ARJAN G + 4 RESIDENTIAL BUILDING PROJECT

TEST CERTIFICATE FOR CONTINUITY & INSULATION TEST


Client Main Contractor MEP Contractor

Malak Al Reem Properties M/s. Mak Oasis M/s. Royal Arrow Electro Mechanical LLC

LOCATION: LV Room DB REF: LV-Panel DATE: 27-Feb-2020


Cable Type/Size INSULATION TEST ( Value in Mega Ω )
S/N TO Continuity
(sqmm) R-Y Y-B B-R R-N Y-N B-N R-E Y-E B-E N-E
1 4CX300 SMDB-A-1F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
2 4CX300 SMDB-A-2F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
3 4CX300 SMDB-A-3F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
4 4CX300 SMDB-A-4F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
5 4CX95 SMDB-LL-GF OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
6 4CX150 SMDB-LL-A-RF OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
7 4CX300 SMDB-B-1F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
8 4CX300 SMDB-B-2F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
9 4CX300 SMDB-B-3F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
10 4CX300 SMDB-B-4F OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
11 4CX150 SMDB-LL-B-RF OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
12 4CX185 Elec Fire Pump OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
13 4CX240 PFC Capacitor OK >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000

TEST INSTRUMENT DETAILS


INSTRUMENT : DIGITAL INSULATION TESTER
MAKE/MODEL :
SERIAL No. :

REMARKS ……………………………………………………………………………………………………………………………
…………….……………………………………………………………………………………………………………………………
Status: (Circle One)

A B ACCEPTED AS NOTED C NOT ACCEPTED

Signature:
Name:
Date: