Professional Documents
Culture Documents
8 Transformer
Sylabus
Construction of Current Transformers, Diference Between CT Cores
those Used for Protective Relays, Calculation of CT Used for Measurement and
Accuracy,
Selecting a CT, Construction of Potential Transformer, Factors to be Considered while
Contents
8.1 Introduction
8.2 Curent Transformers (C.T.)
8.3 Construction of Cument Transformers
8.4 Why Secondary of
C.T. Should not be Open?
8.5 Tems and Definitions Related to C.T.
86 Magnetisation Curve of a C.T. .
. . Winter-17, .
.. Marks 4
8.7
Measurement and Protective C.T.s... ... Summer-15,16,17,18,
Winter-16,17,18,19,20, Marks 7
8.8 Potential Transformers (P.T.
8.9 Construction of Wound Type Potential Transformer
8.10 Ratios of
Instrument
Transformers
8.11 Burden of an Instrument Transformer
8.12 C.T. Errors ..Summer-13,14,19,
. . Winter-19, Marks7
8.13 Calculation of Accuracy of C.T.
8.14 Accuracy Class of C.T.
8.15 Selection of C.T.
Marksz
Summer-16, Winter-18,
8.16 Capacitive Voltage Transformer(CV1)....... Summer-18,
. Marks 3
8.17 Comparison of C.T. and P.T.
8.18 Transient Errors in C.T. and CVT
Transroimers
6.19 Advantages and Disadvantages of Instrument
8.20 Specifications of C.T.
8.21 Specfications of P.T.
8.22 Short Questions and
Answers
(8 1)
wtchgeara r n dP r o t e c t i o n
83
8 2 CuTent and Voltage Transt Current6 nd Voltage Transformer
Switchgear and Protection
nsformer For a transformer,
8.1 Introduction
N2
In heavy currents and high voltage a.c. circuits, the measurement cannot be dono
using the method of extension of ranges of low range meters, by providing
by
able
N ***
8.2 Current Transformers (C.T.) Knnwing this current ratio and the meter reading on the secondary, the actual high
The currents which cannot be sensed or the primary can be obtained
large alternating passed through normal current flowing through
line
ammeters and current coils of wattmeters, energymeters can easily be measured by use
of current transformers along with normal low range instruments.
Camole 8.2.1 A 250 5, current transformer is used along with an ammeter. 1f ammeter
reading is 2.7 A, estimate the line current.
A transformer is a device which consists of two windings called primary and
250
secondary. It transfers energy from one side to another with suitable change in the level Solution: 5
of current or voltage. A current transformer basically has a primary coil of one or more 2
turns of heavy cross-sectional area. In some, the bar carrying high current may act as a But as ammeter is in secondary, I2 = 2.7 A
primary. This is connected in series with the line carrying high current.
Heavy
The secondary of the transformer is made line current To load
up of a large number of turns of fine wire
1 - 135 A
having small cross-sectional area. Thisis
Primary C.T.
usually rated for 5 A. This is connected to the So line current is 135 A.
coil of normal range ammeter. Symbolic SecondaryT*0-5 A * * -
is wound
Primary current e core. The constru Otstruction, the primary
8.3.1. is wound
winding
mer. The heavy
eavy primary
TECHNICAL PUBLICATIONS- an up-thrust for knowledge I n - t h r u s t for k r o w e d g e
Switchgear and Protection 8-4 Current and Voitage on
S w i t c h g e a ra n dP r o t e c t i o n
5
Current and Voltage
winding with used for Transformer
secondary stampings
The
suitable insulation in between
the two. Otherwise the primary
Pinary laminations
have
ansformers must hav
the
in current
high
Secondary-
is wound completely separately area than the Secondaryy Barttype
rOss-sectional leads
and then taped with suitable ordinary transtormers. Due primary
insulating material and reluctance of the Core
this, the
assembled with the secondary insulation
Moulded to
interleaved corners remains
The windings are so designed that without damage, they can withstand short circuit
forces which may be caused due to short circuit in the circuit in which the current
transformer is inserted.
For small line voltages, the tape and varnish are used for insulation. For line voltages
above 7 kV the oil immersed or compound filled current transformers are used.
Review Question
. Explain the constructional details transformer.
of a current
(a) Rectangular (b) Ring (c) Stadium
8.4 Why Secondary of C.T. Should not be Open 7
Fig. 8.3.2 Stampings for current transformers
Eitner It
should not be kept open.
The core material for wound type is nickel iron steel. *svery important that the secondary of C.T. such as
-
1s defined as,
error
Review Question The
ratio
=
K x 100 =
* 100
% Ratio
error
Ip
8.5 Terms and Definitions Related to C.T.
Nominal ratio =
Rated transformation
where Kn
1. Rated primary current: The value of primary current on which the performance of for I
the current transformer is specified by the manufacturer is called rated I Actual secondary current
primary curen
Ip
Actual primary current
2. Rated short time primary current The r.m.s. value of the a.c. current which current
transformercan carry safely for rated time. It should not
damage the transformer duet e angle error: Ideally, the phase of the secondary current is to be displaced
temperature rise or electrodynamic stresses. Such a current rating is associated with time primary current. But actually it is not so. The phase angle between
which may be 0.25, 0.5, 1, 2 or 3 seconds.
oacdy 180 from the
primary current vector and the reversed secondary current vector is called phase angle
error denoted
as e.
3. Rated transformation ratio: It is the ratio of rated
primary current to the rated
secondary current. The rated secondary current is specified on the rating plate of the 13. Composite error: The r.m.s. value of the difference (Kn is -ip) integrated over
current transformer. It is denoted
as Kn. It is also called nominal ratio.
one cycle under steady conditiorn is called composite error. Mathematically it is given by,
4. Actual transformation ratio The ratio of the actual primary 100
secondary current. It is denoted as R.
current to the actual Composite error
TT Kn i,-ipPdt
5. Exciting
current: It is the r.m.s. value of the where ip i are instentaneous primary and secondary currents respectively, n 1s
secondary current taken when
secondary is excited by sinusoidal voltage of rated frequency with open circuited nominal ratio ie. rated transformation ratio and is primary r.m.s.current
Ip
primary winding.
14. Rated accuracy limit value of primary current
primary current The highest
6. Rated errors are within pemissiie
saturation factor: It is the ratio of rated
primary saturation current to ue
pecitied by the manufacturer for which the composite
rated primary current. limits.
to current
transformer, maintaining the specified density Bm
characteristics of aC.T.
Sity Bm.
accuracy of the pertormarne
TECHNICAL PUBLICATIONS up-thrust for knoWiedgs
an up-thrust for knowledge
-
-
an
ECHNICAL PUBLICATIONS
Switchgear and Protection 8-8 8-9
Current and Volta Switcthgear
a n dP r o t e c t i o n Current and Voltage Transformer
Age Transformer
The Fig. 8.6.1 shows the typical magnetisation Peak
flux
flux density
Thus the graph of E, E
Curve of a C.T. oeak Saturaton
density K SaluralOn gives
the required magnetisation
Itis divided into four regions: m characteristicS called
against excitati
excitation The characteristics.
called Knee
1. Region OA: It is nonlinear Knee point the experimentally obtained excitation region
region. The small 8.6.3shows
ampere-tums supplied are used to produce the AB Linear Figacteristics. Theknee point
K in this case is defined
flux in the core. Thus in this region which an increase of 10 in the open Linear
region, C.T. can not whi at
region
reproduce the primary current on the secondary the point
Ankle point as causesan
increase of 50 % in the
side faithfully. Thus ratio error of tit voltage
C.T. is large if Circuit
affecting magnetisation
the
for the relay operation. The magnetisation
characteristics of a C.i. 1s
1. The nature
of the
characteristics of a C.T. are, WuCn 1s Suitable
material
core
2. The
discussed in the last section.
of the ankle point.
While
3.
Length of the cross-sectional area of the core current transformers operate
in the region
magnetic path of the core 4. The
measuring
full range between
ankle and kriee pOint
The Fig.
8.6.2 shows number of turns in the POective current transformers operate
over
C.T. is expected to
the winding because the measuring
characteristics of a CT. experimental set up to obtain the he Portion beyond this range This is
current only, while
.
exciting Current is
Primary
winding tor the
currents about lineany
Single
varied by
varying the E Variac phase
20 % of
its rated value
voltage with the P2o A.C. suppy and it is
of Variac. help t advantageous as
circuit
open Secondary protective C.T. has to
ated current
The Fig. 8.7.1 shows the comparison of the magnetization otential Transformers
C.T. and protecting C.T. for the same rated burden.
characteristic of Types
of
For the same volt-ampere ratings and material used, the protective CT
measuring 6.8.1
T hore
ere
are two
types of potential
transformers,
potential transformer.
cross-sectional area of the core compared to CT. require large conventional
11000
(P.T) V 110
The basic
principle of these
transformers is same 87.5 V
alternating voltage are current and V2 =
as
reduced in
fixed proportion for the
a hign transformers. The
the
help of potential transformers.
The constructiorn of these
measurement purpose wi 875 l000
the normal
transformers is similar to 110
transformer. These are
windings are low power extremely accurate ratio step down transformers. IE
rating V =
8750 V
windings. Primary winding consists
of to be measurea.
large number of turns while PT This is the value of high voltage
secondary has less number of turns
and Review Question
usually rated for 110 V,
High
irrespective of the
primary voltage
voltage 0-110 V
Voltmeter
Load
of a potential transforntE
rating. The
primary is connected
Explain the working principle
Type Potential Transformer
across the
secondary
high voltage line while
is
Secondary of P.T 8.9 Construction of Wound sizes
compared
to
is not an
secondary is
always grounded for
Onventional power transformer. In potential
design.
The
accuracy
1
As a normal
transformer, for potential At the
its ratio can be The shell is preferred transformers
specified as, typ or core type
construction
c o r e type
for high
voltage
at the joints.
ell type is used for low
voltage while
the
air gap
effect of
time of assembly uired to
reduce
reduce the
the leakage
special core is are
used,
to
next to the
So if The coaxial primary and windings is always
voltage ratio of P.T. is reading is known then the hign Feactance. secondary voltage
winding
For high
voltage to be measured, can be known and the voltmeter is a low
transtormers.
knowedge
for
up-thrust
ECHNICAL PUBLICATIONS- an up-thrust for knoge PUBLIOCATIONS
- an
ECHNICAL
Switchgesr and Protection 12 8- 13
Curent and Curent and Voitage
Voltage
S w t d h g e aa
r naProlection
Transformer
voltages, insulation is the main problem. Hence in high voltage potential Transformer ratlo [K,]
primary is divided into number of small sections of short coils to
insulation between coil layers.
reduce trtheansfoneedrmerso, 2)
Nomlinal
The
nominal ratio is defined
e i t h e r current
or
as the ratio of rated
voltage.
primary quantity to the rated
The cotton tape and varmished cambric are used quantity, aprpsa*amsa*roan*****
Reivew Question
1.
Explain the
RCF
K
construction of a wound *******************************************
plate of
transformer is always
its nomna
R of actual of effect
primary voltage
Instrument
s
because
and this causes
Magnitude of actual
secondary voltage
. For P.T. the load on
the secondary changes. It
changes
loss
components
of
current
specific loading
The actual ratio is power factor and core the
as well
magnetising
w e as the
transformers
transtormer.
imits. Such
secondary winding voltage 1s specified
burden of an
instrument
a
permissible load is called
knowledge
for
TECHNICAL PUBLICATIONSan an
up-thrust
up-thrust for knowey TE
PUBLICATIONS
8 14 Current and Voltage
Transfor
S w i l c h i g e a ra n dP r o t e c t i o n
is defined as,
(Secondary winding induced voltage The ratio
error
Actual ratio
% Ratio error=
If only the impedance of the load is considered then burden due to only load can hebe The actual ratio R for a C.T. is given by,
obtained.
*******************
8 Phase
angle of total impedance of secondary including burden
Thus if Zs Secondary impedance = Is+jXs
Review Question
**
ZeImpedance of burden re +jXe
1. Explain the burden of an instrument transformer. then d = tan
/V1
is also not
exactly equal to N2/N1 due to the factors Tent actually it is nnot so. The
o t so.
error
introduced
COS-1, sin 87
e=0m degrees aete d ratio error ana
nls (8.12.4) n0te on phase angie error in C.T.
GTU: Summer-14,19, Marks 7
2. Discuss the factors affecting C.T. errors
the loads are inductive andd is
GTU Summer-13, Winter-19,
Approximate results: In practice, positive and
very
Marks 4
small. 6.13 Calculation of Accuracy of C.T.
sin - 0 and cos 8 - 1 hence the equations (8.12.2) and (8.12.4) becomes,
To calculate the accuracy of C.T. means to determine
its ratio error and ratio
R n+ .(8.12.5) correction factor. The ratio correction tactor 1s the ratio of actual ratio to the nominal
ion factor.
in the core, it
Currents well below the
normal saturation level. The Wu dson
amount of residual fux uer
ratio correction
of I and obtaining the accuracy
class of a C.T,
be obtained. 1, Explain
Selection of C.T.
Review Question .
8.15
be considered while selecting C.T. are,
the calculation of accuracy of
C.T. Thefactors to
1. Explain
primary
current should be selected from standard values.
1. Rated The rated
of C.T. be always greater than equal to the normal service current and
8.14 Accuracy Class current mnu
permissible
overload current.
composite error at 20 times the rated current. i) R.M.S. value of the fault current for a short time.
The accuracy class is defined by a composite error which is the r.m.s. value of the i) The time period for which the fault current persists.
difference between instantaneous primary current and the product of the instantaneous
in) Peak asymmetric value of the fault current.
secondary current and the transformation ratio.
1v) Transient voltage at the instant of fault.
So it l Rated primary current t Is specified as, 750 A for 0.5 sec, 525 A for 1 sec etc.
accuracy limit primary current to the called accuracyi Maximum fault current
factor. The rated primary current 15 ALF
accuracy limit factor is a Rated primary current
generally
10, 15 or 20.
PUBLICATIONS-
an up-thrust for knowledge
TECHNICAL PUBLICATIQNS ECHNICAL
Cunent and
n
S w i l c h g e a ra n d P r o l e c t i o n
8- 21
8- 20 Voltage Current and
Switchgear and Protecton
Transfomer ***************p
Voltag Transformer
C.T. transtorms maximum
The factor indicates how much
faithfully a
ssible failt Vout C+C2 Vin
current.
suitable for the application purpose. 2. The base box consisting of electromagnetic components.
The Fig. 8.16.3 shows a capacitive voltage transformer circuit
Review Question
*
Line
1. Explain the factors to be considered in selecting C.T. for a protective relaying. age
TECHNICAL PUBLICATIONS an
up-thrust for knowledge PUBLICATIONS- an
up-thrust for knowledge
ECHNICAL
S w i t c h g e a ra n dP r o t e c t i o n
-23
- 22 Current and voitage Current and
Voltage Transformer
Switchgear a n d Protection
Transfom
Errors in C.T. and CVT
section and given to an Transient
A voltage is
circuit which
tapped from the
is placed in
cast
ilowest capacitor
aluminium base box. circuit consists
This circuit electromagnetic
tra of
&.18
The
im
measuring e s of protective relays
times are reduced to very low value related
which provides output voltage. This
the final n it is
state. essary to
Hence
necoa
n them. As the cores of C.T saturate during transient period, the action of the high
2. Compare electromagnetic PT
with capacitor type PT. GTU: Winter-18, Marks 3
eneed relays get delayed. A linear core C.T.s are used nowadays which provide
8.17 Comparison of C.T. and P.T. GTU: Summer-18 caturation freetransient behaviour and fast working of protective systems. A linear core
means the core with proper
air gaps. Due to such air gaps, time constant of transient
The comparison of C.T. and P.T. is given in the following table,
oscilations get reduced and the main flux density also reduces. This improves the
transient behaviour of C.T.
Sr. Current Transformer Potential Transformer
No. steady state, the secondary voltage waveform of CVT is exact replica of the
In the
elements used in CVT, the
1. It can be treated as series transformer It can be treated as parallel transformer under primary voltage waveform. But because of the energy storage
the primary voltage is no
under virtual short circuit conditions. open circuit secondary. transientsecondary voltage caused due to sudden change in
distorted due to the transients.
2. Secondary must be always shorted. Secondary is nearly under open circuit longer replica of the primary voltage. The output gets
conditions. Ihe transients caused by CVT are of significant magnitude and comparatively long
Ihese
A small voltage exists across its Full line voltage appears across its terminals duration. The distorted output can last for few cycles of the supply frequency.
terminais as connected in series. errors in the output are called CVT transient errors.
The winding carries full line current. The winding is impressed with full line for large Source lmpedance Ratios
errors are particularly important
of
primary winding are brought out of the line is at ground potential. face problems due
through the same insulator. Hence there E e d operation may the following
factors,
1S saving8 in cost. The CVT transient mainly dependent
errors are
on
voltage level.
to the secondary
Table 8.17.1
.The Thevenin's equivalent capacitance referred
2. The figuration and the value of the burde for the
transient is worse
aults at
a v e voltage
1.
Compare C.T. and P.T. GTU: Summer-18,Marks
a
voltage zero crossing knowledge
for
an up-thrust
PUBLICATIONS-
C: Sum of the stack capacitances. 6.19 Advantages and Disadvantages of Instrument Transformers
L: Equivalent inductance of inductive reactor and transformer.
The advantages of instrument transformers can be listed as,
R: Equivalent resistance of inductive reactor and trarnsformer.
1, The normal range voltmeter and ammeter can be used along with these
Ro Resistance of burden. transformers to measure high voltage and currents.
The Cf, R and Lf are the parameters of the ferroresonance circuit. The Cf and L; in 2. The rating of low range meter can be fixed irrespective of the value of high
parallel forms a high impedarnce parallel resonant circuit tuned at the fundamental voltage or current to be measured.
requency. 3. These transformers isolate the measurement from high voltage and current cireuits.
At harmonic or subharmonic frequencies, the impedance of ferroresonance circuit This ensures safety of the operator and makes the handling of the equipments
drops off sharply and only R remains in the circuit which acts as damping resistor. very easy and safe.
This suppresses the ferroresonance oscillations.
These can be used for operating many types of protecting devices such as relays
. Several instruments
100 High
can be fed economically by single transformer.
30 CVT
60 Extra high 'C Disadvantage
,CVT be used only
40
disadvantage of these instrument transformers is that they can
TOrO y
20 a.c.
circuits and not for d.c. circuits.
20
40
Review Question
- 60 1. List
the transformer.
- 80 uOatages and disadvantages of instrument
100
Fault occurs at
Voltage zero 8.20 Specifications of C.T.
various specifications of C.T. are,
Time
0.05 0.06 0.07 0.08 0.09 0.1 0.11
in sec
1.Type It
covers,
Fig. 8.18.2 CVT transients
reduce the fundamental voltage i)The
1)
C.T. type ing
1 or window type. contact.
The second terminated with tinned cooper rose
l e a d s shall be
TECHNICAL PUBLICATIONS PUBLICATIONSan
up-thrust for knowedge
an
up-thrust for knowledge ECHNICAL
- 26 Curent and
S w i t c h g e a ra n dP r o t e c t i o n
8-227
Switchgear and Protection Voltage Trans Current and
nsfomer point
voltage
Voltage Transformer
and secondary.
ii) Marking of polarities for both primary
Knee
15.
8. Extended
11) Commissioning test which are carried out after erection on site
primary current: It is 120 % of the rated
primary current in accordane 20.
e T h e s e include the use of C.T. in bus zone protection, distance protection
with IS 2705.
aiterential protection, metering purpose etc.
9.
Rated C.T. ratio: It should be specified from the following standard ratings: U
150/5, 300/5, 400/5, 1000/5. Review Question
Secondary with 1 A may be specified if same is desired.
Explain the various specifications of C.i
10. Rated
short time current rating: As per IS 4201.
821 Specifications of P.T.
11. Rated dynamic current: It is ne
usually 2.5 times the rated short
time current ta various specifications of P.T. are,
12. Bore diameter of C.T.
dry type, naturally
Type It covers
mounting, type of
n t i n g , type
insulation, oil
immersed or
ECHNICAL
Switchgeara n dP r o t e c t l o n
- 29
protection
10%. ring C.T.s require hign accuracy over the
6. Voltage variation: Usually specified as
range of 10 % to 120 % of
Ans
It iis betterif C.T. saturates tor
currents
exceeding
current.
ximum
fault c u r r e r n t . core of
protective C.T. is of larger cross-section. Theto
8. Rated insulation level oriented steels having
terials like grain high saturation levels are used for
mater
protection
CTs while nickel-iron alloys having low exciting ampere-turns per unit length of core
9. Creepage distance: Specified in total mm. C.T.s.
are used for measuring
10. Accuracy class: It is 0.2 for metering and 3P for protection as per IS 3156. of burden C.T. ?
a.2 What is the meaning on
Q.3 What are the applications of C.T.s and P.T.s in a power system?
13. Rated transformation ratio
Ans. 1. To sense the current in circulating current diferential protection
14. Rated output in VA 2. In over current phase fault protection. 3. In various types of distance protection.
4. Intermediate C.T.s for feeding protective devices, measuring systems, relays etc.
15. Overvoltage factor: Which is 1.2 continuous, 1.5 times for 30 sec. etc.
Q.4 Why the secondary of C.T. should not be open ?
16. Tests:
These incdude,
Ans.: If the secondary of C.T. is kept open then current through secondary becomes
i) Type tests such as
temperature rise test, lightning impulse test, error zero hence the ampere turns produced by secondary which generaly oppose pnimary
measurement, switching impulse test etc.
ampere turns becomes zero. As there is no counter m.m.f, unopposed primary m.mt
i) Routine tests such verification of
fests
as
polarities,
frequency dry withstand
power
produce high flux in the core. This produces excessive core loss heating the core. it also
on
primary and
secondary, partial discharge measurement, error produces heavy em.f. on primary and secondary side which may damage the
measurement etc.
5lation of the winding. This is dangerous from the operator point of view as w e
ii) Commission tests to be carried out after ience the
secondary of C.T. should not be open
erection on site.
Q5 Define ratio error for instrument transformers.
17. Service: It is for metering purpose or
protection purpose. on load current, power
factor transformation ratio of transformers depends
cally measurement
is introduced in the
Review Question n g current. Due to this large
error
Ans.
1. Rated primary
current.
Turns ratio, Secondary current
Where n I2 =
TECHNICAL PUBLICATIONS an
up-thrust for knowledge PUBLICATIONS- an
up-thrust for knowedge
ECHNICAL