Testing & Commissioning Record Sheet for L.V Cables (Cold Test)
Project Tiltle: DOUBLE TREE RESORTS & SPA BY HILTON
Main Contractor: M/s. Ali Al const. & Development Panel Ref.No: SMDB-ROOF (CHALET-01)
MEP Contractor M/s. Ali Al const. & Development Panel Location: Chalet-1, Roof Electrical Room
Consultant M/S. ATKINS Drawing Ref.No As built Single line diagram attached
Incoming Cable Insulation resistance (MΩ) & Continuity Test
Protective Device Type: MCCB Rating: 28/40A Applied Voltage: 1000 V
(Cold Test)
Source: SMDB-CH-1 Setting: 40A RY RB YB RN YN BN RE YE BE NE Continuity
Supply Cable Size: 4Cx16mm2 CPC: 1Cx16mm2 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 - P
Outgoing Cables Insulation resistance (MΩ) & Continuity Test
Circuit Designation Type of Breaker Applied Voltage: 1000 V
Circuit No. Cable (mm2) (Cold Test)
Cable Rating (A)
From To R-Y R-B Y-B R-N Y-N B-N R-E B-E Y-E N-E Continuity
RYB1 SMDB-ROOF FAHU-1 4Cx10+1Cx6 20 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 - P
Y3 SMDB-ROOF SPACE - - - - - - - - - - - - -
Calibration Certificate No: As Attached Calibration Date: 26.06.13 Calibration Expiry Date: 25.06.2014
Name: M. BASITH
Signature:
Date: 19.11.2013