n/a
7 (178) 0.63 0.62 0.59 0.66 0.62 0.56 0.57 0.56 0.54 0.29 0.21 0.13 0.57 0.41 0.27 n/a n/a n/a
8 (203) 0.65 0.63 0.61 0.71 0.66 0.59 0.58 0.57 0.55 0.35 0.25 0.16 0.70 0.51 0.33 n/a n/a n/a
8-5/8 (219) 0.67 0.64 0.61 0.75 0.69 0.61 0.59 0.57 0.55 0.39 0.28 0.18 0.75 0.57 0.37 0.60 n/a n/a
9 (229) 0.67 0.65 0.62 0.77 0.71 0.62 0.59 0.57 0.56 0.42 0.30 0.20 0.77 0.60 0.39 0.61 n/a n/a
10 (254) 0.69 0.67 0.63 0.82 0.75 0.66 0.60 0.58 0.56 0.49 0.35 0.23 0.82 0.71 0.46 0.64 n/a n/a
10-1/2 (267) 0.70 0.68 0.64 0.85 0.78 0.67 0.61 0.59 0.57 0.53 0.38 0.25 0.85 0.76 0.49 0.66 0.59 n/a
11 (279) 0.71 0.68 0.65 0.88 0.80 0.69 0.61 0.59 0.57 0.57 0.41 0.26 0.88 0.80 0.53 0.68 0.61 n/a
12 (305) 0.73 0.70 0.66 0.94 0.85 0.73 0.62 0.60 0.57 0.65 0.46 0.30 0.94 0.85 0.60 0.71 0.63 n/a
13 (330) 0.75 0.72 0.67 1.00 0.90 0.76 0.63 0.61 0.58 0.73 0.52 0.34 1.00 0.90 0.68 0.73 0.66 n/a
13-3/4 (349) 0.76 0.73 0.68 0.94 0.79 0.64 0.61 0.59 0.79 0.57 0.37 0.94 0.74 0.76 0.68 0.59
14 (356) 0.77 0.73 0.68 0.95 0.80 0.65 0.62 0.59 0.81 0.59 0.38 0.95 0.76 0.76 0.68 0.59
15 (381) 0.79 0.75 0.70 1.00 0.84 0.66 0.62 0.59 0.90 0.65 0.42 1.00 0.84 0.79 0.71 0.61
16 (406) 0.81 0.77 0.71 0.88 0.67 0.63 0.60 0.99 0.71 0.46 0.88 0.81 0.73 0.63
17 (432) 0.83 0.78 0.72 0.92 0.68 0.64 0.61 1.00 0.78 0.51 0.92 0.84 0.75 0.65
18 (457) 0.84 0.80 0.74 0.96 0.69 0.65 0.61 0.85 0.55 0.96 0.86 0.77 0.67
20 (508) 0.88 0.84 0.76 1.00 0.71 0.67 0.62 1.00 0.65 1.00 0.91 0.82 0.71
24 (610) 0.96 0.90 0.82 0.75 0.70 0.65 0.85 1.00 0.89 0.77
30 (762) 1.00 1.00 0.90 0.81 0.75 0.69 1.00 1.00 0.87
36 (914) 0.97 0.87 0.80 0.72 0.95
> 48 (1219) 1.00 1.00 0.90 0.80 1.00
1 Linear interpolation not permitted
2 When combining multiple load adjustment factors (e.g. for a four-anchor pattern in a corner with thin concrete member) the design can become very
conservative. To optimize the design, use Hilti PROFIS Anchor Design software or perform anchor calculation using design equations from ACI 318 Chapter 17.
3 Spacing factor reduction in shear, ƒAV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒAV = ƒAN.
4 Concrete thickness reduction factor in shear, ƒHV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒHV = 1.0.
8 June 2019
Hilti HVU2 Adhesive Capsule System
Figure 3 — Hilti HIS-N and HIS-RN internally threaded insert installation conditions
Cracked Water-saturated
concrete concrete Diamond core drilling
Table 11 — Hilti HIS-N and HIS-RN internally threaded insert installation specifications
Thread Size
Setting information Symbol Units
3/8-16 UNC 1/2-13 UNC 5/8-11 UNC 3/4-10 UNC
Figure 4 — Hilti HIS-N and HIS-RN internally threaded inserts installed with Hilti HVU2 adhesive capsules
June 2019 9
Design of Hilti HVU2 adhesive capsules with HIS-N and HIS-RN inserts per ACI 318-14
Chapter 17
Hilti HVU2 adhesive capsule testing for ICC-ES ESR-4372 did not include the Hilti HIS-N and HIS-RN inserts. Additional testing
was performed with the HIS-N and HIS-RN inserts and the results evaluated per ACI 355.4 and ICC-ES AC308 and published in the
following tables. The tables include the design parameters per ACI 318-14 Ch. 17 and the parameters are calculated using
ACI 318-14 Ch. 17 to develop the Hilti Simplified Design Tables. For a detailed explanation of the Hilti Simplified Design Tables, refer
to section 3.1.8 of PTG Ed. 19.
Фd - 0.65
Anchor
Strength reduction factor for bond failure, water- - 1
category
saturated concrete
Фws - 0.65
1 Design information in this table is based on testing in accordance with ACI 355.4. 6 Bond strength values corresponding to concrete compressive strength f´c = 2,500 psi (17.2
2 See Figure 4. MPa). For concrete compressive strength, f´c, between
3 For all design cases, Ψc,N = 1.0. The appropriate coefficient for breakout resistance for 2,500 psi (17.2 MPa) and 8,000 psi (55.2 MPa), the tabulated characteristic bond strength
cracked concrete (kc,cr) or uncracked concrete (kc,uncr) must be used. may be increased by a factor of (f´c/2,500)n [for SI: (f´c / 17.2)n],
4 Values provided for post-installed anchors under Condition B without supplementary where n is as follows:
reinforcement as defined in ACI 318-14 17.3.3. n = 0 for uncracked concrete, all drilling methods
For cases where the presence of supplementary reinforcement can be verified, the n = 0.26 for cracked concrete, carbide bit or Hilti hollow drill bit
reduction factors associated with Condition A may be used. 7 Characteristic bond strengths are for horizontal and vertical downward direction only. For
5 Temperature range A: Max. short term temperature = 130°F (55°C), max. long term overhead (vertical up) installation, bond strengths must be multiplied by 0.70.
temperature = 110°F (43°C).
Temperature range B: Max. short term temperature = 176°F (80°C), max. long term
temperature = 110°F (43°C). 8
Temperature range C: Max. short term temperature = 248°F (120°C), max. long term
temperature = 162°F (72°C). need not be greater than 2.4, and
Short term elevated concrete temperatures are those that occur over brief intervals, e.g.,
as a result of diurnal cycling. Long term concrete temperatures are roughly constant over
significant periods of time. τk,uncr need not be greater than (use imperial units in all equations)
10 June 2019
Hilti HVU2 Adhesive Capsule System
Table 13 — H
VU2 adhesive capsule design information with Hilti
HIS-N and HIS-RN internally threaded inserts per Diamond core drilling
ACI 318-14 Chapter 17 1,2
Nominal bolt/cap screw diameter (in)
Setting information Symbol Units
3/8 1/2 5/8 3/4
Table 14 — S teel design strength for steel bolt and cap screw for Hilti HIS-N and HIS-RN internally
threaded inserts1,2,3
ASTM A193 Grade B8M
ASTM A193 B7
stainless steel
June 2019 11
Hammer drilling with
Table 15 — H
ilti HVU2 adhesive design strength with lesser of concrete or carbide tipped drill bit, or
bond failure for HIS-N and HIS-RN internally threaded inserts Hilti TE-CD or TE-YD
in uncracked concrete 1,2,3,4,5,6,7,8,9 Hollow Drill Bit
Tension — ФNn Shear — ФVn
Effective
Thread size embedment f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi
in. (mm) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 7,140 7,820 8,650 8,650 15,375 16,840 18,635 18,635
3/8-16 UNC
(110) (31.8) (34.8) (38.5) (38.5) (68.4) (74.9) (82.9) (82.9)
5 8,720 9,555 11,030 12,325 18,785 20,575 23,760 26,540
1/2-13 UNC
(125) (38.8) (42.5) (49.1) (54.8) (83.6) (91.5) (105.7) (118.1)
6-3/4 13,680 14,985 17,305 20,540 29,460 32,275 37,265 44,235
5/8-11 UNC
(170) (60.9) (66.7) (77.0) (91.4) (131.0) (143.6) (165.8) (196.8)
8-1/8 18,065 19,790 22,850 26,945 38,910 42,620 49,215 58,040
3/4-10 UNC
(205) (80.4) (88.0) (101.6) (119.9) (173.1) (189.6) (218.9) (258.2)
12 June 2019
Hilti HVU2 Adhesive Capsule System
Table 17 — H
ilti HVU2 adhesive design strength with lesser of concrete or
bond failure for HIS-N and HIS-RN internally threaded inserts Diamond core drilling
in uncracked concrete 1,2,3,4,5,6,7,8,9
Tension — ФNn Shear — ФVn
Effective
Thread size embedment f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi
in. (mm) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 7,140 7,820 8,215 8,215 15,375 16,840 17,700 17,700
3/8-16 UNC
(111) (31.8) (34.8) (36.5) (36.5) (68.4) (74.9) (78.7) (78.7)
5 8,720 9,555 11,030 11,700 18,785 20,575 23,760 25,205
1/2-13 UNC
(127) (38.8) (42.5) (49.1) (52.0) (83.6) (91.5) (105.7) (112.1)
6-3/4 13,680 14,985 17,305 19,505 29,460 32,275 37,265 42,010
5/8-11 UNC
(171) (60.9) (66.7) (77.0) (86.8) (131.0) (143.6) (165.8) (186.9)
8-1/8 18,065 19,790 22,850 25,590 38,910 42,620 49,215 55,115
3/4-10 UNC
(206) (80.4) (88.0) (101.6) (113.8) (173.1) (189.6) (218.9) (245.2)
Table 18 — H
ilti HVU2 adhesive design strength with lesser of concrete or
bond failure for HIS-N and HIS-RN internally threaded inserts Diamond core drilling
in cracked concrete 1,2,3,4,5,6,7,8,9,10
Tension — ФNn Shear — ФVn
Effective
Thread size embedment f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi f´c = 2500 psi f´c = 3000 psi f´c = 4000 psi f´c = 6000 psi
in. (mm) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa) (17.2 Mpa) (20.7 Mpa) (27.6 Mpa) (41.4 Mpa)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 2,935 3,030 3,190 3,435 6,315 6,525 6,875 7,395
3/8-16 UNC
(111) (13.1) (13.5) (14.2) (15.3) (28.1) (29.0) (30.6) (32.9)
5 4,175 4,315 4,545 4,890 8,995 9,295 9,790 10,530
1/2-13 UNC
(127) (18.6) (19.2) (20.2) (21.8) (40.0) (41.3) (43.5) (46.8)
6-3/4 6,960 7,195 7,575 8,150 14,990 15,495 16,315 17,550
5/8-11 UNC
(171) (31.0) (32.0) (33.7) (36.3) (66.7) (68.9) (72.6) (78.1)
8-1/8 9,135 9,440 9,940 10,690 19,670 20,325 21,405 23,030
3/4-10 UNC
(206) (40.6) (42.0) (44.2) (47.6) (87.5) (90.4) (95.2) (102.4)
1 See Section 3.1.8 of PTG Ed. 19 for explanation on development of load values.
2 See Section 3.1.8 of PTG Ed. 19 to convert design strength value to ASD value.
3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted.
4 Apply spacing, edge distance, and concrete thickness factors in tables 19 – 20 as necessary to the above values. Compare to the steel values in table 14.
The lesser of the values is to be used for the design.
5 Data is for temperature range A: Max. short term temperature = 130°F (55°C), max. long term temperature = 110°F (43°C).
For temperature range B: Max. short term temperature = 176°F (80°C), max. long term temperature = 110°F (43°C) multiply above value by 0.94.
For temperature range C: Max. short term temperature = 248°F (120°C), max. long term temperature = 162°F (72°C) multiply above value by 0.60.
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant
periods of time.
6 Tabular values are for dry or water saturated concrete conditions.
7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8 of PTG Ed. 19.
8 Tabular values are for normal weight concrete only. For lightweight concrete multiply design strength by λa as follows:
For sand-lightweight, λa = 0.51. For all-lightweight, λ a = 0.45.
9 Tabular values are for horizontal and vertical downward direction only. For overhead (vertical up) installation, tabular values must be multiplied by 0.70.
10 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete. For seismic loads, multiply cracked concrete tabular values in tension and shear
by αseis = 0.75.
See section 3.1.8 of PTG Ed. 19 for additional information on seismic applications.
June 2019 13
Table 19 — L
oad adjustment factors for Hilti HIS-N and HIS-RN internally threaded inserts in uncracked
concrete 1,2
HIS-N and Edge distance in shear
HIS-RN Spacing factor in Edge distance factor Spacing factor in Concrete thickness
tension in tension shear 3 ┴ ‖ factor in shear 4
all diameters ƒAN ƒRN ƒAV Toward edge To edge ƒHV
cracked concrete ƒRV ƒRV
Thread size, in. 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4
Embedment in. 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8
hef (mm) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206)
3-1/4 (83) 0.61 n/a n/a n/a 0.40 n/a n/a n/a 0.55 n/a n/a n/a 0.15 n/a n/a n/a 0.31 n/a n/a n/a n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
4 (102) 0.63 0.61 n/a n/a 0.45 0.42 n/a n/a 0.56 0.55 n/a n/a 0.21 0.19 n/a n/a 0.42 0.38 n/a n/a n/a n/a n/a n/a
5 (127) 0.67 0.63 0.61 n/a 0.51 0.47 0.40 n/a 0.57 0.57 0.55 n/a 0.29 0.26 0.17 n/a 0.51 0.47 0.33 n/a n/a n/a n/a n/a
5-1/2 (140) 0.68 0.65 0.62 0.61 0.55 0.50 0.42 0.38 0.58 0.58 0.56 0.55 0.34 0.30 0.19 0.15 0.55 0.50 0.39 0.29 n/a n/a n/a n/a
6 (152) 0.70 0.66 0.63 0.62 0.59 0.53 0.44 0.39 0.59 0.58 0.56 0.55 0.39 0.35 0.22 0.17 0.59 0.53 0.44 0.33 0.60 n/a n/a n/a
7 (178) 0.73 0.69 0.65 0.64 0.67 0.60 0.48 0.43 0.60 0.60 0.57 0.56 0.49 0.43 0.28 0.21 0.67 0.60 0.48 0.42 0.64 0.62 n/a n/a
8 (203) 0.76 0.71 0.67 0.66 0.77 0.67 0.53 0.46 0.62 0.61 0.58 0.57 0.60 0.53 0.34 0.26 0.77 0.67 0.53 0.46 0.69 0.66 n/a n/a
9 (229) 0.80 0.74 0.69 0.68 0.86 0.76 0.57 0.50 0.63 0.62 0.59 0.58 0.71 0.63 0.40 0.31 0.86 0.76 0.57 0.50 0.73 0.70 0.60 n/a
10 (254) 0.83 0.77 0.71 0.70 0.96 0.84 0.62 0.53 0.65 0.64 0.60 0.58 0.83 0.74 0.47 0.36 0.96 0.84 0.62 0.53 0.77 0.74 0.64 n/a
11 (279) 0.86 0.79 0.74 0.72 1.00 0.92 0.68 0.57 0.66 0.65 0.61 0.59 0.96 0.86 0.55 0.41 1.00 0.92 0.68 0.57 0.81 0.78 0.67 0.61
12 (305) 0.90 0.82 0.76 0.74 1.00 0.74 0.61 0.68 0.66 0.62 0.60 1.00 0.98 0.62 0.47 1.00 0.74 0.61 0.84 0.81 0.70 0.64
14 (356) 0.96 0.87 0.80 0.78 0.87 0.71 0.71 0.69 0.64 0.62 1.00 0.78 0.59 0.87 0.71 0.91 0.87 0.75 0.69
16 (406) 1.00 0.92 0.84 0.82 0.99 0.82 0.74 0.72 0.66 0.63 0.96 0.73 0.99 0.82 0.97 0.94 0.80 0.73
18 (457) 0.98 0.89 0.85 1.00 0.92 0.77 0.75 0.68 0.65 1.00 0.87 1.00 0.92 1.00 0.99 0.85 0.78
24 (610) 1.00 1.00 0.97 1.00 0.85 0.83 0.74 0.70 1.00 1.00 1.00 0.99 0.90
30 (762) 1.00 0.94 0.91 0.80 0.75 1.00 1.00
36 (914) 1.00 0.99 0.86 0.80
> 48 (1219) 1.00 0.99 0.90
Table 20 — L
oad adjustment factors for Hilti HIS-N and HIS-RN internally threaded inserts in cracked
concrete 1,2
HIS-N and Edge distance in shear
HIS-RN Spacing factor in Edge distance factor Spacing factor in Concrete thickness
tension in tension shear 3 ┴ ‖ factor in shear 4
all diameters ƒAN ƒRN ƒAV Toward edge To edge ƒHV
cracked concrete ƒRV ƒRV
Thread size, in. 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4 3/8 1/2 5/8 3/4
Embedment in. 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8 4-3/8 5 6-3/4 8-1/8
hef (mm) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206) (111) (127) (171) (206)
3-1/4 (83) 0.61 n/a n/a n/a 0.59 n/a n/a n/a 0.55 n/a n/a n/a 0.19 n/a n/a n/a 0.37 n/a n/a n/a n/a n/a n/a n/a
Spacing (s) / edge distance (ca) / concrete thickness (h), - in (mm)
4 (102) 0.63 0.61 n/a n/a 0.66 0.59 n/a n/a 0.57 0.56 n/a n/a 0.26 0.20 n/a n/a 0.51 0.39 n/a n/a n/a n/a n/a n/a
5 (127) 0.67 0.63 0.61 n/a 0.75 0.66 0.59 n/a 0.58 0.57 0.55 n/a 0.36 0.27 0.17 n/a 0.71 0.55 0.34 n/a n/a n/a n/a n/a
5-1/2 (140) 0.68 0.65 0.62 0.61 0.79 0.69 0.62 0.59 0.59 0.58 0.56 0.55 0.41 0.31 0.19 0.15 0.79 0.63 0.39 0.29 n/a n/a n/a n/a
6 (152) 0.70 0.66 0.63 0.62 0.84 0.73 0.65 0.62 0.60 0.58 0.56 0.55 0.47 0.36 0.22 0.17 0.84 0.72 0.44 0.34 0.63 n/a n/a n/a
7 (178) 0.73 0.69 0.65 0.64 0.94 0.80 0.70 0.67 0.62 0.60 0.57 0.56 0.59 0.45 0.28 0.21 0.94 0.80 0.56 0.42 0.69 0.63 n/a n/a
8 (203) 0.76 0.71 0.67 0.66 1.00 0.88 0.76 0.72 0.63 0.61 0.58 0.57 0.72 0.55 0.34 0.26 1.00 0.88 0.68 0.52 0.73 0.67 n/a n/a
9 (229) 0.80 0.74 0.69 0.68 0.96 0.83 0.78 0.65 0.63 0.59 0.58 0.86 0.66 0.41 0.31 0.96 0.82 0.62 0.78 0.71 0.61 n/a
10 (254) 0.83 0.77 0.71 0.70 1.00 0.89 0.84 0.67 0.64 0.60 0.58 1.00 0.77 0.48 0.36 1.00 0.89 0.72 0.82 0.75 0.64 n/a
11 (279) 0.86 0.79 0.74 0.72 0.96 0.90 0.68 0.65 0.61 0.59 0.89 0.55 0.42 0.96 0.83 0.86 0.79 0.67 0.61
12 (305) 0.90 0.82 0.76 0.74 1.00 0.96 0.70 0.67 0.62 0.60 1.00 0.63 0.48 1.00 0.95 0.90 0.82 0.70 0.64
14 (356) 0.96 0.87 0.80 0.78 1.00 0.73 0.70 0.64 0.62 0.79 0.60 1.00 0.97 0.89 0.76 0.69
16 (406) 1.00 0.92 0.84 0.82 0.77 0.72 0.66 0.64 0.97 0.73 1.00 0.95 0.81 0.74
18 (457) 0.98 0.89 0.85 0.80 0.75 0.68 0.65 1.00 0.87 1.00 0.86 0.78
24 (610) 1.00 1.00 0.97 0.90 0.84 0.74 0.70 1.00 0.99 0.90
30 (762) 1.00 1.00 0.92 0.81 0.75 1.00 1.00
36 (914) 1.00 0.87 0.80
> 48 (1219) 0.99 0.91
1 Linear interpolation not permitted
2 When combining multiple load adjustment factors (e.g. for a four-anchor pattern in a corner with thin concrete member) the design can become very conservative. To optimize the design, use
Hilti PROFIS Anchor Design software or perform anchor calculation using design equations from ACI 318 Chapter 17.
3 Spacing factor reduction in shear, ƒAV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒAV = ƒAN.
4 Concrete thickness reduction factor in shear, ƒHV, is applicable when edge distance c < 3*hef. If c ≥ 3*hef, then ƒHV = 1.0.
14 June 2019
Hilti HVU2 Adhesive Capsule System
For a detailed explanation of the tables developed in accordance with CSA A23.3-14 Annex D, refer to Section 3.1.8 (PTG Ed. 19).
Technical assistance is available by contacting Hilti Canada at (800) 363-4458 or at www.hilti.com.
Hilti HAS threaded rod with setting tip — See Table 1 and Figures 1 and 2 of this document for installation parameters
Rdry - 1.00
Anchor
Strength reduction factor for bond failure, water- - 1
category D.5.3 (c )
saturated concrete
Rws - 1.00
1 Design information in this table is taken from ICC-ES ESR-4372, dated May, 2019, Tables 4 6 Bond strength values corresponding to concrete compressive strength f´c = 2,500 psi (17.2
and 5, and converted for use with CSA A23.3-14 Annex D. MPa). For concrete compressive strength, f´c, between 2,500 psi (17.2 MPa) and 8,000
2 See Figure 2. psi (55.2 MPa), the tabulated characteristic bond strength may be increased by a factor of
3 For all design cases, Ψc,N = 1.0. The appropriate coefficient for breakout resistance for (f´c/2,500)n [for SI: (f´c / 17.2)n].
cracked concrete (kc,cr) or uncracked concrete (kc,uncr) must be used. where n is as follows:
4 For use with the load combinations of CSA A23.3-14 chapter 8. Condition B applies n = 0.26 for uncracked concrete
where supplementary reinforcement in conformance with CSA A23.3-14 section D.5.3 is n = 0.14 for cracked concrete
not provided, or where pullout or pryout strength governs. For cases where the presence 7 For 3/8-in. to 1-in. rods, characteristic bond strengths are for horizontal and vertical
of supplementary reinforcement can be verified, the resistance modification factors downward direction only. For overhead (vertical up) installation, bond strengths must be
associated with Condition A may be used. multiplied by 0.70.
5 Temperature range A: Max. short term temperature = 130°F (55°C), max. long term 8 1-1/4-in. diameter rods to be installed in generally vertically downward direction only.
temperature = 110°F (43°C).
Temperature range B: Max. short term temperature = 176°F (80°C), max. long term
temperature = 110°F (43°C). 9
Temperature range C: Max. short term temperature = 248°F (120°C), max. long term
temperature = 162°F (72°C). need not be greater than 2.4, and
Short term elevated concrete temperatures are those that occur over brief intervals, e.g.,
as a result of diurnal cycling. Long term concrete temperatures are roughly constant over
significant periods of time. τk,uncr need not be greater than (use imperial units in all equations)
June 2019 15
Table 22 — Hilti HVU2 design information with HAS threaded rods per
Diamond core drilling
CSA A23.3-14 Annex D 1,2
Nominal rod diameter (in.)
Ref
Design parameter Symbol Units
A23.3-14
1/2 5/8 3/4 7/8 1 1-1/4 6
Table 23 — Steel factored resistance for Hilti HAS threaded rods for use with CSA A23.3-14 Annex D
HAS-B-105 / HAS-B-105 HDG HAS-R stainless steel
HAS-E-55 / HAS-E-55 HDG
ASTM A193 B7 and ASTM F593 (3/8-in to 1-in)5
ASTM F1554 Gr. 554,6
Nominal ASTM F 1554 Gr.1054,6 ASTM A193 (1-1/8-in to 2-in)4
anchor
diameter Seismic Seismic Seismic
in. Tensile1 Shear2 Shear3 Tensile1 Shear2 Shear3 Tensile1 Shear2 Shear3
ФNsar ФVsar ФVsar,eq ФNsar ФVsar ФVsar,eq ФNsar ФVsar ФVsar,eq
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
16 June 2019
Hilti HVU2 Adhesive Capsule System
June 2019 17
Table 26 — H
ilti HVU2 adhesive factored resistance with lesser
of concrete or bond failure for threaded rod in Diamond core drilling
uncracked concrete 1,2,3,4,5,6,7,8
Nominal Tension — Nr Shear — Vr
Effective
anchor f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa
embedment
diameter (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi)
in. (mm)
in. lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-1/4 7,330 8,195 8,975 9,890 14,660 16,390 17,955 19,785
1/2
(108) (32.6) (36.5) (39.9) (44.0) (65.2) (72.9) (79.9) (88.0)
5 9,355 10,455 11,455 13,225 18,705 20,915 22,910 26,455
5/8
(127) (41.6) (46.5) (51.0) (58.8) (83.2) (93.0) (101.9) (117.7)
6-5/8 14,265 15,950 17,470 20,175 28,530 31,900 34,940 40,350
3/4
(168) (63.5) (70.9) (77.7) (89.7) (126.9) (141.9) (155.4) (179.5)
6-5/8 14,265 15,950 17,470 20,175 28,530 31,900 34,940 40,350
7/8
(168) (63.5) (70.9) (77.7) (89.7) (126.9) (141.9) (155.4) (179.5)
8-1/4 19,825 22,165 24,280 28,035 39,645 44,325 48,555 56,070
1
(210) (88.2) (98.6) (108.0) (124.7) (176.4) (197.2) (216.0) (249.4)
11 30,520 34,120 37,380 43,160 61,040 68,245 74,760 86,325
1-1/4 (10)
(279) (135.8) (151.8) (166.3) (192.0) (271.5) (303.6) (332.5) (384.0)
Table 27 — H
ilti HVU2 adhesive factored resistance with lesser of
concrete or bond failure for threaded rod in cracked Diamond core drilling
concrete 1,2,3,4,5,6,7,8,9
Nominal Tension — Nr Shear — Vr
Effective
anchor f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa
embedment
diameter (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi)
in. (mm)
in. lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-1/4 4,665 4,665 4,665 4,665 9,330 9,330 9,330 9,330
1/2
(108) (20.8) (20.8) (20.8) (20.8) (41.5) (41.5) (41.5) (41.5)
5 6,545 6,860 6,860 6,860 13,095 13,725 13,725 13,725
5/8
(127) (29.1) (30.5) (30.5) (30.5) (58.2) (61.0) (61.0) (61.0)
6-5/8 9,985 10,910 10,910 10,910 19,970 21,820 21,820 21,820
3/4
(168) (44.4) (48.5) (48.5) (48.5) (88.8) (97.1) (97.1) (97.1)
6-5/8 9,985 11,165 12,230 12,730 19,970 22,330 24,460 25,455
7/8
(168) (44.4) (49.7) (54.4) (56.6) (88.8) (99.3) (108.8) (113.2)
8-1/4 13,875 15,515 16,995 18,115 27,755 31,030 33,990 36,230
1
(210) (61.7) (69.0) (75.6) (80.6) (123.4) (138.0) (151.2) (161.2)
11 21,365 23,885 26,165 30,190 42,730 47,770 52,330 60,385
1-1/4 (10)
(279) (95.0) (106.2) (116.4) (134.3) (190.1) (212.5) (232.8) (268.6)
1 See Section 3.1.8 of PTG Ed. 19 for explanation on development of load values.
2 See Section 3.1.8 of PTG Ed. 19 to convert design strength value to ASD value.
3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted.
4 Apply spacing, edge distance, and concrete thickness factors in tables 7 – 10 as necessary. Compare to the steel values in table 23.
The lesser of the values is to be used for the design.
5 Data is for temperature range A: Max. short term temperature = 130°F (55°C), max. long term temperature = 110°F (43°C).
For temperature range B: Max. short term temperature = 176°F (80°C), max. long term temperature = 110°F (43°C) multiply above value by 0.93.
For temperature range C: Max. short term temperature = 248°F (120°C), max. long term temperature = 162°F (72°C) multiply above value by 0.58.
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant
periods of time.
6 Tabular values are for dry or water saturated concrete conditions.
7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8 of PTG Ed. 19.
8 Tabular values are for normal weight concrete only. For lightweight concrete multiply design strength by λa as follows:
For sand-lightweight, λa = 0.51. For all-lightweight, λ a = 0.45.
9 For 1/2-in to 1-in dia. threaded rods, tabular values are for horizontal and vertical downward direction only. For overhead (vertical up) installation, tabular values must be multiplied by 0.70.
10 1-1/4-in diameter rods to be installed in generally vertically downward direction only.
11 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete. For seismic loads, multiply cracked concrete tabular values in tension and shear
by αseis = 0.75.
See section 3.1.8 of PTG Ed. 19 for additional information on seismic applications.
18 June 2019
Hilti HVU2 Adhesive Capsule System
Hilti HIS-N and HIS-RN internally threaded insert – See Table 11 and Figures 3 and 4 of this document for installation parameters
Rdry - 1.00
Anchor
Strength reduction factor for bond failure, water- - 1
category D.5.3 (c )
saturated concrete
Rws - 1.00
1 Design information in this table is based on testing in accordance with ACI 355.4.
2 See Figure 4.
3 For all design cases, Ψc,N = 1.0. The appropriate coefficient for breakout resistance for cracked concrete (kc,cr) or uncracked concrete (kc,uncr) must be used.
4 Values provided for post-installed anchors under Condition B without supplementary reinforcement as defined in CSA A23.3-14 Section D.5.3.
For cases where the presence of supplementary reinforcement can be verified, the reduction factors associated with Condition A may be used.
5 Temperature range A: Max. short term temperature = 130°F (55°C), max. long term temperature = 110°F (43°C).
Temperature range B: Max. short term temperature = 176°F (80°C), max. long term
Temperature range C: Max. short term temperature = 248°F (120°C), max. long term temperature = 162°F (72°C).
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., over significant periods of time.
6 Bond strength values corresponding to concrete compressive strength f´c = 2,500 psi (17.2 MPa). For concrete compressive strength, f´c, between
7 Characteristic bond strengths are for horizontal and vertical downward direction only. For overhead (vertical up) installation, bond strengths must be multiplied by 0.70.
τk,uncr need not be greater than (use metric units in all equations)
June 2019 19
Table 29 — H
VU2 adhesive capsule design information with Hilti
HIS-N and HIS-RN internally threaded inserts per CSA Diamond core drilling
A23.3-14 Annex D 1,2
Nominal rod diameter (in.) Ref
Design parameter Symbol Units
3/8 1/2 5/8 3/4 A23.3-14
psi 505 505 505 505 D.6.5.2
τcr
range A 3
Table 30 — Steel factored resistance for steel bolt/cap screw for Hilti HIS-N and HIS-RN internally threaded
inserts1,2,3
ASTM A193 B7 ASTM A193 Grade B8M Stainless Steel
20 June 2019
Hilti HVU2 Adhesive Capsule System
Table 31 — Hilti HVU2 adhesive factored resistance with lesser Hammer drilling with
of concrete or bond failure for HIS-N and HIS-RN carbide tipped drill bit, or
internally threaded inserts in uncracked Hilti TE-CD or TE-YD
concrete 1,2,3,4,5,6,7,8,9 Hollow Drill Bit
Tension — Nr Shear — Vr
Effective
Thread size embedment f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa
in. (mm) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 7,540 8,430 8,555 8,555 15,080 16,860 17,110 17,110
3/8-16 UNC
(110) (33.5) (37.5) (38.0) (38.0) (67.1) (75.0) (76.1) (76.1)
5 9,135 10,210 11,185 12,115 18,265 20,420 22,370 24,225
1/2-13 UNC
(125) (40.6) (45.4) (49.8) (53.9) (81.3) (90.8) (99.5) (107.8)
6-3/4 14,485 16,195 17,740 20,340 28,970 32,390 35,480 40,675
5/8-11 UNC
(170) (64.4) (72.0) (78.9) (90.5) (128.9) (144.1) (157.8) (180.9)
8-1/8 19,180 21,445 23,490 26,735 38,360 42,890 46,985 53,465
3/4-10 UNC
(205) (85.3) (95.4) (104.5) (118.9) (170.6) (190.8) (209.0) (237.8)
1 See Section 3.1.8 of PTG Ed. 19 for explanation on development of load values.
2 See Section 3.1.8 of PTG Ed. 19 to convert design strength value to ASD value.
3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted.
4 Apply spacing, edge distance, and concrete thickness factors in tables 19 – 20 as necessary to the above values. Compare to the steel values in table 30.
The lesser of the values is to be used for the design.
5 Data is for temperature range A: Max. short term temperature = 130°F (55°C), max. long term temperature = 110°F (43°C).
For temperature range B: Max. short term temperature = 176°F (80°C), max. long term temperature = 110°F (43°C) multiply above value by 0.93.
For temperature range C: Max. short term temperature = 248°F (120°C), max. long term temperature = 162°F (72°C) multiply above value by 0.58.
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant
periods of time.
6 Tabular values are for dry or water saturated concrete conditions.
7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8 of PTG Ed. 19.
8 Tabular values are for normal weight concrete only. For lightweight concrete multiply design strength by λa as follows:
For sand-lightweight, λa = 0.51. For all-lightweight, λ a = 0.45.
9 Tabular values are for horizontal and vertical downward direction only. For overhead (vertical up) installation, tabular values must be multiplied by 0.70.
10 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete. For seismic loads, multiply cracked concrete tabular values in tension and shear by
αseis = 0.75.
See section 3.1.8 of PTG Ed. 19 for additional information on seismic applications.
June 2019 21
Table 33 — H
ilti HVU2 adhesive factored resistance with lesser
of concrete or bond failure for HIS-N and HIS-RN
Diamond core drilling
internally threaded inserts in uncracked
concrete 1,2,3,4,5,6,7,8,9
Tension — Nr Shear — Vr
Effective
Thread size embedment f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa
in. (mm) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 7,540 8,145 8,145 8,145 15,080 16,290 16,290 16,290
3/8-16 UNC
(110) (33.5) (36.2) (36.2) (36.2) (67.1) (72.5) (72.5) (72.5)
5 9,135 10,210 11,185 11,535 18,265 20,420 22,370 23,070
1/2-13 UNC
(125) (40.6) (45.4) (49.8) (51.3) (81.3) (90.8) (99.5) (102.6)
6-3/4 14,485 16,195 17,740 19,365 28,970 32,390 35,480 38,735
5/8-11 UNC
(170) (64.4) (72.0) (78.9) (86.1) (128.9) (144.1) (157.8) (172.3)
8-1/8 19,180 21,445 23,490 25,455 38,360 42,890 46,985 50,910
3/4-10 UNC
(205) (85.3) (95.4) (104.5) (113.2) (170.6) (190.8) (209.0) (226.5)
Table 34 — H
ilti HVU2 adhesive factored resistance with lesser of
concrete or bond failure for HIS-N and HIS-RN internally Diamond core drilling
threaded inserts in cracked concrete 1,2,3,4,5,6,7,8,9,10
Tension — Nr Shear — Vr
Effective
Thread size embedment f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa f´c = 20 MPa f´c = 25 MPa f´c = 30 MPa f´c = 40 MPa
in. (mm) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi) (2,900 psi) (3,625 psi) (4,350 psi) (5,800 psi)
lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN) lb (kN)
4-3/8 2,990 3,110 3,215 3,385 5,980 6,225 6,430 6,775
3/8-16 UNC
(110) (13.3) (13.8) (14.3) (15.1) (26.6) (27.7) (28.6) (30.1)
5 4,235 4,405 4,555 4,795 8,465 8,815 9,110 9,595
1/2-13 UNC
(125) (18.8) (19.6) (20.3) (21.3) (37.7) (39.2) (40.5) (42.7)
6-3/4 7,110 7,400 7,645 8,055 14,215 14,800 15,295 16,105
5/8-11 UNC
(170) (31.6) (32.9) (34.0) (35.8) (63.2) (65.8) (68.0) (71.6)
8-1/8 9,345 9,725 10,050 10,585 18,685 19,455 20,100 21,170
3/4-10 UNC
(205) (41.6) (43.3) (44.7) (47.1) (83.1) (86.5) (89.4) (94.2)
1 See Section 3.1.8 of PTG Ed. 19 for explanation on development of load values.
2 See Section 3.1.8 of PTG Ed. 19 to convert design strength value to ASD value.
3 Linear interpolation between embedment depths and concrete compressive strengths is not permitted.
4 Apply spacing, edge distance, and concrete thickness factors in tables 19 – 20 as necessary to the above values. Compare to the steel values in table 30.
The lesser of the values is to be used for the design.
5 Data is for temperature range A: Max. short term temperature = 130°F (55°C), max. long term temperature = 110°F (43°C).
For temperature range B: Max. short term temperature = 176°F (80°C), max. long term temperature = 110°F (43°C) multiply above value by 0.94.
For temperature range C: Max. short term temperature = 248°F (120°C), max. long term temperature = 162°F (72°C) multiply above value by 0.60.
Short term elevated concrete temperatures are those that occur over brief intervals, e.g., as a result of diurnal cycling. Long term concrete temperatures are roughly constant over significant
periods of time.
6 Tabular values are for dry or water saturated concrete conditions.
7 Tabular values are for short term loads only. For sustained loads including overhead use, see Section 3.1.8 of PTG Ed. 19.
8 Tabular values are for normal weight concrete only. For lightweight concrete multiply design strength by λa as follows:
For sand-lightweight, λ a = 0.51. For all-lightweight, λ a = 0.45.
9 Tabular values are for horizontal and vertical downward direction only. For overhead (vertical up) installation, tabular values must be multiplied by 0.70.
10 Tabular values are for static loads only. Seismic design is not permitted for uncracked concrete. For seismic loads, multiply cracked concrete tabular values in tension and shear by
αseis = 0.75.
See section 3.1.8 of PTG Ed. 19 for additional information on seismic applications.
22 June 2019
Hilti HVU2 Adhesive Capsule System
INSTALLATION INSTRUCTIONS
Installation Instructions For Use (IFU) are included with each product package. They can also be viewed or downloaded online
at www.hilti.com and www.hilti.ca. Because of the possibility of changes, always verify that downloaded IFU are current when
used. Proper installation is critical to achieve full performance. Training is available on request. Contact Hilti Technical Services for
applications and conditions not addressed in the IFU.
MATERIAL SPECIFICATIONS
Figure 5 — Hilti HVU2 adhesive cure time (approx.) Table 36 — Resistance of fully cured Hilti HVU2
adhesive to chemicals
[°C] [°F] Chemical substance Components
Content
Behavior
tcure [Vol. %]
Test mixture A 20/NP 2 95.0
-10…-6 14…22 5h Diesel-Fuel
Biodiesel 5.0
+
-5…-1 23…31 3h
Alcohol Methanol 100.0 -
0…4 32…40 40 min
Aliphatic
5…9 41…49 20 min halogenated
Dichlormethane (Methylene
100.0 -
chloride)
10…19 50…67 10 min hydrocarbons
20…40 68…104 5 min Texapon N 28 3.0
Aqueous organic
Marlipal O 13/8 2.0 +
surfactants/Tensides
Water 95.0
Table 35 — Material properties of fully cured Hilti Organic esters and Ethylacetate 50.0
+
ketones Methylisobutylketone 50.0
HVU2 adhesive
Aqueous organic
Compressive strength @ 73°F (23°C) / 11,200 psi 77.30 N/mm2 Acqueous acetic acid (10%) 100.0 +
acids
50% humidity
Acetic acid 50.0
Tensile strength 1,241 psi 8.56 N/mm2 Organic acids -
Propionic acid 50.0
Water absorption after 24h 0.26%
Inorganic acids Sulfuric acid (20%) 100.0 +
n-Butyraldehyde (Butanal) 50.0
Aliphatic Aldehydes +
n-Heptaldehyde (Heptanal) 50.0
ORDERING INFORMATION
Order information Accessories
Description 9 Item number
① HAS anchor rods with setting tip ① ②
Adhesive capsule HVU2 3/8” x 3 1/2” 2234720
Adhesive capsule HVU2 1/2” x 4 1/4” 2234721 ② HIS-N / HIS-RN internally threaded inserts
③ ④
Adhesive capsule HVU2 5/8” x 5” 2234722
Adhesive capsule HVU2 3/4” x 6 5/8” 2234723 ③ SF 6H-A22 cordless drill driver
June 2019 23