(DATE)

NOTE
MAX CONCRETE PRESSURE IS 50 kPa
A'Beckett
RATE OF RISE = 1.25 m/hr
A'Beckett - Formwork design for Lining Walls - Level B3
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1400

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1401
SINGLE SIDED FRAME GENERAL NOTES

MAXIMO GENERAL NOTES


TAS-T-XTW-0011-8007
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1402 LIFTING GENERAL NOTES

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1403 CAST IN POUR 1,2 AND 3


(SIGNATURE)

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1404 CAST IN POUR 4,5 AND 6

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1405 POUR 1

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1406 POUR 2

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1407 POUR 3

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1408 POUR 4

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1409 POUR 5

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1410 POUR 6
(BLOCK LETTERS)

TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1411 TYPICAL SECTION A-A


HIT-RE 500 V3 + TIE ROD 26mm
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1412 SECTION B-B DRILL DIAMETER=35 mm
DRILL HOLE DEPTH(CONCRETE)=min (520mm)

45°
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1413 SECTION B-B STAGE 2

0
52
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1414 SECTION E-E

RATE OF RISE:
Certified By:

1. ALL DIMENSIONS ARE TO BE CONFIRMED ON SITE FROM CURRENT, DETAIL OF INSTALLED TIERODS
APPROVED "ISSUED FOR CONSTRUCTION" DRAWINGS.
2. FORM TIES ARE TO HAVE A MINIMUM SAFE WORKING LOAD OF 90 KN.
NOTES:
3. THE MAXIMUM CONCRETE POURING RATE IS 1.25 m/Hr VERTICAL. FOR POST INSTALLED 1
4. POUR IN 0.5 m LAYERS MAXIMUM. (HIT-RE 500 V3 + TIE ROD 26mm) . DESCRIPTION
5. MAXIMUM CONCRETE PRESSURE = 50 KPa. TIE ROD NEED TO BE INSTALLED BY 2
6. HEIGHT OF WALL = 5.807 m ANGLE 45°. 1 SINGLE SIDE FRAME
7. CONCRETE POURING RATE IS ASSUMING THE FOLLOWING: THE EMBEDDED LENGTH SHOULD BE AT
LEAST 520 mm.
3
a) DISCHARGE HEIGHT = 2.00 m 2 HEX. NUT 26 OR WING NUT 26
b) CONCRETE TEMPERATURE AT PLACEMENT = 21°C 4
- POST INSTALLED ANCHORS REQUIRE 3 STEEL WASHER
c) COEFFICIENT C1 = 1.0 120 X 120 X 20
PULL OUT TEST BEFORE POURING.
d) COEFFICIENT C2 = 0.45 5
- POST INSTALLED ANCHORS REQUIRE 4 WALER U 200
e) WET DENSITY OF CONCRETE = 2450 KG/m³
PULL OUT TEST BEFORE POURING.
f) POUR RATE VALUE SUPPLIED BY ADCON ENGINEERING IS A 6 5 TIE ROD DW 26
GUIDE ONLY AND THE RESPONSIBILITY REMAINS WITH THE
SITE TO CONFIRM THE ASSUMED CONDITIONS. PUSH-PULL PROP R.M.D OR EQUIVALENT distance between the anchors 7 HEX. NUT DW 26 SW 46/150
6
ITEM DESCRIPTION could be 400~600mm 8
SIZE (mm)
7 TIE ROD DW 26 GR. (950 / 1050)
SHORT PUSH-PULL PROP 1815 to 3095 mm
LONG PUSH-PULL PROP 3050 to 5530 mm 8 THREADED ANCHOR PLATE 26
SHORT TURNBUCKLE 915 to 1235 mm
LONG TURNBUCKLE 1520 to 1840 mm

POST INSTALLED CONCRETE ANCHOR NOTES:


BONDED ANCHORS SHALL BE INSTALLED AS PER MANUFACTURERS SPECIFICATIONS, TO VICROADS SECTION 680 AND BTN006 REQUIREMENTS
MECHANICAL ANCHORS SHALL BE INSTALLED AS PER MANUFACTURERS SPECIFICATIONS (INCLUDING REFERENCING MAXIMUM INSTALLATION TORQUE SETTINGS) AND TO VICROADS
BTN008
RE-USE OF MECHANICAL SCREW-BOLT TYPE CONCRETE ANCHORS IS NOT PERMITTED. ALL INSTALLED ANCHORS SHALL BE NEW.

BONDED ANCHORS SHALL BE PROOF LOAD TESTED TO 1.5 X THE MAXIMUM DESIGN LOAD ON SAMPLE AS PER VICROADS SECTION 680 AND BTN006 REQUIREMENTS.

REINFORCEMENT STEEL NOTES:


EXERCISE CARE WHEN DRILLING FOR INSTALLING OF ANCHORS. CORING, CUTTING OR DAMAGE TO REINFORCEMENT IS STRICTLY NOT PERMITTED. USE A COVER METER TO
LOCATE EXISTING REINFORCEMENT AND PERCUSSION DRILL EACH ANCHOR HOLE. ALL FIXING PLATES TO BE FABRICATED TO MATCH HOLES DRILLED ON SITE.
ALL HOLES SHALL BE BY PERCUSSION DRILLING ONLY, CORING IS NOT PERMITTED.

PROPRIETARY ELEMENTS NOTES:


ALL STEEL LINING WALL SB FRAMES HAS BEEN MADE BY PERI FORMWORK TECHNOLOGY.

Project Drawing No
TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1400 A.0
Consultant Drawn By Designed By
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
This drawing has been prepared by, or compiled from
information provided by, persons other than PTV. To the FORMWORK DRAWING M.M M.M
maximum extent permissible by law, PTV takes no
- - - - - - - - - responsibility for, and makes no representations in relation to,
the completeness, accuracy or quality of any information
contained in this drawing. Each user of this drawing releases
CBD NORTH Checked By Ind. Review
- - - - - - - - - A'Beckett N.A -
08/01/2023 3:07:50 PM

PTV from all and any loss, damage, cost, expense or File Name
- - - - - - - - - liability in relation to the use of, or any reliance on, this
drawing or the information contained in it. LINING WALL B3-B2 Approved Approval Date
- - - - - - - - - Franchisee / Lessee SINGLE SIDED FRAME GENERAL NOTES Sheet No. N.S 01/08/2023
- - - - - - - - -
All written dimensions take precedence over scaled
dimensions.
Up Location Down Location Datum
01 of 01 Drawing Number Revision
- - A.0 01/08/2023 FIRST ISSUE M.M N.A - N.S In Serv.
This drawing is provided only for the information of the
Revised By In Serv Rev. Date
<REDRAWN & REVISED. SUPERSEDES PLAN No.
Description
REV. DATED / / >
Designed Checked Ind. Review Approved
person or organisation to whom PTV provides it. It may
not be provided to, or used by, any other person without
PTV's prior written consent.
East.
North.
ID#
East.
North.
ID#
Scale
NTS
-
Sheet Size
A1
1400 A.0
\\192.168.121.6\Work\project\Adcon\CBD North\FORMWORK\A'Beckett\TAS-T-XTW-0011-8007 -A'Beckett - LINING WALL B3\DWG\TAS-CYP-CBN-NAS-DRG-XTW-TNC-X1400-X1402-I0.dwg