Testing & Commissioning Record Sheet for L.V Cables (Cold Test)
Project Tiltle: DOUBLE TREE RESORTS & SPA BY HILTON

Main Contractor: M/s. Ali Al const. & Development Panel Ref.No: SMDB-ROOF (CHALET-01)

MEP Contractor M/s. Ali Al const. & Development Panel Location: Chalet-1, Roof Electrical Room

Consultant M/S. ATKINS Drawing Ref.No As built Single line diagram attached
Incoming Cable Insulation resistance (MΩ) & Continuity Test
Protective Device Type: MCCB Rating: 28/40A Applied Voltage: 1000 V
(Cold Test)
Source: SMDB-CH-1 Setting: 40A RY RB YB RN YN BN RE YE BE NE Continuity

Supply Cable Size: 4Cx16mm2 CPC: 1Cx16mm2 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 - P
Outgoing Cables Insulation resistance (MΩ) & Continuity Test
Circuit Designation Type of Breaker Applied Voltage: 1000 V
Circuit No. Cable (mm2) (Cold Test)
Cable Rating (A)
From To R-Y R-B Y-B R-N Y-N B-N R-E B-E Y-E N-E Continuity

RYB1 SMDB-ROOF FAHU-1 4Cx10+1Cx6 20 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 - P

XLPE/SWA/PVC & CU.PVC.ECC


RYB2 SMDB-ROOF FAHU-2 4Cx10+1Cx6 20 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 - P

R3 SMDB-ROOF WATER HEAT 3CX6 20 - - - >1000 - - >1000 - - - P

Y3 SMDB-ROOF SPACE - - - - - - - - - - - - -

B3 SMDB-ROOF HEAT PUMP 3CX4 20 - - - - - >1000 - - >1000 - P

R4 SMDB-ROOF WATER HEAT 3CX4 20 - - - >1000 - - >1000 - - - P

Y4 SMDB-ROOF WATER HEAT 3CX4 20 - - - - >1000 - - >1000 - - P

B4 SMDB-ROOF WATER HEAT 3CX4 20 - - - - - >1000 - - >1000 - P

Instrument Make/Model: Megger/MIT310EN101240632 Instrument Serial No: MIT310EN101240632

Calibration Certificate No: As Attached Calibration Date: 26.06.13 Calibration Expiry Date: 25.06.2014

Verified By M/s. Al Ali Const.&


Tested By M/s. ABL Development Witnessed By M/s. Atkins Approved By M/s. Hilton

Name: M. BASITH

Signature:
Date: 19.11.2013