Function of a volume
A s a result, variable volu-
me flow control for each
room is already a practical
flow control device
provides good control accu-
racy, even with unfavourable
upstream flow conditions. The
Control components
The room temperature and
choice, because only as much We should differentiate differential pressure, known volume flow control is the
power is consumed as is re- between a volume flow con- as effective pressure, is con- most common application in
quired to maintain comfort trol device (VAV controller), verted into an electrical sig- VAV systems. The room tem-
conditions. Operating costs which needs electric or pneu- nal and evaluated by a cont- perature controller is added
are significantly reduced by matic power, and the mecha- roller. The controller compa- to the flow rate control cir-
reducing the air flow. This not nical system powered cont- res the actual value with the cuit as a cascade control (Fi-
only has the effect of reducing rollers. The latter being used currently set value, and when gure 2). The following compo-
overall ventilation capacity, more as constant volume con- there is a deviation, it alters nents are necessary as func-
but also results in a reduc- trollers. This article deals with the positioning signal to the tional elements of a complete
tion in the energy consump- those units equipped with damper actuator. The air flow control circuit:
tion of air conditioning (he- electronic components. remains at the set value, in- ∑ Room temperature control-
ating/cooling/humidificati- The air flow is regulated by dependent of the duct pressu- ler and room control unit,
on/dehumidification) as well a control circuit, which means re (Figure 1) ∑ Air flow sensor and trans-
as in a longer service life for measurement - comparison - In a decentralised control ducer,
the filters. Demand-sensiti- adjustment. For measuring, technology, the set value is ∑ Volume flow controller and
ve control is not just a criteri- the VAV controller contains defined by the room tempe- actuator.
on here, but also the control a differential pressure sensor rature controller. This has the In practice the controls
reacts as to how the room is that provides an averaged effect of setting the volume supplier can offer different
being used at any moment. measurement. This sensor flow controller between mini- components that are speci-
It could be far more cost ef- fic to a particular
fective, for example, to redu- project. The com-
ce the ventilation of a non- ponents that are
occupied room rather than to provided can have
completely shut down the air various combina-
supply, in order to avoid ha- tions of the above
ving to fully re-heat the room differential pressure damper listed functions.
again. This would otherwise
sensor
+ - actuator Also each function
make a huge heating effort transducer can be carried out
necessary. by a separate com-
actual value ponent; however
output of room set value this requires the
temperature controller necessary wiring
*) Dipl.-Ing. Klaus E. Tegtmeier, volume flow controller
H. Erwin Kolibabka, both Air
connections and
Terminal Devices Division, ∂ picture 1: Volume flow control device schematic. commissioning.
Gebr. Trox GmbH In most cases, two
or more functions
are combined.
∂ picture 3: Variable volume flow system schematic, e.g. Internet cafe, laboratory.
inquired
The design and installation of
variable volume flow control-
lers promises a simple option
to achieve the required results.
But even here, it can quickly
lead to errors. The IKZ-HAUS-
TECHNIK editorial office asked
Dipl.-Ing. Klaus E. Tegtmeier
of Gebrüder Trox GmbH what
he thinks.
IKZ-HAUSTECHNIK: In your
expert opinion, where do the
most common errors occur
during the design and instal-
lation of a volume flow con- Klaus E. Tegtmeier
troller?
Tegtmeier: From the experi- connections can often oc-
ence of our colleagues in the cur. However, wiring errors
service team, as well as from are often not detected until
our own site visits to many the function test for commis-
completed and up and run- sioning is being carried out.
ning systems, there are two This error must be corrected
quite clear areas of error: the by either re-connecting or re-
installation location and the newing the cables.
wiring of the unit. IKZ-HAUSTECHNIK: How
First of all, when considering can these errors be avoi-
the installation location, ded?
care must be taken to ensu- Tegtmeier: A lot of errors can
re that the device is moun- be avoided when the fitters
ted in the right place. If the are comprehensively infor-
volume flow for each room med and the activities coor-
is preset on each unit, the- dinated. Often, they are left
re is a risk of errors during to their own devices and so-
installation. Consequences: metimes have insufficient, or
the air flow must be reset, at worst, no written guideli-
which is possible but causes nes to hand.
additional and unnecessary There can be no place for
effort and work. However, if mediocre work. However,
the units are installed with we all know it is common
the wrong air flow direction, practise. Nevertheless, one
the whole unit must be com- should not yield to this, but
pletely demounted and rein- should take into conside-
stalled correctly. ration, as early as possible
Our main issue, to which we in the planning stage, that
always come back to, is the the device remains accessib-
accessibility to the control le for servicing. In the buil-
components. The controller ding phase, the building su-
must be commissioned and pervision is required to es-
also even the best technolo- tablish with the technicians
gy can malfunction. Further- that this area remains free
more, the need to change the and accessible.