ABB AG RTU560 / RTU211

Remote Terminal Unit


Connections and Settings
Adaptor 23AD64

Application, characteristics and technical data The DIP switch S2 (1-4) sets the starting ad-
have to be taken from the hardware data dress of the I/O modules. This address is nor-
sheet: mally 1 (S2 (1-4) = Off). Other starting ad-
dresses are necessary, if the whole address
23AD64 1KGT 150 670 space of the I/O modules is needed (see Table
2).
Operation
The Adaptor 23AD64 is an adaptor to connect
RTU211 extension racks. It is also used to ex- Start- S2-1 S2-2 S2-3 S2-4
tend the serial peripheral bus over distances of Address
more than app. 30 cm. The interface adaptor 1 Off Off Off Off
is always used together with the power supply
unit 23PU63. 2 On Off Off Off

Processing Functions 3 Off On Off Off

The adaptor is used to terminate the serial pe- 4 On On Off Off


ripheral bus (Wired-OR Bus). The RS485 or
5 Off Off On Off
Fiber Optical Input (alternative) will be con-
verted to the Wired-OR Bus again. The rack 6 On Off On Off
address can be set by DIP switches. In addi-
tion it will generate automatically the module 7 Off On On Off
address within the rack, while the module
starting address can be set by additional DIP 8 On On On Off
switches individually.
9 Off Off Off On

Settings 10 On Off Off On


The rack address will be set by DIP switch S1 11 Off On Off On
(1-3) according to Table 1.
12 On On Off On
13 Off Off On On
Rack No S1-1 S1-2 S1-3
1 Off Off Off 14 On Off On On
2 On Off Off 15 Off On On On
3 Off On Off 16 On On On On
4 On On Off
5 Off Off On
Table 2: Setting of Starting address
6 On Off On
7 Off On On

Table 1: Setting of Rack Address

Doc.-No.: 1KGT 150 671 V001 1 1


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

Signaling The fiber optical connector X3 will be connected


to the superordinated device (e.g. 23AD63. The
The adaptor has 5 LEDs showing the activities connector X4 can be used for additional racks.
on the serial peripheral bus (see Figure 1). At connector X7 all internal supply voltages are
 LED 1: Activity on X1 or X3 available for test purpose.
 LED 2: Activity on X8 Please note:
 LED 3: Activity on X5 After the first connection 23AD63/23AD64 the
transmission media (RS485 / Fiber Optical) can’t
 LED 4: Activity on X4
be changed anymore.
 LED 5: Power Supply
Addition I/O modules are connected to X5.
Connections Please note: De-energize the system, before
plugging or unplugging this connector
The RS485 Bus will be connected to X1 and
X2. Connection according Table 3. Power Supply
The supply power 24 – 110 V DC for the power
supply unit 23PU63 will be connected to X6
X1-1 X1-2 X1-3 (1,2). The process voltage 24 V DC for addi-
X2-1 X2-2 X2-3 tional modules is available on X6 (4,5).

TB TA Shield Connection Examples


The principle usage of the adaptor 23AD64
Table 3: RS485 Bus Connector X1, X2 within an RTU211 or RTU560 is shown in Figure
Please note: PE (X6-3) must always be con- 2 to 7.
nected to functional earth.

Figure 1: Position of connections and setting elements

2 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
Connections and Settings 23AD64 RTU560 / RTU211

Figure 2: 23AD64 used in RTU211

Figure 3: 23AD64 connected to a star coupler 23SC60

3 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

Figure 4: 23AD64 used with 560CMG10

Figure 5: 23AD64 used in RTU560

4 Doc.-No.: 1KGT 150 671 V001 1


ABB AG
Connections and Settings 23AD64 RTU560 / RTU211

Figure 6: 23AD64 used in RTU560

Figure 7: 23AD64 with module starting address > 1

Dok.-Nr.. 1KGT 150 671 V001 1 5


ABB AG
RTU560 / RTU211 Connections and Settings 23AD64

ABB AG
Power Technologies Division
Power Technology Systems

Kallstadter Str. 1, D-68309 Mannheim


Telephone +49 (0) 621 381 – 7592
Fax +49 (0) 621 381 – 7622

www.abb.com/pt

Subject to alteration