Static Analysis of G+3 Storey building.

Column size = 300 x 450 mm

Beam size = 230 x 450 mm

Wall Load from 0.0m Lvl to 3.0m Lvl = 0.23 x (3-0.45) x 22 = 12.9 =13 KN/m. (Plinth)

Wall Load from 3.0m Lvl to 8.0m Lvl = 0.23 x (5-0.45) x 22 = 23.02 =23 KN/m. (First Floor)

Wall load for Second Floor = same as Plinth.

Wall load for Third Floor = same as Plinth.

Parapett wall load at Terrace lvl. = 0.23 x 1x 22= 5.06KN/m.

Slab Thickness Assume = 125 mm.

Floor Load at Floor level = 4.8 KN/m2.

Floor Load at Terrace level = 6.25 KN/m2.