This document calculates the total heat dissipation required for a 7-panel marine electrical system. It lists the various components in the incomer, busbars, and outgoing feeders along with their ratings, lengths, and individual heat losses calculated based on current and power. It then totals the heat loss for each section and applies a 10% margin to determine the final total heat dissipation of 8,165.58 watts required for the system.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
2K views1 page

Heat Dissipation Calculation

This document calculates the total heat dissipation required for a 7-panel marine electrical system. It lists the various components in the incomer, busbars, and outgoing feeders along with their ratings, lengths, and individual heat losses calculated based on current and power. It then totals the heat loss for each section and applies a 10% margin to determine the final total heat dissipation of 8,165.58 watts required for the system.

Uploaded by

Jaks Jaks
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
  • Heat Dissipation Calculation: Presents a detailed table calculating heat dissipation for Marine Electricals (I) Pvt. Ltd., listing particulars, quantity, rating, unit, length, heat loss, and remarks.

Marine Electricals (I) Pvt. Ltd.

Heat Dissipation Calculation


Length Heat Loss
Sr.No. Particulars Qty Rating Unit Remark
(in mtr) (in watts)
1 Incomer
1.01 Breakers contact 3 20 Amp 0.07 HL = 3 x I2 x 60 x 10-6
1.02 CT 3 15 VA 4.50 HL = 3% of VA
1.03 Indicating lamps 9 1 Watts 9.00 HL = 1 watt per lamp
1.04 Meters / Annunciator / Hooter 2 2 Watts 4.00 HL = 2 watts per meter
1.05 Aux contactors 1 2 Watts 2.00 HL = 2 watts per aux. cont.
1.06 Relays / timers 2 2 Watts 4.00 HL = 2 watts per relay/timer
1.07 Surge Arrestor 3 2 Watts 6.00 HL = 2 watts per Surge Arrestor
1.08 Busbars 3 20 Amp 3.2 0.29 HL = 3 x I2 x 75 x 10-6 x Length
Total heat loss per feeder 29.86
Space heater will be considered if total
heat loss will be lower than heat loss of
1.09 Space Heater 1 200 Watts 200.00 space heater
Considered Heat Loss 200.00
Total I/C feeders 1.00
Total Heat Loss of 20A rated incomer 200.00

2 Incomer
2.01 Breakers contact 3 500 Amp 45.00 HL = 3 x I2 x 60 x 10-6
2.02 CT 3 15 VA 4.50 HL = 3% of VA
2.03 Indicating lamps 9 1 Watts 9.00 HL = 1 watt per lamp
2.04 Meters / Annunciator / Hooter 2 2 Watts 4.00 HL = 2 watts per meter
2.05 Aux contactors 1 2 Watts 2.00 HL = 2 watts per aux. cont.
2.06 Relays / timers 2 2 Watts 4.00 HL = 2 watts per relay/timer
2.07 Surge Arrestor 3 2 Watts 6.00 HL = 2 watts per Surge Arrestor
2.08 Busbars 3 500 Amp 3.2 180.00 HL = 3 x I2 x 75 x 10-6 x Length
Total heat loss per feeder 254.50
Space heater will be considered if total
heat loss will be lower than heat loss of
2.09 Space Heater 1 200 Watts 200.00 space heater
Considered Heat Loss 254.50
Total I/C feeders 5.00
Total Heat Loss of 20A rated incomer 1272.50

3 Outgoing
3.01 Breakers contact 3 2500 Amp 1125.00 HL = 3 x I2 x 60 x 10-6
3.02 PT 3 30 VA 9.00 HL = 3% of VA
3.03 CT 3 15 VA 4.50 HL = 3% of VA
3.04 Indicating lamps 9 1 Watts 9.00 HL = 1 watt per lamp
3.05 Meters / Annunciator / Hooter 5 2 Watts 10.00 HL = 2 watts per meter
3.06 Aux contactors 1 2 Watts 2.00 HL = 2 watts per aux. cont.
3.07 Relays / timers 2 2 Watts 4.00 HL = 2 watts per relay/timer
3.08 Surge Arrestor 3 2 Watts 6.00 HL = 2 watts per Surge Arrestor
3.09 Busbars 3 2500 Amp 3.4 4781.25 HL = 3 x I2 x 75 x 10-6 x Length
Total heat loss per feeder 5950.75
Space heater will be considered if total
heat loss will be lower than heat loss of
3.1 Space Heater 1 200 Watts 200.00 space heater
Considered Heat Loss 5950.75
Total I/C feeders 1.00
Total Heat Loss of 20A rated incomer 5950.75
Total Heat Loss 7423.25 Watts
Design Margin and Mil Heat Loss 10% 742.33 Watts

Total Heat Dissipation for 7-Panel 8165.58 Watts

Heat Dissipation Calculation Page 1 of 1

Marine Electricals (I) Pvt. Ltd.
Heat Dissipation Calculation
Sr.No.
Particulars
Qty
Rating  
Unit
Length 
(in mtr)
Heat Loss