Professional Documents
Culture Documents
TRANSF- BUSBAR
ORMER ZONE
BUSBAR ZONE
ZONE
FEEDER
ZONE
GENERATION ZONE
BUSBAR
ZONE FEEDER
ZONE
Typical Power System
BUSBARS
BUSBARS
BUSBARS
TRANSMISSION DISTRIBUTION
GENERATION TRANSFORMERS
LINES RING FEEDERS
BUSBARS
TRANSMISSION BUSBARS
LINE
TRANSFORMERS
TRANSMISSION TRANSMISSION
LINE FEEDER
GENERATION
= CIRCUIT BREAKER
22kV
150A VCB Typical Distribution
Network
1 MVA
22kV/0.4kV
5%
1600A ACB
MSB
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
Protection System Components
Switching device
Sensors The “Brain”
Vacuum circuit breaker
Current Protective (VCB).
transformer relay
Air circuit breaker (ACB)
Voltage
transformer Moulded case circuit
breaker (MCCB)
Miniature circuit breaker
Current Voltage (MCB)
Contactor
Current Transformer Function
Two basic groups of C.T
1. Measurement C.T.s
- Limits well defined
2. Protection C.T.s
- Operation over wide range of currents
Primary
Secondary
Current Transformer Function
Measuring C.T.s
Require good accuracy up to B
approx 120% rated current.
Require low saturation level Protection C.T.
to protect instruments
Cl 1, 0.5, 0.2..
Protection C.T.s
Accuracy not as high as
above.
Require accuracy up to many
times rated current
5P10, 10P10, 5P20, Class ‘x” Measuring C.T.
H
Protection Class CT
Classes :- 5P, 10P. ‘X’
Designation (Classes 5P, 10P). Example: 15VA 10P20
(Rated VA) (Class) (ALF)
10P ±3 10
Protection Class CT
Class “X”
Specified in terms of :-
+10% Vk
Vk
Exciting Voltage (VS)
+50% Iek
Iek
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
Protection Application
Example 1:
Only OCEF relay used at the MSB
incomer
For all MSB outgoing circuits and SSB
boards, only MCCB are used for protection
purpose
If earth fault of 300A happened in one of
the outgoing circuit in MSB, what will
happen?
22kV
150A VCB Protection Application
OCEF Example 1:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 EF SSB 3
300A
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
Protection Application
Example 1: Consequences
Earth-Fault protection at the MSB incomer
will trip (600A MCCB will not trip because
fault current smaller than 600A), resulting
in supply interruption for all MSB outgoing
& all SSB circuits
This mean almost blackout to the plant !
22kV
150A VCB Protection Application
OCEF Example 1:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 EF SSB 3
300A
SSB 2
100A 100A 100A 100A 100A 100A
60A 60A
D/B D/B M
Protection Application
Example 1:Add EF Relay at MSB
IfEF relays are installed at the MSB
outgoing circuits, then what will happen for
the same fault?
22kV
150A VCB Protection Application
OCEF Example 1:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 EF SSB 3
300A
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
Protection Application
Example 1:Results with EF relay
The EF relays installed at MSB outgoing
circuits (600A circuit) will trip, thus only
this MSB outgoing circuit supply (including
SSB2) is interrupted
Other parts of MSB, SSB1 and SSB3
circuits not affected by this fault will
continue to have supply
22kV
150A VCB Protection Application
OCEF Example 1:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
600A MCCB
400A MCCB 200A 200A
300A MCCB
MCCB MCCB
EF relay EF relay
EF relay ELR ELR
Pump L/T &
Power
SSB 1 EF SSB 3
300A
SSB 2
100A 100A 100A 100A 100A 100A
60A 60A
D/B D/B M
Protection Application
Example 1:Summary
By having EF or Earth Leakage relays at the
MSB incoming and outgoing circuit, the supply
interruption can be limited to only the MSB
outgoing circuit associated with the fault
Other MSB outgoing circuit including the
associated SSB will continue to have supply
Supply interruption is confined to the section
having power system fault
Protection Application
Example 2:
Only EF or Earth Leakage relays used at
all MSB circuits
No EF or Earth Leakage relays used at all
SSB circuits. Only MCCB are installed in
SSB for protection purpose
If earth fault of 100A happened in one of
the outgoing circuit in SSB, what will
happen to the protection system installed?
22kV
150A VCB Protection Application
OCEF Example 2:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
EF
100A M
D/B D/B
Protection Application
Example 2: Consequences
Earth-Fault protection at the MSB outgoing
(600A) will trip, resulting in supply
interruption of all SSB2 circuits
22kV
150A VCB Protection Application
OCEF Example 2:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
EF
100A M
D/B D/B
Protection Application
Example 2: Add EF relays at SSB
IfEF or Earth Leakage relays are installed
at all SSB incomer and outgoing circuits,
then what will happen for the same fault?
22kV
150A VCB Protection Application
OCEF Example 2:
relay
1 MVA
22kV/0.4kV
5%
1600A ACB
OCEF MSB
relay
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
22kV Market Practice 2:
150A VCB -OCEF, EF or ELR relays
OCEF
relay at MSB, on top of MCCB
1 MVA
22kV/0.4kV -All SSB circuits only use
5% MCCB
1600A ACB
OCEF
- Good or Bad practice?
relay
MSB
SSB 1 SSB 3
SSB 2
100A 100A 100A 100A 100A 100A
300A 200A 150A
60A 60A
D/B D/B M
22kV Best Practice:
150A VCB -OCEF, EF or ELR relays
OCEF
relay at MSB & all SSB, together
1 MVA
22kV/0.4kV with MCCB
5% -Will the market follow??
1600A ACB
OCEF
relay
MSB
D/B D/B M
Selection of OC, EF or ELR element for
protection system (General Guideline)
Usually for load current less than 100A, use
ELR/RCCB/ELCB [ ILoad < 100A ]
Usually for load current larger than 100A but
less than 300A, use Earth leakage relays (ELR)
[ 100A < ILoad < 300A ]
Usually for load current larger than 300A but
less than 600A, use Earth-Fault relay
[ 300A < ILoad < 600A ]
Usually for load current larger than 600A, use
combined OCEF relay [ ILoad > 600A ]
ELR Protection System
DIN 310
ELR Relay
3-pole or
4-pole
Principle of Operation
I1 = I2
Installation & Wiring 1
ZCT
Cable
Must ensure that the Neutral line must be included in the ZCT
Installation & Wiring 2
Cable
ZCT
• MK300A
Typical Connection (1)
Connection of Mikro’s earth leakage relay with contactor
Typical Connection (2)
Connection of Mikro’s earth leakage relay with shunt trip
OC & EF Protection
IDMT
OCEF Relay:
Time - Current
Characteristic
Definite Time
Curve
Instantaneous
Fault current
IEC Curve family
Definite Time
Time
F1 F2
F3
Calculate TMS to
give desired
operating time in 0.1
1 10 100
accordance with the Current (Multiples of Is)
grading margin
Overcurrent Protection
Grading Margin
safety margin
Overcurrent Protection
Grading Margin - between relays
R1 R2
Traditional
breaker op time - 0.1
relay overshoot - 0.05
allow for errors - 0.15
safety margin - 0.1
Total 0.4s
10
E
Operating time (s)
1 D
C
0.1
0.01
Current (A) FLB FLC FLD
MK2200
Combined
Numerical
Overcurrent &
Earth-Fault
(OCEF) Relay
Protection Features
Multi-function numerical relay.
3 phase overcurrent & 1 earth-fault
elements.
Two (2) groups of OCEF setting by external
input.
Four (4) IEC IDMT curves & definite time
low-set.
Phase & earth fault currents metering.
Protection Features (cont’d)
Nine (9) previous fault records.
Programmable dry contact for tripping and
signalling.
Multi-function external digital input.
Isolated RS485 Modbus-RTU
communication. Connect to PC for remote
communication or connect to SCADA or
BAS (Building Automation System)
Protection Functions
51 Three phase dependent time
overcurrent (low-set)
50 Three phase definite time or
instantaneous overcurrent (high-set)
51N Dependent time earth-fault (low-set)
50N Instantaneous earth-fault (high-set)
Low-Set (IDMT)
4 user selectable IDMT characteristic
curve:
Normal inverse
Very inverse
Extremely inverse
Long-time inverse
Separate curve selection for overcurrent
and earth-fault
Examples of IDMT Curves
High-Set (DT)
Definite time or instantaneous tripping time
Separate selection for overcurrent and
earth-fault
Can be separately disabled
Inputs
Analogue input
Three 1A or 5A phase current inputs
One 1A or 5A earth fault current input
Digital input
Remote reset input or
External blocking signal input for the
measuring modules
Outputs
One set of NC/NO contact for tripping the
circuit breaker
Four NO contacts that can be programmed
to response to pick-up/trip condition for
earth-fault and/or overcurrent
One set of NC/NO contact to indicate
internal relay failure (IRF)
Typical Connection (3P4W)- MK2200
Typical Connection (3P3W)- MK2200
New MK2200L
Combined
Numerical
Overcurrent &
Earth-Fault
Relay
MK2200L Features (1)
Multi-function numerical relay.
3 phase overcurrent & 1 earth-fault
elements.
Two (2) groups of OCEF setting by external
input.
Four (4) IEC IDMT curves & definite time
low-set.
Phase & earth fault currents metering.
MK2200L Features (2)
Thermal Overload Protection (ANSI 49)
Trip Circuit Supervision Protection (74)
Multi-function external digital input &
output.
Fault, Alarm, Tripping Records with time-
stamp
RS232 Comm. Port & Isolated RS485
Modbus-RTU communication for EMS and
BMS automation.
Thermal overload protection
First-Order Model Based on IEC 60255-8 standard
Specific
thermal capacity Thermal
conductance
w
Θ (t) k
Protected object
Temperature Θ(t) I2
Θ Coolant
a
Temperature Θa
Square of current
L1
L2
L3
E/F OC OC OC
E/F OC OC OC E/F OC OC OC
EF setting independent
EF relay setting must be of neutral current
greater than normal (unbalance) but must
neutral (unbalance) use 3 OC relays for L-N
current faults
MU2300
Numerical
Voltage
Protection
Relay
Protection Features
Multi-function numerical relay.
2 stages under-voltage protection with DT
or inverse time characteristic.
2 stages over-voltage protection with DT or
inverse time characteristic.
Negative Sequence overvoltage & Residual
overvoltage protection with DT or inverse
time characteristic.
Used in single or 3 phase operation
Protection Features (cont’d)
Nine (9) previous fault records.
Programmable dry contact for tripping and
signalling.
Multi-function external digital input.
Isolated RS485 Modbus-RTU
communication. Connect to PC for remote
communication or connect to SCADA or
BAS (Building Automation System)
Typical Connection Diagram
Model MU250 (Voltage Relay)
Numerical design
Under/Over Voltage
Unbalance
Phase Loss
Phase Sequence
Voltage & Frequency
display
3 fault records.
With or without
neutral
Ph-Ph or Ph-N
Typical Connection Diagram
(MU 250)
Model MPR500
( Motor Protection Relay)
Numerical design
Thermal Overload
Overcurrent
Undercurrent
Unbalance
Phase Loss /
Sequence
Earth Fault
Prolonged Start/ stall
rotor
3 fault records.
Thermal Overload Curve
Typical Connection Diagram
(MPR 500)
Thank You
For further information, kindly contact:
Website: www.itmikro.com