COMMISSIONING RECORD SHEET : MAIN/SUB MAIN/FINAL DISTRIBUTION BOARD

Project MEDIA ZONE DEVELOPMENT, ABU DHABI


Panel Reference ESMDB-L4-M1

Panel Location L4-T2-ELE.ROOM Sheet 1 of 1 Rev. 0

PANEL DETAILS INCOMING CABLE IR TEST (MΩ)


REMARKS
Supply cable size : 4C 25 SQMM Source : E-SMDB-B1-L Earth : 1C 16 SQMM CPC : R-Y R-B Y-B R-N Y-N B-N R-E Y-E B-E N-E
Protective device type: Rating : Setting : >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000
CIRCUIT DETAILS COLD TEST
Circui Circuit continuity
Breaker No of Cable ECC RCB Ring Insulation resistance (MΩ)
t designation
No. Amps Type (kA) cores (mm2) (mm2) Rating () R-Y R-B Y-B R-N Y-N B-N R-E Y-E B-E N-E ()

1 ESMDB-L4-M1 CP/SEF-L5-01 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

2 ESMDB-L4-M1 CP/MAF-L5-03 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

3 ESMDB-L4-M1 CP/SPF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

4 ESMDB-L4-M1 CP/LPF-L5-01 32 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

5 ESMDB-L4-M1 CP/LPF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

6 ESMDB-L4-M1 CP/SEF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

7 ESMDB-L4-M1 CP/SEF-L5-03 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

8 ESMDB-L4-M1 CP/MAF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

9 ESMDB-L4-M1 CP/MAF-L5-01 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

10 ESMDB-L4-M1 CP/SPF-L5-01 32 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

11 CP/SEF-L5-01 ISOL SEF-L5-01 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

12 CP/MAF-L5-03 ISOL MAF-L5-03 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

13 CP/SPF-L5-02 ISOL SPF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

14 CP/LPF-L5-01 ISOL LPF-L5-01 32 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

15 CP/LPF-L5-02 ISOL LPF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

16 CP/SEF-L5-02 ISOL SEF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

17 CP/SEF-L5-03 ISOL SEF-L5-03 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

18 CP/MAF-L5-02 ISOL MAF-L5-02 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

19 CP/MAF-L5-01 ISOL MAF-L5-01 20 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK

20 CP/SPF-L5-01 ISOL SPF-L5-01 32 MCCB 35 4 10.0 10.0 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 >1000 OK
*Test all phases and record the MOST Cold Tested by : RAJAMALLU Date : 04.08.2021
Date:04.08.2021 Test instrument serial no : HIOKI-21-15523-01
Company: BILT ACC AECOM
Name: VENKITESH P G
Signature:
Date: