TEST REPORTS

1 CUSTOMER : METRO CASH & CARRY


2 TYPE OF PANELS : 800A LT KIOSK
3 DRAWING No. : VSG/LT/BNB/00
4 RCR NUMBER : 11281-A
5 QUANTITY : 1 NO

TEST ON PANELS

SL.NO DESCRIPTION RESULTS / OBSERVATIONS


1 Visual inspection and Mechanical checks Checked on Panels & Found ok.
2 Dimensions: HXWXD (mm) H1575 X W750 X D800
FABRICATION DETAILS:
a) Material 2 mm CRCA sheet steel
b) Thickness (mm) 2 mm CRCA sheet steel
c) Paint shade (Outside) RAL-7035 Powder Coated- Glossy Finish
3 d) Paint shade (Inside) RAL-7035 Powder Coated- Glossy Finish
e) Cross Hatch Testing for Power Coating Checked and found ok
Plain Gland Plate Provided with Sufficient Space for Cable
f) Cable Entry & Exit
Terminations at the Top of the Panel.
g) Enclosure IP IP42

TECHNICAL ASPECTS

1 GA and IGA Checked as per drawing and found ok

2 BOM as per Approved Drawing Found all components as per BOM

1RX100mmX10mmX1Parallel Aluminum 1RX100mmx10mmx 1Parallel Aluminum Busbar


3 Evidenced
Busbar
4 Tightness of Components Checked and found ok

5 Tightness of Connection Checked and found ok by Pulling method

Earthing Busbar 25mmx3mmx1 Parallel


6 Checked and found ok
Aluminum Busbar
7 Functional test Applied System Voltage to Incoming MCB/MCCB/ACB
Operation (ON/OFF)

Checked ELR Tripping

Checked CT Ratios and Readings of MFM

Checked Operation of All MCBs/MCCBs and ACBs

Page 1 of 3
and Verified Tripping Mode

9 Control ckt. Supply 230V AC All Control Circuit Wired with 1.5Sqmm

Phase- Phase

R-Y

Y-B

B-R
10 IRT (500MΩ, 1000V) before H. V
Phase- Earth

R-E

R-E

R-E

11 HV Test (2.5KV) for 1min. Found ok

Phase- Phase

R-Y

Y-B

B-R
12 IRT (500MΩ, 1000V) after H. V
Phase- Earth

R-E

Y-E

B-E

For

Page 2 of 3
VENKAT SWITCHGEARS

Inspected by: Sankeerth GL

Date: 21-02-2022

Page 3 of 3