TCM and selector internal termination resistors CANNOT be used with component ‘stub’ installations.

A = CAN High
TCM ‘pass through’ connections CANNOT be used with TCM ‘stub’ installations.
B = CAN Low
C = Shield Maximum network length is 40 m. For shielded networks (J1939-11), stub lengths are not included; with unshielded
networks (J1939-15), stub lengths are included in the overall network length. K. Karch - 05/30/05

Two 120 ohm TERMINATION BACKBONE - the cable Stubs must be spaced Allison 4th Generation TCM
RESISTORS required; one at between the two termination > 10 cm apart.
each end of the backbone. resistors. It and the stubs must 49 J1939 SHIELD
They always use blue wedge be 120 ohm impedance cable. 8 J1939 LOW
locks. Parts shown have the As shown, the backbone can CAN1
28 J1939 HIGH
resistor built in the casing. pass through bulkhead
7 INTERNAL TR
connectors. NOTE: Wire twist is
not shown for clarity.

DT04-3P-EP10 Bulkhead receptacle DT06-3S-PP01


(Receptacle type) body DT04-3P-LE08 (Plug type)
Blue Wedge Lock W3P-1939
Blue Wedge Lock W3S-1939 PLUG connectors are SHIELD drain connects Pins 0460-202-1631
Pins 0462-201-1631 typically used on the directly to battery ground Housing DT04-3P-EE01
Housing DT06-3S-E008
backbone side: terminal, and breaks out In-Cab Diagnostic
Green Wedge Lock W3S-P012 of the backbone as close Bulkhead Housing
STUBS tee off of the Pins 0462-201-1631 to its' center as possible. HD10-9-1939P
backbone, and include Housing DT06-3S-EP11 A = Ground E=
the length of wiring on the B = +12 Volt (Unswitched) F = J1587 + (White)
C= G = J1587 - (Blue)
node. Maximum lengths: RECEPTACLE OEMs may wire stubs (Yellow)
D= (Green) H & J = For OEM use
connectors are typically directly to nodes; use of
Shielded Network: 1m used on nodes: 3-pin connectors is not
Unshielded Network: 3 m required. However, they Allison-manufactured
Green Wedge Lock W3P R
Pins 0460-202-1631 simplify troubleshooting 3000 / 4000 Series Selector N
D
NODE - an electronic Housing DT04-3P-EE01 and repair.
14 J1939 SHIELD
controller attached at the 15 J1939 LOW
end of a stub. Number of CAN
Engine ABS 8 J1939 HIGH
nodes allowed:
16
Controller Controller
Shielded Network: 30 7 INTERNAL TR
Unshielded Network: 10

Allison Transmission MY07 Datalink Communications – June 2006 SECTION C: SAE J1939 – 240