You are on page 1of 3

PLC Connection Guide

Fuji NB Series
Website: http://www.fujielectric.com/fcs/index.html

HMI Setting:
Parameters Recommended Options Notes
PLC type Fuji NB Series
PLC I/F RS485 4W
Baud rate 19200
Data bits 8
Parity Odd
Stop bits 1
PLC sta. no. 0

PLC Setting:
Communication mode NITP Protocol / PLC Password (default is 0)

Device Address:
Bit/Word Device type Format Range Memo
B Y HHH 0 ~ 7ff Output Relay
B X HHH 0 ~ 3ff Input Relay
B M HHH 0 ~ fff Internal Relay
B L HHH 0 ~ fff Latch Relay
B C HH 0 - ff Counter
B M_Spe HHHH 0 ~ 81ff Special Relay
B T HHH 0 ~ 1ff Timer
W TV HHH 0 ~ 3ff Timer value
W CV HHH 0 ~ 3ff Counter value
W D HHHH 0 ~ 1fff Data Register
W D_Spe HHHH 0 ~ 81ff Special Register
PLC Connection Guide

Wiring Diagram:
Diagram 1
cMT Series cMT3151

eMT Series eMT3070 / eMT3105 / eMT3120 / eMT3150

MT-iE MT8070iE / MT6070iE / MT8100iE / MT8121iE / MT8150iE

MT-XE MT8121XE / MT8150XE

HMI PLC
COM1 Fuji NB Series
RS485 4W RS422 8P
9P Male RJ45 Male
Rx- 1 4
Rx+ 2 3
Tx- 3 6
TX+ 4 5
GND 5

Diagram 2
cMT Series cMT-SVR / cMT-G01 / cMT-G02 / cMT-HDM / cMT-FHD

mTV mTV

HMI PLC
COM2 Fuji NB Series
RS485 4W RS422 8P
9P Female RJ45 Male
Rx- 7 4
Rx+ 6 3
Tx- 9 6
TX+ 8 5
GND 5
PLC Connection Guide

Diagram 3
cMT Series cMT3071 / cMT3072 / cMT3090 / cMT3103

MT-iE MT8071iE / MT6071iE / MT8072iE / MT6072iE / MT8073iE /


MT8101iE / MT8102iE / MT8103iE
MT-XE MT8090XE / MT8092XE

MT-iP MT6071iP / MT8071iP / MT6103iP / MT8102iP

HMI PLC
COM2 Fuji NB Series
RS485 4W RS422 8P
9P Male RJ45 Male
Rx- 1 4
Rx+ 2 3
Tx- 3 6
TX+ 4 5
GND 5

Diagram 4
MT-iE MT8050iE / MT8053iE

MT-iP MT6051iP / MT8051iP

HMI PLC
COM1 Fuji NB Series
RS485 4W RS422 8P
9P Female RJ45 Male
Rx- 1 4
Rx+ 2 3
Tx- 3 6
TX+ 4 5
GND 5