11KV RMU
SIE SB
ME D. N
NS
ITE o.
Sr. DRAWING No. No of Brief details of MN
o. Qty.
No. shts drg. or module type of
Print

A B C D E F G H I J K L M N O P 100
1 (3) G 7 1 5 7 0 J 8 7 3 5 R 0 0 1 1 RECORD OF DRG.
2 (4) G 7 1 5 7 0 J 8 7 3 5 D 0 0 2 5 DESIGN INSTRUCTIONS
3 (3) G 7 1 5 7 0 J 8 7 3 5 M 0 0 3 6 MSLD
4 (3) G 7 1 5 7 0 J 8 7 3 5 E 0 0 4 6 EQUIPMENT LIST
5 (3) G 7 1 5 7 0 J 8 7 3 5 N 0 0 6 2 NAME PLATE LIST
6
7
8
9 WIRING DIAGRAMS CLIENT's TYPE
10
11 (3) G 7 1 5 7 0 J 8 7 3 5 W 1 0 1 6 K01 (LBS No.-01)
12 (3) G 7 1 5 7 0 J 8 7 3 5 W 1 0 2 6 K02 (LBS No.-02)
13 (3) G 7 1 5 7 0 J 8 7 3 5 W 1 0 3 6 K03 (VCB No.-01)
14 (3) G 7 1 5 7 0 J 8 7 3 5 W 1 0 4 3 ME1
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30

DRG. C=Constructional Drg;Cable Routing Diag; D=Design Instructions/Tech Details; E=Eq. List; F=Front/Rear View; L=Layout of Eq; M=Master Single Line Diag; N=Name Plate List;
CODES P=Panel Fixing Plan;Process Flow Diag; R=Record of Drg; S=Single Line Diag; W=Wiring Diag;Other Electrical Diag; Z=Combination of drg. not covered by other codes
DWG.FILE

Date 14.02.17 Sales Ref.:- IC-LMV-MS/300.....


Client:- LARSEN & TOUBRO LIMITED Description:- 11KV RING MAIN UNIT
Prep. GCS Project:- SCRIPS, OPTCL
Work:- 8DJH ST -RRL+ME,O/D,MOTORISED Item No.:- 100 Qty.:- 3x
Ckd.
W.O. Sh. 1
Issue Remarks Date Name Norm Original/Replacement for/Replaced by:- Details:- RECORD OF DRAWINGS 300... Drg.No.:- (3) G71570 - J8735 - R001 - 1 Sh.
All rights, including righs created by patent grant or registration of a utility model PROCEDURE FOR CARRYING OUT AMENDMENTS
permitted without express written authority. Offenders will be lible for damages.
The reproduction, transmission or use of this document of its contents is not

1 Total no. of sheets, pertaining to a Drawing No. are mentioned only on Sheet No. 1 and on last sheet.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
2 (4)

Alphabate in the 1 st square, of the 4th Block of squares, indicates latest amendment or the status of the issue of the drawing.
3 In case of changes, the amendment to Drawing No. will be carried out only on those sheet, in which changes have taken place and on Sheet No. 1 for the purpose of summary of amendments. The same procedure will continue
for subsequent changes but every additional change will be indicated by use of next alphabet.
e.g. Say amendment ‘A’ takes place in Sheet No. 3,4,7. Then alphabet ‘A’ will appear in 1st square of 4th Block of Drawing No. Written on Sheet No. 3,4,7 & 1. Further, say, next amendment takes place in Sheet No. 3,5,9.
Then alphabet ‘B’ will appear in 1st square of the 4th Block of Drawing No. Written on Sheet No. 3,5,9 & 1. Even though Sheet No. 5 & 9 do not have amendment ‘A’ earlier, they directly will have amendment ‘B’.
or design, are reserved

4 Separate tabular form of amendment column does not appear on Sheet No. 1 but does appear on all remaining sheets.The brief description in these columns indicates the reference of Client’s/Sales Office’s/Work’s letter or actual
changes done in the drawing. The date-column indicates when the amendment has been carried out. The actual and latest changes are highlighted by drawing a circular shape around them and by writing amendment-alphabet in
a triangle near this circular form.

5 Reference Drawing Nos. wherever mentioned, show basic Drawing Nos. without any amendment. The information about the latest issue of any drawing can be obtained only from latest copy of ‘List of Documents’ which is sent
along with set of drawings for every drawing submission

Index Summary of Amendments Date Drawn Checked


A
B
C
D
E
F
G
H
I
J
K
Client :- LARSEN & TOUBRO LIMITED Sales Ref No.: IC-LMV-MS/300….
Project :- OPTCL
W.O.: 300….
Item No .: 100 Qty : xx
Date: 14.02.17 Description : - 8DJH ST RMU
Prep: GCS Type 8DJH ST -RRL+ME
Ckd: Work : - O/D, Ext, Motorised
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- J8735 -D002
Since irrelevant points are deleted, Sr No. may not be in sequence.

Unrestricted Page 1 of 5
Client :- LARSEN & TOUBRO LIMITED Sales Ref No.: IC-LMV-MS/300….
Project :- OPTCL
W.O.: 300….
Item No .: 100 Qty : xx
Date: 14.02.17 Description : - 8DJH ST RMU
Prep: GCS Type 8DJH ST -RRL+ME
Ckd: Work : - O/D, Ext, Motorised
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- J8735 -D002
Since irrelevant points are deleted, Sr No. may not be in sequence.

Main Busbars for more details refer 3.00.00

Three Position switch for more details refer 6.00.00


Three Postion disconenctor (LBS) for details
Refer 4.00.00

VCB for more details refer 5.00.00


written authority. Offenders will be lible for damages. All rights, including righs created by patent grant or
The reproduction, transmission or use of this document of its contents is not permitted without express

1.00.00 System Parameters


1.01.00 Ambient Temperature : 50 ˚ C
1.01.01 Maximum ambient air temperature : 50 ˚ C
1.01.02 Reference ambient temperature for design : 40 ˚ C
1.02.01 Maximum relative humidity : 90%
1.01.03 Main System : 3 Phase 3 Wire AC, 50 Hz
1.01.04 Rated operational voltage : 11 kV
1.01.05 Rated Voltage Ur : 12 kV AC
registration of a utility model or design, are reserved

Rated Power frequency withstand voltage (Phase to


1.01.06 : 28kV
Phase, Phase to Earth, Open contact gap) Ud
Rated Power frequency withstand voltage (Across the
1.01.07 : 32kV
isolating distance)
Rated Lightning Impulse withstand voltage (Phase to
1.01.08 : 75kVp
Phase, Phase to Earth, Open contact gap) Up
Rated Lightning Impulse withstand voltage (Across the
1.01.09 : 85kVp
isolating distance) Up
1.09.10 Altitude : Less than 1000 metres
NOTE : Design ambient temperature is 40 ˚C with current capacity as 630A. However at 50 ˚C, corresponding Derating will be applicable as per ambient temp,; i.e. 565A.

2.00.00 Construction
2.01.00 Type of Product : 8DJH ST Ring Main Unit
2.02.00 Installation
2.02.01 Location : Outdoor
2.02.02 Mounting : Floor Mounting with Cable Trench Beneath
2.02.03 Minimum Clerance from front : 1000 mm
2.02.04 Lifting arrangement : To be lifted along with packing/ lifting arrangement is also provided on the RMU shipping section
2.02.05 Front access : Bolted Cover for Mechanism and LV control In Indoor RMU
2.02.06 Rear access : Not Applicable
2.02.07 Future extension : ONLY LHS, since metering Panel on RHS provided
2.02.08 Alignment with existing RMU : Nil
2.02.09 Pressure Relief Device Loaction : At Rear Bootom on LHS side for each SF6 Gas Veseel
2.02.10 SF6 Pressure Relese direction : Rear Bottom, Inside Trench, away from operator
2.02.11 Partition Class PM
2.02.12 Loss of service continuity category for modules : LSC 2
2.02.13 Internal arc classification : IAC AFLR up to 20kA, 1s (NOT APPLICABLE FOR METERING PANEL)
2.02.14 CRCA sheet thickness for outer enclosure : 2 mm

2.03.00 Degree of protection for enclosure : O/D RMU : IP54 for RMU & FRTU Enclosure, IP3X with Front Cover opened & IP67 for SF6 Gas Vessel
2.04.00 Painting (HV Part)
2.04.01 Procedure : Pre-treatment & painting as per 7 tank process, Siemens standrd practice
2.04.02 Material : Epoxy Resin Based Powder.
2.04.03 Shade : RAL 7032
2.04.04 Paint lawyer thickness : 100 microns +/- 25 Micron Standard
2.04.05 Paint Finish : Structure finish like light orange peel.

Unrestricted Page 2 of 5
Client :- LARSEN & TOUBRO LIMITED Sales Ref No.: IC-LMV-MS/300….
Project :- OPTCL
W.O.: 300….
Item No .: 100 Qty : xx
Date: 14.02.17 Description : - 8DJH ST RMU
Prep: GCS Type 8DJH ST -RRL+ME
Ckd: Work : - O/D, Ext, Motorised
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- J8735 -D002
Since irrelevant points are deleted, Sr No. may not be in sequence.
written authority. Offenders will be lible for damages. All rights, including righs created by patent grant or

2.05.00 Name/Rating Stickers


The reproduction, transmission or use of this document of its contents is not permitted without express

2.05.01 Name/Rating Stickers material/ Details : Aluminium anodised with engraved letter, For Details Refer Name Plate drawing

2.06.00 Others Nameplates/Stickers


2.06.01 Do's and Dont's Sticker : Yes
2.06.02 Do not Drill Stickers at necessery locations : Yes
2.06.03 Danger Sticker Self adhesive : Yes, on all Cable compartment cover
2.06.04 Cable Termination Precaution Sticker : Yes, in any cable compartment cover
2.06.05 Phase Identification Stickers at Bushing : Yes, Standard Phase Identifciation colour coded L1,L2,L3 Stickers
registration of a utility model or design, are reserved

3.00.00 Busbars/Connection : Bolted conenction, inside SF6 Gas


3.01.00 Main Feeder Connections
3.01.01 System : 3 Ph.3W L1,L2,L3
3.01.02 Temperature rise limit : As per IEC 62271-200
3.01.03 Rated Bus bar Current : 630 A
3.01.04 Rated Short Time withstand current Ik : 21 kA for 3 second
3.01.05 Rated Peak withstand current Ip : 52.5 kA
3.01.06 Material of Main Busbar system : Copper
3.01.07 Cross-section for each phase : 1 x 30 x 10 mm, suitable for 630A
3.01.08 Insulation : SF6 Gas
3.01.09 Insulation at joints and tap-offs : SF6 Gas

3.02.00 Earth busbar


3.02.01 Material / Size : Tinned Copper. Size: 1 x 30 x 3 mm
3.02.03 Extension of earth busbar outside the RMU : To be provided on both sides

4.00.00 Load Break Switch Parameters


4.00.01 Rated Feeder Current : 630 A
4.00.03 Insulation : SF6 Gas

4.00.04 Rated Mainly active load breaking current I1(Test Duty 1a) : 630 A

4.00.05 Rated closed loop breaking current I2a(Test Duty 2a) : 630 A

4.00.06 Rated cable charging breaking current I4a(Test Duty 4a) : 68A

4.00.07 Rated line charging breaking current I4b(Test Duty 4b) : 68A
4.00.08 Rated short circuit making current Ima (Test Duty 5) : 52.5 kA
Rated no. of operating cycles, mechanical at no
4.00.09 : 1000/M1 as per IEC
load/classification
Rated no. of operation at active Load Breaking current
4.00.10 : 100/E3 as per IEC
I1/classification
Rated no. of operation at short circuit making current
4.00.11 : 5/E3 as per IEC
Ima/classification
Rated no. of operation at short circuit making current Ima
4.00.12 : 5/E2 as per IEC 62271-102
for earthing switch/classification
Manual Operation of Load Break Switch, (LBS ON/OFF,
4.00.13 : Yes
E/SW ON/OFF)
4.00.14 Motor operation of LBS(ON/OFF) : Yes
4.00.15 Rated cable charging breaking current : 68A
4.00.16 Min SF6 Gas pressure required for VCB & LBS : 1.3 bar

Unrestricted Page 3 of 5
Client :- LARSEN & TOUBRO LIMITED Sales Ref No.: IC-LMV-MS/300….
Project :- OPTCL
W.O.: 300….
Item No .: 100 Qty : xx
Date: 14.02.17 Description : - 8DJH ST RMU
Prep: GCS Type 8DJH ST -RRL+ME
Ckd: Work : - O/D, Ext, Motorised
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- J8735 -D002
Since irrelevant points are deleted, Sr No. may not be in sequence.

5.00.00 Vacuum Circuit Breaker Parameters


5.00.01 Rated Feeder Current 630 A
5.00.03 Insulation Medium : SF6 Gas
written authority. Offenders will be lible for damages. All rights, including righs created by patent grant or
The reproduction, transmission or use of this document of its contents is not permitted without express

5.00.04 Arc Quenching Medium : Vacuum


5.00.05 Rated Operating Sequence : O-3min-CO-3min-CO
5.00.06 Rated Short Time withstand current Ik : 21 kA for 3 second
5.00.07 Rated Peak withstand current Ip : 52.5 kA
5.00.08 Rated Short circuit breaking current Isc : 21 kA
5.00.09 Rated Short circuit making current Ima : 52.5 kA

5.00.10 Rated no. of operating cycles, mechanical /classification : 2000/M1 as per IEC

Rated no. of operating cycles, electrical at rated normal


5.00.11 : 2000/E2
registration of a utility model or design, are reserved

current /classification
5.00.12 Classification : E2,C1, M1
5.00.13 Numbers of short circuit breaking operations n : Up to 20
5.00.14 VCB Closing Time : <30 ms
5.00.15 VCB Opening Time : 50 ms Approx.
5.00.16 Arcing Time : 15 ms Approx.
5.00.17 Breaking Time : <60 ms
5.00.21 Trip Coil Rating : 24V DC Shunt trip coil. Approx. 140 Watt
5.00.29 Aux Switch details : Please refer wiring diagram

6.00.00 Three Position Switch, Off Load (Connected in series with VCB, towards BUS side)
6.00.01 Rated Current : 630 A
6.00.02 Rated short circuit making current Ima : 52.5 kA
Rated no. of operating cycles, mechanical at no
6.00.03 : 1000/M0
load/classification

6.00.04 Rated no. of operation at short circuit making current Ima : 5/E2(IN CONJUGATION WITH VCB)

7.00.00 SF6 Gas Pressure Monitoring


7.00.01 Type of SF6 gas monitoring : Ready for service indicator with Red-Green zone
7.00.02 No. of gas monitoring devices : 1 Nos. per SF6 Vessel
7.00.03 Gas filling facility (Non Return Valve) : 1 Nos. per SF6 Vessel

8.00.00 Shipping Section : complete unit as one shipping section

Unrestricted Page 4 of 5
Client :- LARSEN & TOUBRO LIMITED Sales Ref No.: IC-LMV-MS/300….
Project :- OPTCL
W.O.: 300….
Item No .: 100 Qty : xx
Date: 14.02.17 Description : - 8DJH ST RMU
Prep: GCS Type 8DJH ST -RRL+ME
Ckd: Work : - O/D, Ext, Motorised
Siemens Ltd.
Issue Remarks Date Name EM MS O GIS GOI Details : - TECHNICAL DETAILS
Original / Replacement for
Replaced by :- :
DRG NO. (4) G71570- J8735 -D002
Since irrelevant points are deleted, Sr No. may not be in sequence.

9.00.00 Wiring
9.01.00 Auxiliary Circuits : FRLS (Fire Retardant Low Smoke) Single Core Cu wire, Multistanded, Flexible
9.02.00 Insulation Grade : 1100 V
9.03.00 Size of wire (Control & auxiliary Circuits)
9.03.01 CT circuit If any : 2.5 mm.²/ Red, Yellow, Blue, Black

9.03.03 Control circuit DC If any : 1.5 mm.²/Grey for control ckt. within feeder.
9.03.04 Control circuit AC If any : 1.5 mm.²/Red for Phase & Black for Neutral
9.03.05 Auxiliary Buswire If any : 2.5 mm.² colour coding for AC/DC as per above
9.03.06 Circuit identification : Tubular Printed ferrules at termnations as per " Cross Dependent End Marking"
written authority. Offenders will be lible for damages. All rights, including righs created by patent grant or

9.03.07 Earthing Wire colour : 2.5 mm.² Green


The reproduction, transmission or use of this document of its contents is not permitted without express

9.04.00 Inter-module/ Inter-panel wiring


9.04.01 Within shipping section : To be done at Works
9.04.02 Between shipping section : NA(Since single transport section)

10.00.00 Termination Arrangements


10.01.00 Cables
10.01.01 Power cable entry from : Bottom
registration of a utility model or design, are reserved

10.01.02 Control cable entry from : Bottom


10.01.03 Cable boots/Terminal protector : Yes, being supplied as loose as an accessory
10.01.04 Opening for Load Break Switch feeder : Gland Plate suitable for terminating upto 1x3Cx400mmsq AL XLPE cable.
10.01.05 Opening for VCB feeder : Gland Plate suitable for terminating upto 1x3Cx150mmsq AL XLPE cable.

11.00.00 Control Terminals


11.00.01 Type of terminals for CT if any : Disconnecting Type Melamine TB, Model: CMDT4, Make Connectwell, suitable for Ring Type Lugs
11.00.02 Type of fixed terminals for Control Ckt. : CTS 2.5, Melamine TB, make connectwell, suitable for Pin type lug.
11.00.03 Lugs Details : Ring Type for CT, for others suitable to component make

13.00.00 Current Transfomer


13.00.01 Type of Current Transfomer : Ring type LV CT mounting around cable.
13.00.02 Standard : IEC 60044-1/IS2705
13.00.03 Highest voltage Um for the equipment : 0.72kV for Ring type CT
13.00.04 Permissible permanent over load : 120% of rated current In.
13.00.05 Insulation class : E
13.00.06 Rated short time current : 21kA for 3 Second.
13.00.07 Rated insulation level of secondary winding : 3kV AC for 1 minute
13.00.08 More details for Ratio, Burden accuracy, Make : Pl refer equipment list oe wiring diagram.

14.00.00 Voltage Indication System


14.00.01 Type : DXN8-T, LEELEN
14.00.02 Standard : IEC 61958 for VPIS

16.00.00 Fault Passage Indicator


16.00.01 Type of FPI : Fault Passage Indicator, Make- Siemens, Model- SICAM FPI 6MD2310
16.00.02 Is FPI comlete with CT and cable : Yes

RATTING OF EQUIPMENTS IN RMU


24.00.01 VCB Aux switch 10A
24.00.02 LBS Aux switch 10A
24.00.03 E/S Aux switch 10A
24.00.04 L/R switch 10A
24.00.05 TNC switch 10A
24.00.06 Contactor rating 7A
24.00.07 Motor Rating 80W max. (24VDC)
17.00.00 Special Instructions
17.00.01 All VCB feeders shall have auxiliary powered Protection relay for SC, OC & EF. Make: Siemens,Model 7SR10
17.00.02 Shunt trip coil-Y1 is used in the VCB tripping circuit
17.00.03 All LBS feeders shall have fault passage indicator (S/C & E/F). Make- Siemens, Model- SICAM FPI 6MD2310
17.00.04 All LBS/VCB feeders shall have fixed type Voltage Presence Indication System (VPIS) for checking the voltage presence. Type : DXN8-T, Make : LEELEN, CHINA
17.00.05 Metering Panel-ME1 shall accommodate 230V AC-24V DC Battery Charger.
17.00.06 ME1 panel shall accommodate 1000VA aux. transformer for generation of 230VAC, for input supply to battery charger & 24VDC to all feeder motor operation.
17.00.07 Metering Panel-ME1 shall have RYB indication lamps.
17.00.08 Document holder is shall be provided inside the Metering panel
17.00.09 RMU is Outdoor type, with 2x Motorized LBS + 1x Motorized VCB + Bus Metering Panel, LHS-Extensible.
17.00.10 Each VCB and LBS feeder shall have mechanical operational counter.

Unrestricted Page 5 of 5
14.02.17 Client:- LARSEN & TOUBRO LIMITED
GCS Project:- OPTCL
14.02.17 Client:- LARSEN & TOUBRO LIMITED
GCS Project:- OPTCL
Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU

CORE PART 8DJH ST -RRL+ME, OUTDOOR, LHS-EXTENSIBLE,


A - 1
MOTORIZED VCB, MOTORIZED LBS
12kV, 630A,STC 21kA/3SEC, BIL 28/75kV
SIEMENS MAKE

1 7SR10 RELAY …K55 106701060 - - 1 - 1


SIEMENS MAKE NUMERICAL O/C & E/F RELAY
WITH RS485 MODBUS PROTOCOL
AS PER THE FOLLOWING DETAILS:
INPUT NOMINAL CURRENT:1A
AUXILIARY SUPPLY: 24V DC
MOUNTING : FLUSH
6BI & 6BO
MODEL : 7SR1003-1JA20-2CA0

2 CTS …T1,…T2,…T3 106701062 - - 3 - 3


LOW VOLTAGE RING TYPE CURRENT TRANSFORMER
Current transformer as per IEC IEC 61869-1
CTR : 200-100/1A, CL: 0.5S, 2.5VA
CTR : 200-100/1A, CL: 5P10, 2.5VA
STC 21kA/3SEC, 50Hz
Insulation class E
Contineous Overload 120%
Minimum ID 55mm, Max OD 125mm, Max Height 150mm
MAKE : NARAYANPOWERTECH/RECO/GEMINI

3 CTS …T1,…T2,…T3 106701066 3 3 - - 6


LOW VOLTAGE RING TYPE CURRENT TRANSFORMER
Current transformer as per IEC IEC 61869-1
CTR : 400-200/1A, CL: 0.5S, 2.5VA
STC 21kA/3SEC, 50Hz
Insulation class E
Contineous Overload 120%
Minimum ID 55mm, Max OD 125mm, Max Height 150mm
MAKE : NARAYANPOWERTECH/RECO/GEMINI

Unrestricted EM MS O GIS GOI SIEMENS 1 of 6


Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU

4 COMBINED SHORT CIRCUIT & EARTH FAULT INDICATOR …H71 106701069 1 1 - - 2


SHORT CIRCUIT SETTING: 200/400/500/600/800/1000/1200 A …T4,…T5,…T6
E/F SETTING:10/20/30/40/60/80/100A …T7
S/C &E/F SETTING SELECTABLE AT CT
IMPULSE DURATION : 40/60/80/160/200/300/500 ms
WITH FO CABLE FOR S/C AND E/F (CT TO FPI CONENCTION)
WITH REMOTE RESET FACLITY & SCADA CONTACTS
WITH 3 NOS. OF SHORT CIRCUIT CT (T1,T2,T3)
WITH 1 NOS. OF E/F CT (T7)
TYPE : SICAM FPI 6MD2310
MAKE : SIEMENS
ORDERING CODE : SICAM FPI 6MD2310-0DA00-0AA0

5 TBATTERY CHARGER UNIT WITH BATTERY …V10 106659055 - - - 1 1


SUITABLE FOR MOUNTING ON BASE PLATE
(UNIVERSAL DIN RAIL MOUNTING CLAMP)
INPUT : 88-265 V AC ,
OUTPUT : 24V DC, 10A
WITH APPROVED REPUTED MAKE BATTERIES

WITH POTENTIAL-FREE REMOTE INDICATION CONTACTS FOR:


AC/CHARGER FAIL & BATTERY LOW
WITH MCB FOR INPUT & OUTPUTS
WITH APPROVED REPUTED MAKE BATTERIES
TEMPERATURE COMPENSATED
BATTERY RATING : 24V DC - 42AH (12V x 2) 106659056 - - - 2 2
MAKE : GOGATE ELECTROSYSTEMS/ALAN/EQUIVALENT

6 T3RT20 …K1,…K2 102840578 2 2 1 - 5


SIEMENS MAKE POWER CONTACTOR …K9
AIR BREAK, IN OPEN EXECUTION, THREE POLE (3NO+1NC)
AUXILIARY CONTACTS : 1NC
OPERATING COIL : 24V DC

Unrestricted EM MS O GIS GOI SIEMENS 2 of 6


Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU
TYPE : 3RT20 16-1BB4 2

7 SIEMENS MAKE …S13 102239623 1 1 1 - 3


22.5 mm DIA. 2 POSITION SELECTOR ACTUATOR
MAINTAINED TYPE WITH EXTERNAL BLACK KNOB, NON LOCKABLE
LOCAL-REMOTE OPERATION
ORDERING CODE : 3SB50 00-2AB01

8 SIEMENS MAKE PUSH BUTTON ELEMENT …S13 102241229 1 1 1 - 3


FOR 22.5mm DIA SELECTOR ACTUATOR
SUITABLE FOR PANEL MOUNTING
CONTACT ELEMENTS : 2 NO
ORDERING CODE : 3SB54 00-0E

9 SIEMENS MAKE PUSH BUTTON ELEMENT …S13 102241227 1 1 1 - 3


FOR 22.5mm DIA SELECTOR ACTUATOR
SUITABLE FOR PANEL MOUNTING
CONTACT ELEMENTS : 1 NC
ORDERING CODE : 3SB54 00-0C

10 SIEMENS MAKE …S14 102241019 1 1 1 - 3


22.5 mm DIA. 3 POSITION SELECTOR ACTUATOR
MOMENTARY ON BOTH SIDES ( SPRING RETURN ) WITH
EXTENAL BLACK KNOB FOR ON-OFF-C OPERATION
ORDERING CODE : 3SB50 00-2EB01

11 SIEMENS MAKE PUSH BUTTON ELEMENT …S14 102241223 2 2 2 - 6


FOR 22.5mm DIA SELECTOR ACTUATOR
SUITABLE FOR PANEL MOUNTING
CONTACT ELEMENTS : 1 NO
ORDERING CODE : 3SB54 00-0B

12 TMCB02A …F31 102933112 - - - 1 1


SIEMENS MAKE MCB
BREAKING CAPACITY : 10kA
RATING : 2 AMPS

Unrestricted EM MS O GIS GOI SIEMENS 3 of 6


Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU
POLE :4
RATING VOLTAGE : 415VAC/60VDC
WITH FIXED THERMAL O/L & MGT. S/C RELEASE
MLFB NO: 5SL64027RC

13 T3SB52 35-6HC14 …...H7 104968041 - - - 1 1


SIEMENS LED LAMP(COMPACT TYPE)
COLOUR: RED
VOLTAGE: 42-240V AC/DC
MLFB NO: 3SB52 35-6HC14

14 T3SB52 35-6HF14 …...H8 104968051 - - - 1 1


SIEMENS LED LAMP(COMPACT TYPE)
COLOUR: YELLOW
VOLTAGE: 42-240V AC/DC
MLFB NO: 3SB52 35-6HD14

15 T3SB52 35-6HF14 …...H9 104968048 - - - 1 1


SIEMENS LED LAMP(COMPACT TYPE)
COLOUR: BLUE
VOLTAGE: 42-240V AC/DC
MLFB NO: 3SB52 35-6HF14

16 TPREMIER300 ….P10 106654013 1 1 - - 2


SECURE MAKE
DIGITAL TVM
3 PHASE,4 WIRE,50HZ SYSTEM,
ACC CLASS : 0.5S
TYPE : PREMIER300,FLUSH MOUNTING,SIZE : 175x250 SQMM
CT SEC : 1A, CT RATIO : 400-200/1A
PT SEC: 110V/RT3

17 TPREMIER300 ….P10 106654013 - - 1 - 1


SECURE MAKE
DIGITAL TVM
3 PHASE,4 WIRE,50HZ SYSTEM,

Unrestricted EM MS O GIS GOI SIEMENS 4 of 6


Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU
ACC CLASS : 0.5S
TYPE : PREMIER300,FLUSH MOUNTING,SIZE : 175x250 SQMM
CT SEC : 1A, CT RATIO : 200-100/1A
PT SEC: 110V/RT3

18 TPT11KV …..T20-…...T22 106701073 - - - 3 3


Reco / Narayan Powertech / Gemini MAKE
POTENTIAL TRANSFORMERS IN CAST RESIN EPOXY CASE (FIXED)
SINGLE PHASE WITH PRIMARY FUSE OF 3.15A ….F1-….F3 - - - 3 3
CORE-1 : 11KV/RT3/110V/RT3,30VA,CL.: 0.5
CORE-2 : 11KV/RT3/110V/3,30VA,CL.: 3P
BIL(KVp) : 12/28/75

18.1 APPROVED MAKE …R11 105956270 - - - 1 1


DAMPING RESISTOR FOR PT OPEN DELTA CORE
50 Ohm, 200W

19 AUX. TRANSFORMER FOR CONTROL SUPPLY …T30 106076359 - - - 1 1


PRIMARY VOLTAGE : 11KV/RT3
SECONDARY VOLTAGE : 415V/RT3
BURDEN : 1KVA
ALONG WITH PRIMARY FUSE 3.15A OF PANICKKER MAKE …F11 - - - 1 1
BIL: 12/28/75KVP
MAKE : Reco / Narayan Powertech / Gemini

20 RIGHT ANGLED CABLE BOOTS, KD JOSHI/JASON POLYMER MAKE - 1 1 1 - 3 LOOSE


SUITABLE FOR 11KV APPLICABTION IN RMU
1 SET OF 3x CABLE BOOTS
MAKE : KD JOSHI, TYPE KS-300/JASON POLYMER
SIEMENS APPROVED DESIGN

21 OPERATING HANDLE 2 Nos PER SET OF RMU AS PER CONFIGURATION - 2 LOOSE

22 FIXED TYPE VOLTAGE PRESENCE INDICATION SYSTEM (VPIS) …A51 A7E0050210025 1 1 1 - 3


VOLTAGE RANGE 6-12KV
SUITABLE FOR 8DJH ST RMU

Unrestricted EM MS O GIS GOI SIEMENS 5 of 6


Ref:ED-MV/SOE/STANDARD EQUIPMENT LIST/REV.

Client : LARSEN & TOUBRO LIMITED 12kV Ring Main Unit


Project : OPTCL RMU Type : 8DJH ST -RRL+ME
Contractor:- L&T CONSTRUCTION,PTD IC W.O.: 300…..
SAP No : 300…./110 Quantity: 3
Date : 14.02.17 ESD No.: J8735
Drawing No.: (4) G71570 - J8735 - E004 -
QTY OF EQUIPMENTS GIVEN FOR 1x RMU (PLEASE MULTIPLY WITH ACTUAL QUANTITY FOR TOTAL VALUE)
TOTAL EQPT MPD AMD
Sr. MATERIAL
SPECIFICATION DESIGNATION K01 K02 K03 ME1 QTY
No. NUMBER
1 1 1 1 FOR 1xRMU
TYPE : DXN8-T
LEELEN

23 RMU OPERATION AND MAINTENANCE MANUAL - PER RMU SET - 1 LOOSE

24 TMCB02A …F19 106166431 1 1 1 - 3


SIEMENS MAKE MCB
BREAKING CAPACITY : 10kA
RATING : 6 AMPS
POLE :2
RATING VOLTAGE : 24V DC
WITH FIXED THERMAL O/L & MGT. S/C RELEASE
MLFB: 5SL42027RC

25 TCFL …E2 104944558 - - - 1 1


COMPACT FLOURESENT LAMP 1PH, 240V, 50Hz, 9W
WITH HOLDER
MAKE : PHILIPS/REPUTED

26 TTOGGLE SWITCH …S2 - - - 1 1


1P, TOGGLE SWITCH
RATING: 10A, 240V AC/DC

Unrestricted EM MS O GIS GOI SIEMENS 6 of 6


R3

MADE IN INDIA

14.02.17 Client:- LARSEN & TOUBRO LIMITED


GCS Project:- OPTCL
R3

MADE IN INDIA
Client:- LARSEN & TOUBRO LIMITED
Project:- OPTCL
RS485
SECURE MAKE
TRIVECTOR METER
RS485
SECURE MAKE
TRIVECTOR METER
RS485
SECURE MAKE
TRIVECTOR METER
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PROTECTION
Secure Meter RELAY

K01 K02 K03

E SF6 - READY FOR


SERVICE INDICATOR

FAULT PASSAGE
INDICATOR
F

SWITCHES FOR
LR & TNC

FPI FPI
G
MECHANICAL
OPERATION
COUNTER VPIS VPIS

VPIS FOR VOLTAGE


INDICATION
H

MIMIC DIAGRAM

VPIS
I

LOAD BREAK LOAD BREAK CB OPERATION


SWITCH-1 SWITCH-2 SWITCH 1

Tolerance Mass ; Masse P ap ersize Designa tion


Toleranz Format Datum Benennung
Note:- Dimension and Arrangements are for representation only. (IS O)
D/A1 Name
Name
Date Name

L Actual Product may slightly vary during production. Unit;Einh eit


S cale
Massstab Datum Name
L oca tion Page
mm S tan dort B la tt
Materia l No ./Nr. 1 Materia l No ./Nr. 2 Rele ased Itemnumber
Freigabe
Revision
Revision
S achn ummer
502_8814_9

You might also like