Professional Documents
Culture Documents
Date: 10-03-07
B.Sridhar
Sr.Engineer
CT CORES
Ckt-1
Ckt-2
R
Y
B
N
87 Check Zone
87
Main Zone
R
Y
B
TYPES OF BUS BAR PROTECTION
▪ High Impedance
▪ Low Impedance
BUS FAULT
A B C D
DIFF.
S1 RELAY
P1 - - - -
1000/ 1 0.25A 0.45A 0.3A 0.5A 87
P2 + + + +
S2
1.5A
250A 450A 300A 500A
A B C D
DIFF.
S1 RELAY
P1 - - - -
1000/ 1 0.25A 0.45A 0.3A 1A 87
P2 + + + +
S2
1000A
250A 450A 300A
Bus Tripping scheme
Trip Bus-I
+ -
96
Trip Bus-II -
96
CB CB CB CB Rm Rh Rs
Relay
CT
CB CB
CT CT
Advantages of percentage
biased differential relay
Free of any need for matched CT
characteristic or ratios, low leakage
reactance or resistance.
Other protective relays can be
included in protective circuit.
Stable for even infinite fault level
Insensitive to CT saturation
Detects fault within 1-2 ms and
initiates tripping within 5-7 ms
• End of Slide Bus Bar Protection
Breaker failure relay (LBB)
OR
STRUCK BREAKER PROTECTION
OR
yes
Main / BB Initiate Fault yes Reset Lbb
prot.opt ? Bkr trip Cleared? relay
No No
I>0.2A ? yes
Trip
Normal Initiate fault
Backup
operation Lbb relay Clearance Td
Breakers
200 ms
Operation of LBB relay
Operation of the LBB relay depends on
the time taken by breaker to operate .
If any protection operates the command
signal goes to the trip coil of the CB ,at
the same time it goes to the LBB relay
via timer
If the timer on delay elapses then LBB
relay operates and isolate the protected
circuit from the fault through remaining
consecutive breaker.
Continued..
Setting of the timer is 200 ms. It should
be more than the main breaker
operating time + reset time of fault
detector relay so that backup breaker
should not operate.
The presence of the current through CT
for the LBB relay , is detected by over
current relay for identification of fault.
SPECIAL CONSIDERATIONS
1289R
with NGR
1089R
Future
NELAMANGALA KOLAR NELAMANGALA I&II SALEM BAY
1289L 1089L 789L 489L
1189B 1189A 889B 889A 589B 589A
1152 852 552
AEG Areva BHEL
400 KV BUS -I
1389 1589 1689 1889
BHEL Make
FUTURE
1589L AT# II Spare Unit AT# I 1689L
BUS
Autotransformer-II
3x167 MVA CGL
Unit-7 Unit-6 Unit-5 Unit-4 Unit-3 Unit-2 Unit-1 Autotransformer-I
4x167 MVA BHEL
Reactor
33 KV BUS TO FORM
TERRITIARY DELTA 1MVA 33/0.433KV
L289LS L189LS
L289D L189D
L252 L152
L289F CGL L189F NGEF
L289C L189C
Thank You