ABB Utilities

IT
RTU560
Industrial Remote Terminal Unit
Connections and Settings
Communication Unit 560CMU80

Application, characteristics and technical data interfaces (CP1, CP2, CPA) and one Ethernet
have to be taken from the hardware data sheet: 10BaseT LAN interface (only R0002).
The 560CMU80 may be mounted at defined
560CMU80 1KGT 150 493 positions for communication unit in the housing.
The module has no configuration elements
Operation (jumpers).
The connection to the RTU560 system bus is
The communication unit 560CMU80 is the CMU
done via 48pole DIN-F socket connector
board (CMU = communication unit) of the remote
according to DIN 41612.
terminal unit. The 560CMU80 controls process
events and communication via max. three serial

Modem1 / RJ45 Modem AMD SCC


AMD
85C30 Com / 2 x 5 pole
SC400
Modem2 / RJ45 Modem

CP1 / RJ45 RS232


FPGA BIOS
ASIC +
CP2 / RJ45 DIP32
SPA-BUS

RS232

E-Bus SPB / 80C251+ SMSC RS232 MMI / DB9


DIN41612 RS485 DualPort 37C93x
RAM RS485 CPA / RJ45

10BaseT / RJ45 SMSC Compact


91C94 Flash
optional

PC104-Bus

Fig. 1: Block diagram communication unit 560CMU80

MMI sub-D connector (9-pole)


MMI interface
The MMI interface is available at the 9-pole sub-D Pin Signal Input/Output
connector (male) on top of the housing.
1 DCD input
The baud rate is fixed to 38400 bit/s, 8 bit, 1 stop
bit and no parity. The following signals (Fig. 2:) 2 RxD input
1
6
are used by the RTU560 software.
3 TxD output
9
5
4 DTR output

5 GND -
Male
7 RTS output

8 CTS input

Fig. 2: MMI interface

Doc.-No.: 1KGT 150 510 V002 1 1


ABB Utilities

Connections and Settings 560CMU80 IndustrialIT RTU560

CPA, CP1 and CP2 interface Ethernet interface (R0002 only)


The CPA, CP1 and CP2 interfaces are available The Ethernet communication interface 10BaseT
on RJ45 connectors on board. The interfaces use supports different functions.
RS232 or RS485 signals. • Webserver diagnostics with download of
configuration files and firmware
CP1 and CP2 interface RS232 mode
• Protocol IEC 60870-5-104, DNP3.0 over
In the RS232 mode the signals are used LAN/WAN
according to Fig 3:
Signaling
CP1 and CP2 Interface RS232 The LED “CE” of the 560CMU80 is software-
RJ45
Pin Signal Input/Output controlled. The definition and operation of the
1 DCD Input 1 LED "CE" must be taken from the release specific
function description.
2 RxD Input
8 The LEDs R(xD) and T(xD) are directly connected
3 TxD Output
to the receiver / transmitter of the communication
4 DTR Output line.
5 GND - The LEDs A, C and L are directly connected to
6 Not used the Ethernet controller (Table 1).
7 RTS Output
8 CTS Input LED Color Meaning

A green Activity (Ethernet)


Fig. 3: CP1 and CP2 interface RS232 mode
C yellow Copy data (Ethernet)

CPA interface RS485 mode L green Link (Ethernet)


In RS485 mode the signals are used according to
T(xD) green Transmit data ports 1,2,A
Fig. 4.
R(xD) green Receive data ports 1,2,A
CPA Interface RS485
CE yellow Communication error ports 1,2,A
Pin Signal Input/Output RJ4

1 Not used 1
Table 1: Meaning of LEDs
2 TA - Input/Output
3 TB + Input/Output 8

4 Not used
5 GND -
6 Not used
7
8

Fig. 4: CPA interface RS485 mode

2 Doc.-No.: 1KGT 150 510 V002 1


ABB Utilities

IndustrialIT RTU560 Connections and Settings 560CMU80

Modem connection X11/X12 Firmware version


A modem (560MOD8x) can be plugged into the The actual firmware will be delivered on a
board connectors X11/X12. The modem has an CompactFlashTM memory card. A new firmware
internal connection to the modem interface file can be loaded with the Web diagnostic tool
connectors. The signals depend on the modem into the removable CompactFlashTM memory card.
type (560MOD8x)(Fig. 5). Changing of CompactFlashTM is possible.

CP1 and CP2 Modem Interface X9 - X7 Settings


Pin Signal The settings of the hardware and for operation of
the communication interface of the 560CMU80
1 LA have to be made with the RTUtil NT tool.
The settings of the communication parameters will
2 LA1 be done within the "Hardware Tree" in the RTUtil
NT.
3 LB

4 LB1 The settings of the Ethernet interface (R0002


only) are node name, IP address and connected
5 - stations.
6 -

Fig. 5: CP1 and CP2 modem interface

ALARM / WARNING
ALARM and WARNING are activated by the
watchdog or by a RTU560E communication unit.
On signaling ALARM the signal WARNING is also
activated (Fig. 6).

WRN
ALR WRN

1
WRN
ALR
1
ALR

ATR
30 s

Plug-in
terminal strip

Fig. 6: Logic block diagram

Doc.-No.: 1KGT 150 510 V002 1 3


ABB Utilities

Connections and Settings 560CMU80 IndustrialIT RTU560

ALR
WRN - X3

10BaseT - X5
CPA - X6

LA

LA1
Modem2 - X7

LB
MMI-X2
LB1
CP2- X8

MODEM-MODULE2-X12
LA

LA1
Modem1 - X9

LB

LB1
CP1 - X10

Compact Flash-X13

MODEM-MODULE1-X11 560CMU80

Fig. 7 Board layout

ΑΒΒ
ABB Utilities GmbH
Kallstadter Str.1, 68309 Mannheim
Telefon: +49 (0) 621 381-7592
Telefax: +49 (0) 621 381-7622
www.abb.de/uta

4 Doc.-No.: 1KGT 150 510 V002 1