You are on page 1of 1

3x1Cx300 sq.

mm-N2XY-TP
1x1Cx300 sq.mm-N2XY-N
25000A
MDB-03

PFI-03, RYB-1
Capacity: 630KVAR

1250A-TP-MCCB (Setting: 90%)

2x1Cx150 sq.mm-Cu-XLPE-TP
1x1Cx150 sq.mm-Cu-XLPE-N

PRAN Group
DB No: 29 RYB-2
Panel Busbar Details:

PROJECT:
Husky m/c No-06
TCL: 320 KW 630A-TP-MCCB (Setting: 80%)

PRAN Industrial Park


Bagpara, Palash, Narsingdi
2x1Cx150 sq.mm-Cu-XLPE-TP
1x1Cx150 sq.mm-Cu-XLPE-N
DB No: 32 RYB-3
Hotfill-HP-Compressor
TCL: 330 KW 630A-TP-MCCB (Setting: 80%)
160mmX5mmX1Pc-1200A-N Copper busber
30mmX5mmX1Pc-240A-ECC Copper busber
160mmX5mmX2Pc-2560A-TP Copper busber

2x1Cx185 sq.mm-Al-XLPE-TP
DB No: 56 1x1Cx185 sq.mm-Al-XLPE-N

PRAN Dairy Limited


RYB-4
B/G-Central AHU
MDB-03
TCL: 350 KW
630A-TP-MCCB (Setting: 75%) TCL: 1500KW
Y B
A A A

1X4Cx25 sq.mm, N2XY-3P+N


VS

DB No: 82
DTW-02 RYB-5
V

TCL: 55 KW
400A-TP-MCCB (Setting: 50%)
DESIGNED BY:

Sharif Uddin
Sr. Maint. Engr
CT Ratio: 2500:5A

2x1Cx150 sq.mm-N2XY-TP

Power Station-Unit-1
Incoming cable details:

DB No: 50 1x1Cx150 sq.mm-N2XY-N


Husky-7 RYB-6
TCL: 330 KW
630A-TP-MCCB (Setting: 80%)
Brand: GE (Mpact-Plus)

Length-Main SYNC to MDB-25 meter


TP-ACB-2500A (Setting 95%)

2x1Cx150 sq.mm-N2XY-TP
1x1Cx150 sq.mm-N2XY-N
FEED FROM MAIN SYNCHRONIZATION BUSBAR (Outgoing-3)

DB No: 30 RYB-7
Husky-4
TCL: 330 KW 630A-TP-MCCB (Setting: 80%)
APPROVED BY:

PRAN Dairy Limited


Engr. Md. Idris Ali
Deputy Chief Engineer
1x240 sq.mmX5-N2XY/Phase and 1x240 sq.mmX2-neutral
N-Neutral

A-Ammeter

1x1.5 RM-Flexible-Cu R-8


V-Voltmeter

ACB Controlling
SP-06A
SP-Single Pole
TP-Tripple Pole

1x1.5 RM-Flexible-Cu R-9


ACB Controlling
SP-06A
1x1.5 RM-Flexible-Cu R-10
ACB-Air Circuit Breaker

CT-Current Transformer

ACB Controlling
SP-06A
VS-Selector Switch for Volt
TCL-Total Connected Load

1x1.5 RM-Flexible-Cu R-11


MDB-Main Distribution Board

Cooling Fan SP-06A


ECC-Earth Continuity Conductor

DRAWING TITLE:

SLD of MDB-3

1X1CX6RM,BYA(DOOR)

You might also like